Text

',.

APPENDIX A NOTICE OF VIOLATION Virginia Electric and Power Company Surry Power Station Docket Nos. 50-280 & 50-281 License Nos. DPR-32 & DPR-37 As a result of the inspection conducted on October 26-30, 1981, and in accordance with the Interim Enforcement Policy, 45 FR 66754 (October 7, 1980), the following violation was identified.

10 CFR 20.203(b) requires that each radiation area shall be conspicuously posted with a sign or signs bearing the radiation caution symbol and the words: Caution Radiation Area.

10 CFR 20.202(b)(2) states 11 Radiation Area 11 means any area, accessible to personnel, in which there exists radiation at such levels that a major portion of the body could receive in any one hour a dose in excess of five millirem, or in any five consecutive days a dose in excess of 100 millirems.

Contrary to the above, on October 28, 1981, waste drums reading 10 mrem/hr at eighteen inches were stored in the yard area within the radiation con-trolled area.

The area where the drums were stored was not posted as a radiation area.

This is a Severity Level V Violation (Supplement IV).

Pursuant to the provisions of 10 CFR 2.201, you are hereby required to submit to this office within thirty days of the date of this Notice, a written statement or explanation in reply, including:

(1) admission or denial of the alleged viola-tion; (2) the reasons for the violation if admitted; (3) the corrective steps which have been taken and the results achieved; (4) corrective steps which will be taken to avoid further violations; and (5) the date when full compliance will be achieved.

Consideration may be given to extending your response time for good cause shown.

Under the authority of Section 182 of the Atomic Energy Act of 1954, as amended, this response shall be submitted under oath or affirmation.

The responses directed by this Notice are not subject to the clearance procedures of the Office of Management and Budget as required by the Paperwork Reduction Act of 1980, PL 96-511.

Date: DEC O g 1981


- -- - --- ------------~,

I 8202050376 820126 PDR ADOCK 05000280 G

PDR