Forwards LERs 80-040/03L-0,80-041/03L-0 & 80-042/03L-0
Date released: 12/25/2019 Download: ML18139A903


LER 80-041/03L-0:on 801112,snubber 2-WFPD-HSS-18 Found to Have Bent rod-eye & Was Declared Inoperable.Caused by Improper Alignment of Pipe Clamp to Snubber.Snubber Replaced
ML19345D869
Person / Time
Site: Surry 
Issue date: 12/11/1980
From: Joshua Wilson
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19345D869 (2)
LER 80-042/03L-0:on 801115,found Emergency Diesel Generator 3 Failed to Start Manually from Control Room.Caused by Vanes on Air Motor Worn Beyond Acceptance Limits.Vanes Repaired
ML18139A905
Person / Time
Site: Surry 
Issue date: 12/11/1980
From: Joshua Wilson
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML18139A905 (3)
LER 80-040/03L-0:on 801114,found Charging Pump Svc Water Pump 2-SW-P10A Developed Low Discharge Pressure of 10 Psig. Caused by Matl Entrained in Water & Being Deposited on Pump Impeller.Pump Disassembled,Cleaned & Returned to Svc
ML18139A904
Person / Time
Site: Surry 
Issue date: 12/11/1980
From: Joshua Wilson
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML18139A904 (2)
Forwards LERs 80-040/03L-0,80-041/03L-0 & 80-042/03L-0
ML18139A902
Person / Time
Site: Surry 
Issue date: 12/11/1980
From: Joshua Wilson
Virginia Power (Virginia Electric & Power Co)
To: O'Reilly J P
NRC Office of Inspection & Enforcement (IE Region II)
References
Download: ML18139A902 (1)