CONT~"OL BLOCK:  !-!_ _ ._ __.__..._......i.._l..._...J*, 0 !PLEASE PRINT OR TYPE ALL REQUIRED INFORMATION!

8 L*v I A 9

Is I P I 5 I 1 101 o LICENSEE CODI: 14 15 Io I -* I oI oI o Io 1- Io Io 1014 1e111 l1101 I 10 LICENSE NUMBER 25 26 LICENSE. TYPE. ;JO 57 CAT SS "T

e

~~~~! ~ I 01 s Io Io 10 I 21 s I o 101 o j 7 Io 17 I s1 o101 ° 18 1° 16 I 8 I O JG) 60 61 DOCKET NUMBER 68 69 EVENT DATE 74 75 REPORT DATE BO EVENT DESCRIPTION AND PROBABLE CONSEQUENCES @

2 L While performing Perio'di-c Tes-t 22 ** 2 , which is designed *to prove the operability of the 3 L diesel fuel oil transfer pumps, it was found that the circuit breaker for 1-EE-P-lF was

[3J L open. This is contrary to Technical Specification 3 .16 .A. 5 and is reportable as per

} ] L Technical Specification 6.6.2.b(2)The alternate flow path through 1-EE-P-lC was operable. The health and safety of the public were not affected.

))

B 9 BO SYSTEM CAUSE CAUSE COMP. VALVE CODE CODE SUBCDDE COMPONENT CODE SUBCODE SUBCODE

}]

6 I El El@

9 10

~@

11 w@ le I Kl 12 13 TI BIR I K 1@ ~@) ~@

18 19 20 SEQUENTIAL OCCURRENCE REPORT REVISION

@ LER,RO LVENTVEAR . REPORTNO. CODE TYPE NO.

REPORT NUMBER j 8 Io j l==.J Io 14 I 4! 1,1 I28O I 31 LI l=:J LQJ 21 22 23 24 26 27 29 30 31 32 ACTION FUTURE EFFECT SHUTDOWN {22) ATTAl.:HMENT NPRD-4 PRIME COMP. COMPONENT TAKEN ACTION ON PLANT METHOD HOURS Rr" SUBMITTED FORM!:iUB. SUPPLIER MANUFACTURER W@LlJ@

33 34

~@

3~

~ I 0 I O I O I I Lil@ W@)

36 37 40 41 4:2 I.Ll@

43 IC 44 11 I 11 047I CAUSE DESCRIPTION ANO CORRECTIVE ACTIONS @

l The breaker was inadvertently opened by personnel working in the vicinity o.f the MCC. The JJ I breaker was reclosed and i?eri~dic-Test 22.*i ~a~ complet:ed* satisfactorly.

}] . ....._ ________________________________~-------'

TI TI BO B 9 FACILITY STATUS  % POWER OTHER STATUS

'3a'

\:/

METHOD OF DISCOVERY DISCOVERY DESCRIPTION

~

\:31

~~@ I O I OI ~@1-I __N_A_ _ _ _ .-..J W@.._l __....;:O~p;.;;:e=-r=-at;::.;o;..;;r~o.;;;.b;;:_se.;;.;.:rv;..;...;...a...;.t.;;;.io;...n~-----.----........

B 9 10 12 1"3 44 45 46 SD ACTIVITY CONTENT ~

AMOUNT OF ACTIVITY ~ @

~

B w (§)

RELEASED OF RELEASE 9

LI@)l.____NA 10 11 44 *s NA LOCATION OF RELEASE 80 PERSONNEL EXPOSURES .

NUMBER ~ TYPE DESCRIPTION@

?J -1 a I o Io 10~@

8 9 11 12 1._3--------------------------------------.--JBO NA PERSONNEL INJURIES I:";\

NUMBER DESCRIPTION~

~]8 I9 oIo Io 11I@ ~ 1 : 1 : - - - - - - - - - - - - -NA -------------------------.-----B...lO LOSS OF OR DAMAGE TO FACILITY '4J' TYPE OESCRIPTIOIII ~

NA

~~@ .

8 9 10 BO PUBLICITY ~

ISSUED~ DESCRIPTION~ NRC USE ONLY .,

D U ! . 1 6 ~ - - = - = : - = - - - - - - - - - N - A_ _ _ _ _ _ _ _ _ __J I I I I I I I I I I I I I!

8 0 0 8°0 8 0 3 7'3 80 -;;

8 9 68 69 0

NAME OF PRE PARER-_...;J;...:.. * ...;L~. 1_s_o_n,;____________

_W:.;.1::.* PHONE: (804) 3 57-3184 II.

0

.t.. ATTACHMENT 1 SURRY POWER STATION, UNI~

DOCKET NO: ~0-230 REPORT NO: 80-044/031-0 EVENT DATE: 07-07-80 TITLE OF EVENT: TRANSFER PUMP BREAKER INADVERTANTLY OPENED

1. Description of Event:

While performing Periodic Test 22.2, which is. des.igned to prove the operability of the diesel fuel oil transfer pumps., it was. found that the circuit breaker for 1-EE-P-lF was open. This is contrary to Technical Specification 3.16.AiS and_is Reportable *as per Technical Specification 6.6.2.b. (2).

2. Probable Consequences and Status of Redundant Systems:

The alternate_ flow path through 1-EE-P-lC was operable and capable of supplying fuel oil to #3 emergency diesel day tank. The health and safety of the public were not affected.

3. Cause:

The breaker was inadvertently opened by personnel working in the vicinity of the motor control center.

4. Irmnediate Corrective Action:

Reclosed the circuit breaker and tested the pump as per Periodic Test 22.2.

5. Subsequent Corrective Action:

_None Required

6. Action Taken to Prevent Recurrence:

None Required

7. Generic Implications None