Forwards IE Circular 80-15, Loss of Reactor Coolant Pump Cooling & Natural Circulation Cooldown. No Written Response Required
ML18139A393
Person / Time
Site: Surry, North Anna  
Issue date: 06/20/1980
From: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To: Ferguson J
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
References
NUDOCS 8007020434
Download: ML18139A393 (8)


Text

,*

I UNITED STATES e

CLEAR REGULATORY COMMISSION REGION II 101 MARIETTA ST., N.W., SUITE 3100 ATLANTA, GEORGIA 30303 JUN 2 0 7980 Virginia Electric and Power Company ATTN: J. H. Ferguson Executive Vice President-Power P. 0. Box 26666 Richmond, VA 23261 Gentlemen:

This Circular is forwarded for information. No written response to this IE Circular is required. If you have any questions related to this matter, please contact this office.

Enclosures:

1.

IE Circular No. 80-15

2.

List of Recently Issued IE Circulars cc w/encl:

W.R. Cartwright, Station Manager Sincerely, James P.

Director P. G. Perry, Senior Resident Engineer J. L. Wilson, Manager

/

e UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D. C.

20555 June 20, 1980 SSINS No.: 6835 Accession No.:

8005050073 IE Circular No. 80-15 LOSS OF REACTOR COOLANT PUMP COOLING AND NATURAL CIRCULATION COOLDOWN Description of Circumstances:

This Circular contains information on the St. Lucie Unit 1 response to a total loss of component cooling water (CCW) flow to reactor coolant pumps.

Pres-surizer level and primary system pressure response indicate that voids were formed in the reactor vessel during the ensuing natural circulation cooldown.

The void was believed_ to have been steam in the area located directly under the reactor vessel head.

At time 0226 on June 11, 1980 with St. Lucie Unit 1 at full power, an electrical short across a solenoid valve terminal board caused one of two series containment isolation valves in the CCW return from all reactor coolant pumps (RCP) to fail shut.

The terminal. short resulted from environmental effects of a minor steam leak in the immediate vicinity of the solenoid valve.

After unsuccessful attempts to restore CCW flow, the *reactor was tripped manually at time 0233.

Wit~in two minutes, all four RCPs were also manually tripped.

A natural circulation cooldown was initiated at approximately 0300.

Compdnent cooling water flow to RCPs was restored at 0400.

The solenoid operated air valve whose terminal board had shorted was bypassed with a temporary air line to reopen the CCW valve (HCV-14-6).

Although variations in seal leakoff flowrates were observed, the seals on the four idle RCPs did not fail. St. Lucie has Byron Jackson reactor coolant pumps with three stage mechanical seals plus a vapor seal.

Controlled reactor coolant bleedoff flow is used for seal cooling and lubrication.

The pumps do not have a seal water injection system.

The natural circulation cooldown continued uneventfully until after time 0600.

The highest cooldown rate achieved was approximately 65 to 70 F per hour.

Between 0600 and 0630 RCS pressure was reduced from 1140 to 690 psi by charging water through the pressurizer auxiliary spray line. Pressurizer level increased rapidly around 0700 while charging via the auxiliary spray line.

Pressurizer level continued variations for approximately five hours while the cooldown and depressurization continued.

When charging was shifted to the RCS loops, pressurizer level decreased at rates lower than the rates of increase in level when charging through the auxiliary spray line.

During a two minute interval while charging into the pressurizer auxiliary spray line at 88 gpm, pressurizer level rose at a rate approximately ten times greater than the charging flowrate.

., : -~-

-**.. - -.- ----- *: - -. -~- --.- ----.... -. ~..

IE Circular No. 80-15 June 20, 1980 Pag~ 2 of 4 The cause of pressurizer level variations appears to be formation of a steam void in the reactor head area due to a temperature lag with respect to bulk coolant temperature that developed because of insufficient cooling flow in that area during natural circulation cooldown.

Gas concentration in a 0730 RCS sample was determined by the licensee to be 32 cc/kg hydrogen and 16 cc/kg nitrogen.

These concentrations were not high enough to cause a significant volume of gas to come out of solution.

The indicated subcooling margin (Tsat - Thot) ranged between 220 and 150 F when the reactor head steam void developed between 0600 and 0700.

The minimum required subcooling of 50 F was not approached during the cooldown until around time 1219 at a pressurizer pressure of approximately 110 psig.

An annotated record of pressurizer level is enclosed only to illustrate the high amplitudes and rates of pressurizer level variations.

Insufficient information is contained in the enclosure to enable detailed evaluation of the RCS behavior.

Shutdown cooling using low pressure safety injection (LPSI) pump lB was established at time 1051.

At time 1227, LPSI pump IA was started taking suction from the refueling water tapk (RWT) and discharging into the low pressure safety injection header common to both LPSI pumps.

The common recirculation line motor operated isolation valves to the RWT were opened at 1226.

LPSI IA was operating with its recirculation (miniflow) line open.

The LPSI pump lB recirculation line should have been closed.

The pressurizer was filled to what was believed to be a water solid condition by charging at 88 gpm and using LPSI pump IA to inject water and maintain near shutoff head pressure on the RCS.

RCS pressure rose from the minimum 110 psig to 200 psig (time 1300 r~ading) during the time LPSI pump IA was operating.

The cold calibrated pressurizer level instrument indication rose to 64 percent and remained constant while hot calibrated channels rose to 100% level.

Temperature correction data for the cold calibrated level instrument didn't extend to 360 F, which was the approximate pressurizer temperature when the pressurizer indicated full.

Constant level on the cold calibrated channel indicated the pressurizer was solid,. but continued charging flow at 88 gpm was not causing pressure to rise above 200 psig, as it should have had the RCS been solid.

Letdown had been secured while filling the pressurizer.

The indica-tions of a steam void in the reactor vessel head were no longer evident after RCS pressure increased although the exact time when the void disappeared has not been established.

During the time LPSI pump IA was operating with miniflow recirculation to the RWT, the absence of rising pressure in response to charging flow was investi-gated.

RWT level increased 0.3 feet (approximately 4500 gal.) *during this period.

Miniflow from LPSI pump lB operating in the shutdown cooling mode is believed to have been the discharge path from the RCS to the RWI'.

After shutdown cooling system warmup, the LPSI pump lB miniflow manual isolation valve had been shut. After RWT level increased, this valve was found one turn open, which would have allowed miniflow back to the RWI' from LPSI pump lB.

At time 1357, LPSI pump IA operating in the injection mode was secured and

i I. -*- --. -* -**------- --. - -, -----

e IE Circular No. 80-15 June 20, 1980 Page 3 of 4 miniflow was isolated.

Continued charging with two pumps at 88 gpm total flowrate caused a slight rise in both pressurizer pressure (to 260 psig) and cold calibrated pressurizer level.

Letdown in excess of charging flowrate was established at 1430, and by 1500 a steam bubble was drawn in the pressurizer with level in the indicating range.

The RCS was degasified over the next day, then depressurized and drained to inspect and replace all RCP seals. All seals have been removed and visual inspection showed no signs of degradation of these seals.

This event is significant for several reasons. It is an example of a natural circulation cooldown during which a steam void formed under seemingly normal conditions that was large enough to cause large, rapid variations in pres-surizer level.

The possibility of a total loss of component cooling water to reactor coolant pumps due to the single ~ailure of any one of four CCW contain-ment isolation valves was highlighted.

Inadequate control of LPSI system alignment allowed an unanticipated discharge of reactor coolant directly to the refueling water tank apparently through a pump recirculation line.

Recommended Action for Power Reactor Licensee Consideration:

1.

Disseminate this information to all licensed operating personnel working at power reactor facilities.

These personnel should become aware of the possibility of steam void formation in the reactor vessel head during natural circulation cooldown even when a high subcooling margin exists in the reactor coolant loops.

2.

Review and revise natural circulation cooldown and shutdown cooling procedures to caution operators against the anomalous conditions that occurred and to include appropriate recovery action if they do occur.

3.

Establish a natural circulation cooldown and depressurization rate envelop that will both preclude steam void formation and assure adequate core cooling.

Incorporate this envelop in cooldown procedures.

4.

Evaluate the design of component cooling water systems to determine vulnerability to single failures that could cause loss of RCP cooling, common cause failures of RCP seals and.reactor coolant system leaks through failed seals at multiple locations.

5.

Consider installation of a reactor vessel head metal temperature monitoring system, if not already installed. It should aid the operator in preventing a reactor head to bulk coolant temperature differential large enough to form a steam void during natural circulation cooldown.

e IE Circular No. 80-15 June 20, 1980 Page 4 of 4 If you have questions regarding this matter, please contact the Director of the appropriate NRC Regional Office.

No written respons~ to this Circular is required.

Enclosure:

Annotated record of pressurizer level

I I.

I I

I

..: V.) '-

).\\ () :-t '

('t\\-,,- ~

~~J::~

~ fl.':!::

~ "'" -

l'tJ

~.... l?'i

-I;,

'- ~

,.,. lb

~ :t h\\ ~

Cl\\)

"1 0 "'

ib "'

O' r-0233.

~ 0.30d 0400 o;oo

.*,J PF~CENT. LEVEL

. -~. -** -~

,t*

DE PRESSU ~t t e l/40pPij.,...,q~ p1,*1 STo.P L.ETbotAI\\I 2 CHIJR.G11u:.,umP.s STo 'P f:fFb 3 c HA!e.G-IAJG J)umPs STRRT FEEb I#*::::::-:-- I C M iQR.C. HJ t; p v M ~

ST~R.T" LErbow"'

'* ~-

1 I i Io 0¢,

J /00 j

/4 00 r

I i

/SOo I

/800 I i

-r -

t...:

.(

STII~ r-L°P~

J.A INTEt:Tf oN Te, ~Ct FRct\\"\\ RWr SEcu. ~.E" kPSI.l.A

.T Dn,:, w-,,,J c:;.

PlR auaeLE' l_

ST!l~T * ~ /lb.

CHAR c..,*,.,c; J)untP sroP tNb CHA~ G.JHt.. 'P'-lM p

- ----*~-................. --- *.,--.. *-. --~-**** --*-*- -------.. --.,-*

IE Circular No. 80-15 June 20, 1980 e

RECENTLY ISSUED IE CIRCULARS Circular No.

80-15 80-14 80-13 80-12 80-11 80-10 80-09 80-08 80-07 80-06 80-05 80-04 Subject Loss of Reactor Coolant Pump Cooling and Natural Circula-tion Cooldown Radioactive Contamination of Plant Demineralized Water System and Resultant Internal Contamination of Personnel Grid Strap Damage in Westinghouse Fuel Assemblies Valve-Shaft-To-Actuator Key May Fall Out of Place When Mounted Below Horizontal Axis Emergency Diesel Generator Lube Oil Cooler Failures Failure to Maintain Environmental Qualification of Equipment Problems With Plant Internal Communications Systems BWR Technical Specification Inconsistency - RPS Response Time Problems with HPCI Turbine Oil System Control and Accountability Systems for Implant Therapy Sources Emergency Diesel-Generator Lubricating Oil Addition and Onsite Supply Securing of Threaded Locking Devices on Safety-Related Equipment Date of Issue 6/20/80 6/24/80 5/18/80 5/14/80 5/13/80 4/29/80 4/28/80 4/18/80 4/3/80 4/14/80 4/1/80 3/14/80 Enclosure Issued to All holders of OLs and CPs All holders of Power and Research Reactor licensees (Operating and Construction Permits), and Fuel Cycle licensees All holders of Reactor OLs and CPs All holders of Reactor 01s and CPs All holders of a power reactor OL or CP All holders of Reactor 01s and CPs All holders of a power reactor OL or CP All General Electric BWR's holding a power reactor 01 All holders of a power reactor 01 or CP Medical licensees in Categories G and Gl All holders of a power reactor OL or CP All holders of a power reactor OL or CP