DIGITAL INSTRUMENTATION AND CONTROLS DI&C-ISG-06 Licensing Process Interim Staff Guidance Draft Revision 2 July 2018
- concurrence via e-mail OFFICE NRR/DE/EICB*
NRR/DE/EICB*
NRO/DEI/ICE*
RES/DE/ICEEB*
QTE*
NAME SDarbali RStattel DZhang BDittman JDougherty DATE 5/3/2018 5/3/2018 5/4/2018 5/9/2018 3/15/2018 OFFICE NRR/DLP/PLPB/PM NRR/DIRS/IRGB/LA*
NRR/DLP/PLPB/BC*
NRR/DE/EICB/BC*
RES/DE/ICEEB/BC*
NAME JGolla ELee DMorey MWaters RJenkins DATE 7/10/2018 05/10/2018 7/10/2018 7/12/2018 7/12/2018 OFFICE NRO/DEI/ICE/BC*
NRO/DCIP/D*
NRR/DIRS/D*
NRR/DRA/D*
RES/DE/D*
NAME IJung TMcGinty CMiller (HJones for)
MFranovich BThomas DATE 5/7/2018 7/10/2018 6/22/2018 5/20/2018 7/19/2018 OFFICE NRO/DEI/DD*
NRR/DORL/D*
NRR/DE/D*
OGC - NLO*
NRR/DE/D*
NAME RCaldwell JGiitter (TInverso for)
EBenner RWeisman EBenner DATE 7/16/2018 5/17/2018 7/16/2018 7/31/2018 7/31/2018
Contents A
Introduction...................................................................................................................... 1 B
Purpose........................................................................................................................... 1 B.1 Background.................................................................................................................... 2 B.1.1 Scope of I&C Modification....................................................................................... 3 B.1.2 Documentation Reviewed....................................................................................... 3 B.1.3 DI&C Review Scope................................................................................................ 3 B.2 Description of DI&C-ISG-06 Revision............................................................................. 4 C
Digital I&C LAR Review Processes................................................................................. 5 C.1 Tier 1, 2, and 3 Review Process Overview..................................................................... 7 C.2 Alternate Review Process Overview.............................................................................. 9 C.2.1 Details of License Amendment Request Content.................................................. 11 C.2.2 Licensee Prerequisites for the Alternate Review Process..................................... 12 C.3 Review Process............................................................................................................ 13 C.3.1 Pre-Application (Phase 0) Coordination Meeting(s).............................................. 13 C.3.2 Application, Review and Audit............................................................................... 15 C.3.2.1 Tier 1, 2, and 3 Review Process.................................................................... 15 C.3.2.2 Alternate Review Process.............................................................................. 17 C.3.3 Post-License Amendment Issuance...................................................................... 18 D
Review Areas for the License Amendment Process...................................................... 18 D.1 Plant System Description............................................................................................. 19 D.1.1 Information To Be Provided................................................................................... 19 D.1.2 Evaluation.............................................................................................................. 19 D.2 System Architecture..................................................................................................... 20 D.2.1 Existing Architecture.............................................................................................. 20 D.2.1.1 Information To Be Provided........................................................................... 20 D.2.1.2 Evaluation...................................................................................................... 20 D.2.2 New System Architecture...................................................................................... 20 D.2.2.1 Information To Be Provided........................................................................... 20 D.2.2.2 Evaluation...................................................................................................... 23 D.2.3 New System Functions.......................................................................................... 24 D.2.3.1 Information To Be Provided........................................................................... 24 D.2.3.2 Evaluation...................................................................................................... 26 D.2.3.3 System Requirements Documentation........................................................... 26 D.2.4 Functional Allocation............................................................................................. 28 D.2.4.1 Information To Be Provided........................................................................... 28
DI&C-ISG-06, Draft Revision 2 Page ii of iv D.2.4.2 Evaluation...................................................................................................... 29 D.2.5 System Interfaces.................................................................................................. 29 D.2.5.1 Information To Be Provided........................................................................... 29 D.2.5.2 Evaluation...................................................................................................... 31 D.2.6 Fundamental Design Principles in the New Architecture....................................... 33 D.2.6.1 Information To Be Provided........................................................................... 33 D.2.6.2 Evaluation...................................................................................................... 34 D.3 Hardware Equipment Qualification............................................................................... 38 D.3.1 Information To Be Provided................................................................................... 38 D.3.2 Evaluation.............................................................................................................. 39 D.4 I&C System Development Processes........................................................................... 40 D.4.1 Information To Be Provided................................................................................... 40 D.4.2 Evaluation.............................................................................................................. 41 D.4.2.1 System and Software Development Activities................................................ 42 D.4.2.2 Project Management Processes.................................................................... 48 D.4.2.3 Software Quality Assurance Processes......................................................... 49 D.4.2.4 Software Verification and Validation Processes............................................. 50 D.4.2.5 Configuration Management Processes.......................................................... 51 D.5 Applying a Referenced Topical Report Safety Evaluation............................................ 52 D.5.1 Information To Be Provided................................................................................... 52 D.5.1.1 Addressing Platform Changes after Approval of a Topical Report................. 52 D.5.1.2 Resolution of Topical Report Plant-Specific Action Items.............................. 52 D.5.2 Evaluation.............................................................................................................. 53 D.6 Compliance/Conformance Matrix for IEEE Standards 603-1991 and 7-4.3.2-2003..... 53 D.7 Technical Specifications............................................................................................... 56 D.7.1 Information To Be Provided................................................................................... 56 D.7.2 Evaluation.............................................................................................................. 57 D.7.2.1 Technical Specifications................................................................................. 57 D.7.2.2 Setpoint Changes........................................................................................... 57 D.8 Secure Development and Operational Environment.................................................... 58 D.8.1 Information To Be Provided................................................................................... 58 D.8.2 Evaluation.............................................................................................................. 58 D.9 Other Review Guidance for Tier 1, 2, and 3 Reviews................................................... 59 D.9.1 Software Requirements Specification................................................................... 59 D.9.1.1 Information To Be Provided........................................................................... 59 D.9.1.2 Evaluation...................................................................................................... 59
DI&C-ISG-06, Draft Revision 2 Page iii of iv D.9.2 Software Design Specification............................................................................... 60 D.9.2.1 Information To Be Provided........................................................................... 60 D.9.2.2 Evaluation...................................................................................................... 60 D.9.3 Changes to Referenced Platform Design.............................................................. 60 D.9.3.1 Information To Be Provided........................................................................... 60 D.9.3.2 Evaluation...................................................................................................... 61 D.9.4 Software Safety Analysis....................................................................................... 61 D.9.4.1 Information To Be Provided........................................................................... 61 D.9.4.2 Evaluation...................................................................................................... 61 D.9.5 Configuration Management Activities.................................................................... 61 D.9.5.1 Information To Be Provided........................................................................... 61 D.9.5.2 Evaluation...................................................................................................... 61 D.9.6 Testing Activities................................................................................................... 61 D.9.6.1 Information To Be Provided........................................................................... 61 D.9.6.2 Evaluation...................................................................................................... 62 D.9.7 System IntegrityTime Response/Deterministic Performance............................. 62 D.9.7.1 Information To Be Provided........................................................................... 62 D.9.7.2 Evaluation...................................................................................................... 62 D.9.8 Platform and System-Level Failure Modes........................................................... 63 D.9.8.1 Information To Be Provided........................................................................... 63 D.9.8.2 Evaluation...................................................................................................... 63 D.9.9 Qualification of Commercial Computers................................................................ 63 D.9.9.1 Information To Be Provided........................................................................... 63 D.9.9.2 Evaluation...................................................................................................... 64 D.9.10 Hardware Development Process........................................................................... 64 D.9.10.1 Information To Be Provided........................................................................... 64 D.9.10.2 Evaluation...................................................................................................... 65 Enclosure ASample Summary of Initial Public Meeting To Discuss Plans To Request NRC Approval in Support of a Digital I&C Modification License Amendment Request...................... A.1 Enclosure BInformation Provided in Support of a License Amendment Request for a Digital I&C Modification......................................................................................................................... B.1 Enclosure CSample Safety Evaluation Table of Contents for a Digital I&C License Amendment............................................................................................................................... C.1
DI&C-ISG-06, Draft Revision 2 Page iv of iv List of Figures Figure B.1 Structure of DI&C-ISG-06........................................................................................... 5 Figure C.1 DI&C Licensing Process and Post-License Amendment Issuance Process for Tiers 1, 2, and 3.................................................................................................................. 8 Figure C.2 DI&C Licensing Process and Post-License Amendment Issuance Process for Alternate Review...................................................................................................... 12 List of Tables Table D.1 IEEE Standards 603-1991 and 7-4.3.2-2003 Compliance/Conformance Table........ 54
A Introduction This interim staff guidance (ISG) defines the licensing process used to support the review of license amendment requests (LARs) associated with safety-related digital instrumentation and control (DI&C) equipment modifications in operating plants and in new plants once they become operational. This guidance is consistent with the U.S. Nuclear Regulatory Commissions (NRCs) policy on DI&C equipment and is not intended to be a substitute for NRC regulations.
This ISG provides guidance for activities performed before LAR submittal and during LAR review. The NRC staff uses the process described in this ISG to evaluate compliance with NRC regulations.
The purpose of NRC review activities is to evaluate the following for compliance with Federal regulations:
facility and equipment proposed use of the equipment including human factors engineering considerations processes performed for development life cycle phases NRC staff reviews are not intended to include evaluation of all aspects of I&C system design and implementation. The review scope should be of sufficient detail to allow the reviewer to conclude that the proposed equipment modification complies with applicable regulations.
Throughout this ISG, the criteria of Institute of Electrical and Electronics Engineers (IEEE)
Standard (Std) 603-1991, IEEE Standard Criteria for Safety Systems for Nuclear Power Generating Stations, and IEEE Std 7-4.3.2-2003, IEEE Standard Criteria for Programmable Digital Devices in Safety Systems of Nuclear Power Generating Stations, as endorsed by Regulatory Guide (RG) 1.152, Criteria for Use of Computers in Safety Systems of Nuclear Power Plants, are used to perform the review of the proposed DI&C equipment modification.
The staff should use these criteria to review the proposed DI&C equipment design in accordance with applicable regulatory requirements and the plants licensing basis.
Review of DI&C equipment modifications should include an assessment of the acceptability of system development life cycle activities, including the expected level of licensee involvement and oversight of the plant modification. While process is important, it is not a substitute for a review of the design of the system architecture, the human-system interfaces, and hardware and software architectures to determine if the four fundamental design principles of redundancy, independence, deterministic behavior (i.e., predictability and repeatability), and defense-in-depth and diversity are met to ensure the design provides adequate safety.
B Purpose This ISG provides guidance for the NRC staffs review of LARs supporting installation of DI&C equipment in accordance with licensing processes defined in Office of Nuclear Reactor Regulation (NRR) Office Instruction LIC-101, License Amendment Review Procedures, Revision 5 (Agencywide Documents Access and Management System (ADAMS) Accession No. ML16061A451). This ISG identifies information the NRC staff should review for DI&C equipment.
DI&C-ISG-06, Draft Revision 2 Page 2 of 66 This ISG should also be used in conjunction with NRR Office Instruction LIC-109, Acceptance Review Procedures, Revision 2 (ADAMS Accession No. ML16144A521), to determine whether the application contains sufficient information for NRC staff review. This ISG is also designed to be used with the NRCs review and approval process for topical reports, defined in NRR Office Instruction LIC-500, Topical Report Process, Revision 6 (ADAMS Accession No. ML18016A217). Where a licensee references (i.e., bases their design on) an NRC-approved platform topical report, the NRC staff should be able to, where appropriate, limit its review to assessing whether the application of the DI&C modification conforms to the topical report approval. Because this ISG was developed on the basis of established guidance, it is designed to work in concert with that guidance. As a result, this ISG references other guidance documents for review criteria.
The staff should ensure that the review is conducted according to the latest revision of these NRR Office Instructions. In the event that the guidance in this ISG conflicts with the guidance found in one of the NRR Office Instructions, the guidance in the latest revision of the Office Instructions should be used.
B.1 Background This ISG provides two processes for submittal and performance of a DI&C LAR review: (1) the Tier 1, 2, and 3 Review Process,1 and (2) the Alternate Review Process, both of which are described in Section C. The NRC staff evaluates proposed DI&C equipment to ensure that equipment meets regulatory requirements. These evaluations use the guidance in NUREG-0800, Standard Review Plan for the Review of Safety Analysis Reports for Nuclear Power Plants: LWR Edition (SRP), Chapter 7, Instrumentation and Controls, and other associated guidance. When a license amendment is submitted, under 10 CFR 50.90 licensees must fully describe the changes desired. Thus, licensees are obligated to describe the functions of I&C equipment identified in the Final Safety Analysis Report (FSAR), as updated, and the equipment that implements the functions. Additionally, licensees must identify those parts of the licensing basis being updated as a result of the proposed change.
The NRC staff review includes evaluating documentation of plans and processes that support system development activities and their outcomes (e.g., life cycle phase products, test results) to support a staff conclusion on whether system operation is acceptable.
SRP Appendix 7.0-A, Review Process for Digital Instrumentation and Control Systems, and Branch Technical Position (BTP) 7-14, Guidance on Software Reviews for Digital Computer-Based Instrumentation and Control Systems, guide the NRC staff in reviewing digital systems in support of safety evaluations. For reviews using the Alternate Review Process, this ISG provides additional guidance for performing early-stage reviews of digital safety-related systems in support of safety evaluations. The NRC staff reviews the system design and development process to support a determination that the design meets regulatory requirements and that, in safety-related applications in nuclear power plants, the process is of sufficiently high quality to produce systems and software suitable for use.
1 The Tier 1, 2, and 3 terminology used in this ISG is unique to DI&C-ISG-06. The terminology in this ISG does not involve the categories of information in a Design Control Document defined in 10 CFR Part 52 and is not otherwise connected to the 10 CFR Part 52 terms Tier 1 and Tier 2 used for those Part 52 categories.
DI&C-ISG-06, Draft Revision 2 Page 3 of 66 B.1.1 Scope of I&C Modification The licensee, with feedback from the NRC staff through the pre-application (Phase 0) coordination meeting(s), will develop and docket the information necessary to support the safety evaluation of the modification or new installation. This process applies to a range of modifications: from component(s) through partial, complete, or multiple systems.
Additionally, the NRC staff recognizes that licensees may use NRC-approved DI&C platform topical reports in different ways. The NRC-approved topical reports can be applied within the envelope of their generic approval or with deviations to suit the plant-specific application, provided that a licensee justifies the deviation as proposed for implementation at its facility.
Licensees can also propose to use a platform for which there is no generic approval.
B.1.2 Documentation Reviewed The NRC staff should review the information necessary to make a safety determination using the review criteria found in SRP Chapter 7. It is the responsibility of the licensee to ensure that the documentation provided demonstrates regulatory compliance for the safety-related system.
The design information submitted to the NRC for review should have passed the licensees design verification process prior to its submission.
Documentation to support NRC safety evaluation activities should be submitted to the NRC on the licensees docket. Confirmatory information for docketed material and other background information should be made available to the NRC staff for review and audit activities. Actual document submittals are expected to be unique for each DI&C project.
Enclosure B of this ISG provides a template that may be used to determine the information to be provided in support of a LAR. The NRC staff is expected to determine the document submittal status, submittal timing, and document audit availability for each applicable item in Enclosure B during the acceptance review period.
Some documents associated with software development are expected to be revised as system development activities progress. These are sometimes referred to as living documents.
During the acceptance review period, it should be decided whether a version of the document should be submitted to the NRC and when (i.e., in what phase) to submit it. It is normally not necessary for licensees to submit each version of these living documents to support the safety evaluation. Each living document should contain sufficient information to demonstrate compliance with applicable regulatory requirements. In some cases, it may also be necessary to provide access to current versions of a living document to support audit activities.
B.1.3 DI&C Review Scope Consistent with LIC-101, the NRC staffs review of an LAR will be limited to the scope of the DI&C modification. During the review, the staff will create a draft safety evaluation that identifies where additional information is needed to support the evaluation. Requests for additional information (RAIs) should have a clear nexus to information required to make a safety determination regarding the DI&C modification. The NRC staff reviews the information necessary to make this safety determination using the review criteria found in SRP Chapter 7, and using either the Tier 1, 2, and 3 Review Process or the Alternate Review Process described in Section C of this ISG. The review will include any impact on other systems that have an interface with the system under review.
DI&C-ISG-06, Draft Revision 2 Page 4 of 66 The NRC I&C staff does not review the DI&C modification for compliance with Title 10 of the Code of Federal Regulations (10 CFR) 73.54, Protection of digital computer and communication systems and networks. However, the I&C staff should review any cyber security design features included as part of a safety system for the purposes of complying with 10 CFR 73.54 to ensure that their inclusion does not adversely affect the reliable performance of the safety function.
For industry standards endorsed by NRC guidance, the staff should review the design for conformance with the changes and exceptions in endorsing RGs to determine if the plant proposed licensing basis criteria are met.
B.1.4 Review Areas Outside the Scope of this ISG Some DI&C equipment modifications may involve human factors engineering (HFE) considerations (e.g., HFE analyses and design processes). In these cases, an HFE safety evaluation should be performed in accordance with SRP Chapter 18, Human Factors Engineering, NUREG-0711, Human Factors Engineering Program Review Model and NUREG-1764, Guidance for the Review of Changes to Human Actions, with close coordination with the I&C evaluation under Chapter 7.
The modification described in the LAR may also impact other review areas. The NRC staff should review the information necessary to make a safety determination using the review criteria found in the SRP for all relevant review areas.
B.2 Description of DI&C-ISG-06 Revision This revision to DI&C-ISG-06 incorporates lessons learned from DI&C LAR reviews that used the previous revision of this ISG. The ISG was reorganized to enhance clarity, and the Tier 1, 2, and 3 Review Process has been streamlined to reduce the amount of docketed material, while increasing the focus on the information needed to reach a safety determination. This revision also provides an Alternate Review Process that may be used if the NRC staff decision of whether to issue or deny the license amendment is to be completed earlier (i.e., before completion of detailed design, implementation, or testing).
Figure B.1 illustrates the structure of this ISG in relation to these review processes. Figure B.1 includes placeholders to maintain alignment as a visual aid to show which sections are common to both the Tier 1, 2, and 3 Review Process and the Alternate Review Process, and which sections are unique to one or the other.
Revision 2 of this ISG is intended to supersede Revision 1; however, on-going reviews may continue to use Revision 1.
DI&C-ISG-06, Draft Revision 2 Page 5 of 66 Figure B.1 Structure of DI&C-ISG-06 C Digital I&C LAR Review Processes NUREG-0800 provides guidance to the NRC staff for performing safety reviews of LARs submitted under 10 CFR 50.90, Application for amendment of license, construction permit, or early site permit. This ISG assumes use of the RGs and industry standards in SRP Table 7-1, Section C.3 describes how the two review processes described in Sections C.1 and C.2 are applied to the review of DI&C modifications.
Section C Digital I&C Review Processes Section D.1 Plant System Description Section D.2 System Architecture Section D.3 Hardware Equipment Qualification Section D.4 I&C System Development Processes Section D.5 Applying a Referenced TR Safety Evaluation Section D.6 Compliance/Conformance Matrix for IEEE Stds 603-1991 and 7-4.3.2-2003 Section D.7 Technical Specifications Section D.8 Secure Development and Operational Environment Section C.2 Alternate Review Process Overview Section C.1 Tier 1, 2, and 3 Review Process Overview Section C.1 refers to the review guidance described in Sections D.1 through D.3, and D.5 through D.9 Section C.2 refers to the review guidance described in Sections D.1 through D.8 Section A - Introduction Section B - Purpose Section D.1 Plant System Description Section D.5 Applying a Referenced TR Safety Evaluation Section D.6 Compliance/Conformance Matrix for IEEE Stds 603-1991 and 7-4.3.2-2003 Section D.7 Technical Specifications Section D.8 Secure Development and Operational Environment Section D.9 Other Review Guidance for Tier 1, 2, and 3 Reviews Section D.2 System Architecture Section D.3 Hardware Equipment Qualification
DI&C-ISG-06, Draft Revision 2 Page 6 of 66 Regulatory Requirements, Acceptance Criteria, and Guidelines for Instrumentation and Control Systems Important to Safety. The staff should use the most current revision of these guidance documents and the most recently endorsed edition of these standards or the revisions and editions agreed upon during the pre-application (Phase 0) coordination meeting(s).
Previous licensing actions are those with a similar change and regulatory basis. Searching for, identifying, and using previous reviews in the review process maximizes staff efficiency, minimizes requests for additional information, and ensures consistency of licensing actions.
However, approval of a digital system or component at one plant does not necessarily serve as the basis for approving the same system or component at another plant. Each LAR is a plant-specific licensing action.
Based on proposed system changes, the reviewer should determine whether any regulatory criteria from the SRP, documented in Chapter 7.1, Instrumentation and ControlsIntroduction, and Table 7.1, should apply in addition to that identified in the LAR. The criteria should be used as appropriate based on the scope of the modification.
This ISG describes two processes for evaluating DI&C LARs: (1) the Tier 1, 2, and 3 Review Process, and (2) the Alternate Review Process. Section C.1 provides the review process for Tiers 1, 2, and 3. Under the Tier 1, 2, and 3 Review Process, the NRC staff decides whether to issue or deny the license amendment after the factory acceptance testing (FAT) is completed and the results have been evaluated.
For the Tier 1, 2, and 3 Review Process, acceptability of DI&C platform and application software2 for safety system functions is based on the following:
- a. determination that acceptable plans were prepared to control software development activities
- b. information showing that the plans were followed in an acceptable software life cycle
- c. information showing that the process produced acceptable design outputs In Enclosure B of this ISG, Columns 1, 2, and 3 (for the Tier 1, 2, and 3 processes, respectively) provide a template that may be used when the NRC staff decides whether to issue or deny the license amendment in the late stages of design and development after completion of FAT. This method involves a two-phase submittal to allow licensing review activities to be performed in parallel with the design implementation and test activities of the software development process.
Section C.2 describes the Alternate Review Process. Under the Alternate Review Process:
- a. the NRC staff decides whether to issue or deny the license amendment after the system design (see Section C.2.1) is completed and evaluated
- b. system development activities will continue during LAR review and after NRC staff decides whether to issue or deny the license amendment, in compliance with specific license conditions
- c. the LAR references (i.e., is based on) an NRC-approved DI&C platform topical report 2
Software refers to the programs used to direct operations of a programmable digital device. Examples include computer programs and logic for programmable hardware devices and data pertaining to its operation. (From IEEE Std 7-4.3.2-2016). This includes logic developed using hardware description languages.
DI&C-ISG-06, Draft Revision 2 Page 7 of 66 For the Alternate Review Process, acceptability of the DI&C platform is based on the tiered review process (see Section C.1) as documented in the applicable topical report. Acceptability of the system application is based on the following:
- a. the I&C system development processes, as summarized in accordance with Section D.4,
- b. the licensees oversight and evaluation of the vendors I&C system development process activities, and
- c. the regulatory commitments the licensee makes to confirm that the vendor produces life cycle outputs that meet the associated life cycle design requirements (e.g. System Requirement Specification).3 In Enclosure B, Column AR (for Alternate Review Process) may be used if the NRC staff decision of whether to issue or deny the license amendment is to be completed before detailed design, implementation, and/or testing. The information docketed can be derived from a variety of documents including conceptual design, system requirements, hardware requirements, software requirements, and human-system interface requirements.
For both the Tier 1, 2, and 3 Review Process, and the Alternate Review Process, the staff reviews information related to the application system development. For the Alternate Review Process, Section D.4 focuses on the application system development processes, since the NRC staff decides whether to issue or deny the license amendment before system development is completed. For the Tiers 1, 2, and 3 Review Process, Section D.9 focuses on the evaluation of design outputs and system validation test results, which should be available during later stages of the application system development. The NRC staff audits the documentation and development products that are referenced in the LAR. Enclosure B provides guidance on the content of the LAR.
C.1 Tier 1, 2, and 3 Review Process Overview Because DI&C plant modifications represent a significant licensee resource commitment, a phased approach is appropriate. In this approach, the NRC staff initially reviews critical, fundamental system information before reviewing subsequent DI&C system development and testing information. Therefore, the NRC staff encourages the use of public meetings before the submittal of the LAR to discuss issues regarding the system development. The purpose of this activity is to reduce regulatory uncertainty through the early resolution of issues that may challenge the staffs ability to assess the systems compliance with NRC regulations. The NRC staff recognizes that for some projects, certain information may not be available upon initial submittal of the LAR; thus, information sufficient to address all review topics is not expected to be submitted until later in the evaluation period. The licensee and the NRC discuss the timing of specific information availability in the Phase 0 meetings and establish the timing during the acceptance review period.
3 The phrase design requirements and the like, as used here, do not refer to NRC regulatory requirements, but to system or component design or operating characteristics upon which the licensee relies to accomplish the stated system or component safety functions. Throughout this ISG, context will indicate whether requirements are NRC regulatory requirements or design requirements as explained in this footnote.
DI&C-ISG-06, Draft Revision 2 Page 8 of 66 Figure C.1 below is a flowchart of the overall review process. This figure illustrates the various review phases, discussed in Sections C.3.
Figure C.1 DI&C Licensing Process and Post-License Amendment Issuance Process for Tiers 1, 2, and 3 The NRC staff recognizes that licensees can use and apply an NRC-approved topical report for an I&C platform in different ways. Therefore, the NRC staff should consider applications to be within one of the following tiers of review.
Tier 1 Tier 1 applies to license amendments proposing to reference an NRC-approved topical report (on a DI&C platform or component(s) including hardware, software, and developmental tools) in full conformance with its approval. A Tier 1 review would rely on the previous review of the
DI&C-ISG-06, Draft Revision 2 Page 9 of 66 referenced DI&C platform topical report. In Enclosure B, the Tier 1 column (1) shows the information that a licensee would typically submit in support of a Tier 1 review. This list would not include those documents already reviewed and approved by the NRC staff. See Section D.5 for applying an NRC-approved topical report safety evaluation.
Tier 2 Tier 2 applies to license amendments proposing to reference an NRC-approved topical report (on a DI&C platform or component(s) including hardware, software, and developmental tools) with deviations to suit the specific application. Deviations could include, for example, a revised software development process or new hardware. A licensee assessment of deviations from the approved topical report should be part of the LAR. Typically, an application citing licensing experience from another plants previous approval would also be considered a Tier 2 review.
However, this determination depends on the similarities of the application. In Enclosure B, the Tier 2 column (2) shows the information that a licensee would typically submit in support of a Tier 2 review. However, the changes from the previously approved topical report, as identified in the Phase 0 meetings, should determine the information provided. Tier 2 safety evaluations generally include Tier 1 review scope and review of any deviations from the approved safety evaluation or topical report.
Tier 3 Tier 3 applies to license amendments proposing to use a new DI&C platform or component(s) that the NRC has not previously approved via a DI&C platform topical report. A Tier 3 review will necessitate a complete review of the DI&C platform concurrent with the LAR. In Enclosure B, the Tier 3 column (3) shows the information that a licensee would typically submit in support of a Tier 3 review. NRC staff Tier 3 evaluations generally combine the scope of both a Tier 1 review and topical report review. The typical review of a topical report includes hardware, software, developmental tools, and associated developmental methods (e.g., application restrictions and integration methods).
These tier labels are a general guide for defining the scope or complexity of a review. The tables in Enclosure B are examples of information to be provided for review, as explained throughout this ISG. A licensee may have different names for similar documents. Regardless of the titles of the documents submitted, the LAR should contain sufficient information to address the criteria discussed in Sections D.1 through D.3 and D.5 through D.9, as applicable to Tiers 1, 2, and 3. It is possible that the plant-specific application of a digital system may eliminate the need for review of certain listed documents and necessitate the inclusion of other unlisted documents.
C.2 Alternate Review Process Overview The NRC staff recognizes that there are different approaches available to licensees regarding use and application of NRC-approved topical reports. Because DI&C modifications represent a significant licensee resource commitment, an alternate approach is provided for review and approval at an earlier stage in the overall system life cycle.
The Alternate Review Process provides an alternative to the Tier 1, 2, and 3 Review Process for reaching a safety determination of a proposed plant modification. The Tier 1, 2, and 3 Review Process includes NRC evaluation of software design, implementation, and testing. The Alternate Review Process is based on detailed system design information (see Section C.2.1),
DI&C-ISG-06, Draft Revision 2 Page 10 of 66 additional design information as described in Section D.2, and application planning and processes as described in Section D.4. For the NRC staff to reach a safety determination using the Alternate Review Process, the licensee is expected to provide the necessary information at the time of LAR submission.
For this alternate approach, the licensee provides critical, fundamental system information to the NRC staff for review and approval before taking subsequent steps in the DI&C hardware and software development process. As in the process described in Section C.1 above, the NRC staff encourages the use of public meetings before submittal of the LAR to discuss issues regarding the system development. The licensee recognizes that there is a licensee risk that the system design submitted and approved by NRC may have implementation challenges that necessitate a modification. The modification could require NRC review and approval of a subsequent LAR, or could be completed without NRC approval through the 10 CFR 50.59 process, which is subject to NRC inspection.
The Alternate Review Process provides a single-step license amendment submittal process for licensee use. Like Tiers 1 and 2, the Alternate Review Process is applicable to license amendments proposing to reference an NRC-approved topical report. In Enclosure B, the Alternate Review Process column (labeled AR) lists the information that the licensee typically should submit in support of an Alternate Review Process review. See Section D.5 for applying a topical report safety evaluation previously approved by the NRC.
The NRC staff encourages the use of pre-application coordination meetings before submittal of the LAR to discuss issues regarding the system development. The early meetings help ensure that the licensee will meet regulatory requirements early in the process. During pre-application coordination meetings, licensee and NRC staff discuss any design features that may challenge the NRC staffs ability to assess the systems compliance with NRC regulations.
Unlike the Tier 1, 2, and 3 Review Process, the Alternate Review Process does not include provisions for Phase 2 document submittals. Accordingly, the reviewer should verify that all information identified in Enclosure B is included as part of the application submittal. A safety evaluation conducted for an Alternate Review Process submittal will base its safety conclusions on information provided in accordance with Enclosure B and any supplemental information.
The staff should evaluate key licensee regulatory commitments (see Section C.2.2) related to the design, implementation, and testing activities as potential license conditions. Such potential license conditions should: (1) address issues of high safety or regulatory significance, (2) be worded such that the meaning is clear and not open to different interpretations, and (3) explicitly define the conditions for satisfaction of the condition. Such license conditions should (1) not be open ended, (2) not address voluntary requests, or (3) require NRC action to complete. If the NRC staff determines that a regulatory commitment should be a license condition, the staff should request the appropriate license changes as part of the docketed submittal. For those regulatory commitments that dont warrant a license condition but are relied on by the staff as an element of the staffs approval of the proposed amendment, the staffs safety evaluation can rely on the regulatory commitment if the commitment is subsequently incorporated into the FSAR. As part of the NRC oversight process, the NRC staff may perform one or more inspections to evaluate compliance with the license conditions associated with the license amendment.
DI&C-ISG-06, Draft Revision 2 Page 11 of 66 C.2.1 Details of License Amendment Request Content When the licensee elects to use the Alternate Review Process and the NRC accepts the LAR for review, the NRC staff will review the application planning and processes related to the detailed hardware and/or software design, implementation, and testing activities. The Alternate Review Process is based on the use of a topical report previously approved by the NRC and the topical report vendor is expected to develop the system.
The staff will review design information related to the site-specific configuration at a level that is sufficient to demonstrate compliance with the applicable regulations and associated guidance as described in the SRP. The NRC staff should credit the results of previous topical evaluations to the extent practicable to support its review of the information described in Figure B.1 (e.g.,
system architecture, equipment qualification). The NRC staff should examine plant specific action items in the topical approval to identify information that will be needed to demonstrate regulatory compliance. The staff should confirm that the licensee has addressed topical plant specific items, including items that the licensees identifies as regulatory commitments (e.g.,
detailed design, implementation, and integration activities) as described above.
The docketed LAR should contain information sufficient to demonstrate regulatory compliance.
The Alternate Review Process provides guidance for information to be included in an LAR. This information can be derived from a variety of concept, system requirement, hardware or software requirement, or design documents, each of which may be considered as providing sufficient system design information in the context of the Alternate Review Process. The level of information and detail in the LAR needed for demonstrating compliance with regulatory requirements may vary by design, configuration, and operational features that are unique to the proposed digital modification.
The NRC staff should verify that the licensee has demonstrated that the development life cycle outputs meet the specified design requirements. The LAR should describe the licensees Vendor Oversight Plan, which ensures that the vendor executes the project consistent with the LAR and the 2015 version of the American Society of Mechanical Engineers Standard Nuclear Quality Assurance (NQA)-1, Part II, Quality Assurance Requirements for Nuclear Facility Applications, Subpart 2.7, Quality Assurance Requirements for Computer Software for Nuclear Facility Applications.
The staff should use additional review guidance from relevant portions of SRP Chapter 7 to determine the level of design detail needed to address specific acceptance criteria in conjunction with the guidance in these sections. For example, Section D.2.2.1 states, in part, The LAR should demonstrate how any self-test portions of the service/test functions provide fault detection capabilities. Although this section of this ISG does not reference SRP Chapter 7, the reviewer may use additional review guidance related to self-test and self-diagnostics from SRP BTP 7-17, Guidance on Self-Test and Surveillance Test Provisions.
For the Alternate Review Process, the Enclosure B tables provide examples of information to be provided for review, as explained throughout this ISG. A licensee may have different names for similar documents. Regardless of the titles of the documents submitted, the LAR should contain sufficient information to address the criteria discussed in the applicable technical evaluation in Sections D.1 through D.8. It is possible that the plant-specific application of a digital system may depend on the use of other unlisted documents. The licensee and staff should identify and discuss these differences during the pre-application coordination meeting(s).
DI&C-ISG-06, Draft Revision 2 Page 12 of 66 Figure C.2 below is a flowchart of the overall Alternate Review Process. This figure illustrates the various stages of the review, discussed further in Sections C.3.
Figure C.2 DI&C Licensing Process and Post-License Amendment Issuance Process for Alternate Review C.2.2 Licensee Prerequisites for the Alternate Review Process To use the Alternate Review Process, the staff should verify the following items are addressed in the LAR:
- 1. A description of the licensees Vendor Oversight Plan. The plan ensures that the vendor executes the project consistent with: (1) the LAR and (2) the 2015 version of NQA-1, Part II, Subpart 2.7. The Vendor Oversight Plan helps ensure that the vendor will meet both the process and technical regulatory requirements. Vendor oversight is a series of interactions with the vendor and progresses throughout the entire system development
DI&C-ISG-06, Draft Revision 2 Page 13 of 66 life cycle. The plan should address the intended interactions between design, test, verification and validation (V&V), and quality assurance (QA) within the vendors organization.
- 2. A reference to an NRC Approved DI&C Topical Report. This reference should address the following aspects:
- a. The proposed DI&C modification should reference (i.e., be based on) an NRC-approved DI&C topical report. The NRC approved DI&C topical report is also referred to as the -A version.
- b. The proposed DI&C modification should be within the scope of the referenced topical reports applicability.
- c. The vendor of the NRC-approved topical report should commit to performing detailed software design, implementation, and testing.
- 3. Appropriate Licensee Regulatory Commitments in Consideration of Early NRC Staff Decision of Whether to Issue or Deny the License Amendment
- a. The LAR should include appropriate regulatory commitments to complete plant-specific actions that are included in the referenced topical report.
- b. The LAR should include appropriate regulatory commitments to complete life cycle activities under the licensees QA program. Note that these activities would be included in a Tier 1, 2, and 3 licensing review, but are not covered in the Alternate Review Process because they would take place after the NRC staff decides whether to issue or deny the license amendment.
C.3 Review Process C.3.1 Pre-Application (Phase 0) Coordination Meeting(s)
Before submittal of an LAR for a DI&C modification, it is beneficial to have an overall design concept that adequately addresses NRC regulatory requirements and policy on key issues. The NRC staff intends to use the pre-application (Phase 0) coordination meeting process to discuss with licensees how their proposed DI&C modification LAR will address the following:
- a. the appropriate review process (i.e., Tier 1, 2, and 3 Review Process or Alternate Review Process), and appropriate tier of review (if applicable) (see Sections C.1 and C.2);
- b. key design concepts, including the four fundamental design principles (see Section D.2.6);
- c. significant deviations from current guidance;
- d. significant deviations from the NRC-approved topical report;
- e. application of the selected system (platform) to the plant system (see Section D.5);
- f.
defining the portion of the plant system to be replaced and its impact on the plant, calibration, surveillance testing (and associated impacts on plant staff), and FSAR impacts;
- g. identification of the level of licensee involvement of the modification project, including the expected level of participation by licensee staff who are assigned responsibilities for oversight of vendor activities;
DI&C-ISG-06, Draft Revision 2 Page 14 of 66
- h. any tools proposed for providing NRC read-only access to licensee documents (e.g.,
SharePoint site);
- i.
establishment of an appropriate licensee living document schedule; and
- j.
any other unique or complex topics associated with the proposed design.
These pre-application coordination meetings are intended to be two-way discussions in which the licensee presents the concept, and the NRC staff provides feedback on the critical aspects of the proposed design that are likely to affect the NRC staffs evaluation. Before submitting an LAR, the staff should expect that the licensee has an overall design concept that adequately addresses NRC regulatory requirements and policy on each of the key issues.
Further, these discussions should include whether the licensee is proposing the use of an NRC-approved topical report. If an NRC-approved topical report is to be used, these discussions should include any changes the vendor has made (or will make as part of this project) to the platform after the NRC has reviewed and issued a safety evaluation on the NRC-approved topical report. These discussions should also include any planned deviations from staff positions, and specifics of the platform or application software processes. Licensees are encouraged to discuss topics from other review areas (e.g., how to use best-estimate evaluations with realistic assumptions or models and the impact on the uncertainties associated with the results).
These discussions should also address the level of licensee involvement in the plant modification project, including the licensees expectations of their staff who are assigned responsibility for oversight of vendor development, implementation and testing activities.
Having this discussion before a LAR is prepared ensures that the licensee takes into account impacts on the project schedule, translation and traceability of system requirements, current plant processes, technical specification surveillance, operating procedures, and maintenance and training activities.
These meetings should also address the schedule and scope of audits and potential inspections, which may be updated as the NRC staffs review progresses.
All proposed deviations from the submittal information guidance in Enclosure B should be discussed in the pre-application (Phase 0) coordination meeting(s). The pre-application (Phase 0) coordination meeting summary should document any associated common understandings.
Following each public meeting, the NRC staff should capture the topics discussed in a meeting summary. This summary should include a preliminary NRC staff understanding of the licensees concept (or those subparts of the overall concept discussed) and identify the areas significant to this preliminary assessment. The staff should include a discussion of the applicability of the review process selected (i.e., Tier 1, 2, and 3 Review Process or Alternate Review Process) is applicable for the proposed modification. If the Tier 1, 2, and 3 Review Process is selected, the staff should include a discussion of the tier applicability for the proposed modification. Enclosure A to this document presents an example of a meeting summary.
DI&C-ISG-06, Draft Revision 2 Page 15 of 66 C.3.2 Application, Review and Audit Once a licensee has a design that adequately addresses NRC criteria, the staff should expect the licensee to prepare and submit an LAR (see Enclosure B for information to be provided with the LAR).
The NRC staff should perform an acceptance review of the application in accordance with the NRR Office Instruction LIC-109 to determine whether the application contains sufficient information for NRC staff review. The staff should verify that the licensee has identified any design features and concepts that may affect the staffs preliminary assessment made during the pre-application (Phase 0) coordination meeting process. The NRC should document the acceptability of an application in a letter to the licensee.
Sections C.3.2.1 and C.3.2.2 further describe the LAR review process for the Tier 1, 2, and 3 Review Process, and the Alternate Review process, respectively.
C.3.2.1 Tier 1, 2, and 3 Review Process C.3.2.1.1 Initial Application (Phase 1)
To the extent possible, the LAR should address the criteria associated with the areas defined in Sections D.1 through D.3 and D.5 through D.9.
Some information may not be available upon initial application, and the review process may be more efficiently administered by beginning before that information is available. Therefore, a DI&C modification application may be found to be sufficient for review provided that a clear schedule for submission of omitted information is included. The staff will issue notice of the amendment and provide for an opportunity to request a hearing on it when complete information has been submitted. Proposed changes to the schedule in advance of any document due date should be discussed with the NRC staff, and the staffs agreement to such a change should be documented in a public meeting summary, or a stand-alone letter to the licensee.
As determined during both the Phase 0 meeting(s) and the review, the staff should verify that additional documents have been made available electronically for NRC information as requested by the NRC. Electronic documents can be established on a vendors shared site, to allow the NRC to audit the documents and to determine if these documents need to be submitted on the docket. Because the NRC staff must maintain information sufficient to support its safety evaluation, it may determine that certain documents or portions of documents need to be submitted on the docket under oath or affirmation.
During Phase 1, the NRC staff should draft the safety evaluation and issue RAIs for the information or clarifications necessary to finish the review of the docketed material. These activities should be conducted in accordance with NRR Office Instruction LIC-101. The NRC staff should also communicate those areas of review that, based on the available information, appear to be acceptable.
The staff should verify that the licensee has responded to the RAIs before the Phase 2 information is submitted. Although the NRC staff may have additional questions based on the responses to the Phase 1 RAIs, the staff should make sure that the licensee does not delay submission of the Phase 2 information.
DI&C-ISG-06, Draft Revision 2 Page 16 of 66 It is important that the NRC staff and the licensee communicate closely so that both parties remain cognizant of deliverables and due dates. During the review, the staff should have publicly-noticed periodic conference calls with the licensee to discuss staff questions. Following each call, the NRC staff should document the topics discussed in a meeting summary.
Questions raised by the staff can be kept in an open items list, along with the responses from the licensee. The open items list can contain information to track issues to closure. The staff may determine that some items and responses should be formalized into RAIs.
If necessary, the NRC staff should conduct one or more audits in accordance with NRR Office Instruction LIC-111, Regulatory Audits, (ADAMS Accession No. ML082900195). The NRC staff should be aware that some information may be in documentation available only at the licensees or vendors facility. The information examined in this manner should be documented in the audit report. The NRC project manager, in consultation with the licensee and NRC technical staff, should schedule the audit. If any of the audited information is relied upon to complete the SE, the NRC staff should request the licensee to submit the information on the docket under oath or affirmation.
C.3.2.1.2 Continued Review (Phase 2)
After responding to the Phase 1 RAIs, and with sufficient lead time to support the requested approval date, the staff should verify that the licensee has submitted a supplement containing sufficient information to address aspects of the review areas not submitted in the initial LAR or subsequent responses to RAIs (see Enclosure B for information to be submitted before the requested approval date). The NRC staff should expect the licensee to adhere to previously established submittal schedules.
During Phase 2, the NRC staff should continue the RAI process until the licensee has provided sufficient information for a decision to be made on the acceptability of the proposed digital modification. If necessary, during the Phase 2 process, the NRC staff should conduct one or more audits in accordance with NRR Office Instruction LIC-111.
Audits may cover information from both Phase 1 and Phase 2. Audits may result in more requests for information to be docketed. The NRC staff intends to perform the audits as early in the process as is reasonable. However, an effective and efficient audit process can only occur if the LAR and supplements are sufficiently detailed about the later phases of the system development life cycle.
Although the plans and other available information should be submitted as early as possible, certain documentation may be deferred based on the Phase 0 meeting discussions. All information must be submitted before the safety evaluation can be completed.
Phase 2 should conclude with the issuance of a safety evaluation documenting the approval or denial of the licensees proposed DI&C modification. While Figure C.1 contains post-license amendment issuance activities, the licensing process covered by this ISG ends when the NRC staff decides whether to issue or deny the license amendment.
Consistent with licensing review guidance, the staff should develop a safety evaluation that documents the basis for approval. The safety evaluation should document applicable regulatory requirements; the information provided by the licensee, including regulatory commitments; a summary of the staff evaluation; and the basis for the determination that the application meets applicable requlatory requirements. Since regulatory commitments made by a licensee in
DI&C-ISG-06, Draft Revision 2 Page 17 of 66 support of a license amendment request are neither legally binding nor under regulatory control, the staffs safety evaluation should not rely on such commitments as a basis for any part of the staffs approval of a proposed amendment. However, under certain conditions, the NRC staff may convert a regulatory commitment into a license condition based on the determination of its high safety or regulatory significance. If the NRC staff determines that a regulatory commitment should be converted into a license condition, the staff should request the appropriate license changes as part of the docketed submittal. Further, the LAR may propose to modify the FSAR to reflect certain information, and the staff may rely on such information since it will be under control of the change requirements in 10 CFR 50.59.
In addition, the staff should separately identify in the safety evaluation potential items for inspection as recommendations to help inform the focus of post-license amendment inspections. However, the potential items for inspection cannot be relied upon or be used as a safety basis for LAR approval. NRC headquarters staff should keep the NRC inspection staff aware of the LAR review scope, activities, and milestones.
C.3.2.2 Alternate Review Process The LAR should address the criteria associated with Sections D.1 through D.8. Along with the LAR, the submission should include the information necessary to support NRC review and be submitted on the docket under oath and affirmation. The documents will contain materials necessary to reference in the safety evaluation.
As determined during both the pre-application coordination meeting(s) and the review, the staff should verify that the licensee has made additional documents available electronically for NRC information as requested by the NRC. Electronic documents can be established on a vendors shared site to allow the NRC to audit the documents and to determine if these documents need to be submitted on the docket. Because the NRC staff must maintain information sufficient to support its safety evaluation, it may determine that certain documents or portions of documents need to be submitted on the docket under oath or affirmation. The NRC staff should not print or copy documents made viewable this way, in whole or in part.
It is important that the NRC staff and the licensee communicate closely so that both parties remain cognizant of deliverables and due dates. During the review, the staff should have publicly-noticed periodic conference calls with the licensee to discuss staff questions. Following each call, the NRC staff should document the topics discussed in a meeting summary.
Questions raised by the staff can be kept in an open items list, along with the responses from the licensee. The open items list can contain information to track issues to closure. The staff may determine that some items and responses should be formalized into RAIs The NRC staff should draft the safety evaluation and issue RAIs for the information or clarifications necessary to finish the review of the docketed material. These activities should be conducted in accordance with NRR Office Instruction LIC-101. The NRC staff should also communicate those areas of review that, based on the available information, appear to be acceptable.
If necessary, the NRC staff should conduct one or more audits in accordance with NRR Office Instruction LIC-111. The NRC staff should be aware that some information may be in documentation available only at the licensees or vendors facility. The information examined in this manner should be documented in the audit report. The NRC project manager, in consultation with the licensee and NRC technical staff, should schedule the audit. If any of the
DI&C-ISG-06, Draft Revision 2 Page 18 of 66 audited information is relied upon to complete the SE, the NRC staff should request the licensee to submit the information on the docket under oath or affirmation.
During the review of an LAR, certain items may be identified that apply to system configuration, testing, or operation that will be completed after the safety evaluation is issued. The NRC staff should identify such items separately in the safety evaluation as potential items for inspection to inform the focus of post-license amendment vendor and site inspections. However, the potential items for inspection cannot be relied upon or be used as a safety basis for LAR approval. NRC headquarters staff should keep the NRC inspection staff aware of the LAR review scope, activities, and milestones.
While Figure C.2 contains post-license amendment issuance activities, the licensing process covered by this ISG ends when the NRC staff decides whether to issue or deny the license amendment.
C.3.3 Post-License Amendment Issuance If the NRC staff determines to approve an LAR for a DI&C system, licensees may complete the design (in the case of the Alternate Review Process) and install the system. In doing so, licensees will implement associated procedural and technical specifications (TS) changes and complete startup testing. SRP Chapter 7.0,Section V, contains guidance for establishing inspections.
For the Alternate Review Process, NRC quality assurance and vendor inspection staff may inspect the software design and implementation activities prior to its transfer to the site, in accordance with applicable inspection procedures. Section D.4.2.1.9 describes I&C system testing.
The NRC staff may inspect the system testing, startup testing, and other documents in accordance with applicable inspection guidance (e.g., Inspection Procedure 52003, Digital Instrumentation and Control Modification Inspection.). NRC technical staff may need to advise and assist NRC inspection staff as appropriate to verify the development, implementation, and/or installation phases of the approved digital modification.
Upon approval of an LAR, changes are controlled and implemented by licensee programs which, in turn, are governed by 10 CFR Part 50, Domestic Licensing of Production and Utilization Facilities, Appendix B, Quality Assurance Criteria for Nuclear Power Plants and Fuel Reprocessing Plants, and other regulatory requirements. The regulation in 10 CFR 50.59, Changes, tests and experiments, governs the need for prior NRC review and approval of changes to the facility and procedures as described in the FSAR.
D Review Areas for the License Amendment Process As noted in Figure B.1 and Enclosure B, Sections D.1 through D.3 and D.5 through D.9 are applicable to Tiers 1, 2, and 3, whereas Sections D.1 through D.8 are applicable to the Alternate Review Process.
DI&C-ISG-06, Draft Revision 2 Page 19 of 66 D.1 Plant System Description Reviewing the existing plant system description allows the reviewer to understand how the components of the existing plant system interact to accomplish the design function. The plant system description should include all affected plant equipment and the interfaces with operations and maintenance. Depending on the plant modification, the plant system description could consist of one or more systems, one or more subsystems, and/or one or more components. This description should be from an integrated hardware and software perspective to develop a clear understanding of the overall system. Understanding the existing plant system provides a solid foundation for the subsequent reviews and evaluations against the acceptance criteria.
D.1.1 Information To Be Provided The licensees submittal should provide documentation (through text and drawings) to describe the affected plant equipment. The documentation should describe the design basis and operational, maintenance, calibration, surveillance, and engineering functions implemented.
The licensees submittal should provide documentation and descriptions to allow the reviewer to identify the digital equipment being used, how the digital equipment functions, how the various digital equipment items are interconnected, and any software in the system. The digital equipment should be identified to the revision level for both hardware and platform software (see Section D.5). In cases where the NRC has evaluated the digital equipment proposed, the NRC staff should verify that the licensee refers to the description and evaluation, including any available ADAMS accession numbers. The staff should verify that the licensee has identified all changes or deviations from the previously evaluated digital equipment. The staff should evaluate all changes to previously approved aspects (see Section D.5).
The documentation and description should be on two levels. First, the individual channels or divisions should be described, including the signal flows between the various digital equipment items. Second, the overall system should be described, with particular emphasis on additional hardware items not included in the description of the channels or divisions, such as voters, communications with workstations or non-safety-related systems, bypass functions/switches, and diverse actuation systems (DASs).
The acceptability of a safety system is based on the systems ability to perform design basis functions (e.g., trip on high level, display of proper indications) and the systems conformance to regulatory requirements (e.g., independence). This information should be contained in the system design description and in safety analysis reports to demonstrate that the design meets the requirements.
D.1.2 Evaluation The reviewer should determine if the LAR information presents a comprehensive explanation of the system. From this, the reviewer should determine the scope of review and identify any constraints on the approval of the system. The NRCs understanding of the plant system and digital equipment should be documented in the safety evaluation to explain system operation and to support the technical evaluations of other sections.
DI&C-ISG-06, Draft Revision 2 Page 20 of 66 D.2 System Architecture D.2.1 Existing Architecture D.2.1.1 Information To Be Provided The licensees submittal should provide documentation to describe the physical and functional architecture of the existing system through text and diagrams (e.g., functional/architecture block diagrams and functional logic diagrams). This description should include the following:
- a. system design functions
- b. service/test functions
- c. provisions for separation and independence within the system (e.g., channels, trains, isolation)
- d. connections and internal interfaces within the safety system, including cross-divisional interfaces and interfaces between components
- e. connections to human-system interfaces
- f.
connections between safety-related systems
- g. connections between safety-related and non-safety-related systems and identification of signal and data isolation devices
- h. temporary connections (e.g., for maintenance workstations)
- i.
interface with supporting systems (e.g., electrical power supply)
- j.
physical location(s) of system equipment in the plant This description should also identify which portion(s) of the system are being replaced. (While system design functions are listed here, Section D.2.3.1 describes their design bases.)
D.2.1.2 Evaluation The reviewer should understand that the changes to the replacement system may result in changes to existing input and output interfaces with the plant and interfaces with control room displays, indicators, and controls. This understanding should include a review of the systems role in meeting post-accident monitoring requirements.
The NRCs understanding of the existing system architecture should be documented in the reviewers safety evaluation to support the technical evaluations of other sections.
D.2.2 New System Architecture D.2.2.1 Information To Be Provided The LAR should describe and illustrate the new plant system architecture. Changes to the existing architecture should be clearly designated and described, including the reason for the changes. This description provides a basis for discussion of the fundamental design principles in Section D.2.6.
DI&C-ISG-06, Draft Revision 2 Page 21 of 66 The LAR should provide documentation to describe the physical and functional architecture of the replacement digital equipment through text and diagrams (e.g., functional/architecture block diagrams and functional logic diagrams). Sufficient information should be provided to enable the staff to understand the changes needed for installation of this new digital equipment. The information should reflect the new plant system architecture and design. The information should define how the changes affect the existing plant (e.g., architectural restrictions on size, location, cooling, or power supplies).
The LAR should describe the new digital equipment, reflecting the final plant system, installed in the plant and should clearly describe any changes made to items (a) to (j) in Section D.2.1.1.
The description should include changes resulting from the use of the new digital equipment and any other changes made under other processes that have the potential to affect the safety function of the new digital equipment (e.g., eliminating single-point vulnerabilities within divisions, adding redundant power supplies). The LAR should document any restrictions on the new system architecture based on physical plant location, such as size, cooling, or power supply.
The LAR should identify the digital equipment vendor and the NRC-approved topical report and revision based on the approving safety evaluation.
The LAR should describe all design functions and service/test functions. Sections D.2.3.1 and D.2.3.2 describe how the staff should evaluate these functions. The licensees submittal should describe each design function that is performed by the portion(s) of the system being replaced.
All new design functions proposed in the LAR should also be described. These design functions are safety functions implemented in the application-specific software, programmable logic, hardware (e.g., hardware voters and relays), credited manual operator actions (MOAs), or some combination of these.
The LAR should describe service/test functions together with the design functions. Service/test functions are digital equipment features to support the design functions. The service/test functions, unlike the design functions, are not directly related to the performance of safety functions, but relate to specific activities of the digital equipment, including the functions necessary for configuration, validation, operation, periodic testing, maintenance, incorporation of design modifications, self-test, self-diagnostics, and maintaining a secure operational environment (SOE). The topical report may have described the service/test functions. These functions may also be implemented in application software, which the topical report may not have described. Although any portions of the service/test functions that remain unchanged from the topical report should not require repeating a prior evaluation, these portions should be identified in the LAR.
The LAR should demonstrate how any self-test portions of the service/test functions provide fault detection capabilities and thus conform with IEEE Std 7-4.3.2-2003, Clauses 5.5.2 and 5.5.3, consistent with IEEE Std 603-1991, Clause 5.7. The discussion of self-tests and self-diagnostics should demonstrate compliance to existing applicable TS and any proposed change to TS.
The LAR should demonstrate how the design detects malfunctions. The following are examples of issues that could be applicable to the replacement design:
- a. How the application interfaces with and uses the self-test and self-diagnostic features defined in the NRC-approved topical report and evaluated in the safety evaluation. This
DI&C-ISG-06, Draft Revision 2 Page 22 of 66 should include a discussion of the malfunction detection coverage considering the combination of TS surveillances and the automated features.
- b. How the design implements communications messages. This should include a description of the types and purposes of each message, the format of each message, the response of the receiver to invalid data, methods used to detect repeated messages, alarming on malfunctions, along with the use of each message (e.g., voting, bypass).
Error detection means provided in communications messaging and processing (see DI&C-ISG-04, Revision 1, Highly Integrated Control RoomsCommunications Issues, Section 1, Item 12, dated March 6, 2009 (ADAMS Accession No. ML083310185)) apply to communications messages used by safety functions. This section of the LAR should demonstrate conformance to the DI&C-ISG-04 assessment containing this data.
- c. How the design prevents software failures from affecting the watchdog timer timing and timeout. This should address hardware and software malfunction coverage for the watchdog timers, including a description of the annunciation and the effects on the plant during and after any reset function initiated by an expiring watchdog timer.
- d. Treatment and detection of malfunctions in the system inputs, including sensors and transmitters, in the system logic including internal voters within the safety system or voters external to the safety system, and malfunctions in the system outputs including discrete output switches, analog modulating outputs, and the actuated devices as well as feedback of actual position or condition where employed. This should include the expected failure state(s) of each input, the response of the system to each failure, the expected failure state(s) of each output, and the response of the plant to each failure.
These should be based on the platform failure modes and effects analysis (FMEA) and consider the FMEA for the plant application.
- e. Use of an external safety-related system to perform continuous channel cross-checks, as well as logic cross-checks between divisions, to provide a means to detect drift and other malfunctions in external devices and system inputs.
For review efficiency, the LAR should provide an information-only markup of the plants FSAR, showing how the new design will be reflected in the FSAR. The content of the FSAR may be based on RG 1.70, Standard Format and Content of Safety Analysis Reports for Nuclear Power Plants (LWR Edition), or RG 1.206, Combined License Applications for Nuclear Power Plants (LWR Edition), as applicable. Any TS markups should be included based on the content in Section D.7.
If the design includes a DAS, then the architecture section of the LAR should contain information, which could include diagrams, to describe the interconnections and interactions between the DAS and the following:
- a. the primary protection system
- b. any portions of the existing system that remain
- c. the priority logic (if applicable)
- d. credited manual operator actions
- e. maintenance, test, surveillance, and other similar actions
- f.
detection of DAS and DAS interface malfunctions If the design interfaces with instruments that are used for other purposes, such as post-accident monitoring, the LAR should describe methods (e.g., isolation devices) used to ensure that the new digital equipment does not adversely affect the function of those instruments. If the design
DI&C-ISG-06, Draft Revision 2 Page 23 of 66 affects indications used by the operator for manual control, the LAR should describe how those modifications affect the ability of the operator to implement manual actions, in accordance with IEEE Std 603-1991, Clause 5.8.1. The LAR should describe the interface and controls associated with status indication and bypass indication, in accordance with IEEE Std 603-1991, Clauses 5.8.2, 5.8.3, 5.8.3.1, 5.8.3.2, and 5.8.3.3. If the design affects indications used by the operator for manual control, status indications, or indication of bypasses, the LAR should describe how the modifications support the ability of the operator to use the indications, in accordance with IEEE Std 603-1991, Clause 5.8.4.
D.2.2.2 Evaluation The safety evaluation should include a description of the new architecture.
The reviewer should evaluate whether the LAR describes the architecture of the replacement system through text and diagrams, with emphasis on changes from the existing system. The reviewer should evaluate whether the drawings in the LAR explain the modification, block diagrams showing channels and divisions, and drawings showing changes to human-system interfaces. The reviewer should evaluate whether the LAR text describes what is being changed and how the change meets regulations and general or licensed plant design criteria (see Section D.2.6).
The reviewer should evaluate whether the LAR defines the extent to which the replacement system architecture is constrained by the existing plant architecture (including electrical divisions and mechanical trains), sensor and actuator physical arrangement, capabilities of the sensors and actuators, existing plant wiring, and functions performed by the existing system.
The reviewer should evaluate whether the LAR defines the mapping of logic channels and logic divisions to electrical divisions, as well as any mapping to engineered safety features mechanical trains.
The reviewer should evaluate whether added, deleted, or modified connections (including temporary connections for maintenance) between the following are described and meet regulatory criteria:
- a. between safety-related systems
- b. between safety-related and non-safety-related systems The reviewer should evaluate whether the LAR justifies changes, including modifications, additions, and deletions, and demonstrates that the changes do not adversely affect plant safety for each of the following:
- a. plant system design functions
- b. connections within the safety system, including cross-divisional interfaces and connections to human-system interfaces
- c. connections between safety-related systems
- d. connections between safety-related and non-safety-related systems and identification of signal and data isolation devices
- e. indications used for manual control
- f.
temporary connections (e.g., for maintenance workstations)
DI&C-ISG-06, Draft Revision 2 Page 24 of 66 The reviewer should evaluate whether changes to the system design functions are identified, documented, and justified to meet the revised licensing basis.
The reviewer should confirm that the service/test functions described in the LAR meet the requirements of IEEE Std 603-1991, Clause 5.7. Section D.2.3.2 discusses the evaluation of the service/test functions. The reviewer should evaluate whether the self-test and self-diagnostic portions of the service/test functions provide adequate fault detection capabilities to conform to the guidance in IEEE Std 7-4.3.2-2003, Clauses 5.5.2 and 5.5.3 (thereby meeting the requirements of IEEE Std 603-1991, Clause 5.7). The reviewer should evaluate the level of detail included in the LAR for the malfunctions detected by the service/test functions to ensure that these malfunctions are annunciated.
If the design includes a DAS, then the reviewer should evaluate whether the LAR describes how the integration of the system and DAS meets regulatory requirements. Section D.2.5 discusses the evaluation of DAS interfaces. Sections D.2.6.2.2 and D.2.6.2.4 describe how the staff should evaluate the implementation of independence, defense-in-depth, and diversity between the DAS and the proposed system.
If the LAR discusses any interfaces with post-accident monitoring instrumentation, the reviewer should evaluate whether the replacement design adversely affects the required capabilities and data display functions.
If the design affects indications used by the operator for manual control, status indications, or indication of bypasses, the reviewer should evaluate those changes in accordance with IEEE Std 603-1991, Clauses 5.8.1, 5.8.2, 5.8.3, 5.8.3.1, 5.8.3.2, 5.8.3.3, and 5.8.4.
SRP Appendix 7.1-C, Guidance for Evaluation of Conformance to IEEE Std 603, provides acceptance criteria for IEEE Std 603 for those clauses applicable to this section. SRP Appendix 7.1-D, Guidance for Evaluation of the Application of IEEE Std 7-4.3.2, provides acceptance criteria for IEEE Std 7-4.3.2 for those clauses applicable to this section.
D.2.3 New System Functions D.2.3.1 Information To Be Provided The LAR should describe the existing functions (i.e., design functions and service/test functions) performed by the portion(s) of the system being replaced. The LAR should also describe new functions.
Each design functions description should include equipment from sensor to actuated device(s) including logical operation, manual versus automatic, and any interdependencies (e.g., signal split and use in a safety function as well as in a display in the control room).
Each design functions description should include the following:
- a. identification of the safety functions, including the trip/actuation functions credited for each anticipated operational occurrence and postulated accident
- b. all monitored variables used to control each protective action
- c. minimum number and location of sensors and equipment relied upon for protective purposes
DI&C-ISG-06, Draft Revision 2 Page 25 of 66
- d. functionality, including input/output ranges and setpoints (for trip functions, the documentation defines the margins between setpoints and allowable values (e.g., those including all applicable uncertainties))
- e. performance, including accuracy and response times (where appropriate, performance requirements are defined for different initial plant conditions and design-basis events)
- f.
appropriate signal filtering, signal validation, and interlocks to minimize the potential of spurious actions
- g. the safety classification of each safety function and whether there are independence constraints from other functions based on safety classifications
- h. the range of transient and steady-state conditions throughout which the safety systems should perform, including conditions (e.g., environmental, plant process) with the potential to degrade the functions of safety system performance The LAR should address each IEEE Std 603-1991 requirement in Clause 4 for each design function. While most IEEE Std 603-1991 requirements in Clause 4 may be addressed for each design function, some may be addressed for the system. For example, IEEE Std 603-1991, Clause 4.9, may identify reliability methods used for all design functions.
The LAR should address each of the listed IEEE Std 603-1991 requirements for each service/test function. As with design functions, some service/test functions may be addressed for the system. The service/test functions should demonstrate compliance with the following:
- a. Clauses 5.2 and 7.3, Completion of Protective Action
- b. Clause 5.5, System Integrity
- c. Clauses 5.7, 6.5, 6.5.1, and 6.5.2, Capability for Testing and Calibration
- d. additional specifications for digital equipment, extending the Clause 5.5 guidance in IEEE Std 7-4.3.2-2003, Clause 5.5.2, Test and Calibration, as reflected in IEEE Std 603-1991, Clause 5.7
- e. additional specifications for digital equipment, extending the Clause 5.5 guidance in IEEE Std 7-4.3.2-2003, Clause 5.5.3, Fault Detection and Self-Diagnostics, as reflected in IEEE Std 603-1991, Clause 5.7
- f.
Clause 5.8, Information Displays
- g. Clause 5.9, Control of Access
- h. Clause 5.10, Repair
- i.
Clauses 6.6 and 7.4, Operating Bypasses
- j.
Clauses 6.7 and 7.5, Maintenance Bypass
- k. Clause 6.8, Setpoints (partial compliance, for variables with multiple setpoints depending on plant condition)
The discussion of self-tests and self-diagnostics should demonstrate compliance to any proposed TS for new system functions.
The LAR should state how the quality requirements of IEEE Std 603-1991, Clause 5.3, are being (or will be) met.
DI&C-ISG-06, Draft Revision 2 Page 26 of 66 D.2.3.2 Evaluation Through review of system design information, the reviewer should confirm that the design-basis information provided in the LAR satisfies Clause 4 of IEEE Std 603-1991. The system design information includes design function descriptions, functional block diagrams, descriptions of operation, architectural descriptions, and other submitted design details.
The reviewer should evaluate whether the test and calibration portions of the service/test functions meet the needs for those features to support the design functions of applicable modes of plant and system operation. The reviewer should evaluate whether the platform-specific service/test functions meet the IEEE Std 603-1991 clauses listed in Section D.2.3.1. The service/test functions (e.g., internal diagnostics, calibration, and surveillance test support) may have been previously reviewed as part of the digital equipments topical report safety evaluation.
The reviewer should evaluate whether the LAR addresses any application-specific implementation of service/test functions and any changes to the service/test functions since topical report approval.
Section D.7.2.1 addresses the evaluation of TS and the self-tests and self-diagnostics that are implemented for new system functions.
SRP Appendix 7.1-C provides acceptance criteria for IEEE Std 603-1991 for those clauses applicable to this section. SRP Appendix 7.1-D provides acceptance criteria for IEEE Std 7-4.3.2-2003 for those clauses applicable to this section.
D.2.3.3 System Requirements Documentation D.2.3.3.1 Information To Be Provided The NRC staff should verify that the licensee has submitted a System Requirements Specification (SyRS) or other document with equivalent content. While the document may have a different title, the content should be consistent with the descriptions below. The SyRS is used to confirm that what is being designed is consistent with what is being reviewed in the LAR. The SyRS is a product of the modification lifecyle development process and bounds the design.
For the Alternate Review Process, this section uses the definitions from the International Electrotechnical Commission Std 61513, Nuclear PlantsInstrumentation and Control Important to SafetyGeneral Requirements for Systems, paraphrased below to fit modifying and replacing existing systems, rather than designing new systems.
The SyRS provided should address the overall architecture of the I&C systems, including but not limited to the following:
- a. defining system requirements for the I&C functions in the modifications scope and the modifications effects on associated systems and equipment within the plants safety analysis
- b. defining the plant layout for the modification scope
- c. defining the operational context for the modification scope and changes resulting from the modification
DI&C-ISG-06, Draft Revision 2 Page 27 of 66
- e. identifying the required design criteria for the modification scope, including ensuring that features providing defense-in-depth in the existing system are not compromised and to minimize the potential for common-cause failure (CCF)
- f.
describing how the modification fits within the overall architecture of the plants I&C systems and any changes to the architecture
- g. defining system interfaces and the reasons for the interfaces (see Section D.2.5.1)
The SyRS should address the requirements that are specific to digital implementations. The licensee will ensure implementation of requirements and processes needed to ensure that the modification can be integrated, commissioned, operated, and maintained.
The SyRS should describe the system-level design, hardware and software design requirements, and the arrangement of equipment to assess the allocation of design functions described in Section D.2.4. The I&C architecture, plant design bases, and functional assignments are inputs to the SyRS.
The SyRS should contain provisions for digital equipment quality to comply with IEEE Std 603-1991, Clause 5.3.
The SyRS should contain functional and performance requirements that are consistent with the replacement system functions in Section D.2.3.1.
The SyRS should establish the following for each design function:
- a. Functionality, including input/output ranges and setpoints. For trip functions, the specification defines the margins between setpoints and allowable values (e.g., those including all applicable uncertainties)
- b. Performance, including accuracy and response times. Where appropriate, performance requirements are defined for different initial plant conditions and design basis events
- c. Appropriate signal filtering, signal validation, and interlocks should be specified to minimize the potential for spurious actions The SyRS should specify boundaries and interfaces with other systems, including isolation measures. Other boundary and interface information specified should include the following:
- a. intended location and the physical constraints relevant to the installation of the system in the plant
- b. physical and functional interfaces of the system with the supporting systems and equipment
- c. physical and functional interfaces of the system with other systems and equipment with which it exchanges information
- d. interfaces with the operator or maintenance technician The SyRS should specify environmental conditions applicable to the system (see Section D.3). The normal and extreme ranges of environmental conditions that the system is
DI&C-ISG-06, Draft Revision 2 Page 28 of 66 required to withstand should be specified in accordance with the constraints imposed from the plant design framework. Environmental conditions specified should include the following:
- a. temperature, humidity, pressure, and radiation during normal operation and accident conditions
- b. conditions imposed by potential hazards external to the system including seismic conditions, electromagnetic interference, and flooding
- c. power supply and heating and ventilation conditions
- d. specify environmental qualification of hardware based on design bases functions (For computer-based systems, this qualification addresses the hardware (including its ability to perform its safety functions under the applicable environmental conditions), the operating system software (if applicable), and representative application software, both integrated in the hardware, based on IEEE Std 7-4.3.2-2003, Clause 5.4, and IEEE Std 603-1991, Clause 5.4)
The SyRS should establish the requirements for any service/test functions available in the systems NRC-approved platform. The requirements for these functions are determined on a case-by-case basis depending on equipment complexity. These functions could include self-diagnostics/testing, maintenance, etc.
D.2.3.3.2 Evaluation The reviewer should evaluate the SyRS to confirm:
- a. That the SyRS contains the Section D.2.3.3.1 information; and
- b. That the Section D.2.3.3.1 information is consistent with the design information contained in the LAR.
D.2.4 Functional Allocation D.2.4.1 Information To Be Provided The LAR should demonstrate the allocation of design and service/test functions (see Section D.2.2.1 for the description of these functions) to the various elements of the proposed architecture (e.g., hardware, software, and operators using human-system interfaces).
The LAR should describe, using text and drawings, how functions (e.g., logic functions) are distributed into physical hardware.
The LAR should demonstrate how the range of response times in the new design falls within the range of response times credited in the accident analysis for the applicable modes of replacement system operation.
The LAR should describe the mapping of logic drawings (i.e., functions) to logic elements in the system. The LAR should demonstrate the mapping of design functions and auxiliary features to software, hardware, MOAs, or some combination of the software, hardware, and MOAs.
DI&C-ISG-06, Draft Revision 2 Page 29 of 66 D.2.4.2 Evaluation The reviewer should evaluate whether the range of system response times given in the LAR includes all interlock and monitoring functions identified in the system architecture and SyRS.
The reviewer should evaluate whether the response time range falls with the range of response times credited in the accident analysis for the applicable modes of replacement system operation.
Regulatory guidance for reviewing digital system real-time system architectures in I&C systems is contained in SRP BTP 7-21, Guidance on Digital Computer Real-Time Performance.
The reviewer should evaluate whether the rationale provided by the LAR for each interface justifies the presence of each interface or logical group of interfaces defined in the LAR. The reviewer should evaluate whether the list of interfaces is complete.
The reviewer should evaluate whether the LAR defines and justifies any changes to the existing logic drawings, as well as changes to the existing plant interfaces and their effect on plant safety and licensing basis.
During this evaluation, the reviewer should consider IEEE Std 603-1991, Clauses 5.1 and 5.6.
SRP Appendix 7.1-C provides acceptance criteria for IEEE Std 603-1991 for those clauses applicable to this section. SRP Appendix 7.1-D provides acceptance criteria for IEEE Std 7-4.3.2-2003 for those clauses applicable to this section.
D.2.5 System Interfaces D.2.5.1 Information To Be Provided The LAR should provide documentation and drawings as necessary to illustrate, explain, and justify data distribution within and external to the system, including all interfaces, hardwired or data communication, whether point-to-point, multiplexed, or networked. This discussion should include those aspects of the design that maintain independence between channels and divisions.
The LAR should identify and describe each of the following, whether existing, modified, deleted, or added:
- a. input and output interfaces with the plant and plant sensor or actuators, whether hardwired or using some form of data communication, including requirements for any required isolation
- b. interfaces with control room displays, indicators, controls, and alarm systems, including the systems role and interfaces with post-accident monitoring and any reference by emergency plan implementing procedures, including requirements for any required isolation (including credited manual operator actions)
- c. human-system interfaces for the licensees maintenance and engineering workstations used for test and maintenance, whether considered internal or external to the new plant system, including requirements for any required isolation
DI&C-ISG-06, Draft Revision 2 Page 30 of 66 The LAR should identify and describe each of the following:
- a. Support and auxiliary systems, normal power sources, emergency power sources, and heating, ventilation, and air conditioning (HVAC). The LAR should address the impact of single failure in a supporting system, the diverse means of annunciating such failures, and the means of repair and restoration. This includes the HVAC and the diverse means of annunciation of HVAC failure, along with a coping procedure.
- b. Communication features from the NRC-approved topical report that are proposed for the replacement system.
- c. How identified hazards are controlled in communication features.
- d. How hazards are handled in the design, demonstrating elimination or at least mitigation of the hazards in each interface or logical group of interfaces.
- e. How malfunctions are detected by the self-test and self-diagnostics for each interface or logical group of interfaces.
- f.
Features that affect the SOE (see Section D.8.1).
- g. If multidivisional controls and displays are applied, how the controls and displays are applied in accordance with DI&C-ISG-04.
The LAR should describe methods applied in the hardware and in the logic to ensure that malfunctions in the interfaces minimize the potential for spurious actuation.
For each data communication interface, the LAR should demonstrate how the SOE is maintained when using that interface and reference the secure development and operational environment (SDOE) discussion in the LAR.
The LAR should demonstrate that any interface requiring electrical isolation is provided with sufficient electrical isolation, based on the electrical hazards present and the electrical isolation criteria in SRP BTP 7-11, Guidance on Application and Qualification of Isolation Devices.
The LAR should describe the use of power sources, electric and non-electric, and should state how the system continues to perform its credited safety functions while power sources are bypassed for maintenance for compliance with IEEE Std 603-1991, Clauses 8.1, 8.2, and 8.3.
The LAR should demonstrate how the communication features meet the criteria of IEEE Std 603-1991, Clauses 5.6.1, 5.6.2, 5.6.3, 5.6.3.1, 5.6.3.2, 5.6.3.3, and 5.6.4 and IEEE Std 7-4.3.2-2003, Clause 5.6.
The LAR should demonstrate how each clause in DI&C-ISG-04 is being met or justify the proposed alternatives when an individual clause is not met. If priority logic modules are provided or priority logic is embedded in a digital system, the LAR should demonstrate conformance with the guidance of DI&C-ISG-04.
The LAR should define interfaces between the different elements of the proposed architecture that are within the scope of the modified portion(s) of the system. Interfaces should include all communication interfaces with permanently installed and temporary workstations.
DI&C-ISG-06, Draft Revision 2 Page 31 of 66 The LAR should describe and justify the use of redundancy in interfaces internal to a division for satisfying existing reliability goals or otherwise meeting or exceeding the reliability of the existing system. The description of redundancy should include methods to detect malfunctions in redundant links, to inform maintenance staff, and to support troubleshooting, repair, and restoration.
The LAR should describe use of systems in multi-unit stations and demonstrate how malfunctions in one station will not affect the other station or stations, addressing IEEE Std 603-1991, Clause 5.13.
The LAR should describe the human-system interfaces to be provided, addressing changes from the existing human-system interfaces. The LAR should describe or reference the human factors engineering processes and results used for compliance with IEEE Std 603-1991, Clause 5.14.
The discussion of self-tests and self-diagnostics should demonstrate conformance to any proposed TS associated with system interfaces.
D.2.5.2 Evaluation The reviewer should consider that DI&C-ISG-04, Section 3, applies to workstations without regard to the following:
- a. whether the workstations are permanently installed or portable
- b. whether the workstations provide direct or indirect control of safety equipment (e.g., non-safety-related workstations that interface with safety-related workstations to control safety equipment)
- c. whether the workstations control safety equipment through means other than direct data communications (e.g., translation of data communication signals to hardwired signals through use of associated circuits to the safety system)
Regarding the guidance in DI&C-ISG-04 that addresses communications features in safety systems to cope with any operation, malfunction, design error, communication error or software error or corruption, the NRC reviewer should determine whether the LAR submittals address the following:
- a. information that identifies communications hazards for the plant-specific system, hardware and/or application software in addition to those reviewed in the NRC-approved topical report and an explanation of how these hazards are controlled
- b. information on elimination, or at least mitigation, of the plant-specific design communication hazards that the NRC-approved topical report does not address The NRC reviewer should evaluate the following:
- a. the description of the interfaces between the portions of the system being replaced and the portions of the system and the plant that are unchanged
- b. whether the LAR defines the connections between this system and other safety systems with a rationale and set of requirements for each connection
DI&C-ISG-06, Draft Revision 2 Page 32 of 66
- c. whether the LAR defines the connections between this system and any non-safety-related systems with a rationale and set of requirements for each connection
- d. whether the LAR documents the functionality and purpose of sensors and actuators and how the sensors and actuators interface with the logic
- e. whether the LAR defines any connection allowing communication from a non-safety system to a safety system with a demonstrated and justified purpose and whether the safety system is designed with protection from any adverse action by the non-safety system
- f.
whether the safety function and the SOE for the safety system are compromised by any connection
- g. whether the LAR demonstrates the required electrical isolation for any signal crossing electrical or classification boundaries
- h. whether the LAR defines the hardwired interfaces, including any manual actuation means provided for operator use
- i.
whether the defined use of the hardwired interfaces is consistent with the previous system and with any changes and the rationale for the changes
- j.
whether the information or controls associated with MOA are subject to a digital CCF that would adversely affect the ability to perform the credited safety function manually Although features that affect the SOE are mentioned here, Section D.8 presents guidance for their review.
The reviewer should evaluate how the communication features meet the criteria of IEEE Std 603-1991, Clauses 5.6.1, 5.6.2, 5.6.3, 5.6.3.1, 5.6.3.2, 5.6.3.3, and 5.6.4, and IEEE Std 7-4.3.2-2003, Clause 5.6, and how the communication features address the electrical isolation criteria in SRP BTP 7-11. The reviewer should evaluate each hardwired connection, or logical group of similar hardwired connections, for electrical isolation and data independence.
The reviewer should evaluate whether the function of each hardwired connection is described, including whether the hardwired connection provides a discrete or an analog signal and the use of that signal in the receiving equipment. The reviewer should evaluate whether the function of each data communication connection is described, including the content of the data packet and methods used to minimize data corruption, as well as the use of that signal in the receiving equipment.
Section D.7.2.1 addresses the evaluation of TS and the self-tests and self-diagnostics that are implemented for system interfaces.
The reviewer should evaluate whether the LAR provides appropriate isolation by describing the electrical connections in sufficient detail to define the electrical division assigned to the connection, where cross-divisional signals change electrical divisions through isolation, how divisional (or equipment location) isolation is maintained, and how isolation is provided between electrical divisions or equipment locations. This is especially critical for connections such as anticipatory trips, where non-safety systems provide anticipatory trip signals to safety systems.
The reviewer should evaluate whether those portions of the design associated with multi-unit stations comply with IEEE Std 603-1991, Clause 5.13.
DI&C-ISG-06, Draft Revision 2 Page 33 of 66 The reviewer should evaluate whether the human-system interfaces and human factors engineering portions of the LAR comply with IEEE Std 603-1991, Clause 5.14.
The reviewer should evaluate whether each applicable clause in DI&C-ISG-04 has been addressed in sufficient detail, or whether the proposed alternatives address the underlying hazard. The LAR should provide an explanation, but not a detailed evaluation, for why criteria do not apply, to enable the reviewer to forego the associated reviews. The proposed alternative is assessed against the following regulatory requirements and guidance:
- a. IEEE Std 603-1991, Clause 5.6, provides requirements for independence.
- b. IEEE Std 7-4.3.2-2003 provides guidance on how digital systems can meet the independence requirement in IEEE Std 603-1991, Clause 5.6.
BTP 7-11 applies to the use of electrical isolation devices for connections between redundant portions of safety systems or between safety and non-safety systems.
- d. SRP Section 7.9, Data Communications Systems, also contains guidance for data communication systems.
The reviewer should evaluate whether the LAR addresses conformance with the independence guidance in DI&C-ISG-04 for any digital multidivisional safety-related controls and displays and any digital multidivisional non-safety-related controls and displays.
The reviewer should evaluate whether the LAR addresses conformance with the guidance in IEEE Std 603-1991, Clause 5.12, Auxiliary Features, and in IEEE Std 7-4.3.2-2003 for traditional auxiliary features (e.g., HVAC, emergency power).
The reviewer should evaluate whether the use of electric and non-electric power sources complies with the requirements in IEEE Std 603-1991, Clauses 8.1, 8.2, and 8.3.
If separate priority logic modules are provided, the reviewer should evaluate whether the LAR describes how the design conforms to the guidance in Section 2 of DI&C-ISG-04 and in Sections 1 and 3 of that ISG as appropriate for the design. If priority logic is embedded in a digital system, the reviewer should evaluate whether the LAR identifies, describes, and demonstrates how the design conforms to the guidance in DI&C-ISG-04, Section 2.
SRP Appendix 7.1-C provides acceptance criteria for IEEE Std 603-1991 for those clauses applicable to this section. SRP Appendix 7.1-D provides acceptance criteria for IEEE Std 7-4.3.2-2003 for those clauses applicable to this section.
D.2.6 Fundamental Design Principles in the New Architecture This section explains the new architecture in terms of the fundamental design principles.
D.2.6.1 Information To Be Provided In accordance with Section D.2.2.1, the LAR should include a description of the replacement system architecture that is intended to provide a basis for discussion of the fundamental design principles. This information supports the discussions in all five of the subsections below (i.e.,
redundancy, independence, deterministic behavior, defense-in-depth and diversity (D3), and
DI&C-ISG-06, Draft Revision 2 Page 34 of 66 simplicity). Additional information needed to support a particular subsection is described in that subsection.
D.2.6.2 Evaluation SRP Appendix 7.1-C provides acceptance criteria for IEEE Std 603-1991 for those clauses applicable to these sections. SRP Appendix 7.1-D provides acceptance criteria for IEEE Std 7-4.3.2-2003 for those clauses applicable to these sections.
D.2.6.2.1 Redundancy Redundancy helps ensure that single failure will not cause the loss of a safety systems ability to perform safety functions.
D.2.6.2.1.1 Information To Be Provided The NRC staff should verify that the licensee has demonstrated the use and application of redundancy in the new architecture.
The NRC staff should verify that the licensee has demonstrated, by implementing an FMEA, that the use and application of redundancy in the new architecture ensure that the safety functions can be achieved in the event of a postulated single failure. The FMEA should document the postulated failures and the effects of the failures on the plant, as well as on the system. The FMEA should provide sufficient detail on the evaluation of failures, such as failure of an individual input, an input module, a processing module, a voter, an output module, and an individual output.
The NRC staff should verify that the licensee has demonstrated that the use and application of redundancy in the new architecture supports the associated TS (e.g., limiting conditions for operation (LCOs), action statements, and surveillance requirements). If the LAR includes changes to the associated TS, then this demonstration should address the proposed TS.
D.2.6.2.1.2 Evaluation The reviewer should evaluate whether the scope and level of detail are sufficient to demonstrate that the new architecture meets the following clauses of IEEE Std 603-1991 when applying the associated guidance of IEEE Std 7-4.3.2-2003:
- a. Clause 5.1, Single-Failure Criterion
- b. Clause 5.15, Reliability
- c. Clause 6.7, Maintenance Bypass
- d. Clause 7.5, Maintenance Bypass For the single-failure criterion, the reviewer should evaluate whether the use and application of redundancy in the new architecture conform to the guidance in RG 1.53, Application of the Single-Failure Criterion to Nuclear Power Plant Protection Systems, which endorses IEEE Std 379, IEEE Standard for Application of the Single-Failure Criterion to Nuclear Power Generating Station Safety Systems.
DI&C-ISG-06, Draft Revision 2 Page 35 of 66 The reviewer should evaluate whether the use and application of redundancy in the new architecture meet the following general design criteria (GDC) of Appendix A, General Design Criteria for Nuclear Power Plants, to 10 CFR Part 50:
- a. GDC 21, Protection System Reliability and Testability
- b. GDC 24, Separation of Protection and Control Systems Section D.7.2.1 addresses the evaluation of TS and redundancy.
D.2.6.2.2 Independence Independence ensures that failures are not propagated across independent domains.
D.2.6.2.2.1 Information To Be Provided The NRC staff should verify that the licensee has demonstrated the use and application of physical, electrical, and functional independence in the new architecture. Section D.2.5 addresses data communications independence.
D.2.6.2.2.2 Evaluation The reviewer should evaluate whether the scope and level of detail are sufficient to demonstrate that the new architecture meets the following clauses of IEEE Std 603-1991 when applying the associated guidance of IEEE Std 7-4.3.2-2003:
- a. Clause 5.6, Independence
- b. Clause 5.11, Identification
- c. Clause 6.3, Interaction with Other Systems The reviewer should evaluate whether the use and application of physical and electrical independence in the new architecture conform to the guidance in RG 1.75, Criteria for Independence of Electrical Safety Systems, which endorses IEEE Std 384, IEEE Standard Criteria for Independence of Class 1E Equipment and Circuits.
The reviewer should evaluate whether the use and application of functional independence in the new architecture ensure that physically and electrically independent portions of safety systems do not depend on information from other independent portions of the safety system. Note that coincidence voting is permitted to depend on information from other independent portions of the safety system. The reviewer should evaluate whether the use and application of independence in the new architecture meet the following GDC:
- a. GDC 13, Instrumentation and Control
- b. GDC 21, Protection System Reliability and Testability
- c. GDC 22, Protection System Independence
- d. GDC 23, Protection System Failure Modes
- e. GDC 24, Separation of Protection and Control Systems
DI&C-ISG-06, Draft Revision 2 Page 36 of 66 D.2.6.2.3 Deterministic Behavior Deterministic behavior ensures predictable and repeatable behavior of systems performing safety functions.
D.2.6.2.3.1 Information To Be Provided The NRC staff should verify that the licensee has demonstrated the use and application of deterministic behavior in the new architecture.
D.2.6.2.3.2 Evaluation The reviewer should evaluate whether the scope and level of detail are sufficient to demonstrate that the new architecture meets the following clauses of IEEE Std 603-1991 and the associated guidance of IEEE Std 7-4.3.2-2003 (as applicable):
- a. Clause 5.2, Completion of Protective Action
- b. Clause 5.5, System Integrity
- c. Clause 6.1, Automatic Control
- d. Clause 6.2, Manual Control
- e. Clause 7.1, Automatic Control
- f.
Clause 7.2, Manual Control The reviewer should evaluate whether the use and application of deterministic behavior in the new architecture meet the following GDC:
- a. GDC 13, Instrumentation and Control
- b. GDC 21, Protection System Reliability and Testability
- c. GDC 23, Protection System Failure Modes
- d. GDC 29, Protection Against Anticipated Operational Occurrences The reviewer should evaluate whether the deterministic behavior of the new architecture ensures the following:
- a. Input signals and system characteristics result in output signals through known relationships among system states and responses to those states.
- b. The system produces the same outputs for a given set of input signals (and the sequence of inputs) within well-defined response time limits to allow timely completion of credited actions.
The reviewer should evaluate whether the deterministic behavior of digital data communication outputs ensures the following:
- a. System timing requirements derived from the analyses of design-basis events are satisfied by the replacement system architecture.
- b. The replacement system architecture and communication protocols provide features to ensure that the system produces the correct response to inputs within the time credited to produce a response.
- c. The design adequately identifies and accounts for hazards that could challenge predicted behavior.
DI&C-ISG-06, Draft Revision 2 Page 37 of 66 If an NRC-approved platform is used and the following two conditions are met, then the review should focus on acceptable use of the communications in the system design and architecture:
- a. The system design and architecture information specify the use of the platforms standard data communications.
- b. The deterministic behavior of these communications has already been reviewed and approved by the NRC as part of the topical report.
Compliance with any restrictions on the DI&C platform communications should be reviewed to confirm compliance with the conditions identified in the NRC-approved topical report safety evaluation. The review should evaluate whether the credited response time can be met using the standard communication methods provided by the platform.
D.2.6.2.4 Defense-in-Depth and Diversity Defense-in-depth and diversity are methods that can be used to protect against CCFs.
D.2.6.2.4.1 Information To Be Provided The NRC staff should verify that the licensee has demonstrated, via a D3 evaluation, that the use and application of D3 in the new architecture ensure that safety is maintained in the event of a postulated CCF.
D.2.6.2.4.2 Evaluation The reviewer should evaluate whether the scope and level of detail are sufficient to demonstrate that the new architecture meets the following GDC:
- a. GDC 13, Instrumentation and Control
- b. GDC 22, Protection System Independence
- c. GDC 24, Separation of Protection and Control Systems The reviewer should evaluate whether the licensees D3 assessment conforms to the guidance in SRP BTP 7-19, Guidance for Evaluation of Diversity and Defense-in-Depth in Digital Computer-Based Instrumentation and Control Systems, including use of an analysis as described in NUREG/CR-6303, Method for Performing Diversity and Defense-in-Depth Analyses of Reactor Protection Systems.
The reviewer should evaluate whether the use and application of D3 in the new architecture meets 10 CFR 50.62, Requirements for reduction of risk from anticipated transients without scram (ATWS) events for light-water-cooled nuclear power plants.
D.2.6.2.5 Simplicity of Design Evaluation of this principle relies more heavily on engineering judgment that the other fundamental design principles; therefore, rather than attempting to evaluate the adequacy of the modified system designs simplicity solely using a set of defined criteria, the reviewer should evaluate the rationale for those design decisions that result in the replacement system architecture being more complex than it might be otherwise.
DI&C-ISG-06, Draft Revision 2 Page 38 of 66 D.2.6.2.5.1 Information To Be Provided The NRC staff should verify that the licensee has demonstrated the use and application of simplicity in the new architecture, focusing on the resultant simplicity (or lack thereof) of design decisions that affect redundancy, independence, deterministic behavior, and D3.
The NRC staff should verify that the licensee has demonstrated, for design decisions resulting in more complex approaches than might otherwise have been chosen, that the benefit(s) obtained, particularly with respect to the other fundamental design principles, justify the reduction in simplicity. Design decisions involving such tradeoffs may be driven by the need to satisfy a regulatory requirement (e.g., surveillance testing, improved maintainability and/or operability for faulted conditions).
D.2.6.2.5.2 Evaluation The reviewer should evaluate, for design decisions resulting in more complex approaches than might otherwise have been chosen, whether the benefit(s) obtained, particularly with respect to the other fundamental design principles, justifies the reduction in simplicity.
The reviewer should evaluate whether the new architecture meets IEEE Std 603-1991, Clause 6.4, Derivation of System Inputs.
D.3 Hardware Equipment Qualification D.3.1 Information To Be Provided The NRC staff should verify that the licensee has demonstrated that the system will perform its safety functions under the design-basis conditions at the location in which the equipment will be installed. This information should be found in equipment qualification test plans, methodologies, and test reports. The NRC staff should verify that the licensee has included a summary of documents referencing detailed test reports to support this conclusion (e.g., seismic test reports or analysis, electromagnetic compatibility reports, environmental test reports). The summary should document the results of the qualification testing. The summary should compare the standards and test limits to which the equipment has been qualified and should compare the equipment qualification test limits to the licensee-established plant environmental conditions.
The LAR should describe and justify any discrepancies between equipment qualification test limits and expected plant environmental conditions.
In the Tier 1, 2 and 3 Review Process, the information should be provided as follows:
Phase 1:
Equipment Qualification Testing Plans (Including Electromagnetic Interference (EMI), Temperature, Humidity, and Seismic)
Phase 2:
(1) Qualification Test Methodologies (2) Summary of EMI, Temperature, Humidity, and Seismic Test Results The NRC staff should verify that, in those cases where the hardware qualification has previously been demonstrated by the vendor and evaluated by the NRC staff, the licensee has referenced that evaluation. The LAR should identify and justify any deviations or revision changes.
DI&C-ISG-06, Draft Revision 2 Page 39 of 66 D.3.2 Evaluation The reviewer should evaluate whether the information demonstrates that the hardware is designed to operate within the specified environment. This includes both the normal operating conditions and the worst conditions expected during abnormal and accident conditions in which the equipment is expected to perform its safety function.
The following provide regulatory criteria for the design of safety-related equipment to withstand environmental conditions:
- a. 10 CFR Part 50, Appendix A, GDC 2, Design Bases for Protection Against Natural Phenomena, and GDC 4, Environmental and Dynamic Effects Design Bases
- b. 10 CFR 50.55a(h), which incorporates, based on the date the construction permit was issued, either IEEE Std 279, IEEE Standard: Criteria for Protection Systems for Nuclear Power Generating Stations, Clause 4.4, or IEEE Std 603-1991, Clause 5.4
- c. RG 1.152, Criteria for Use of Computers in Safety Systems of Nuclear Power Plants, which endorses IEEE Std 7-4.3.2-2003, Clause 5.4
- d. RG 1.209, Guidelines for Environmental Qualification of Safety-Related Computer-Based Instrumentation and Control Systems in Nuclear Power Plants, which endorses IEEE Std 323, IEEE Standard for Qualifying Class 1E Equipment for Nuclear Power Generating Stations, including five enhancements and exceptions
- e. RG 1.180, Guidelines for Evaluating Electromagnetic and Radio-Frequency Interference in Safety-Related Instrumentation and Control Systems To comply with the regulatory requirements, the information provided should demonstrate through environmental qualification that I&C systems meet design basis and performance criteria when the equipment is exposed to normal and adverse environments. The testing should include exposure to the most severe conditions expected at the location of the equipment, including temperature, humidity, radiation, electromagnetic and radio interference, and seismic input. While testing against all of these stressors, the system should be functioning with software and diagnostics representative of those used in actual operation. This includes, as appropriate, exercising and monitoring the memory, the central processing unit, inputs, outputs, display functions, diagnostics, associated components, communication paths, and interfaces.
For digital systems located in mild environments, Regulatory Position 1 in RG 1.209 states that the NRC does not consider the age conditioning in IEEE Std 323, Section 6.2.1.2, to apply because of the absence of significant aging mechanisms. However, if significant aging mechanisms are identified, the qualification program should address them. An aging mechanism is significant if, in the normal or abnormal service environments, it causes degradation during the installed life of the system that progressively and appreciably renders the equipment vulnerable to failure. Such mechanisms may be addressed by testing (e.g., preconditioning before testing), operating experience, or surveillance and maintenance.
Where feasible, the preconditioning and surveillance and maintenance assessments should be based on quantifiable acceptance criteria. If the system has one or more significant aging mechanisms, preconditioning is necessary before testing to the degree that the mechanism is not accounted for by surveillances and maintenance. For example, if an aging mechanism exists and there is a surveillance performed to quantify the progress of the aging mechanism,
DI&C-ISG-06, Draft Revision 2 Page 40 of 66 the system should be preconditioned to account for the acceptance criteria of the surveillance plus the expected aging until the next performance of the surveillance.
The NRC staff should evaluate the various test plans to ensure that the plans are rigorous enough to support the conclusion that the environment should not have a negative effect on the ability of the system to perform its safety function in the worst-case environment in which it needs to operate. Environmental criteria are generally plant dependent, not absolute. A digital system may, for example, have a degree of seismic hardening that makes it suitable for use in a plant with a small design-basis earthquake, but may be unsuitable for use in another plant where the design-basis earthquake is more severe. The same may be true of the worst-case temperature environment. If a system is tested to be able to withstand 120 degrees Fahrenheit (F), it is suitable for use in a plant where the worst-case temperature at the location of the system reaches only 118 degrees F, but unsuitable for use in a plant where the worst-case temperature may be 125 degrees F. The NRC staff should be looking for the comparison that shows that the equipment qualification envelopes the worst-case plant conditions for each environmental stressor at the location of the equipment.
If any portions of this equipment will be subject to harsh environment, then additional disciplines should be involved in the review of equipment qualification for meeting GDC 4 and 10 CFR 50.49, Environmental qualification of electric equipment important to safety for nuclear power plants, to ensure that the requirements for equipment qualification to harsh environments are met.
D.4 I&C System Development Processes D.4.1 Information To Be Provided The NRC staff should verify that the licensee has described the proposed framework being used to design and develop I&C safety systems under the Alternate Review Process. This framework should supplement the licensees overall QA program descriptions with specific system, hardware, and software development activities, including a description of the proposed development life cycles, development documents to be produced, and management activities that will be implemented in the design and development of I&C safety systems. Development documents expected to be available during the LAR review should be identified in the pre-application (Phase 0) coordination meeting(s).
The framework should describe the following system development process activities:
- a. Create the concepts on which the system design will be based.
- b. Translate these concepts into system requirements.
- c. Allocate system requirements to system elements (e.g., software, hardware, and human-system interfaces).
- d. Implement the design into hardware and software functions.
- e. Integrate system elements such as software and hardware.
- f.
Test the unit functions and the completed system to confirm that system requirements have been implemented correctly.
- g. Perform appropriate human factors engineering for the human-system interfaces throughout the development process.
DI&C-ISG-06, Draft Revision 2 Page 41 of 66
- h. Analyze hazards and incorporate requirements that eliminate or mitigate identified hazards throughout the development process.
- i.
Perform V&V activities on work products throughout the development process.
The NRC staff should verify that the licensee has demonstrated that the software life cycle process follows the guidance in RG 1.173, Developing Software Life Cycle Processes for Digital Computer Software Used in Safety Systems of Nuclear Power Plants, or alternately, describe how the regulatory requirements referenced in RG 1.173 are satisfied. Demonstration that the software life cycle process follows the guidance consists of the following:
- a. description of the software life cycle processes to be used
- b. identification of any planned exceptions and clarifications
- c. description of how these planned exceptions and clarifications meet the underlying regulations The NRC staff should verify that, for any RGs referenced, the licensee has demonstrated how the RG-specific activity follows the guidance of the RG or, alternately, describe how the underlying regulatory requirements referenced in the RG are satisfied. Demonstration for RG-specific activity consists of the following:
- a. description of the RG-specific activity
- b. identification of any planned exceptions and clarifications
- c. description of how these planned exceptions and clarifications meet the underlying regulations The NRC staff should verify that the licensee has identified which of the development activities are addressed as part of the development process defined for an NRC-approved topical report and those activities that are part of the application-specific software development process (i.e.,
development processes that will be used but have not been previously reviewed and approved by the NRC). The NRC staff should also verify that the licensee has addressed the applicable plant-specific action items (PSAIs) defined in the referenced topical reports (see Section D.5).
D.4.2 Evaluation Using the criteria in this section, the reviewer will evaluate whether the proposed framework described in the LAR is adequate to deliver a high-quality I&C safety system.
The activities, including relevant PSAIs, that are part of the development process defined for NRC-approved DI&C platform activities should be credited to the degree allowed by the platform safety evaluation. The LAR review should focus on the application-specific software development activities not previously reviewed and approved by the NRC. If the licensee is using an NRC-approved development process for application development (e.g., software program manual), then the LAR should credit these processes to the degree allowed by the applicable safety evaluation of the software program manual including relevant PSAIs.
The reviewer should evaluate whether the software life cycle process description demonstrates that the software life cycle process meets the guidance of RG 1.173 or how the underlying regulatory requirements referenced in RG 1.173 are satisfied.
DI&C-ISG-06, Draft Revision 2 Page 42 of 66 Sections D.4.2.1.1 through D.4.2.1.9 describe the criteria against which the NRC reviewer should evaluate the I&C life cycle process described in the LAR. Sections D.4.2.1.1 through D.4.2.1.4 address life cycle activities that are part of the NRC review scope during the LAR review for the Alternate Review Process. Sections D.4.2.1.5 through D.4.2.1.9 describe process evaluations that are part of the NRC review scope during the LAR review for the Alternate Review Process. The licensee is responsible for ensuring vendor use of procedures and acceptability of all vendor work products discussed in Sections D.4.2.1.1 through D.4.2.1.9.
D.4.2.1 System and Software Development Activities To evaluate whether a licensee has described measures that satisfy Criterion III, Design Control, of 10 CFR Part 50, Appendix B, the reviewer should determine if the LAR describes input information, life cycle activities, and output information necessary to develop I&C safety systems, in accordance with applicable regulatory guidance and the design bases. In addition, the LAR should describe the use of industry standards, including any international standards.
The development of I&C safety systems should progress according to a defined life cycle, which is part of the overall system development framework. Although the staff has not recommended a particular life cycle model, the reviewer should evaluate whether the LAR contains a description of life cycle activities and tasks, including inputs and outputs that will be implemented in the development of the proposed I&C safety system. The LAR should also describe the analysis, review, and test activities that will be implemented. The licensee may choose among many different life cycle models for system, hardware, software, and human factors engineering development. Generally, these models differ in the timing of the various activities and tasks used to produce a high-quality product.
The reviewer should evaluate whether the licensee has described a life cycle model that includes processes tailored and relevant to its particular development project and digital technology to implement the activities listed in Sections D.4.2.1.1 through D.4.2.1.9 below.
Based on the common understanding reached during the pre-application (Phase 0) meeting(s),
the staff may evaluate a sample of referenced system development process documents to be made available for audit during the LAR review to confirm that the life cycle activities are being (or will be) effectively implemented. The review procedure in SRP BTP 7-14, Section B.4, should be applied to the extent the design documents are available during the LAR review.
D.4.2.1.1 Plant and I&C System Safety Analysis The reviewer should evaluate whether the plant and I&C system safety analysis process description addresses the following:
- a. To meet Clause 4 of IEEE Std 603-1991, this information should be consistent with the plant safety analysis provided in the plants updated FSAR. The LAR should describe changes to the plant safety analysis associated with the I&C system modification and justify the acceptability of the changes to the plant design basis (see Section D.2).
- b. The reviewer should evaluate whether the software safety analysis defines a software integrity level (SIL) scheme to classify software criticality, as specified in IEEE Std 1012, IEEE Standard for System and Software Verification and Validation, and as endorsed by RG 1.168, Verification, Validation, Reviews, and Audits for Digital Computer Software Used in Safety Systems of Nuclear Power Plants. A software criticality analysis should be performed to determine the SIL of the software necessary to
DI&C-ISG-06, Draft Revision 2 Page 43 of 66 accomplish each safety function. Software that implements auxiliary features or self-diagnostic functions that may be of a lower safety classification should have a SIL consistent with the highest SIL in the hardware module.
D.4.2.1.2 I&C System Requirements The reviewer should evaluate whether the I&C system requirements process description addresses the following:
- a. I&C system requirements process development should describe the identification, development, documentation, review, approval, and maintenance of I&C system requirements. It should include the technical elements described in Section D.2.
- b. All identified system requirements, including software and hardware as applicable, should be analyzed, reviewed, approved, baselined, updated as necessary, and placed under configuration management (CM).
- c. A means for requirements traceability should be developed, documented, tracked, and maintained. The requirements traceability documentation should provide bidirectional traceability (from plant system requirements to system validation testing and from plant system requirements to I&C system requirements).
- d. The I&C system requirements should be used as input to the ongoing life cycle activities.
D.4.2.1.3 I&C System Architecture The reviewer should evaluate whether the I&C system architecture process description addresses the following:
- a. An I&C system architecture should be developed on the basis of a defined methodology that provides all necessary I&C functions needed to ensure safe plant operation. It should include the technical elements described in Section D.2.
- b. The I&C system architecture should be documented, analyzed, reviewed, approved, baselined, updated as necessary, and placed under CM.
- c. The I&C system architecture should be used as input to the ongoing life cycle activities.
D.4.2.1.4 I&C System Design The reviewer should evaluate whether the I&C system design process description addresses the following:
- a. The design process description should cover how the detailed design of the I&C system is developed to conform to the plant licensing and design basis, based on the architectural design and encompassing the technical elements described in Section D.2.
- b. The I&C system design should demonstrate bidirectional traceability of the system requirements to the I&C system design (including the architecture and functional logic designs).
- c. I&C system safety analyses should be reviewed to identify hardware, software, or human-system interfaces that have the potential to cause a hazard or are credited to eliminate or mitigate hazards. The review principles in SRP BTP 7-14, Section B.3.1.9.4, should be applied to the review of the I&C system safety analyses.
DI&C-ISG-06, Draft Revision 2 Page 44 of 66 I&C system safety analyses may be performed by one or more organizations (e.g.,
design group or V&V team) rather than a single safety organization.
- d. The I&C system design should be analyzed, reviewed, approved, baselined, updated as necessary, and placed under CM.
- e. The I&C system-level design should be used as input to the ongoing life cycle activities.
D.4.2.1.5 Software Requirements The reviewer should evaluate whether the I&C software requirements process description addresses the following:
- a. Software requirements should be developed to document the functions to be performed by the software. RG 1.172, Software Requirement Specifications for Digital Computer Software and Complex Electronics Used in Safety Systems of Nuclear Power Plants, provides an acceptable approach for preparing software requirements and should be applied to the extent practicable when reviewing the software development process description in the LAR. The system requirements allocated to software should be identified. The reviewer should evaluate whether the process for developing the software requirement specifications described in the LAR follows the guidance of RG 1.172 or how the underlying regulatory requirements referenced in RG 1.172 are satisfied.
Demonstration for the software requirement specification development will address the following:
FunctionalityDescribe what the software is supposed to do.
External interfacesDescribe how the software interacts with people, the systems hardware, other hardware, and other software.
PerformanceDescribe the speed, availability, response time, and recovery time of various software functions.
AttributesDescribe portability, correctness, maintainability, security, and others.
Design constraints imposed on an implementationDescribe any applicable standards in effect, implementation language, policies for database integrity, resource limits, operating environment(s), etc.
Ranking requirements for importance or stability for safety systems is not mandatory.
The reviews of the software requirements development process should focus on activities not previously reviewed and approved by the NRC unless there are changes in the NRC acceptance criteria.
- b. The reviewer should evaluate whether the software requirements process description addresses the following:
The software requirements should be analyzed, reviewed, approved, baselined, updated as necessary, and placed under CM. Software requirements should be baselined before initiating software design.
The software requirements should be derived from and traceable to the system design, I&C system architecture, and system requirements.
DI&C-ISG-06, Draft Revision 2 Page 45 of 66 The independent V&V team should develop the system V&V test plans. SRP BTP 7-14, Section B.3.1.12.4, contains the applicable review guidance for the system V&V test plans.
The most recently baselined software requirements should be used as input to the ongoing life cycle activities.
D.4.2.1.6 Software Design The reviewer should evaluate whether the I&C software design process description addresses the following:
- a. The software design decomposes the software requirements to document the design and implementation of software components, modules, and units used to implement the I&C system. A software unit is the highest element in the software hierarchy. Software units are composed hierarchically of software components and software modules. SRP BTP 7-14 does not endorse any RGs for the technical review of software designs. The reviewer should use the review guidance in items (b) through (j) below for evaluating the process for developing a software design; the guidance should be applied to the extent practicable for the Alternate Review Process LAR review.
- b. The software design should be developed and define the detailed design for each software element of the system and how the software components, modules, and units are to be constructed.
- c. The software design should document, at a minimum, the methods by which software components, modules, and units will be refined into lower levels, including software modules to allow coding, compiling, and testing, and the division of the software into a set of interacting components, modules, and units, including the description of those components, modules, and units, defining their interfaces and dependencies in a structured fashion.
- d. The software design and implementation should fulfill applicable software requirements.
- e. The relationship between component(s), and software module(s), and software unit(s) should be established.
- f.
The software design should describe how adequate coverage of software requirements is achieved. There should be no unnecessary functions. Predeveloped digital platforms and preexisting software (e.g., operating system software) may contain features that are not used (or not configured for use) in a specific I&C system. In those instances, the NRC staff should verify that unless otherwise demonstrated as part of the platform qualification, the licensee has identified those unused capabilities. The staff should evaluate whether those functions may affect performance of the safety function and identify any compensatory measures taken.
- g. The documented acceptance and use of support software and tools (e.g., code generating tools, compilers, assemblers, operating systems, coverage analyzers, automated test tools, traceability tools, simulators, and emulators) should be consistent with the guidance in IEEE Std 7-4.3.2-2003, Clause 5.3.2, as endorsed in RG 1.152.
- h. The software design should be analyzed, reviewed, approved, baselined, updated as necessary, and placed under CM.
DI&C-ISG-06, Draft Revision 2 Page 46 of 66
- i.
The independent V&V team should develop the system V&V test designs.
- j.
The most recently baselined software design should be used as input to the ongoing life cycle activities.
D.4.2.1.7 Software Implementation The reviewer should evaluate whether the software implementation process description addresses the following:
- a. The software implementation process should define the criteria for testing software components, modules, and units and the test procedures and data for testing software components, modules, and units.
- b. The software implementation process should describe the translation of the detailed design into code in the selected programming language.
- c. The code should be capable of executing the safety design features and methods developed during the software design process.
- d. The use of documented coding rules, guidelines, methods, standards, and other applicable criteria should be defined and enforced. The coding rules and standards should facilitate understanding, analysis, review, testing, and readability of the implemented code.
- e. The correct implementation of software requirements in each software component, module, and unit should be verified to ensure accuracy and conformance with design requirements.
- f.
Software unit (or component) testing should be performed as software is developed to ensure that it satisfies design requirements. The primary testing methods and standards, test cases used, test coverage, and test results should be documented, controlled, and maintained. The applicable review principles for software unit testing activities can be found in SRP BTP 7-14, Section B.3.2.4, and should be applied to the description of the test process and controls for the Alternate Review Process LAR review. Demonstration for the software implementation process consists of the following:
description of the general approach, resources, and schedule for software unit testing determination of the features to be tested design of the set of tests test execution and evaluation controls The software unit testing process reviews should focus on activities not previously reviewed and approved by the NRC unless there are changes in the NRC acceptance criteria.
The reviewer should evaluate whether the software implementation process description demonstrates that the software life cycle process meets the guidance of RG 1.171, Software Unit Testing for Digital Computer Software Used in Safety Systems of Nuclear Power Plants, or how the underlying regulatory requirements referenced in RG 1.171 are satisfied.
DI&C-ISG-06, Draft Revision 2 Page 47 of 66
- g. Demonstration for the development of software test documentation consists of a description of the software test documentation structure and content.
It is acceptable for a licensee to adapt test documentation to reflect important process differences, technology differences, and exceptions related to the use of integrated design environment tools. IEEE Std 829, IEEE Standard for Software and System Test Documentation, allows test documents to be combined or eliminated.
The reviews of the software test documentation process should focus on activities not previously reviewed and approved by the NRC unless there are changes in the NRC acceptance criteria.
The reviewer should evaluate whether the software implementation process description demonstrates that the process meets the guidance of RG 1.170, Test Documentation for Digital Computer Software Used in Safety Systems of Nuclear Power Plants, or how the underlying regulatory requirements referenced in RG 1.170 are satisfied.
- h. The software implementation should be analyzed, reviewed, approved, baselined, updated as necessary, and placed under CM.
- i.
The software implementation activities should be traceable to the software design, I&C system architecture, and system requirements.
- j.
The independent V&V team should develop the system V&V test procedures.
- k. The most recently baselined software implementation should be used as input to the ongoing life cycle activities.
- l.
The software implementation process should ensure that software items fulfill the design documentation. Applicable review guidance for code listings can be found in SRP BTP 7-14, Section B.3.3.4.3, and should be applied to the extent practicable for the Alternate Review Process LAR review.
D.4.2.1.8 Software Integration The reviewer should evaluate whether the software integration process description addresses the following:
- a. A software integration process should be developed to describe the methods for integrating software components and modules into software units. Aggregates of components and modules tested during implementation should be integrated into a software unit, in accordance with the integration process. The review principles for the software integration process can be found in SRP BTP 7-14, Section B.3.1.4.4, which may need to be adapted to tool-based methods of modern DI&C platforms.
- b. Critical elements of the software integration process should include, but are not limited to identifying software components, modules, and units for integration, defining and implementing the integration environment, managing interfaces, and identifying item integration sequences. Applicable review guidance for documenting these activities can be found in SRP BTP 7-14, Section B.3.3.5.3, and can be used to inform the review of the software integration process description to the extent practicable for the Alternate Review Process LAR review.
- c. Software integration testing should be conducted to verify that software requirements have been adequately implemented for this stage of the software development. The applicable review guidance for this activity is contained in SRP BTP 7-14,
DI&C-ISG-06, Draft Revision 2 Page 48 of 66 Section B.3.2.4, and can be used to inform the review of the description of the software integration testing process to the extent practicable for the Alternate Review Process LAR review.
- d. The software integration results should be documented, analyzed, reviewed, approved, updated as necessary, and placed under CM.
- e. The software integration results should be derived from and traceable to the software design, I&C system architecture, and I&C system requirements.
- f.
The most recently baselined software integration should be used as input to the ongoing life cycle activities.
D.4.2.1.9 I&C System Testing The reviewer should evaluate whether the I&C system testing process description addresses the following:
- a. A system test plan should document the integration and testing of all software items, hardware, manual processes, and other system interfaces that constitute the I&C system, consistent with the architectural design. The independent V&V team should develop the V&V test plans. The applicable review guidance for the system V&V test plans is found in SRP BTP 7-14, Section B.3.1.12.4.
- b. System testing should consider all of the integrated software components, modules, and units that have successfully passed integration testing, as well as the software system itself, integrated with any applicable hardware systems and human-system interfaces.
- c. System testing should be conducted on a complete, integrated system, using a baselined version of the hardware and system software, to evaluate the systems performance of the I&C system requirements.
- d. The test plan should include tasks to integrate and test all software, hardware, and human-system interfaces, to prepare the test environment, to write test cases (inputs, outputs, and test criteria), and to test interfaces with other systems.
- e. System test results should be documented. Not everything can be tested, and some items are verified and validated by analysis or review. For those items verified by test, test results should be analyzed to verify that I&C system requirements have been satisfied. Applicable review guidance for documenting test results is found in SRP BTP 7-14, Section B.3.2.4, and should be applied to the extent practicable for the Alternate Review Process LAR review.
- f.
Testing should validate the control, mitigation, or elimination of hazards in the I&C system design.
- g. The system test results should be documented, analyzed, reviewed, approved, updated as necessary, and placed under CM.
- h. The system test results should be used as input to the ongoing plant system design, installation, and test activities.
D.4.2.2 Project Management Processes The reviewer should evaluate the LAR description of the project management or organizational processes that will be employed by the QA program and used to define the projects organization, planning, execution, monitoring, control, and closure activities of the entire I&C
DI&C-ISG-06, Draft Revision 2 Page 49 of 66 safety system development effort. The project management concepts listed in SRP BTP 7-14, Sections B.3.1.1.4 and B.3.1.2.4, can be used to inform the review of the software management process description.
Use of NUREG/CR-6463, Review Guidelines on Software Languages for Use in Nuclear Power Plant Safety Systems, issued June 1996, as cited in SRP BTP 7-14, Section B.3.1.2.4, is not relevant if using tool-based methods of modern DI&C platforms and will apply only to the software coding languages used in the system development.
When the reviewer evaluates the LAR description of the organizational and project management processes, the reviewer should focus on the following:
- a. measures for the creation of plans to control the system development environment, including hardware and software in accordance with Criterion V, Instructions, Procedures, and Drawings, of Appendix B to 10 CFR Part 50, with the planning process resulting in a set of documents that will be used to control and oversee the development of system elements, including hardware and software
- b. controls for identifying the project scope, determination of deliverables, lines of communication, formal and informal reviews, and interfaces with other internal and external organizations
- c. provisions for the establishment, documentation, and maintenance of a schedule that considers the overall project, as well as interactions of milestones
- d. provisions for risk management, including problem identification, impact assessment, and development of risk-mitigation plans for risks that have the potential to significantly affect system quality goals, with appropriate metrics for tracking resolution progress, with additional guidance on software-related project risk activities of IEEE Std 7-4.3.2-2003, Clause 5.3.6
- e. establishment of quality metrics throughout the life cycle to assess whether the quality requirements of IEEE Std 603-1991, Clause 5.3, are being met, with additional guidance from IEEE Std 7-4.3.2-2003, Clause 5.3
- f.
adequate control of software tools to support system development and software V&V processes, with additional guidance in IEEE Std 7-4.3.2-2003, Clause 5.3.2
- g. provisions for the documentation and resolution of problems and nonconformances found in the system elements
- h. provisions for effective oversight of life cycle activities The NRC review of software project management should focus on the application-specific software development activities rather than the platform development process defined in an NRC-approved DI&C platform unless there are changes in the NRC acceptance criteria.
Through all aspects of this design, all changes and modifications should be documented and controlled. The project management function should incorporate the impacts of change in the project risks, schedule, and budget.
D.4.2.3 Software Quality Assurance Processes The reviewer should evaluate the LAR description of the software quality assurance processes.
SRP BTP 7-14, Section B.3.1.3.4, can inform the review of the software quality assurance
DI&C-ISG-06, Draft Revision 2 Page 50 of 66 process description to the extent practicable for an Alternate Review Process LAR review. The process used to develop the DI&C safety system should conform to the licensees approved QA program.
Clauses 5.3.3 and 5.3.4 of IEEE Std 7-4.3.2-2003 provide guidance on V&V activities and independent V&V, respectively.
The reviewer should evaluate whether the software life cycle process description demonstrates that the software life cycle process meets the guidance of RG 1.168 or how the underlying regulatory requirements referenced in RG 1.168 are satisfied. IEEE Std 1028, IEEE Standard for Software Reviews and Audits, provides guidance acceptable to the NRC staff for carrying out software reviews, inspections, walkthroughs, and audits, subject to certain provisions.
Although IEEE Std 1028 describes how to perform systematic software reviews, it does not establish the need to conduct specific reviews. Demonstration for the software review and audit activities should define which reviews in the software development process are systematic software reviews.
The NRC review of software QA should focus on the application-specific software development activities rather than the platform development process defined in an NRC-approved DI&C platform unless there are changes in the NRC acceptance criteria.
D.4.2.4 Software Verification and Validation Processes The reviewer should evaluate the LAR description of the software V&V processes. The applicable review guidance for software V&V processes is found in IEEE Std 1012, as endorsed by RG 1.168. The IEEE standard and RG 1.168 are referenced in SRP BTP 7-14, Sections B.3.1.10 and B.3.2.2. To the extent practicable, the IEEE standard and RG should be used to inform the review of the software V&V process description for the Alternate Review Process LAR review.
The reviewer should evaluate whether the software V&V processes follow the guidance of RG 1.168 or, alternately, describe how the regulatory requirements referenced in RG 1.168 are satisfied. Demonstration for the software V&V processes will address the following:
- a. V&V organization responsibilities
- b. V&V processes, activities, and tasks
- c. V&V reporting
- d. V&V administrative controls for anomaly resolution and reporting, task iteration policy, and deviation policy
- e. V&V test documentation It is acceptable for a licensee to adapt software V&V programs activities and tasks to reflect important process differences, technology differences, and exceptions related to the use of integrated design environment tools. Secure development and operating environment vulnerability assessments performed in accordance with the guidance in RG 1.152 can replace security analyses described in IEEE Std 1012, Clause 5 and Tables 1 and 2.
DI&C-ISG-06, Draft Revision 2 Page 51 of 66 The NRC review of software V&V should focus on the application-specific software development activities rather than the platform development process defined in an NRC-approved DI&C platform unless there are changes in the NRC acceptance criteria.
D.4.2.5 Configuration Management Processes The reviewer should evaluate the LAR description of the CM processes. Although some CM activities are performed by the vendor(s), ownership of the system design modification and oversight of vendor activities rests with the licensee. This responsibility includes ensuring that as the design proceeds through to completion, the licensee is ensuring that the final vendor design and implementation will support the plant needs for performing periodic surveillance and maintenance in accordance with plant technical specification requirements, and supports the specific plant operating procedures. Unless the licensee takes responsibility for oversight of the vendors product development and configuration management activities at the outset of the development process, the gap can begin to widen between what the functional performance requirements document specifies, what the vendor is going to provide, and the impact on current processes and practices.
The applicable review guidance for CM processes can be found in IEEE Std 828, as endorsed by RG 1.169, Configuration Management Plans for Digital Computer Software Used in Safety Systems of Nuclear Power Plants. SRP BTP 7-14, Sections B.3.1.11.4 and B.3.2.3, reference the IEEE standard and RG 1.169. To the extent practicable, reviewers should use the IEEE standard and the RG to inform their review of the CM process description for the Alternate Review Process LAR review. RG 1.152 endorses IEEE Std 7-4.3.2-2003, subject to the positions and modifications identified in the RG. IEEE Std 7-4.3.2-2003, Clause 5.3.5, provides guidance on CM.
The reviewer should evaluate whether the CM processes follow the guidance in RG 1.169 or, alternately, describe how the regulatory requirements referenced in RG 1.169 are satisfied.
Demonstration for the CM processes will address the following:
- a. the responsibilities and authorities for managing and accomplishing the planned CM activities
- b. the activities to be performed in applying CM to the project
- c. coordination of CM activities with the other activities in the project
- d. tools used for CM activities The LAR should describe the organizational responsibilities for CM and for any designated configuration control board. The licensee may specify how modified software, hardware, or documentation should be tested and verified. These controls do not have to be defined within the CM process; instead, these controls are typically defined as part of the V&V process. The description of the CM process should include information on documenting and managing system-build documents, as found in SRP BTP 7-14, Section B.3.3.5.3.
The NRC review of CM process controls should focus on the application-specific software and hardware development activities rather than the platform development process defined in an NRC-approved DI&C platform unless there are changes in the NRC acceptance criteria.
DI&C-ISG-06, Draft Revision 2 Page 52 of 66 D.5 Applying a Referenced Topical Report Safety Evaluation NRR Office Instruction LIC-101, Appendix B, Guide for Processing License Amendments, Section 4.2, Use of Precedent and References to Topical Reports, states the following:
If a licensee in its application or the NRC staff during its review identifies a deviation from the process or limitations associated with a topical report, the staff should address the deviation in its safety evaluation for the plant-specific license amendment application...
This section describes how the NRC staff should assess a referenced NRC-approved I&C topical report. This review would include evaluating how the licensee addressed plant-specific (or application-specific) action items in the cited NRC-approved topical report and the review of deviations from previously approved systems, hardware, software, or methodologies.
Section D.5 is not applicable if there is no topical report previously approved by the NRC.
D.5.1 Information To Be Provided D.5.1.1 Addressing Platform Changes after Approval of a Topical Report The LAR should identify changes to the system, hardware, software, or design life cycle methodology from a topical report previously approved by the NRC. The intent is to leverage prior NRC approvals and allow the NRC staff to evaluate any changes to ensure that safety conclusions reached by a previous review are not invalidated.
When changes affect the original NRC-approved topical report safety evaluation, the LAR should provide information that supports review of these changes during the safety evaluation.
Where appropriate, the LAR should cross-reference any NRC-approved documents to the items listed in Enclosure B. The LAR should state whether the cited document has changed since the last NRC review. For documents, including system, hardware, and software descriptions that have changes affecting the conclusions of the safety evaluation, the NRC staff should verify that the licensee has submitted, on the docket, a report describing the changes. If the changes are minor, the licensee can choose to include a description of the change in the LAR. The information provided should include adequate justification to allow the NRC staff to evaluate the acceptability of the change.
D.5.1.2 Resolution of Topical Report Plant-Specific Action Items A safety evaluation for an NRC-approved topical report may have a section titled Plant-Specific Action Items or Application-Specific Action Items or a similar title. These are open items that the licensee is expected to address in the LAR when using the NRC-approved topical report for a plant modification. The LAR should describe how each PSAI item is or will be resolved.
In the case of the Alternate Review Process for an LAR, the NRC staff should verify that the licensee has described the process for addressing those plant-specific items related to detailed design, implementation, testing, and ongoing life cycle activities (including associated V&V activities). Based on topical report review in accordance with SRP BTP 7-14, some topical reports include plant-specific items stating that the NRC staff should review detailed design, implementation, testing, and ongoing life cycle activities. For the Alternate Review Process, this is to be interpreted as the role of the licensee in accordance with the licensees QA program and Vendor Oversight Plan.
DI&C-ISG-06, Draft Revision 2 Page 53 of 66 The LAR should evaluate PSAIs involving planning documents against the regulatory guidance in Section D.4 or include a description of applicable licensee processes or programs used to address the PSAIs.
D.5.2 Evaluation The reviewer should evaluate whether the plant-specific application is bounded by the intended use of the platform as described in the NRC-approved topical report. If there are plant-specific deviations from the NRC-approved topical reports PSAIs, the reviewer should evaluate each deviation against appropriate regulatory criteria.
The reviewer should evaluate changes to the system, hardware, software, or design life cycle methodology from a previous NRC-approved topical report. The NRC staff should review changes that have affected safety evaluation conclusions to determine whether the changes continue to comply with regulatory requirements.
The reviewer should evaluate the resolutions for PSAIs. For the Alternate Review Process, the reviewer should evaluate the resolutions for PSAIs specific to detailed design, implementation, and testing against the regulatory guidance in Section D.4. Any PSAI that involves planning documents should be reviewed against the regulatory guidance in Section D.4 or covered by licensee processes or programs. For PSAIs that are addressed in the LAR and implemented by the licensee subsequent to issuance of the license amendment, a license condition may be established to verify that these PSAIs have been implemented in accordance with the design described in the application before system operation or at a time established in the license condition.
D.6 Compliance/Conformance Matrix for IEEE Standards 603-1991 and 7-4.3.2-2003 The reviewer should evaluate that the DI&C modification complies with IEEE Std 603-1991 and conforms to the guidance in IEEE Std 7-4.3.2-2003. The staff can develop a compliance/conformance matrix to perform this evaluation, if one is not provided in the LAR.
This section contains an example of such a compliance/conformance matrix. This example matrix provides a row for each clause in IEEE Std 603-1991 and in IEEE Std 7-4.3.2-2003.
Extended clauses are provided if needed to point to different LAR sections. The table also provides titles from the standards, defining the clause.
In the appropriate Compliance/Conformance column cell, each row states whether the LAR submittal complies with (C), partially complies with (PC), takes an exception (E), or does not apply (N/A) to each clause and extended clause (row). Rather than documenting methods of compliance with each IEEE standard clause in this matrix, the table indicates each clause and extended clause (row) in all the LAR sections (at the lowest subdivision of LAR section numbering) where the LAR, for each clause or extended clause, demonstrates one of the following:
- a. how full compliance is achieved
- b. why partial compliance is acceptable and why full compliance is not required
- c. why the alternative exception proposed is acceptable
- d. why the clause does not apply
DI&C-ISG-06, Draft Revision 2 Page 54 of 66 For the example provided in Table D.1, IEEE Std 7-4.3.2-2003 does not provide any additional guidance for Clause 4 requirements in IEEE Std 603-1991. However, IEEE Std 7-4.3.2-2003 defines several extended clauses under Clause 5.3. For both examples, each cell in Compliance and LAR Section would be completed, and the LAR should discuss the methods to be used to meet IEEE Std 603-1991 when applying the associated guidance of IEEE Std 7-4.3.2-2003.
The DI&C-ISG-06 Section column refers to the potential topic where the subject clause is discussed. The section or sections depend on the review process (i.e., Alternate Review Process or Tiers 1, 2, or 3).
Clauses under IEEE Std 7-4.3.2-2003 that are marked with an asterisk (*) indicate that the standard does not add anything beyond IEEE Std 603-1991.
Table D.1 IEEE Standards 603-1991 and 7-4.3.2-2003 Compliance/Conformance Table IEEE Std 603 Clause IEEE Std 7-4.3.2 Clause Title Compliance LAR Section DI&C-ISG-06 Section 4.1 4*
Safety System Design Basis D.2.3.1, D.9.1, D.9.2, D.3 4.2 D.2.3.1 4.3 D.2.3.1 4.4 D.2.3.1 4.5 D.2.3.1, D.3 4.6 D.2.3.1 4.7 D.2.3.1, D.3 4.8 D.2.3.1, D.9.8 4.9 D.2.3.1, D.9.8 4.10 D.2.3.1 4.11 D.2.3.1 4.12 D.2.3.1 5.1 5.1*
Single-Failure Criterion D.2.6.2.1.1, D.9.8 5.2 5.2*
Completion of Protective Action D.2.3.1, D.2.6.2.3.1, D.9.1, D.9.2, D.9.8 5.3 5.3 Quality D.2.3.1, D2.3.3.1, D.3, D.4 5.3.1 Software Development D.4 5.3.1.1 Software Quality Metrics D.4 5.3.2 Software Tools D.4
DI&C-ISG-06, Draft Revision 2 Page 55 of 66 IEEE Std 603 Clause IEEE Std 7-4.3.2 Clause Title Compliance LAR Section DI&C-ISG-06 Section 5.3.3 Verification and Validation D.4, D.9.6 5.3.4 Independent V&V (IV&V)
Requirements D.4 D.9.6 5.3.5 Software Configuration Management D.4, D.9.5 5.3.6 Software Project Risk Management D.4 5.4 5.4 Equipment Qualification D.2.3.3.1, D.3.1 5.4.1 Computer System Testing D.3.1 5.4.2 Qualification of Existing Commercial Computers D.3, D.9.9 5.5 5.5 System Integrity D.2.3.1, D.2.6.2.3.1, D.9.7 5.5.1 Design for Computer Integrity D.2.6.2.3.1, D.9.7 5.5.2 Design for Test and Calibration D.2.3.1 5.5.3 Fault Detection and Self-Diagnostics D.2.2.1, D.9.8 5.6 5.6 Independence D.2.6.2.2.1, D.9.1, D.9.2 5.6.1 Between Redundant Portions of a Safety System D.2.5.1 5.6.2 Between Safety Systems and Effects of Design-Basis Event D.2.5.1 5.6.3 Between Safety Systems and Other Systems D.2.5.1 5.6.4 Detailed Criteria D.2.5.1 5.7 5.7*
Capability for Testing and Calibration D.2.3.1, D.9.1, D.9.2 5.8 5.8*
Information Displays D.2.3.1, D.9.1, D.9.2 5.8.1 Displays for Manually Controlled Actions D.2.2.1 5.8.2 System Status Indication D.2.2.1 5.8.3 Indication of Bypasses D.2.2.1 5.8.4 Location D.2.2.1 5.9 5.9*
Control of Access D.2.3.1 D.8 5.10 5.10*
Repair D.2.3.1, D.9.1, D.9.2 5.11 5.11 Identification D.2.6.2.2.1, D.9.5 5.12 5.12*
Auxiliary Features D.2.5.1
DI&C-ISG-06, Draft Revision 2 Page 56 of 66 IEEE Std 603 Clause IEEE Std 7-4.3.2 Clause Title Compliance LAR Section DI&C-ISG-06 Section 5.13 5.13*
Multi-Unit Stations D.2.5.1 5.14 5.14*
Human Factors Considerations D.2.5.1 5.15 5.15 Reliability D.2.6.2.1.1, D.9.8 6.1 6*
Automatic Control D.2.6.2.3.1 6.2 Manual Control D.2.6.2.3.1 6.3 Interaction between the Sense and Command Features and Other Systems D.2.6.2.2.1 6.3.1 Requirements D.2.6.2.2.1 6.3.2 Provisions D.2.6.2.2.1 6.4 Derivation of System Inputs D.2.3.1 D.2.6.2.5.1 6.5 Capability for Testing and Calibration D.2.3.1, D.9.1, D.9.2 6.5.1 Checking the Operational Availability D.2.3.1 6.5.2 Assuring the Operational Availability D.2.3.1 6.6 Operating Bypasses D.2.3.1 6.7 Maintenance Bypass D.2.3.1, D.2.6.2.1.1 6.8 Setpoints D.2.3.1, D.7.1 7.1 7*
Automatic Control D.2.6.2.3.1 7.2 Manual Control D.2.6.2.3.1 7.3 Completion of Protective Action D.2.3.1, D.9.1, D.9.2 7.4 Operating Bypass D.2.3.1 7.5 Maintenance Bypass D.2.3.1, D.2.6.2.1.1 8.1 8*
Electrical Power Sources D.2.5.1 8.2 Non-electrical Power Sources D.2.5.1 8.3 Maintenance Bypass D.2.5.1
- The standard does not add anything beyond IEEE Std 603-1991.
D.7 Technical Specifications D.7.1 Information To Be Provided The LAR should provide proposed TS changes that demonstrate compliance with 10 CFR 50.36, Technical specifications. This includes proposed changes to instrument setpoints included in the TS. If the TS includes a setpoint control program, changes to that program should be identified.
Self-diagnostics in digital equipment can be used in some cases as an alternate means of accomplishing some surveillance requirements (SRs), or justifying less frequent manual
DI&C-ISG-06, Draft Revision 2 Page 57 of 66 surveillance and calibration. Performance of channel checks, channel calibrations, etc., may no longer be necessary if the digital equipments internal self-test and self-diagnostic functions can be credited. The SRs necessary to ensure the operability of the system and its components should be reflected in the proposed TSs. Any extension, modification, or deletion of TS should be documented and justified by the licensee.
In addition to a markup copy of the TS, the NRC staff should verify that the licensee has justified each change. This includes providing a detailed basis for how the digital equipment is used to support each added, modified, or deleted SR. These justifications, taken together, should demonstrate that the proposed TS provide for maintaining safe operation of the facility with respect to its associated functions.
D.7.2 Evaluation D.7.2.1 Technical Specifications The reviewer should evaluate the proposed TS in accordance with 10 CFR 50.36.
The reviewer should evaluate how the LAR allocates self-test and self-diagnostic features to system elements for those features used to support TS. The reviewer should evaluate whether the combination of self-test and self-diagnostic capabilities defined in the LAR, in combination with manual testing and external cross-checks, are sufficient to support existing TS and any proposed TS changes. This evaluation should include consistency between the TS and the self-tests and self-diagnostics implemented in the architecture (see Section D.2.2.1) for new system functions (see Section D.2.3.1) and to address system interfaces (Section D.2.5.1).
This evaluation should also include consistency between the TS and the TS assumptions regarding redundancy (Section D.2.6.2.1.1).
Reviewers evaluate TS LCOs being proposed for deletion against the four 10 CFR 50.36(c)(2)(ii) criteria that require establishment of an LCO for a system function. If none of the criteria apply to the system or function addressed by an existing LCO, the LCO may be deleted. Additionally, LCOs being proposed for addition should adequately define the lowest functional capability or performance levels of the system required for safe operation of the facility. This review includes the adequacy of the proposed LCOs and the potential need for additional LCOs that have not been proposed for addition to the TS.
The SRs associated with the LCOs that will govern system operation should be sufficient to test, calibrate, and inspect the system and its functions such that the necessary operability aspects of the system are ensured and the LCOs are met. As with the review of the LCOs, the staff should evaluate proposed SRs and the need for additional SRs.
SRP BTP 7-17, provides review guidance in this area.
D.7.2.2 Setpoint Changes Setpoints should meet IEEE Std 603-1991, Clause 6.8, in consideration of the uncertainties between the process analytical limit documented in Clause 4.4. The setpoint should be determined using a documented methodology.
Additional guidance on the establishment of instrument setpoints can be found in RG 1.105, Setpoints for Safety-Related Instrumentation, and Regulatory Issue Summary (RIS) 2006-17,
DI&C-ISG-06, Draft Revision 2 Page 58 of 66 NRC Staff Position on the Requirements of 10 CFR 50.36, Technical Specifications, Regarding Limiting Safety System Settings During Periodic Testing and Calibration of Instrument Channels, dated August 24, 2006 (ADAMS Accession No. ML051810077). SRP BTP 7-3, Guidance on Protection System Trip Point Changes for Operation with Reactor Coolant Pumps out of Service, provides additional guidance on multiple setpoints used to allow operation with reactor coolant pumps out of service.
The reviewer should verify that the information provided describes the hardware and software in detail sufficient for the NRC staff to conclude that IEEE Std 603-1991, Clause 6.8, has been met.
D.8 Secure Development and Operational Environment D.8.1 Information To Be Provided The LAR should demonstrate the proposed DI&C system is adequately robust to perform its safety function under design-basis conditions, including normal and adverse environments. The LAR should provide information describing a secure environment, including any issues that may affect the secure environment and the DI&C equipment.
For Tiers 1, 2, and 3, the LAR should provide information describing the vulnerability assessment and the SDOE controls that address Regulatory Position 2.1, Concepts Phase, through Regulatory Position 2.5, Test Phase, of RG 1.152.
For the Alternate Review Process, the LAR should provide the following information to address RG 1.152:
- a. a description of the vulnerability assessment
- b. a description of the secure development environment controls
- c. the System Requirements Specification (see Section D.2.2.2) for the SOE controls All SDOE and software information identified in RG 1.152, Regulatory Position 2, including the test phase specifications and results validating the requirements for the SOE, should be available for review by the NRC staff. The need to submit any of this information should be determined during the licensing review.
Documentation detailing how the licensee implemented (or will implement, in the case of the Alternate Review Process) SDOE controls should be available for review by the NRC staff.
D.8.2 Evaluation The reviewer should determine whether the LAR demonstrates compliance with RG 1.152, Regulatory Position 2, for the SDOE of the system under review. For Tier 1 and the Alternate Review Process, the review is limited to the application software and hardware.
The NRC staff should review the vulnerability assessment description and verify that the licensee has performed a vulnerability assessment identifying the vulnerabilities that could affect the secure development and reliable and secure operation of the digital safety system.
RG 1.152, Section B, page 5, presents a discussion of vulnerabilities that could affect the
DI&C-ISG-06, Draft Revision 2 Page 59 of 66 reliability of the system. RG 1.152, Section C, Regulatory Position 2.1, contains guidance for performing the vulnerability assessment.
The NRC staff should review the information provided to determine that the digital safety system:
- a. was (or will be, in the case of the Alternate Review Process) designed, developed, and tested in a secure development environment
- b. will be protected from inadvertent actions in an SOE as defined in RG 1.152 The NRC I&C staff review does not evaluate the adequacy of cyber security features for compliance with 10 CFR 73.54.
D.9 Other Review Guidance for Tier 1, 2, and 3 Reviews The guidance in this section focuses on the evaluation of design outputs and system validation test results, which should be available during later stages of DI&C system development. This guidance is intended to be applied to Tier 1, 2, and 3 reviews as needed. Because Alternate Review Process evaluations are to be completed before completion of late-stage product development activities, the documentation necessary to perform the evaluations covered in this section are not expected to be available to the NRC reviewer before the NRC staff decides whether to issue or deny the license amendment.
D.9.1 Software Requirements Specification D.9.1.1 Information To Be Provided Review (Phase 1): Software Requirements Specification SRP BTP 7-14, Section B.3.3.1, Requirements ActivitiesSoftware Requirements Specification, contains the review guidance for a Software Requirements Specification (SRS).
This section contains SRP references to applicable guidance:
- a. RG 1.172
- b. IEEE Std 830, IEEE Recommended Practice for Software Requirements Specifications, which describes an acceptable approach for preparing an SRS for safety system software
- c. NUREG/CR-6101, Software Reliability and Safety in Nuclear Reactor Protection Systems, issued November, 1993 (ADAMS Accession No. ML072750055),
Section 3.2.1, Software Requirements Specification, and Section 4.2.1, Software Requirements Specifications The SRS documents the results of the requirements phase activities by the design team and identifies the aspects of the safety system to be addressed in the software design.
D.9.1.2 Evaluation Errors in the specification of criteria or misunderstanding of their intent can be a significant source of software errors. The SRS should be carefully examined to ensure that criteria are consistent, correct, understandable, traceable, unambiguous, and verifiable. The complexity of
DI&C-ISG-06, Draft Revision 2 Page 60 of 66 the SRS depends on the complexity of the system being proposed, and the level of detail should reflect that level of complexity.
The staff may need to review two SRSs, one for the platform software and another for the applications software. Each of these may be reviewed separately.
Each SRS should be traceable to one or more safety system criteria, and the requirements traceability matrix should show where in the software the requirement is being performed. The key to an adequate SRS is its understandability.
The NRC staff should review the SRS using review guidance in SRP BTP 7-14, Section B.3.3.1.3, and should review a limited number of criteria during a thread audit, as described in SRP BTP 7-14, Section B.3.2.2. The NRC staff should expect to find sufficient V&V documentation to show that there was a 100 percent V&V of the software criteria by the V&V organization.
D.9.2 Software Design Specification D.9.2.1 Information To Be Provided Review (Phase 1): Software Design Specification The review guidance for the Software Design Specification (SDS) is contained in SRP BTP 7-14, Section B.3.3.3, Design ActivitiesSoftware Design Specification. This section contains SRP applicable review guidance in NUREG/CR-6101, Section 3.3.2, Software Design Specification, and Section 4.3.2, Software Design Specifications.
The engineer who implements the software design is the primary user of the SDS. The V&V team ensures that the software accurately reflects the software requirements. The SDS should be detailed enough to enable the V&V team to determine how software specifications are to be implemented. The SDS should also be traceable to software implementation code or function block diagrams.
D.9.2.2 Evaluation The NRC staff should review the SDS using the review guidance in SRP BTP 7-14, Section B.3.3.3.3, and should perform a sample review of specifications using a thread audit technique. The NRC staff should expect to find sufficient V&V documentation to show that there was a 100 percent V&V of the software design specifications by the V&V organization.
D.9.3 Changes to Referenced Platform Design D.9.3.1 Information To Be Provided Review (Phase 1): Design Analysis Report (System, Hardware, Software, and Methodology Modifications)
The LAR should identify all changes made to hardware, software, or design life cycle methodology of a referenced NRC-approved topical report.
DI&C-ISG-06, Draft Revision 2 Page 61 of 66 D.9.3.2 Evaluation The NRC staff should review the changes from the NRC-approved topical report and determine if the safety conclusions reached by a previous review remain valid. If the platform vendor has a platform change review process, the NRC staff should review the results of that process and determine if the staff concurs with the conclusions relative to the NRC-approved topical report impact.
If the changes affect the platform topical report safety evaluation conclusions, an effort separate from the LAR review may need to be undertaken to update the platform topical report safety evaluation.
D.9.4 Software Safety Analysis D.9.4.1 Information To Be Provided Review (Phase 2): Safety Analysis SRP BTP 7-14, Section B.3.2.1, Acceptance Criteria for Safety Analysis Activities, presents the review guidance for the implementation of a Software Safety Analysis (SSA). The acceptance criterion for SSA implementation is that the tasks in that plan have been carried out.
D.9.4.2 Evaluation The reviewer should verify that the LAR presents documentation showing that the SSA tasks have been successfully accomplished.
D.9.5 Configuration Management Activities D.9.5.1 Information To Be Provided Review (Phase 2): As-Manufactured, System Configuration Documentation SRP BTP 7-14, Section B.3.2.3, contains this SRP reference to applicable guidance: RG 1.169 endorses IEEE Std 828, subject to specific provisions identified in the RG, as providing guidance that is acceptable for carrying out CM. Although some CM activities are performed by the vendor(s), ownership of the system design modification and oversight of vendor activities rests with the licensee (see Section D.4.2.5).
D.9.5.2 Evaluation The reviewer should verify that the LAR presents documentation showing that the CM tasks for associated activity groups have been successfully accomplished.
D.9.6 Testing Activities D.9.6.1 Information To Be Provided Review (Phase 2): Summary Test Reports (Including FAT)
SRP BTP 7-14, Section B.3.2.4, contains SRP references to applicable guidance:
DI&C-ISG-06, Draft Revision 2 Page 62 of 66
- a. In RG 1.168, Sections 7.b, Regression Analysis and Testing, and 7.d, Test Evaluation, contain guidance related to testing activities.
- b. RG 1.170 endorses IEEE Std 829, with a few noted exceptions, and identifies an acceptable method for addressing test documentation.
- c. RG 1.171 endorses IEEE Std 1008, IEEE Standard for Software Unit Testing, with a few noted exceptions, and identifies an acceptable method for addressing software unit testing.
D.9.6.2 Evaluation The software validation activities should demonstrate that all validation tests specified by the Software Verification and Validation Plan were successful. FAT is one of those activities.
D.9.7 System IntegrityTime Response/Deterministic Performance D.9.7.1 Information To Be Provided Review (Phase 1):
(1) System Response Time Analysis Report (2) Design Report on Computer Integrity, Test and Calibration, and Fault Detection Review (Phase 2): (1) System Response Time Confirmation Report (2) Hardware Reliability Analysis Clause 5.5 of IEEE Std 603-1991 requires that the safety systems be designed such that the system can accomplish its safety functions under the full range of applicable conditions enumerated in the design basis. Review criteria for system integrity is provided in SRP Chapter 7, Appendix 7.1-C, Section 5.5, System Integrity.
A special concern for digital computer-based systems is confirmation that system real-time performance is adequate to ensure completion of protective action within the critical points of time identified as required by Clause 4.10 of IEEE Std 603-1991.
D.9.7.2 Evaluation Evaluation of computer system hardware integrity should be included in the evaluation against IEEE Std 603-1991. The licensees software safety analysis activities should demonstrate computer system software integrity (including the effects of hardware-software interaction).
The NRC staff should assess whether tests have been conducted on safety system equipment components and the system racks and panels as a whole to demonstrate that the safety system performance is adequate to ensure completion of protective actions over the range of transient and steady-state conditions of both the energy supply and the environment. The tests should show that if the system does fail, it fails in a safe state, and that failures detected by self-diagnostics should also place a protective function into a safe state.
SRP BTP 7-21 provides supplemental guidance on evaluating response time for digital computer-based systems and discusses design constraints that allow greater confidence in the
DI&C-ISG-06, Draft Revision 2 Page 63 of 66 results analyses or prototype testing to determine real-time performance. The information provided should be sufficient for the NRC staff to determine if adequate testing and analysis have been performed on the system as a whole and its components. The review of system integrity should determine if the design provides for safety systems to fail in a safe state, or into a state that has been demonstrated to be acceptable on some other defined basis, if conditions such as disconnection of the system, loss of energy, or adverse environments are experienced.
This aspect is typically evaluated through evaluation of the licensees failure modes and effects analysis.
D.9.8 Platform and System-Level Failure Modes D.9.8.1 Information To Be Provided Review (Phase 2): (1) System Level Failure Modes and Effects Analysis (2) Platform Level Failure Modes and Effects Analysis The FMEA should justify the acceptability of each failure effect. Reactor trip system functions should typically fail in the tripped state. Engineered safety feature actuation system (ESFAS) functions should fail to a predefined safe state. For many ESFAS functions, this predefined safe state should be that the actuated component remains as-is.
D.9.8.2 Evaluation Computer-based safety systems should, upon detection of inoperable input instruments, automatically place the protective functions associated with the failed instrument(s) into a safe state (e.g., automatically place the affected channel(s) in trip), unless the affected channel has already been placed in a bypass mode (e.g., this could change a two-out-of-four logic to a two-out-of-three logic). Hardware failures or software errors detected by self-diagnostics should also place a protective function into a safe state or leave the protective function in an existing safe state. Failure of computer system hardware or software error should not inhibit manual initiation of protective functions or the performance of preplanned emergency or recovery actions. During either partial-or full-system initialization or shutdown after a loss of power, control output to the safety system actuators should fail to a predefined, preferred failure state.
A system restart upon restoration of power should not automatically transfer the actuators out of the predefined failure state. Changes to the state of plant equipment from the predefined state following restart and reinitialization (other than changes in response to valid safety system signals) should be in accordance with appropriate plant procedures.
D.9.9 Qualification of Commercial Computers D.9.9.1 Information To Be Provided Review (Phase 1): Commercial-Grade Dedication Plan(s)
Review (Phase 2): Commercial-Grade Dedication Report(s)
Clause 5.4.2 of IEEE Std 7-4.3.2-2003 presents the fundamental criteria for demonstrating that a commercial computer will perform its intended safety functions. Additional guidance is provided in EPRI TR-106439, Guideline on Evaluation and Acceptance of Commercial Grade Digital Equipment for Nuclear Safety Applications, issued October 1996, as accepted by the
DI&C-ISG-06, Draft Revision 2 Page 64 of 66 NRC safety evaluation dated July 17, 1997 (ADAMS Accession No. ML12205A284), and EPRI TR-107330, Generic Requirements Specification for Qualifying a Commercially Available PLC for Safety-Related Applications in Nuclear Power Plants, issued December 1996, as accepted by the NRC safety evaluation dated July 30, 1998 (ADAMS Accession No. ML12205A265).
For commercial-grade software intended for use in safety-related systems, one of the critical characteristics is implementation of a high-quality development process. In essence, the NRC staff should verify that the licensee has demonstrated that the process used to develop the commercial software was as rigorous as that for software used in safety-related applications. If this cannot be demonstrated, then compensatory measures should be taken, such as extensive operating experience and, if necessary, additional analyses, tests, or inspections.
EPRI TR-106439 provides guidance for the evaluation of existing commercial computers and software to comply with the criteria of Clause 5.4.2 of IEEE Std 7-4.3.2-2003. The guidance of SRP BTP 7-14 may be applied to the evaluation of vendor processes described in EPRI TR-106439. EPRI TR-107330 provides more specific guidance for the evaluation of existing programmable logic controllers (PLCs).
D.9.9.2 Evaluation The qualification process (e.g., as described in the Commercial-Grade Dedication Plan) should be done by evaluating the hardware and software design using the criteria of IEEE Std 7-4.3.2-2003. Acceptance should be based on information demonstrating that the digital system or component, including hardware, software, firmware, and interfaces, can perform its specified functions and has been developed in accordance with a high-quality development process. The acceptance and its basis should be documented (e.g., in a Commercial-Grade Dedication Report) and maintained with the qualification documentation.
If traditional qualification processes cannot be applied, commercial-grade dedication is an alternative approach to verifying that a component is acceptable for use in a safety-related application. The objective of commercial-grade dedication is to verify that the item being dedicated is equivalent to equipment developed under a 10 CFR Part 50, Appendix B, program.
The dedication process for the digital safety-related system (e.g., as described in the Commercial-Grade Dedication Plan) should entail identification of the physical, performance, and dependability (see EPRI TR-106439) critical characteristics necessary to provide adequate confidence that the proposed digital system or component can achieve the safety function. The dedication process should apply to the computer hardware, software, and firmware that are necessary to accomplish the safety function. The dedication process for software should include an evaluation of the development process and the implementation of the development process.
In IEEE Std 7-4.3.2-2003, Clauses 5.4.2.1 through 5.4.2.2 describe the preliminary and detailed phase activities for commercial-grade item dedication.
D.9.10 Hardware Development Process D.9.10.1 Information To Be Provided Review (Phase 1): Hardware Development Process
DI&C-ISG-06, Draft Revision 2 Page 65 of 66 The NRC staff should verify that the licensee has demonstrated that the hardware development process and the quality control methods used during system development will meet regulatory criteria by providing information that governs the process and methods. The LAR should include information that covers both the development methods used during the design of individual hardware modules and the design of the application-specific system to be used in implementing the safety function. The quality control methods used for system development should be consistent with a 10 CFR Part 50, Appendix B, QA program and with the criteria of IEEE Std 603-1991, Clause 5.3 Quality.
D.9.10.2 Evaluation The reviewer should evaluate the licensee information on the hardware development process to determine whether the licensee satisfies the following criteria:
- a. 10 CFR 50.54(jj) and 10 CFR 50.55(i) require that structures, systems, and components be designed, fabricated, erected, constructed, tested, and inspected to quality standards commensurate with the importance of the safety function to be performed.
- b. 10 CFR 50.55a(h) incorporates, based on the date the construction permit was issued, either IEEE Std 279, Clause 4.3, or IEEE Std 603-1991, Clause 5.3.
- c. 10 CFR Part 50, Appendix A, GDC 1, Quality Standards and Records.
- d. RG 1.164, Dedication of Commercial-Grade Items for Use in Nuclear Power Plants.
As mentioned in Section B of this ISG, where a licensee references (i.e., bases their design on) an NRC approved platform topical report, the NRC staff should be able to, where appropriate, limit its review to assessing whether the application of the DI&C modification conforms to the topical report approval. The NRC staff should verify that, where the hardware development process and quality control methods used have previously been described by the vendor and evaluated by the NRC staff, the licensee has referred to that description and the safety evaluation applies to the plant specific DI&C modification. The NRC staff should verify that the licensee has identified and justified deviations from previously reviewed and approved processes or methods and revision changes since NRC approval.
Enclosure A Page 1 of 2 DI&C-ISG-06 Enclosure ASample Summary of Initial Public Meeting To Discuss Plans To Request NRC Approval in Support of a Digital I&C Modification License Amendment Request MEMORANDUM TO:
[NAME], Director Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation
[NAME], Director Division of Engineering Office of Nuclear Reactor Regulation FROM:
[NAME], Project Manager Plant Licensing Branch [X-X]
Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation
SUBJECT:
SUMMARY
OF [MONTH DAY, YEAR], CATEGORY 1 PUBLIC MEETING TO DISCUSS [LICENSEE] PLANS TO REQUEST NRC APPROVAL OF A DIGITAL I&C PLANT MODIFICATION OF [SYSTEM] USING [PLATFORM]
On [DATE], the U.S. Nuclear Regulatory Commission (NRC) staff conducted a Category 1 public meeting to discuss [LICENSEE]s plans for modifying the [PLANT] [SYSTEM] to the
[PLATFORM] digital instrumentation and control (I&C) system.
The purpose of this meeting was to discuss the initial design concepts and any site-specific issues identified by [LICENSEE]. These discussions focused on how the [LICENSEE] should address the review area of [REVIEW AREA].
In these discussions, the licensee identified the following characteristics and design specifications that contribute to the [PLATFORM]s compliance with criteria in [REVIEW AREA].
Item 1 Item 2 The NRC staff provided feedback to [LICENSEE] noting that the following aspects of the design, based on the available high-level information, seemed consistent with the NRC staffs position on [REVIEW AREA]:
Item 1 Item 2 The following review areas were discussed:
relevant precedents for similar systems in other plants communications interfaces secure development and operating environment plant-specific action items for [platform]
regulations and general design criteria to be addressed applicable guidance to be considered
Enclosure A Page 2 of 2 DI&C-ISG-06 development process planning and implementation unique requirements for existing system design defense-in-depth and diversity The NRC discussed guidance criteria for determination of the appropriate review process and tier level in relation to the proposed [PLANT][SYSTEM] based on current project status and the design and implementation schedules for the [PLANT][SYSTEM]. The NRC made a preliminary determination that this evaluation can be performed under the [Tier 1, 2, and 3 or Alternate Review Process] guidance. Based on this determination, the licensee committed to prepare its license amendment request (LAR) in accordance with [REVIEW PROCESS AND/OR TIER LEVEL] guidance provided in this interim staff guidance.
[For Tier 1, 2, or 3 submittals for Phase 1, and 2] The NRC discussed guidance criteria for phased submittals in relation to the proposed [PLANT][SYSTEM] based on planned development activities. The NRC made a preliminary determination that Phase 1 submittal documentation will be provided with the LAR and that Phase 2 documentation will be provided by [an agreed upon date, before issuance of the safety evaluation.] [For Alternate Review Process submittals only] The NRC discussed guidance criteria for submittals in relation to the proposed [PLANT][SYSTEM] based on planned development activities. A preliminary determination was made concerning the documentation submittal schedule.]
The NRC staff identified the following aspects of the design for which additional information is needed before the staff can evaluate whether the proposed modification is fully consistent with the NRC staffs position on [REGULATORY POSITION]:
Item 1 Item 2 Concurrence for this memorandum shall include the Chief, Instrumentation & Controls Branch, the Chief, Plant Licensing Branch X-X, and any other Branch Chiefs whose review authorities may have been discussed. Concurrence may also include division level management, as appropriate.
Enclosure B Page 1 of 2 DI&C-ISG-06, Draft Revision 2 Enclosure BInformation Provided in Support of a License Amendment Request for a Digital I&C Modification This enclosure can be used as a cross-reference or checklist for addressing the descriptive material identified in the body of this interim staff guidance. It is intended to be used in conjunction with the referenced sections of this interim staff guidance provided in parentheses for each row.
The list of information in this enclosure represents a typical system modification. Different information may be provided, depending on the scope and complexity of the system modification, to support the U.S. Nuclear Regulatory Commissions (NRCs) evaluation against the applicable acceptance criteria.
Tier Plant-Specific Information Submitted with License Amendment Request (Phase 1 for Tier 1, Tier 2, Tier 3)
A R 1 2 3 1.1 X
(Summary of) Application Software Planning and Processes (see D.4) 1.2 X
(Summary of) Vendor Oversight Plan (see C.2.2) 1.3 X X X Approved Topical Report Safety Evaluation (see D.5) 1.4 X X X X System Description (see D.1) 1.5 X X X X System Architecture (see D.2) 1.6 X X X X (Summary of) Hardware Equipment Qualification (see D.3) 1.7 X X X X (Unified Compliance/Conformance Matrix for) IEEE Stds 603-1991 and 7-4.3.2-2003 (see D.6) 1.8 X X X X (Changes to) Technical Specifications (see D.7) 1.9 X X X X Setpoint Methodology and Calculations (see D.7)
Provided when TS setpoint methodology changes or calculations deviate from or are not addressed in an applicable referenced NRC-approved TR 1.10 X X X X Secure Development and Operational Environment (see D.8) 1.11 X X X Software Requirements Specification (see D.9.1) 1.12 X X X Software Design Specification (see D.9.2) 1.13 X X X Design Analysis Reports for Platform Changes (see D.9.3) 1.14 X X X System Response Time Analysis Report (see D.9.7) 1.15 X X Design Report on Computer Integrity, Test and Calibration, and Fault Detection (see D.9.7) 1.16 X Commercial-Grade Dedication Plan (see D.9.9) 1.17 X Quality Assurance Plan for Hardware (see D.9.10) 1.18 X (Summary of) Hardware Development Process (see D.9.10)
Enclosure B Page 2 of 2 DI&C-ISG-06, Draft Revision 2 Tier Phase 2 - Submitted before Requested Approval (Tier 1, Tier 2, Tier 3 only)
Note: This table does not apply to Alternate Review Process applications.
1 2
3 2.1 X X X Safety Analysis (see D.9.4) 2.2 X X X As-Manufactured, System Configuration Documentation (see D.9.5) 2.3 X X X Summary Test Reports (Including Test Results up to FAT) (see D.9.6) 2.4 X X X System Response Time Confirmation Report (see D.9.7) 2.5 X X X Reliability Analysis (see D.9.7) 2.6 X X X System-Level Failure Modes and Effects Analysis (see D.9.8) 2.7 X X X Qualification Test Methodologies (see D.3) 2.8 X X Platform-Level Failure Modes and Effects Analysis (see D.9.8) 2.9 X X (Summary of) Electromagnetic Interference, Temperature, Humidity, and Seismic Testing Results (see D.3) 2.10 X Commercial-Grade Dedication Report(s) (see D.9.9)
Enclosure C Enclosure CSample Safety Evaluation Table of Contents for a Digital I&C License Amendment 1.0 Introduction........................................................................................................................
2.0 Regulatory Evaluation........................................................................................................
3.0 Technical Evaluation..........................................................................................................
3.1 System Description and Configuration..............................................................................
3.2 Proposed Technical Specification Changes......................................................................
3.3 System Interfaces Including Digital Instrumentation Communications..............................
3.4 Defense-in-Depth and Diversity.........................................................................................
3.5 Setpoint Methodology and Calculations............................................................................
3.6 Response Time Performance............................................................................................
3.7 System Development Process...........................................................................................
3.7.1 Software Planning Documents..........................................................................................
3.7.2 Software Process Implementation.....................................................................................
3.7.3 Software Design Outputs...................................................................................................
3.8 Equipment Qualification.....................................................................................................
3.8.1 Environmental Qualification...............................................................................................
3.8.1.1 Temperature and Humidity Qualification...........................................................................
3.8.1.2 Seismic Qualification.........................................................................................................
3.8.2 Electromagnetic Compatibility Qualification.......................................................................
3.8.3 Radiation Qualification.......................................................................................................
3.9 Deviations from Prior Licensing Topical Reports...............................................................
3.10 Confirmation of Licensing Topical Reports Safety Evaluation Plant-Specific Actions......
3.12 Tests and Self-Test Diagnostics........................................................................................
3.13 System Failure Analysis....................................................................................................
3.14 Determinism.......................................................................................................................
3.15 Compliance with IEEE Std 603-1991 Requirements.........................................................
3.16 Conformance to IEEE Std 7-4.3.2-2003............................................................................
3.17 Secure Development and Operational Environment.........................................................
3.18 Inspection Follow-up Items................................................................................................
4.0 Conclusion.........................................................................................................................
5.0 References........................................................................................................................
6.0 Acronyms...........................................................................................................................