ML18096A899
| ML18096A899 | |
| Person / Time | |
|---|---|
| Site: | Salem |
| Issue date: | 08/14/1992 |
| From: | Miltenberger S Public Service Enterprise Group |
| To: | NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM) |
| References | |
| GL-88-17, NLR-N92112, NUDOCS 9208240017 | |
| Download: ML18096A899 (2) | |
Text
Public Service Electric and Gas Company Steven E. Miltenberger Public Service Electric and Gas Company P.O. Box 236, Hancocks Bridge, NJ 08038 609-339-1100 Vice President and Chief Nuclear Officer AUG 14 1992 NLR-N92112 United States Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 Gentlemen:
GENERIC LETTER 88-17 LOSS OF DECAY HEAT REMOVAL SALEM GENERATING STATION UNIT NO. 1 DOCKET NO. 50-272 By letter dated December 28, 1990 (ref: NLR-N90233), Public Service Electric & Gas Company (PSE&G) submitted a schedule for implementation of the Reactor Coolant System (RCS) Level Indication and the Continuous Monitoring of Decay Heat Removal (DHR) System Performance.
As described in the above referenced letter, the proposed modifications included: A) the installation of two independent differential pressure transmitters between the RCS sample lines of loop 1 and 3, and the vent line in the pressurizer spray piping, and B) to monitor DHR system parameters by using the plant computer with display and alarm functions provided at the computer CRT located on the control console.
Accordingly, as requested by your letter dated January 24, 1991, PSE&G notifies you that it has successfully implemented the commitments of NLR-N90233 for Salem Unit 1 during its tenth Refueling Outage.
Should there be any questions with regard to this submittal, please do not hesitate to contact us.
-- _"' 920824001 7 920814
~DR _ADOCK 05000272 p
PDR Sincerely, _
C/?/?~~~~r_~
Document Control Desk NLR-N92112 C
Mr. J. c. Stone Licensing Project Manager Mr. T. Johnson Senior Resident Inspector 2
Mr. T. Martin, Administrator Region I Mr. Kent Tosch, Chief New Jersey Department of Environmental Protection Division of Environmental Quality Bureau of Nuclear Engineering CN 415 Trenton, NJ 08625 AUG 14 1992