ML18082A669

From kanterella
Jump to navigation Jump to search
Forwards Addl Info in Response to NRC 800618 Request Re Auxiliary Feedwater Sys.Auxiliary Feedwater Sys for Both Units Are Identical in Design,Including Equipment & Automatic Initiation Logic
ML18082A669
Person / Time
Site: Salem  
Issue date: 07/01/1980
From: Mittl R
Public Service Enterprise Group
To: Schwencer A
Office of Nuclear Reactor Regulation
References
NUDOCS 8007030161
Download: ML18082A669 (14)


Text

..

J PS~G Public Service Electric and Gas Company 80 Park Place Newark, N.J. 07101 Phone 201 /430-7000 July l, _l980 Director of Nuclear Reactor Regulation United States Nuclear Regulatory Coinrnission Washington, :D., c.

20S55 Attention:

Gentlemen:

~r. :A. Schwencer, Acting Chief Licensing Branch No. 3 *

  • Division of Licensing AUXILIARY FEEDWATER SYSTEM NO. 1 AND 2 UNITS SALEM NUCLEAR GENERATING STATION DOCKET NOSe 50-272 AND S0~.3ll Public Service Electric and Gas hereby submits additional information in response to your concerns regarding.the Auxiliary Feedwater System. 'This informat.lon was requested at a meeting with members of your staff on June lB, l980.,

The Auxiliary Feedwater Systems for both Sal'em. 1. and 2 are identical in design, including equipment and automatic initiation logic~ _as indicated in our letter dated June 27,._l9B:O.

Should. you have any questions, do not hesitate to contact us.

Enclosure CC:

1879 1979

?J;;r-rs,

R. :L. Mittl General Manager -

Licensing and Environment Enginee~ing and Construction

])ilr. :S. :A. Varga, Chief Operating Reactors Branch No. 1 Division of Licensing 95-2001 (300M) 1-79

v July l, l980 Director of Nuclear Reactor Regulation United States Nuclear Regulatory Commission Washington, D. c.

20555 Attention:

Gentlemen:

Mr. A. Schwencer, Acting Chief Licensing Branch No. 3 Division of Licensing AUXILIARY FEEDWATER SYSTEM NO. 1 AND 2 UNITS SALEM NUCLEAR GENERATING STATION DOCKET NOS. 50-272 AND 50-311

.,,, r J'J Public Service Electric and Gas hereby submits additional information in response to your concerns regarding the Auxiliary Feedwater System.

This information was requested at a meeting with members of your staff on June 18, l980.

The Auxiliary Feedwater Systems for both Salem 1 and 2 are identical in design, including equipment and automatic initiation logic, as indicated in our letter dated June 27, 1980.

Should you have any questions, do not hesitate to contact us

  • Enclosure CC:

Cf N;f,,*, :.

(

  • ,~*

. ~~y.'tr~~y.*yt~-rs, J

I t*.j,',/ :****/

R. L. Mittl General Manager -

Licensing and Environment Engineering and Construction Mr. s. A. Varga, Chief Operating Reactors Branch No. 1 Division of Licensing

Additional Information Auxiliary Feedwater System No. l and 2 Units Salem Nuclear Generating Station

1.

Salem 2 FSAR Amendment 43 addresses branch technical position RSB 5-1, Cold Shutdown Requirements.

We note that the long-term auxiliary feedwater supply source (service water system) may contain salt in solution.

Justify the salt content of this water (for the time period required to satisfy RSB 5-1) against the follow-ing considerations:

a.

degradation of steam generator shell side heat transfer due to salt plating or tubes,

b.

clogging of steam generator secondary side flow paths by clumps of accumulated salt,

c.

corrosion effects of the salt.

Also describe provisions (procedures, special equipment, etc.) which would be used to attenuate the effects of the salt (a,b,c, above).

Response

1.

ASSUMPTIONS Based upon the information contained in the response to Branch Technical Position RSB 5-1 (FSAR Amendment 43, Question 9.61), the following scenario has been evaluated:

A.

There has been a loss of offsite power.

Coincident with the loss of offsite power the turbine and reac-tor systems are tripped, and the plant begins decay heat removal using emergency supplies.

.. B.

Auxiliary Feedwater is initially provided from the 220,000 gallon Seismic Category l Auxiliary Feed-water Storage Tank (AFST).

This tank contains con-densate grade make-up water.

When the supply of water in the AFST has been depleted, Auxiliary Feed-water pump suction is transferred from the AFST to the Seismic Category l Service Water System.

This system is supplied directly from the tidal section of the Delaware River.

The salinity of the river at this point will vary with the overall hydrological environment of the area.

Plant records show that normally the Total Dissolved Solids (TDS) content of the river is in the range 9,000 -

13,000 ppm at Salem.

In the absence of a reliable value for the upper limit of TDS previou~ly experienced in this part of the river, and to provide maximum con-servatism in evaluating the effects of the postu-lated incident, it is assumed that at the time of the incident the river will have a TDS value of 35,000 ppm as sodium chloride.

This value corres-ponds to the salt concentration accepted as being representative of "international sea water", and will have a higher TDS content than the most concen-trated brackish water postulated for the Delaware River in the area of the Salem Station.

C.

Decay heat removal is achieved using three of the four steam generators.

Cooling is achieved by dumping steam to atmosphere via Power Operated Relief Valves (PORV).

D.

The three available steam generators are maintained at Normal Working Level (NWL) throughout the major part of the scenario.

Level is maintained using only Seismic Category l water supplies.

E.

Following the loss of offsite power the unit is held at the Hot Standby condition.

After 43 hours4.976852e-4 days <br />0.0119 hours <br />7.109788e-5 weeks <br />1.63615e-5 months <br /> at the no load condition, Reactor Coolant System cooldown is initiated.

After 5 hours5.787037e-5 days <br />0.00139 hours <br />8.267196e-6 weeks <br />1.9025e-6 months <br /> of cooldown the plant is at 350°F and the Residual Heat Removal System is valved in-line.

At this point, decay heat removal via the steam generators ceases, and the RHR system is used to continue the heat removal process.

2.

PLANT PARAMETERS Number of Loops Power Rating (MWTh)

Temp., No Load (°F)

Temp., RHR On (°F)

Available Steam Generators SG Volume at NWL (FT3)

Volume AFST (gallons, demin.)

TDS of Service Water (ppm)

=

4

=

3,423 547 350 3

3,425

= 220,000

=

35,000

3.
4. TOTAL WATER REQUIREMENT HOURS AT NO LOAD WATER 5 HOUR COOLDOWN TOTAL WATER NO LOAD (GALLONS)

(GALLONS)

(GALLONS) 2 82,075 138,087 220,162 12 212,491 119,103 331,594 24 332,756 111,287 444,043 168 1,280,973 93,030 1,374,003 SALT WATER CONCENTRATION Figure 1 shows that 0.602 x 106 gallons of water will be required to maintain the plant at the no load condition for 43 hours4.976852e-4 days <br />0.0119 hours <br />7.109788e-5 weeks <br />1.63615e-5 months <br /> plus at least a 5 hour5.787037e-5 days <br />0.00139 hours <br />8.267196e-6 weeks <br />1.9025e-6 months <br /> cooldown to begin RHR operation.

0.22 x 106 gallons of this water will be supplied from the AFST, and should not contribute sig-nificantly to the salt burden of the Steam Generators.

Thus the salt water requirement to meet RHR operation within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> is (0.602 -

0.22) 106 gallons

= 0.382 x 106 gallons Based upon the assumption that this salt water will con-tain 35,000 ppm TDS as sodium chloride, then the weight of salt introduced into the three available Steam Gener-ators will be 50.75 tonnes.

At 350°F, three Steam Generators will contain 258.67 tonnes of water.

Thus, the concentration of salt in the SG water will be 50.75 258.67

= 0.20 t/t From standard solubility tables, and using the same notation as above, the solubility of sodium chloride at room temperature is 0.36 t/t, increasing to 0.58 t/t at the no load temperature.

2 * )

(References 1 and 2 and Figure

5.

RESPONSE TO NRC CONSIDERATIONS A.

Degradation of heat transfer due to salt plate-out.

Salt water will be first admitted to the steam generators twelve hours after the loss of offsite power incident.

By this time the thermal flux at the steam generator tube wall will be relatively low, and there will be no tendency to hide out normally soluble ionic species.

It is anticipated that steam release from the PORVs will tend to be increasingly intermittent as decay heat decreases.

Thus, the net effect will be similar to bulk boil-ing, rather than the superheat driven mode of boil-ing normally associated with steam generation for power production purposes.

In addition, the data provided in 4 above, shows that the concentration of salt in the bulk water is well below the solubility limit of sodium chloride throughout the range of temperatures expected during

1 operation at the hot standby condition (0.20 vs.

0.44 at 350°F, and 0.58 at 547°F).

There is, therefore, no evidence to suggest that there will be any decrease in heat transfer capa-bility due to the deposition of salt on the steam generat6r tube surfaces during the postulated period of hot standby operation.

B.

Clogging of SG Flow Paths by Salt Accumulation The concentration factor and sodium chloride solu-bility data discussed in previous parts of this response indicate that the internals of the steam generator totally immersed in the bulk liquid phase should not be subject to salt precipitation and clogging.

Similar consideration of the steel sur-faces at the water/steam interface suggests that although some salt deposition is likely, the de-position will not be at a fixed boundary because of level changes caused by intermittent steam release via the PORVs.

In addition, any re-wetting will be carried out with a liquid which has considerable salt solubilization capability.

Based upon these considerations, it is unlikely that salt bridging wil occur at the water/steam interface.

Zones above this interface are not expected to become clogged with salt since evaporation is a process which puri-fies the solvent phase.

Thus any salt carried upward by liquid phase entainment should be washed back down into the bulk liquid by relatively pure water (condensed steam).

C.

Corrosion Effects of Salt The corrosion of carbon steels in hot concentrated sodium chloride solutions is controlled by the metal alloying constituents, solution flow rate, oxygen concentration, temperature, and solution pH.

Literature values for carbon steel corrosion rates at steam generator operating temperatures vary from 0.012 inches/week (Reference 3) to 0.21 inches/week (Reference 4).

Tests carried out on ASTM SA 285 grade C steel, used by Westinghouse as Tube Support Plate material, show that a corrosion rate of approximately 0.015 inches/week can be expected when this material is exposed to concentrated sea water at 540°F (Reference 5).

The ligament between the tube and flow hole in the Salem steam generators is 0.083 inches wide.

Based upon these data, tube support plate corrosion must be expected.

Other carbon steels present in the steam generator will also be corroded by the hot concentrated sea water.

The condition of these carbon steel internals under hot standby conditions does not compromise the integrity of the primary to secondary steam genera-tor boundary, since their function is to act as anti-vibration support or steam separation equipment during normal power operation.

Data generated in single tube model boiler tests performed by Westinghouse indicate than Inconel 600 will pit at about 0.005 inches/week in hot concen-trated sea water environments.

Corroborative information of this behavior is contained in Reference 6.

Nominal tube wall thickness in the Salem steam generators is 0.050 inches.

Thus only shallow tube wall penetration should be anticipated as a result of 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> of operation at hot standby with concentrated sea water in the steam gene-rators.

No perforation of tube wall is anticipated during the period of this scenario.

6.

CONCLUSION The above discussion evidences that a loss of offsite power incident, followed by a 48 hour5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> period when only Seismic Category 1 water supply systems are available, will have no impact upon safety concerns at Salem.

Both primary circuit integrity and heat removal capability

J will be maintained throughout the postulated period of operation at hot standby, until the plant can begin heat removal via the RhR system.

From the safety standpoint, no provisions are necessary to attentuate the effects of salt wter ingress under the conditions postulated for this scenario.

  • REFEEENCES
1.

CR: Handbook of Chemistry and Physics

2.

Communication from W. T. Lindsay, Jr., Westinghouse Chemical Service Consultant

3.

Potter and Tease -

Corrosion Science Vol. 12, No. 4, April 1972.

4.

~. M.

~~ijbregts -

VGB Speiswassertagung 1970.

') *

,"'1

  • J.

W o o t t e n -

~\\I e s t i n g ho u s e C 1 a s s 2 Re s ea r ch Re po r t 77-186-DEN'l'S-Rl.

o.

U.,J. f<obr..:rts et.al. -

AEC Researcl1 and Developm12nt

U) z 0

i-:1 i-:1

~

l.O 0

rl 1.5 1.0 0.5 I

0 HOT STANDBY WATER REQUIREMENTS I

I I

REQUIREMENT FOR COOLDOWN TO RHR OPERATION

/

/

/

I I

I 50 I

I

\\

//

vy NO LOAD REQUIREMENT II~

WATER AVAILABLE IN AFST 100 150 ELAPSED TIME (HOURS)

FIGURE l 200 SODIUM CHLORIDE SOLUBILITY (BASED ON DATA SUPPLIED BY W. T. LINDSAY, JR.)

0 10 N

r::

tYl

~

~

u rO z 9

Cl)

~

0

~

E-t H

H 8

H P'.1

J H

0

(/)

7 150 200 250 300 TEMPERATURE (OC)

FIGURE 2

&

  • 2.

SERVICE WATER SPOOL PIECE CONNECTION The Station Operating Procedures will be revised to provide for installation of the spool-piece connection between the SWS and the AFW System upon receipt of a "Tornado Warning" in the vicinity of the Salem Station.

3.

AFW ALTERNATE SUCTION The Alternate AFW suction line from Demineralized Water Storage Tank passes through the switchgear room.

rhis line is normally maintained in an isolated and dry con-dition.

Modifications will be made to the normally-open drain valve on this isolated section of pipe such that it will be piped directly to a floor drain to preclude any potential for flooding the switchgear room.

Additionally, the Station Alarm List provides for changeover to an alternate suction path for the AFW pumps upon initiation of a low level alarm in the AFST and an inability to correct the low level condition.

4.

SINGLE SUCTION PATH FROM AFST In order to provide assurance that inadvertent failure (or closure) of the suction valve from the AFST (AFl) will not result in a degraded condition of the AFW System, PSE&G will remove the intervals from AFl.

This modification was discussed with and approved by the NRC staff and will provide conformance with recommendation GL-2 in NUREG-0611.

M P80 64 12 1/11