Discusses Util Understanding of 10CFR50.48 & App R to 10CFR50.NRC Requested to Review Encl Logic Diagrams & Provide Comments on Completeness & Accuracy
ML18051A771
Person / Time
Site: Palisades Entergy icon.png
Issue date: 01/18/1984
From: Vandewalle D
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To: Crutchfield D
Office of Nuclear Reactor Regulation
References
NUDOCS 8401250249
Download: ML18051A771 (11)


Text

~

consumers

.Power company General Offices: 1945 West Parnall Road, Jackson, Ml 49201 * {517) 768-0550 January 18, 1984 Dennis M Crutchfield, Chief Operating Reactor Branch No 5 Nuclear Reactor Regulation US Nuclear Regulatory Commission Washington, DC 20555 DOCKET 50-255 - LICENSE DPR PALISADES PLANT - FIRE PROTECTION - UNDERSTANDING 10 CFR 50.48 AND APPENDIX R TO 10 CFR 50 10 CFR 50.48 provides the schedular requirements for implementing the technical requirements of Appendix R to 10 CFR 50. Consumers Power Company was advised by an NRC letter dated November 24, 1980 that Sections III.G, III.J, III.L and III.O of Appendix R were requirements for the Palisades Plant and that the remaining Sections of Appendix R were adequately fulfilled by the closure of open items resulting from the "Pre-Appendix R" review of the Palisades Plant against the guidelines of Standard Review Plan 9.5.1 "Fire Protection" dated May 1, 1976. (The "Pre-Appendix R" review is summarized by References 1 through 6.)

Historically, Consumers Power Company has worked to provide, in a timely manner, the Palisades Plant with fire protection features which met or exceed-ed the guidelines provided in Standard Review Plan 9.5.1 as well as our understanding of Appendix R requirements.

Given the recent NRC findings of non-compliance with Appendix R at several nuclear power plants, Consumers Power Company initiated a self-audit program to evaluate and resolve, as necessary, differences from Appendix R require-ments. The charter of this self-audit program is to accomplish the following:

0 Organize a review committee consisting of Plant and General Office personnel 0

Develop a common and comprehensive understanding of the Appendix R requirements 0

Review existing commitments against Appendix R requirements 0

Evaluate whether existing commitments are comprehensive (given new understanding of Appendix R)

OC0184-0004A-NL02~-

(--8-4_0_1_2_5=-0=2=--=4=9~8~4011S --.- ~.

PDR ADOCK 05000255  !

F PDR

DMCrutchfield, Chief 2 Palisades Plant FIRE PROTECTION January 18, 1984 0

Organize documentation packages to substantiate compliance with Appendix R 0

Recommend corrective action(s), as necessary 0

Report the results of the self-audit to the NRC. The report shall summarize the review process and describe any differences from Appendix R requirements and the subsequent resolution The results of the self-audit will be submitted by April 2, 1984. The results will fully address the guidance (definitions) provided in Generic Letter 83-33, October 19, 1983.

Consumers Power Company has made a concentrated effort to organize the requirements of Appendix R and subsequent NRC Staff guidance into the logic diagrams attached. The logic diagrams reflect our current understanding of 10 '

CFR 50.48 and Appendix R requirements. It is requested that the NRC Staff provide a formal review of the logic diagrams and provide comments as to the completeness and accuracy. (Comments were informally solicited from various NRC Staff members and considered prior to this submittal.)

Director, Nuclear Licensing CC Administrator, Region III, USNRC NRC Resident Inspector - Palisades Attachments OC0184-0004A-NL02

DMCrutchf ield, Chief 3 Palisades Plant FIRE PROTECTION January 18, 1984 REFERENCES

1. NRC, Docket 50-255, May 11, 1976, Request to Initiate review of Palisades Plant Against Standard Review Plan 9.5.1 dated May 1, 1976
2. Consumers Power Company, Docket 50-255, March 31, 1977 "Fire Protection Program Evaluation"
3. Consumers Power Company, Docket 50-255, September 29, 1977, "Fire Protection - Containment"
4. NRC, Docket 50-255, September 1, 1978, "Fire Protection Safety Evaluation Report"
5. NRC, Docket 50-255, March 19, 1980, "Supplement 1 to September 1, 1978 Fire Protection Safety Evaluation Report"
6. NRC, Docket 50-255, February 10, 1981, "Supplement 2 to September 1, 1978 Fire Protection Safety Evaluation Report" OC0184-0004A-NL02

ATTACHMENT Consumers Power Company Palisades Plant - Docket 50-255 LOGIC DIAGRAMS DEPICTING CONSUMERS POWER COMPANY'S UNDERSTANDING OF 10 CFR 50.48 AND APPENDIX R TO 10 CFR 50 January 18, 1984 7 Pages OC0184-0004B-NL01

SYMBOL MEANING EXAMPLE 6

g HEADER TEXT ONL-OIFFERENCE NOTIFICATION LEVEL 1- NOTIFY NRC. NRC APPROVAL REQUIRED PRIOR TO IMPLEMENTATION 2- LATER 3-LATER 4-LATER OUTPUT=FALSE 5- NOTIFY NRC OF SIGNIFICANT DIFFERENCES J~Ch1PP~6e~[Rj~C~erns~E~~~5N~R ~bR0¥6 D~~~[kMENT AT I ON.

NA- NOT APPLICABLE OUTPUT= TRUE OUTPUT STATEMENT OR CONOITIOO. THE OUTPUT IS 0 00 ASSUMED TO BE 'Ft!ILSE' UNTIL THE INPUT IS DETERMINED TO BE 'TRUE'. IF NO INPUT EXISTS THE STATEMENT OR CONDITION HUST BE EVALUTED AND A DETERMINATION HADE AS TO

  • TR\JE' OR 1 FALSE'.

THE DIFFERENCE NOTIFICATION JNPUT=UNVERIFIEO INPUT=TRUE INPUT LEVEL MAY BE USE TO IMPLEMENT ALTERNATE MEASURES 5

COIIDITION 'C' OUTPUT

~

LOGIC SYMBOL -ANO GATE.

THE OUTPUT IS 'TRUE' IF ANO ONl.Y IF ALL INPUTS ARE 'TRUE'.

THE OUTPUT IS 'FALSE' IF ANY INPUT 15 'FALSE',

IW'UT INPUT PRC APER . JURE 4 CARD EOUIPMENT 15 FREE Of WATER OAHAGE FROM THE 0 ISCHARGE OF FIRE FIGHTING HOSES LESS THAN 4' IN DIAHETER OUTPUT LOGIC SYMBOL-OR GATE.

THE OUTPUT IS ' TRUE' IF ANY INPUT IS 1 TRUE"

  • THE OUTPUT IS FALSE IF NO INPUT JS 'TRUE',

INPUT INPUT ALL FIRE FIGHTING EQUIPMENT IS SHIELDED FROM HOSES ARE 5' DIRECT OR INDIRECT SPRAY FROM IN DIAMETER THE DISCHARGE OF ALL FIRE FIGHTING HOSES Also Available Un OUTPUT LOGIC SYMBOL* INHIBIT GATE.

Aperture Card

~

THE OUTPUT IS 'TRUE' IF ANO ONLY IF THE INPUT IS ' TRUE' AND THE

?1 CONDITIONAL}

INPUT CONDITIONAL INPUT IS 'TRUE' -THE OUTPUT IS *FALSE' IF EITHER THE INPUT OR CONDITIONAL INPUT IS 'FALSE'.

HOTOR CONTROL SWITCH }

3 SET TO 'ON' POSITION INPUT THE MOTOR HAS A FUNCTIONAL ELECTR lCAL POWER SUPPLY ANO CABLING SYSTEH SHORT _HAND

~---~

'1*

NOTATION FOR COMMON IIII WHERE A. B. C. D, AND E REPRESENT ANY LOG IC 2

E REQUIREMENT SYMBOL OR STATEMENT MOTOR CONTROL SWITCH SET TO 'ON' }

POSITION !FOR A GIVEN PIECE OF EOUIPHENTI THE MOTOR HAS A FUNCTIONAL ELECTRICAL POWER SUPPLY ANO CABLING SYSTEM NOTE1 THERE EXISTS A COHHON REQUIREMENT TO START ANY GIVEN MOTOR. STARTING EQUIPMENT A DOES NOT IMPLY THAT EQUIPMENT B, C, OR 0 lS STARTED, FURTHER. A DISFUNCT IONAL CABLING SYSTEM FOR EQUIPMENT A DOES NOT IMPLY A DISFUNCTIONAL CABLING SYSTEM FOR EQUIPMENT B, C, DR D.

D'!. J, L. STERRETT 10-10-83 NUCLEAR P')WER PLANT LICENSING RC:QU IREMENTS c*. L. 'II, BAUER

~l;Tl!l*HEAO 12-12-83 CONSUMERS POWER CO AND DESIGN CRITERIA LEGEND APP, N. L. HASKELL 12*28*83


----~---------

ORIGINAL ISSUE DLF LWB APP.0.J.VANDEVALLE 12-28-BJ JACKSON, MICHIGAN

[40, 100lSK12Hl83. 002 NONE REV.

LRflC-001-GEN 0 BY APP.

I REFERENCE DRAWINGS DESCRIPTION 0£SCRIPTION D c 8 I A DFI 122883 J I I H G F E 8401250249-0\

. CWC.NO.

I I I I I ,

l l. PRIOR TO IMPLEMENTATION OF APPENDIX R THE NRC STAFF IDENTIFIED THE

~~~~~~~ APPENDIX TO RESOLVER OPEN NRC T THE FACILITY SATISFIES THE PROVISIONS OF BRANCH TECHNICAL POSTION BTP APCSB Cl.5-1 OR NRC STAFF ACCEPTANCE BEFORE AUUUST Jq76.

'.Also Available O:n Hll CFR 5!11.46 10 CFR 51!J.4B, FIRE PROTECTION TECHNICAL REDUIREMENTS ARE SATISFIED <SCHEOULAR THE STAFF IDENTIFIED NO 'BACKFIT' REQUIREMENT FOR EITHER PALISADES OR BIG ROCK POINT WITH REGARDS 6

'.Aperture Card TO APPENDIX R SECTIONS III.A.

REDUIREMENTS ADDRESSED, SHEET 6l 111.S.IlLC,lll.0,III.E, 111.F,JU.H,Ill.l,Jll.K, AUTHOR. CPCO ~

REF1 INTl=RPR N "'" 40 ~~E~:Nm*~c LETTERS!

.~

BRP, 11/24/80, ENCLOSURE 2 PAL, 11/24/80, ENCLOSURE 2 I

FIRE PROTECTION PLAN 10 CFR 50, APPENDIX A GENERAL DESIGN CRITERION 3 EACH OPERATING PLANT SHALL HAVE A FIRE PROTECTION PLAN THAT SATISFIES 10 CFR CRITERION 3- FIRE PROTECTION.

50 APPENDIX A. CRITERION 3. THIS PLAN STRUCTURES, SYSTEMS, ANO COMPONENTS SHALL DESCRIBE THE FOUOWING1 IMPORTANT TO SAFETY SHALL BE OESIGNEO

1. THE OVERALL FIRE PROTECTION PROGRAM FOR AND LOCATED TO MINIMIZE, CONSISTENT THE FACILJTY WITH OTHER SAFETY REOUIAEMENTS, THE
2. IDENTIFY THE VARIOUS POSITIONS WITHIN PROBABILITY AND EFFECT OF FIRES AND THE LICENCEES ORGANIZATION THAT ARE EXPLOSIONS. NONCOMBUSTIBLE AND HEAT RESPONSIBLE FOR THE PROGRAM RESISTANT MATERIALS SHALL BE USED WHEREVER PRACTICAL THROUGHOUT THE UNIT,
3. STATE THE AUTHORITIES THAT ARE DELEGATED TO EACH OF THESE POSITIONS TO PARTICULAR1. Y IN LOCATIONS SUCH AS THE CONTAINMENT ANO CONTROL ROOM. FIRE 5

IMPLEMENT THOSE RESPONSIBILITIES DETECTION ANO FIGHTING SYSTEMS OF

4. OUTLINE THE PLANS FOR FIRE PROTECTION, APPROPRIATE CAPACITY ANO CAPABILITY FIRE DETECTION AND SUPPRESSION SHALL BE PROVIDED AND DESIGNED TO CAPABILJTY, ANO LIMITATION OF FIRE MINIMIZE THE ADVERSE EFFECTS OF FIRES DAMAGE ON STRUCTURES, SYSTEMS. ANO COMPONENTS
5. DESCRIBE SPECIFIC FEATURES NECESSARY TO IM?ORTANT TO SAFETY. FIREFIGHTING IMPLEMENT t1H4J SUCH AS1 SYSTEMS SHALL BE DESIGNED TO ASSURE THAT A. ADMINISTRATIVE CONTROLS PERSONNEL REQUIREMENTS FOR FIRE PREVENTION THEIR RUPTURE OR INADVERTENT OPERATION DOES NOT SIGNIFICANTLY IMPAIR THE SAFETY CAPABlLITY Of THESE STRUCTURES, SYSTEMS, AND COMPONENTS.
c. MANUAL FIRE SUPPRESSION ACTIVITIES
o. AUTOMATIC ANO MANUAL Y OPERATED FIRE DETECTION AND SUPPRESSION SYSTEMS ~~~~~~~~~rx A TO rn CFR 50. 10 CFR ~

E. THE MEANS TO LIMIT FIRE DAMAGE TO

  • ~

STRUCTURES. SYSTEMS. OR COMPONENTS SO THAT THE CAPABILITY TO SAFELY SHUT DOWN THE PLANT IS ENSURED.

AUTHOR1 NRC ~

REF: 121 CFR 513.48 IAJ

~~"""-"") OPERATE PRIOR TO JANUARY I. 1q7q ~ ~'"""'"" LICENSED TO OPERATE AFTER JANUARY 1. 1q7q } 4 p Rc ACCEPTANCE CRITERIA DETAILS OF ACCEPTANCE CRITERIA FOR PLANTS LICENSED TO OPERATE AFTER JANUARY I, 197q ARE PROV{OEO ELSEWHERE ANO CLflRENTL Y ARE NOT REFLECTED IN THIS DRAWING Ap ERT uRE AUTHOR1 CPCO I DNI ,r ATER REF: INTERPRETATION 113 CFR 50.48

  • ~

cARD STOP NRC "STAFF ACCEPTANCE' MAY BE USEC IN PLACE OF A PARTICULAR SECTION OF APPENDIX R EXCEPT FOR THE FOLLOWING SECTIONS1 Jll.G. 111.J, III.L. ANO 111.0 . }

SEE NOTE 1 3 OR I I I APPENDIX R SECTION IU.G. APPENDIX R SECTION 111.J, APPENDIX R SECTION 111.0, NRC STAFF ACCEPTANCE, NRC STAFF ACCEPTANCE BEFORE MEET 10 CFR 513, APPENDIX R FlRE PROTECTION OF EMERGENCY LIGHTING OIL COLLECTION SYSTEM FOR FACILITY SATISFIES PROVISIONS AUGUST 1976 SC.FE SHUTDOWN CAPABILITY REACTOR COOLANT PUMP OF BRANCH TECHNICAL POSITION THE FOLLOWING APPENDIX R REQUIREMENTS MUST BE MET ANO EMERGENCY LIGHTING UNITS WJTH AT LEAST BTP APCSB <J.5-1 FIRE PROTECTION FEATURES WERE ACCEPTED APPENDIX R SECTION 111.L, AN 8-HOUR BATTERY POWER SUPPLY SHALL BE THE REACTOR COOLANT PUMP SHALL BE SECTION llJ - SPECIFIC REOUTREMENTS BY THE STAFF IN COMPREHENSIVE FIRE ALTERNATIVE ANO DEDICATED PROVIDED IN ALL AREAS NEEDED FOR EQUIPPED WITH AN OIL COLLECTION SYSTEM THE FIRE PROTECTION FEATURES PROPOSED PROTECTION SAFTY EVALUATION REPORTS SHJTDOWN CAPABILITY OPERATION OF SAFE SHUTDOWN EQUIPMENT IF THE CONTAINMENT JS NOT INERTEO DURING OR IMPLEMENTED BY THE LICENSEE HAVE Ill.A - WATER SUPPLIES FOR FIRE SUPPRESSION SYSTEMS ISSUED BEFORE APPENDIX IAJ TO BRANCH UI.B - SECTIONAL ISOLATION VALVES ANO IN ACCESS ANO EGRESS ROUTES THERETO. NORMAL OPERATION. THE OIL COLLECTION BEEN ACCEPTED BY THE NRC STAFF AS TECHNICAL POSITION BTP APCSB 9.5-1 WAS THE TECHNICAL REQUIREMENTS SYSTEM SHALL BE DESIGNED. ENGINEERED, SATISFYING THE PROVISIONS OF APPENOIX PUBLISHED IN AUGUST 1Ci76 111.C - HYDRANT ISOLATION VALVES OF SECTION 111.G ANO AUTHOR; NRC REF1 APPENDIX A.SECTION llI.J

~ ANO INSTALLED THAT* FAILURE WILL NOT (Al TO BRANCH TECHNICAL POSITION BTP A?CSB IU.O - MANUAL FIRE SUPPRESSION 111.L ARE SATISFIED LEAD TO FIRE DURING NORMAL OR DESIGN 'J.5-1 REFLECTED IN STAFF FIRE AUTHOR1 NRC REF1 113 CFR 50.48 !Bl

~ 111.E - HYDROSTATIC HOSE TESTS BASIS ACCIDENT CONDITIONS ANO THAT PROTECTION SAFETY EVALUATION REPORTS 111.F - AUTOMATIC FIRE DETECTION AUTHOR: CPCO REF: NONE

~ THERE IS REASONABLE ASSURANCE THAT THE ISSUED PRIOR TO THE EFFECTIVE OATE OF IU.G - AS SHOWN LROC-002-GEN SYSTEM WILL WITHSTAND THE SAFE SHUTDOWN THIS RULE <EFFECTIVE DATE1 FEBRUARY 17. JCJ811 EARTHQUAKE tSEE REGULATORY GUIDE 1.2'1 45 FR 766132. 11/lCi/801 III.H - FIRE BRIGADE LROC-21132-GEN SH 2 PARAGRAPH C.21 III.I - FIRE BRIGADE TRAINING SH 2 SUCH COLLECTION SYSTEM SHALL BE CAPABLE AUTHOR:NRC REF1 113 CFR 521.48 fBI

~ 111.J - AS SHOWN LROC-2102-GEN OF COLLECTING LUBE OIL FROM ALL 111.K - ADMINISTRATIVE CONTROLS

<E-61 POTENTIAL PRESSURIZED ANO UNPRESSURIZED LEAKAGE SITES IN THE REACTOR COOLANT III.L Ul.M AS SHOWN LROC-002-GEN FIRE BARRIER CABLE PENETRATION SEAL QUALIFICATION 2

PUMP LUBE OIL SYSTEMS. LEAKAGE SHALL BE Ill.N - FIRE ODORS COLLECTED AND ORAINEO TO A VENTED m.o - AS SHOWN LROC-002-GEN CLOSED CONTAINER THAT CAN HOLD THE AUTHOR: NRC ENTIRE LUBE OIL SYSTEM INVENTORY, A FLAME ARRESTER IS REQUIRED IN THE VENT REF1 113 CFR 50.48 !Bl ~

IF THE FLASH POINT CHARACTERISTICS OF THE OIL PRESENT THE HAZARD OF FIRE FLASH BACK. LEAKAGE POINTS TO BE PROTECTED SHALL INCLUDE LIFT PUMP ANO PIPING. OVERFLOW LINES, LUBE OIL COOLER, OIL FILL ANO DRAIN LINES AND PLUGS, FLANGED CONNECT IONS ON OIL LINES, ANO LUBE OIL RESERVOIRS WHERE SUCH FEATURES EXIST ON THE REACTOR COOLANT PUMPS. THE ORAJN LINE SHALL BE LARGE ENOUGH TO ACCO~OATE THE LARGEST POTENTIAL OIL LEAK.

AUTHOR: NRC REF1 APPENDIX R.SECTION 111.0 I I - J.L. STERRETT-~

OAT(

NUCLEAR FOWER PLANT

., I I ~.

L.W.BAUER 12-12-83 S.Cl:TDl.t:OO-~

CONSUMERS POWER co LICENSING RoOU!REMENTS ANO DESIGt I CRITERIA 10 CFR 50.48 ANO APPENOIX R OAAWINt;NO.

REFERENCE DRAWINGS t

RE1.l[lt.T( DESCRIPTION 1>DP.

0 l"za...I DArEI I

ORIGINAL ISSUE OLF LWB BY APP.

APP.N.L. HASKELL Cl'1SION*"'"

12-28-63 APP.0.;;:~~~E,!'~lL 12-28-83 JACKSON, MICHIGAN

{40,l00lSK121083.007 SCALE NONE FIRE PR.JTECTION I

I ORAW!NQNO.

LRDC-002-GEN I'~" I REV.

0

)

I BY RE1. DESCRIPTION .~.

RSZl310584 J, H G F E D c B A 8401250249--0Z.-

NOTES*

1. FIRE AREAS 1 A' Tl-IRU 1 Z' CONSTITUTE A SAFETY GOAL1 SAFE SHUTOOWN COMPLETE SET OF FIRE AREAS THROUOHOUT THE PLANT.

PRC DURING THE POSTFIRE SHUTDOWN, THE REACTOR COOLANT SYSTEM PROCESS THE NRC STAFF HAS ESTABLISHED THE VARitlBLES SHALL BE MAINTAINED WITHIN THOSE PREDICTED FOR A LOSS OF NORMAL FOLLOWING DEFINITION OF A FIRE AREA A. C. POWER. ANO THE FISSION PRODUCT tREFERENCE GENERIC LETTER 83*33.

BOUNDARY INTEGRITY SHALL NOT BE OCTOBER l<t. 1CJ83J AFFECTE01 I.E.,

APERTURE THERE SHALL BE NO FUEL CLAD OAHAGE, 'A FIRE AREA IS DEFINED AS THAT RUPTURE OF ANY PR I MARY COOLANT BOUNDARY PORTION OF A BUILDING OR PLANT THAT IS OR RUPTURE OF THE CONTAINMENT BOUNDARY SEPARATED FROM OTHER AREAS BY BOUNDARY RESULTING FROM FIRE DAMAGE FIRE BARRIERS NALLS. FLOORS.ANO 6 CEILINGS WITH ANY OPENINGS OR PENETRATIONS PROTECTED VITH SEALS OR CARD CLOSURES HAVING A FIRE RESISTANCE RATING EOUAL TO THAT REQUIRED OF THE BARRIER>. OPEN STAIRWELLS ANO HATCHWAYS IN CEILINGS ANO FLOORS ARE NOT FIRE AREA BOUNOAR IES.

FOR BOUNDARY FIRE BARRIERS, USING

\/ALLS. FLOORS, CEILUJOS, DAMPERS, DOORS, SAFETY GOAL1 HOT SHUTDOWN/STANDBY SAFETY GOAL* COLO SHUTDOWN ETC. EXISTING PRIOR TO APPENDIX R, THE THE CAPABILITY SHALL ALWAYS EXIST TO THE CAPABILITY SHALL EXIST TO ACHIEVE RATING REQUIRED OF A BOUNDARY FIRE ACHIEVE Al'() MAINTAIN HOT SHUTDOWN/ COLO SHUTDOWN CONDITIONS 'illTHJN 72 BARRIER IS BASED ON THE GUIDANCE IN STANDBY UNTIL SUCH TIME AS THE HOURS ANO TO MAINTAIN APPENDIX A TO BTP ASB CJ. 5- h I.E., THE COLD SHUTDOWN CONDIT IONS THEREAFTER RATING OF THE BARRIER OR BOUNDARY MUST CAPABILITY EXISTS TO ACHIEVE ANO Also Available On MAINTAIN COLD SHUTDOWN CONDITIONS NOTE1 SHUTDOWN CONDITIONS AS SPECIFIED IN THE STANDARD TECHNICAL SPECIFICATIONS.

NOTE1 SHUTOO'll'N CONDITIONS AS SPECIFIED IN THE STANDARD TECHNICAL SPECIFICATIONS EXCEED WITH MARGIN THE FIRE LOADING IN THE AREA ANO NEED NOT NECESSARILY BE A 3-HOUR RATED BOUNDARY UNLESS THE FIRE AUTHOR: NRC ONL1 I LOADING WARRANTS SUCH A BOUNDARY. FOR Aperture Card HOT 5HUTOOWN-BWR1 HOT STANOBY-P'ilR.

RF APPENDIX R Tlf.Ll<Dl INSTALLATION OF NEV BOUNDARY FIRE BARRIERS PURSUANT TO SECTION 111.G.2.A.

THE FIRE RATING OF SUCH BOUNOARlES MUST BE THREE HOURS. OR AN EXEMPTION HUST BE JUSTIFIED AND REQUESTED.

THE EVALUATIONS BY SOME LICENSEES MADE PRIOR TO APPENDIX R \/ERE BASED ON FIRE 5 ZONES WHICH 00 NOT MEET THE STRICT DEFINITION OF FIRE AREAS CLARIFIED ABOVE. IN SOME CASES, THE SEPARATION COMMON OF REDUNDANT TRAINS UNDER CONSIDERATION REQUIREMENT WITHIN THE 'FIRE ZONE BOUNDARIES' ANO THE SEPARATION BETWEEN FIRE ZONES DOES NOT COMPLY 'll'ITH THE SEPARATION, I.E **

BARRIER OR DISTANCE, REQUIREMENTS OF APPENDIX R. SUCH CONFIGURATIONS NEEO TO BE EVALUATED UNDER THE EXEMPTION PROCESS.'

2. SYSTEMS 1 A' THRU ' Z* CONST ITU TE A COMPLETE SET OF SYSTEMS NECESSARY TO PERFORM A GIVEN VITAL FUNCTION ONE TRAIN VITAL FUNCTIONi INVENTORY CONTROL VITAL FUNCTIONi PROCESS MONITORING OPERAT INO PROCEDURES IF WHICH IS NOT DAMAGED BY FIRE WHICH MAINTAIN THE REACTOR COOLANT LEVEL THE PROCESS MONITORING FUNCTION SHALL PROCEDURES SHALL BE IN EFFECT TO ORIGINATES IN A GIVEN FIRE AREA. THERE ABOVE THE TOP OF THE CORE FOR BWR, ANO BE CAPABLE OF PROVJOINO DIRECT READINGS IMPLEMENT THIS CAPABILITY IS NO CORRELATION BETWEEN SYSTEM 'A' BE W'ITHIN THE LEVEL INDICATION IN THE OF THE PROCESS VAR 1 ABLES NECESSARY TO AUTHOR* NFIC ANO FIRE AREA 'A',

PRESSURIZER FOR PWR PERFORM ANO CONTROL TKE REACTIVITY REF1 APPENDIX R, 111.L.3 CONTROL. INVENTORY CONTROL ANO HEAT *THE SHUTDOWN CAPABILITY FOR A SPECIFIC AUTHOR1 NRC ONL1 I REMOVAL VITAL FUNCTIONS FIRE AREA HAY BE UNIQUE FOR EACH SUCH AP NDIX R Ifl.L. I ANO l.L.2 AREA, OR IT MAY BE ONE UNIQUE HOT SHUTDOWN/ } COLO SHUTDOWN 5 TANOBY ONLY ONLY COMBINATION OF SYSTEMS FOR ALL SUCH AREAS. 1 <REFERENCE APPEND IX R TO 10 CFR 50, SECTION 111.L.31 4 MANPOWER THE NUMBER OF OPERATING SHIFT PERSONNEL EXCLUSIVE OF FIRE BRIGADE MEMBERS, REOUIREO TO OPERATE SUCH EQUIPMENT ANO SYSTEMS SHALL BE ON SITE AT ALL TIMES AUTHOR1 NAC RF APPENDIX R III ** 4 ONL1 I EXAMPLE CHYPDTHET ICALl VITAL FUNCTION1 REACTICITY CONTROL COMPLETE SET OF SYSTEMS1

- CONTROL ROD INSERTION

  • 8' - BORAT ION SYSTEH r---------- -----~--~------------- ----------------------- ----------------------- -----------,

l DEFINE FIRE AREAS DEFINE FIRE AREAS DEFINE FIRE AREAS DEFINE FIRE AREAS 1 I ONE TRAIN OF SYSTEMS NECESSARY TO ONE TRAIN OF SYSTEMS NECESSARY TO ONE TRAIN OF SYSTEMS NECESSARY TO ONE TRAIN OF SYSTEMS NECESSARY TO I I ACHIEVE ANO MAINTAIN A GIVEN VITAL ACHIEVE AND MAINTAIN A GIVEN VITAL ACHIEVE ANO MAINTAIN A GIVEN VITAL ACHIEVE ANO MAINTAIN A GIVEN VITAL ]

gr~~5~~~~~rn~~oi~;~~~~~CN
ACTIVITIES WHICH ORIGINATE IN f"IRE AREPi I A'

~N=~~~~5~1~ai~;~~i~R~~~ON ACTIVITIES WHICH ORIGINATE IN FIRE AREA I B' gr~=g~~~i:~~I~~~J~~i~~~~i~R~~~~ON CT IV I TIES 'll'HICH ORIGINATE JN FIRE AREA I c*

gr~~~~g~~~~:~5~1=~~oi~~i~~i:i~R~~~~ON ACTIVITIES WHICH ORIGINATE JN FIRE AREA I z* :

~SEE NOTE I 3 I AUTHOR1 CPCO DM...1 I AUTHOR1 CPCO DNL1 1 AUTHOR: CPCO ONL1 I AUTHOR1 CPCO ONL1 I I I RF INTERPRETATION OF APPENDI A R F IN APR TATION OF APPEND X R R F INTERPRETATION OF APPENDIX R I l __________ -----~----------------- ----------------------- ----------------------- -----------~

.---------~ ------------~--------- ------------------------------------------------ -----------.

~~l~~Asli:~Fs~~~~~N .~;sTl~H~~~A:s o~l~~A~':~Fs~~~~~N.~;sT,~H~~~~A~~s ~~,~~A~':~Fs~~~~~~N ,;;sTl~;~~~A~~s 2

~:~~Enl~~F~~*IE~~~T~* =~l~~AIN A I & 2 I GIVEN VITAL FUNCTION IN THE EVENT OF FIRE I OR FIRE SUPPRESSION ACTIVITIES IN A DEFINE SAFE SHUTOO'll'N SYSTEMS-TRAINS I & 2

~~~~~~Fri::~~~~~~~~:~t~:

OR FIRE SUPPRESSION ACTIVITIES IN A A

GIVEN VITAL FUNCTION IN THE EVENT OF FIRE

~~~r~aL~H~~F~~~*JEe~~T~~* ~~1~iAIN A GIVEN VITAL FUNCTION IN THE EVENT OF FIRE OR'FIRE SUPPRESSION ACTIVITIES IN A I & 2

~~=~r~aL~H~~F~~~-IEe~~Tg:o* ~~1~iAIN A ~SEE 2 I t. 2 GIVEN VITAL FUNCTION IN THE EVENT OF FIRE OR FIRE SUPPRESSION ACTIVITIES IN A I

I NOTE I GIVEN FIRE AREA. GIVEN FJRE AREA. GIVEN FIRE AREA. GIVEN FIRE AREA. I

[ AUTHOR1 CPCO AUTHOR! CPCO AUTHOR: CPCO 0 ' I AUTHOR1 CPCO I

[ R F INTERPRETATION F APPENDIX A R F* NTERPRETATJON OF APPENOIX R R F INTERPR TATION OF APPENOTX R REF INTERPR TATION OF APPENDIX R I L---------- ----~~-------~------ ----~------------------------------------------- -----------1 LRDC- 002* OEN SH 3 L_----(*SHEET 3 CF-61

... NUCLEAR LICENSING POWER PLANT

~~~~~~~~~~~~-f-~~--~~~~-~~--~--~~~~~-t___,___,-+-~~~~~~~~~~~~~-+~f---+--+-~-+-~~~~~~~~~~~~~-J--t-~i~'"-R_.H_._S_A_TT_ER_EL_L_l~l~0-_7-_8_ 1 i-~~~-j---~~~~~--~~~~~~~-t~~~--~~~~~~~~-*~~~~~-j___,f---t-~~~~~~~~~~~~~-+~f---i--+-~-+-~~~~~~~~~~~~~-J--t-~-j~<<~L~.*-*mB~AUITTE<.R,-~l=2 *~l~ 2 -~

83"1 CONSUMERS POWER co AND DESIGNREOU IREMENTS CRITERIA 10 CFR 50. 49 & APPENDIX R

=============================================-~-~~=~~~~~-t--i~-t-~~~~~~~~~~~~~-+--if--~0--fc1 ~~-l---O-R-IG-l-N-A-L--clS~S~UE::-~~~~~~-+O-L~F~L-W~B+":':~::~~~~~;,~~~~;~~~~L-LE~:=_~~~~:~~:, JACKSON, MICHIGAN t-~~-N-ON-E~~~F~l~RE~P1J~~:~~~~N~~---~--l REFERENCE DRAWINGS AEV. DATE DESCRIPTJON BY DATE DESCRJPTION BY APP, [40, i00JSK121093.003 LrOC-002-GEN 2 .*

OF2122883 J I I H G F E D c B A L

8401250249-b~

.llifil!!!.

EXAMPLE (HYPOTHETICAL> -----ELECTRICAL CABLE OF CONCERN LRDC-002-GEN SH 2

--PIPING m-u SYSTEM A TRAIN I PLUS SUPPORT ALL EOUIPHENT FOR TRAIN 1 2', INCLUOING

  • EQUIPMENT SUBJECT TO ALL NECESSARY SUPPORT SYSTEMS ANO HALOPERATION DUE TO ASSOCIATED ELECTRIC POWER SUPPLIES, SHALL BE CIRCUITS, HOT SHORTS, OPEN CIRCUITS, { IOENTIFIED AND CABLE ROUTING DETAILS NOTES OR SHORTS TO GAOUNO, KNO'W'~ SEE EXAMPLE. THIS SHEET.
1. LETTER, NRC TO CPCO, 4-7-82, ENCLOSURE 2 DEFINES ASSOCIATED CIRCUITS AS FOLLOWS:

THE DEFINITION FOR ASSOCIATED CIRCUITS IS NOT EXACTLY THE SAME* AS THE 6 DEFINITION PRESENTED IN JEEE-384-1q77.

DIESEL JACKET COOLING PUMP

  • 1 ASSOCIATED CIRCUITS OF CONCERN ARE DEFINED AS THOSE CABLES <SAFETY RELATED, NON-SAFETY RELA TEO, CLASS lE, AND NON-CLASS IEJ THAT:
1. HAVE A PHYSICAL SEPARATION LESS THAN OFF SITE POWER IS UNAVAILABLE FOR THAT REQUIRED BY SECTION Jll.0.2 OF

( FOR 72 HOURS IREF1 APP R, 11 J. LI APPENDIX R, ANO:

2. HAVE ONE OF THE FOLLOWING A. A COMMON POWER SOURCE WITH SHUTDOWN DEFINE EQUIPMENT - TRAIN I EQUIPMENT !REDUNDANT OR AL TERNATIVEI BORATION A GIVEN PIECE OF EQUIPMENT lTRAIN 'I' ANO THE POWER SOURCE IS NOT PUMP *1 All EOUJPHENT FOR TRAIN
  • 1' SHALL BE ELECTRICALLY PROTECTED FROM THE IDENTIFIED ANO CABLE ROUTING DETAILS AND ALL IT'S SUPPORT SYSTEMS) SHALL HAVE A FUNCTIONAL ELECTRICAL POWER CIRCUIT OF CONCERN BY COORDINATED KNOWN BREAKERS, FUSES, OR SIMILAR AUTHDR1 CPCO SOURCE. THE POWER SYSTEM'S SUPPORT SYSTEMS SYSTEM A TRAIN 2 PLUS SUPPORT SHALL ALSO BE FUNCTIONAL. DEVICES, OR REF1 NONE EXAMPLE:

REPEAT FIGURE, CHANGE EQUIPMENT LABLE TO *2 AUTHORi NRC REF t APPEND IX R,

~ FIRE AREA

~ - - - es.s.O.t:lAJflLCJllC!Jll. _

TRAIN B

8. A CONNECTION TO CIRCUITS OF

~~~~~~~ ~~~6 £~~~~~~~ Y AFFECT 5 THE SHUTDOWN CAPABILITY !E.O.,

AHR/RCS ISOLATION VALVES, ADS VALVES, PORV, STEAM OENEMTOR ATMOSPHERIC DUMP VALVES, INSTAUMENTATION, STEAM BYPASS, ETC.>, OR SECTION llJ.0.2.A OF APPENDIX R TO 10 CFR 50 REQUIRES THAT CONS IOERATION BE 0 IVEN TO COMMON 'HALOPERAT ION DUE TO HOT SHORTS, REOUIREHENT OPEN CIRCUITS, OR SHORTS TO GROUND.'

Also Available On FIRE AREA

~-

Aperture Card DEFINE SUPPORT SYSTEM'S EQUIPMENT THE SUPPORTINO FUNCTIONS SHALL BE CAPABLE OF PROVIDING THE PROCESS DEFINE SUPPORT SYSTEM'S EOUIPHENT TRAIN 'I' IS DEPENDENT ON NO SUPPORT FUNCTIONS f2zzzz===

COOLING, LUBRICATION, ETC. NECESSARY AUTHOR1 CPCO TO PERMIT THE OPERATION OF TRAIN 'I' TRAIN B EQUIPMENT REF1 NONE AUTHOR. NRC DNL1 I C. A COMMON ENCLOSURE <E.G.. RACEWAY, PANEL, JUNCTIONJ WITH THE SHUTDOWN REF1 APP NO X R tr . . 2 l CABLES <REDUNDANT AND AL TERNATIVEl AND, (I) ARE NOT ELECTRICALLY PROTECTED 4

BY CIRCUIT BREAKERS, FUSES, OR SIMILAR DEVICES, OR 121 VILL ALLOW PROPAGATION OF' THE FIRE INTO THE COMMON ENCLOSURE FIRE AREA COMM-_o_N, ,AS,'~,qt:lA.JEQ. _CJF!CJ.JlT__

PRC ENCLOSURE T---"'

zz222222222222zzJ TRAIN B APERTURB_

CARD FREE OF SUPPRESSION OAHAGE ONE TRAIN OF ALL SYSTEHSFEOUIP RE<OUIREO FOR HOT/COLO SHUTDOWN IS FREE OF DAMAGE THE ELECTRICAL CABLE FOR A G !VEN PIECE OF EQUIPMENT CTRAIN 'I' ANO ALL IT'S SUPPORT SYSTEMS! SHALL BE AOEOUATEL Y

  • ASSOCIATED CIRCUITS' !SEE NOTE 1)

A GIVEN PIECE OF EQUIPMENT FOR TRAIN ' I '

ANO ALL OF IT' S SUPPORT SYSTEMS SHALL BE ADEQUATELY PROTECTED FROM THE 3

FROM FIRE SUPPRESSION ACTIVITIES OR SEPARATED FROM ALL TRAIN

  • 2' EQUIPMENT EFFECTS OF 'ASSOCIATED CIRCUITS' FROM THE RUPTURE OR INADVERTENT CABLES ANO All CABLES OF TRAIN '2' ' S AUTHOR1 NRC ON 1 I OPERATION OF FIRE SUPPRESSION SYSTEMS SUPPORT SYSTEMS

<CONSIDER ALL ESSENTIAL POWER, CONTROL. REF1 APP A JI[. 0. 2.A AUTHOR1 NRC AND INSTRUMENT CABLES!

REF1 APP A, 111. G. 3 ONL1 I IG-61

{ COLO SHUTDOWN ONLY I STOP AUTHOR: CPCO REF1NONE LROC-002-GEN SH 5 2 LRDC-002-0EN SH 5 (J-6)

REDUNDANT TRAINS OF SYSTEMS/EQUIPMENT ARE LOCATED IN THE SAME FIRE AREA AND ARE SUSCEPTIBLE TO SUPPRESSION DAMAGE AUTHOR* CPCO ONL1 I REF1 NONE NUCLEAR F 'JWER PLANT

"' R, M. SATTERELLI 10-7-B LICENSING FEOUIREMENTS c~.

~PP.

LW. BAUER N. L. HASKELL 12-12-83 12~ 28- 83 CONSUMERS POWER co AND DESIGN CRITERIA 10 CRF 50. 48 & APPENDIX R ORIGINAL ISSUE DLF LWB ~P.O. J, VANDEWALLE 12-28-83 JACKSON. MICHIGAN 1-~~-N-D-NE~~~,l~R~E~P"°R~~~~~~.;.o~N~~~,,,=,-,~=,,-,,~

[)RAWlllCNO. B* BY APP.

[40, 100JSK1210B3.004 LRDC-002-GEN 3 0 REFERENCE DRAWINGS DESCRIPTION DATE DESCRIPTION DF3122883 J I I H G F E 0 c B I A 8401250249-t>f

~

EXAM~LE -----ELECTRICAL CABLE OF CONCERN

--PIPING I. LETTER, NRC TO CPCO, 4-7-82, ENCLOSURE 2 DEFINES ASSOCIATED CIRCUITS AS FOLLOWS1 SYSTEM A TRAIN I PLLJS SUPPORT THE DEFINITION FOR ASSOCIATED CIRCUITS

  • EOUIPHENT SUBJECT TO 15 NOT EXACTLY THE SAME AS THE HALOPERATION OVE TO ASSOCIATED DEFINITION PRESENTED IN IEEE-3B4-1CJ77.

CIRCUITS. HOT SHORTS, OPEN CIRCUITS, OR SHORTS TO GROUND. ASSOCIA.TEO CIRCUITS OF CONCERN ARE DEFINED AS THOSE CABLES tSAFETY RELATED.

SUPPORT SYSTEM NON-SAFETY RELATED, CLASS IE. ANO NON-TRAIN

  • 1 POWER CLASS lEI THAT1 I. HAVE A PHYSICAL SEPARATION LESS THAN DIESEL

~

~NERATDR THAT AEOUIREO BY SECTION Ul.G.2 OF 6 APPENDIX R, AN01 DIESEL JACKET COOLING PUHP *1 2. HAVE ONE OF THE FOLLOWING A. A COMMON POWER SOURCE WITH SHUTDOWN EQUIPMENT CREOUNOANT OR AL TERNATIVEl SUPPORT SYSTEM TRAIN

  • I De ANO THE POWER SOURCE JS NOT ELECTRICALLY PROTECTED FROM THE CIRCUIT OF CONCERN BY COORDINATED SEAL COOLING BREAKERS, FUSES, OR SIMILAR PUMP *1 DEVICES. OR EXAMPLE*

BORATION ~ FIRE AREA PUMP *1  : _ _ _ f!S.S.O"lftTfQ _tjilCJJH.. -

SYSTEM A, TRAIN 2 PLUS SUPPORT REPEAT FIGURE. CHANGE EOUIPHENT LASLE TO *2 TRAIN B B.. A CONNECTION TO CIRCUITS OF EOUIPM91T WHOSE SPURIOUS OPERATION WOULD AOVERSEL Y AFFECT THE SHUTDOWN CAPABILITY CE .. G**

AHR/RCS ISOLATION VALVES, ADS VALVES. PORV, STEAM GENERATOR ATMOSPHERIC DUMP VALVES, INSTRUMENTATION. STEAM BYPASS.

ETC.I. OR SECTION III.G.2.A OF APPENDIX R TO 5 10 CFR 50 REOUIRES THAT CONSIDERATION BE GIVEN TO

'HALOPERAT ION DUE TO HOT SHORTS. OPEN CIRCUITS. OR SHORTS TO GROUND.'

Mao- '.Available Oii TRAIN A FIRE AREA

"*'Aperture Card IVALvE.l_ _

~

_ _ flSS_OJ:lf!JfQ _C,Jll<;_UJT__

LRDC-002-GEN SH. 3 SH. 3 TRAIN B CD-31 C. A COMMON ENCLOSURE CE.G., RACEWAY, PANEL. JUNCTION> WITH THE SHUTDOWN CABLES !REDUNDANT AND ALTERNATIVE!

ANO, m ARE NOT ELECTRICALLY PROTECTED BY CIRCUIT BREAKERS, FUSES, OR SIMILAR DEVICES, OR (2l WILL ALLOW PROPAGATION OF THE FIRE INTO THE COMMON ENCLOSURE SPURIOUS OPERATION} COMMON ENCLOSURE }

csee NOTE 1.2.Bl !SEE NOTE I. 2. CJ COMMON POWER SOURCE}

!SEE NOTE 1.2.AI FIRE AREA 4 COM_M_O_N, ,AS,'~qctAJEQ J:l~CJ.JlT__

ENCLOSURE ZZ2ZZZ2ZZ2ZZ2ZZ2d I T ___ _,

TRAIN B ADEQUATE CABLE SEPARATION COMMON POliER SOURCE ISOLATE EQUIPMENT DETECT ION ANO PROCEDURES PREVENT FIRE PROPAGATION ELECTRICAL PROTECTION ADEQUATE CABLE SEPARATION .SHALL BE THE EQUIPMENT PDVER SOURCE IS PROVIDE A MEANS TO ISOLATE THE EQUIPMENT PROVIDE ELECTRICAL ISOLATION THAT PREVENTS PROVIDE A MEANS TO DETECT SPURIOUS PROVIDE APPROPRIATE MEASURES TD PROVIDE ELECTRICAL PROTECTION Cl. E.,

PROVIDED TD ENSURE PHYSICAL ISOLATION ELECTRICALLY PROTECTED FRDH THE CIRCUIT ANO/OR COMPONENTS FROM THE F IRE AREA SPURIOUS OPERATION. POTENTIAL ISOLATION OPERATIONS ANO THEN PROCEDURES TD DEFEAT PREVENT PROPAGATION OF THE FIRE BREAKERS. FUSES OR SIMILAR DEVICESl BETVEEN TRAIN ' l ' ' S EQUIPMENT CABLING OF CONCERN BY COORDINATED BREAKERS. PRIOR TO THE FIRE ti. E., REHOVE PO\IER OEV ICES INCLUDE BFIEAl<ERS. FUSES. THE HALOPERATION OF EQUIPMENT II. E**

ANO THE 'ASSOCIATED CIRCUIT' FUSES. OR SIMILAR DEV ICES CABLES. OPEN CIRCUIT BREAKERSJ AMPLIFIERS, CONTROL SVITCHES. CURRENT XFRS. CLOSURE OF THE BLOCK VAi.VE IF PORV AUTHOR1 NRC ON 15 AUTHOR1 NRC DNL15 FIBER OPTIC COUPLERS, RELAYS AND TRANSDUCERS SPURIOUSLY OPERATES. OPENING OF THE AUTHOR1 NRC ONL1 5 AUTHORi NRC AUTHOR; NRC DNL15 BREAKERS TO REMOVE SPURIOUS OPERATION OF REF1 SAME AS NOT REF1 SAH AS NOTE I REF1 SAME AS NOT 1 SAFETY INJECTION! REF* SAME AS NOTE 1 I REF1 SAME AS NOTE I AUTHOR1 NRC ONL1 5 REF1 SAME AS NOTE I tG-61 ACCEPTABLE INTERUPTTNG DEVICE THE ACCEPTABILITY OF A PARTICULAR INTERRUPTING DEVICE IS CONSIDERED DEMONSTRATED IF THE FOLLOWING CRITERIA. 3 ARE HET1 tll THE INTERRUPTING DEVICE OESION BE FACTORY TESTEO TO VERIFY OVERCURRENT PROTECT ION AS DES IGNEO IN ACCORDANCE WITH THE APPLICABLE UL. ANSI. OR NEMA STANDARDS.

C2J THE PO~ER SOURCE SHALL SuPPLY THE NECESSARY FAULT CURRENT FOR SUFFICIENT Ill! FDR LOii ANO MEDIUM VOLTAGE SVITCHGEAR TIME TO ENSURE THE PROPER COORDINATION (4B0 V ANO A60VE> CIRCUIT BREAKER/

VITHOUT LOSS OF FUNCTION OF THE SHUTDOVN PROTECTIVE RELAY PERIOOIC TESTING SHALL LOADS. DEMONSTRATE THAT THE OVERALL COOROINATIDN SCHEME REMAINS WITHIN THE LIMITS AUTHOR1 NRC ONL15 SPECIFIED IN THE DESIGN CRITERIA. THIS REF1 SAME AS NOTE I TESTING MAY BE PERFORMED AS A SERIES OF OVERLAPPING TESTS.

<Illl MOLDED CASE CIRCUIT BREAKERS SHALL PERIODICALLY BE MANUALLY EXERCISED AND INSPECTED TO INSURE EASE OF OPERATION.

ON A ROTATING REFUELING OUTAGE BASIS A SAMPLE OF THESE BREAKERS SHALL BE TESTED TO DETERMINE THAT BREAKER DRIFT JS WITHIN THAT ALLOWED BY THE DESIGN CRITERIA.

BREAKERS SHOULD BE TES TEO IN ACCORDANCE

'11 ITH AN ACCEPTED QC TEST ING METHODOLOOY SUCH AS MIL STD 10 5 O.

UV> FUSES \IHEN USED AS INTERRUPTING OEVICES 00 NOT REOUJRE PERIODIC TEST!NO.

DUE TO THEIR STABILITY, LACK OF DRIFT.

AND HIGH RELIABILITY. AOHINISTRATIVE CONT'AOLS HUST INSURE THAT REPLACEMENT FUSES VITH RATINGS OTHER THAN THOSE 2

SLECTED FOR PROPER COOROINATINO ARE NOT ACCIOENTALLY USED.

AUTHOR1 NAC ONL15 PRC REF1 SAME AS NOT I 1l\PERTURE CARD NUCLEAR POWER PLANT DR. R. M. SATTERELLI 10-7-B i:~. L. II. BAUER SO:(:fl0:.*00 12- 12-83 CONSUMERS POWER co LICENSING REOU IAEMENTS

  • AND DESIGN CRITERIA 10 CRF 50. 48 & APPENDIX R l----*l---------------~1--------------------l-+--f---------------<--+--l~~.,,.-+--=7"'c-cc,--c::::~-------t--=i--~r'~w~.N~.~L.~~~S~KE~LL,__~*~2*~2~*-=*'1 1----N-O-NE--~F_._...R~P~R*;~~~C"~aT70~~D~N-~~~~"=,.-<

JACKSON, MICHIGAN 1------1----l'------------f-------------------~li-f---+--------------f--i----i-~"-j-::!ll;ij....:O~R~l~G~IN~A~L:....-'.IS~S~U~E'----------J:'..DL~F-J-':::LW~B:µ;"~'*~o.~0 ~~~:~,~~,~~:~~:L~L~E~12~*~28~-a~JI C40, !00JSK121083.008 LROC- 002- GEN 0 rlEFERENC!:: ORti;.*JNGS DESCRIPTION DATE DESCRIPTION BY APP.

DF1122783 J I I H G F E D c B I A s4o 1250249-oS

Y' NOTES LROC-~0'3*GEN SH 3 rLROC;::;*:N SH*

<E-6J I. THE t*lC STAFF INTERPRETS

  • IN' TO HEAN 1 THROUGHOUT'

!REFERENCE GENERIC LETTER 83-33 Also Available On ... - .... OCTOBER 1q, 1qa31 Aperture Card ' 2. 'A FIXED FIRE SUPPRESSION SYSTEM SHALL

HAVE DISCHAROE HEADS ANO THE DlSTRJBUTION PIPING FOR SUCH HEAOS

' .............~OMMON 1NSTALI.EO. HOSE STATIONS DO NOT SATISFY REOUIREHENT THIS REQUIREMENT.*

IREFERENCE OEtERIC LETTER. 83-33 6 OCTOBER 1q, 1't831

3. ALTERNATIVE SHUTOOVN CAPABILITY IS LRDC-~002-GEN SH 3 PROVIDED BY REROUTING, RELOCATING OR HODIFICATION OF EXISTING SYST£HS1

) DEDICATED SHUTOOVN CAPABILITY IS

... -- . CONTROL STATION! LOCAL ISEE NOTE '41 CONTROL STATIOtu CONTROL ROOM PROV IOED BY lNSTALL ING NEV STRUCTURES ANO SYSTEMS FOR THE PURPOSE OF POST-FIRE

' CONTROL CAN BE ESTABLISHED FOR EITHER CONTROL CAN BE ESTABLISHED FOR EITHER SHUTDOWN.

' TRAIN OF A GIVEN SYSTEH/EOUIPHENT FROM TRAIN OF A GIVEN SYSTEH/EQUIPHENT FROH <REFERENCE 10 CFR 50, APPENOIX R COLO SHUTDOWN } AN EMERGENCY CONTROL STATION !EXCLUDING THE CONTROL ROOH AND THE SYSTEM' St SECTION 111.G, FOOTNOTE 21.

' '.. ,/ ONLY ALTERNATIVE OR DEDICATED SHUTOOlilN EQUIPMENT'S REQUIRED ANO ASSOCIATED 1 SHUTDOWN SYSTEMS INSTALLED TO ENSURE C0"°40N LRD~C-5=-TQ~N SH 3 SYSTEMS, ANO THE SYSTEM' S/EOUIPMENT' S CIRCUITRY IS FREE OF FIRE DAMAGE POSTFIRE SHUTDOWN CAPABILIY NEED NOT BE REOulRED ANO ASSOCIATED CIRCUITRY IS AUTHO~ NRC ONL1 I DESIGNED TO MEET SEISMIC CATEGORY I REQUIREMENT <H-21 FREE OF FIRE DAMAGE. R F1APP R ur G CRITERIA. SINGLE FAILURE CRITERIA. OR

..... - .... PROCEDURES SHALL BE IN EFFECT TO IMPLEMENT THIS CAPABILITY*

OTHER DESICiN BASIS ACCIDENT CRITERIA.

EXCEPT WHERE REQUIRED FOR OTHER REASONS,

' E. G. , BECAUSE OF INTERFACE WITH OR

~ '

IMPACT ON EXISTINO SAFETY SYSTEMS, OR BECAUSE OF ADVERSE VALVE ACTIONS OUE TO CONTROL STATION1 ALTERKATE OR DEDICATED SHUTOOVN

.... ,,,./ FIRE DAMAGE.'

!REFERENCE 10 CFR 50 APPENDIX R.

ALTERNATIVE OR OEOICATEO ISEE NOTE 31 COl<><DN SECTION I II. L. 61 REQUIREMENT SHUTDOVN CAPABILITY ANO ITS ASSOCIATED CIRCUITS, INOEPENOENT OF '4. *OPERABILITY OF THE HOT SHUTDOWN 5 CABLE SYSTEMS OR COMPONENTS JN THE SYSTEMS, JNCLUOING THE ABILITY TO AREA. ROOM OR ZONE UNOER CONSIDERATION COH><ON OVERCOME A FIRE OR FIRE SUPPRESSANT SHALL BE PROVIDED IN EACH CASE WHERE IT REQUIREMENT INDUCED MALOPERATJON OF HOT SHUTDOVN CAN NOT BE DEMONSTRATED THAT ONE TRAIN EQUIPMENT AND THE PLANT'S PO'iER OF SYSTEMS/EQUIPMENT NECESSARY TO DISTRIBUTION SYSTEH, HUST EXIST WITHOUT ACHIEVE ANO MAINTAIN HOT SHUTOOWN REPAIRS. MANUAL OPERATION OF VALVES, CONDITIONS, FROM EITHER THE CONTROL. LIMITED DAMAGE REPAIR PROCEDURES tSEE NOTE 51 SVJTCHES ANO CIRCUIT BREAKERS IS ALLOWED ROOH OR EMERGENCY CONTROL STATIONS, DAMAGE TO COLO SHUTDOWN SYSTEMS/ MATERIALS FOR REPAIR OF COLO SHUTOOWN REPAIR PROCEDURES SHALL BE IN EFFECT TO TO OPERATE EQUIPMENT AND ISOLATE SYSTEMS IS FREE OF DAMAGE EGUIPHENT SHALL BE LIHITEO SO THAT THE SYSTEMS/EOUIPHENT SHALL BE READILY IMPLEMENT REPAIR TO COLD SHUTDOWN AND IS NOT CONSIDERED A REPAIR. HOWEVER, SYSTEMS CAN BE HADE OPERABLE ANO COLD AVAILASt.E ON SITE EDUIPEHENT THE REMOVAL OF FUSES FOR ISOLATION IS AUTHOlb NRC ONL1 I SHUTDOWN CAN BE ACHI VEO 'IHTHIN 72 HOU R F1APP R 111.G.3 AUTHOR1 NRC ONL1 1 AUTHOR: NRC DNL1 I NOT PERMITTED. ALL MANUAL OPERATIONS AUTHOR1 NRC DNL1 I RF1APPR Ill.LS REF1APPR III.LS HUST BE ACHIEVABLE PRIOR TO THE FIRE OR REF1APP R 11 ** 5 FIRE SUPPRESSANT INDUCED MAl..OPERATlONS FIRE DETECTION REACHING AN UNRECOVERABLE PLANT INSTALL FIRE DETECTION IN tSEE NOTE 1J CONDITION, THE AREA, ROOM, OR ZONE UNDER <REFERENCE ITEM S OF ATTACHMENT C CONSICERAT ION TO NRC INTERNAL CORRESPONDENCE,

' SECY-83-26q, JULY 5, 1q93J AUTHOR1 NRC Fr APP R 111.0.3 , , COMMON

.... ~--' REQUIREMENT 5. 'OPERABILITY OF THE HOT SHUTOOWN StSTEHS. INCLUDING THE ABILITY TO FIXED FIRE SUPPRESSION OVERCOME A FIRE OR FIRE SUPPRESSANT INSTALL A FIXED <SEE NOTE 2l FIRE INDUCED KALOPERATION OF HOT SHUTOOVN SLIPPRESSION SYSTEM IN (SEE NOTE II THE AND EQUIPMENT AND THE PLANT'S POWER AREA. ROOM, OR ZONE UNDER CONSIDERATION DISTRIBUTION SYSTEH, HUST EXIST 4 AUTHOR1 NRC WITHOUT REPAIRS. MANUAL OPERATION OF REF1APP R 111.G.3 VALVES. SWITCHES ANO CIRCUIT BREAKERS CABLE SEPARATION OUTSIDE CONTAINMENT IS ALLOWED TO OPERATE EQUIPMENT ANO ISOLATE SYSTEMS ANO IS NOT THE CABLE SE PARAT ION CRITERIA FOR CONSIDERED A REPAIR. HOWEVER, THE CABLES ROUTED OUTSIDE CONTAINMENT ARE REMOVAL OF FUSES FOR ISOLATION JS SATISFIED NOT PERM I TTEO. ALL MANUAL OPERA T IONS ALTERNATE SHUTDOWN CABUS ANO/OR EQUIPEHENT HUST BE ACHIEVABLE PRIOR TO THE HUST BE INDEPENDENT OF BOTH TRAIN

  • 2' AUTHOIU CPCO DNL1 I FIRE OR FIRE SUPPRESSANT INDUCED F~R THE AREA. ROOM OR ZONE UNDER CONSIDERATION HALOPERATIONS REACHING AN UNRECOVERABLE PLANT CONDIT ION.

HODIFlCATIONS, E.O., WIRING CHANGES, ARE ALLOWED TO SYSTEMS ANO/OR DR COMPONENTS NOT USED FOR HOT SHUTOOVN, WHOSE FIRE OR FIRE SUPPRESSANT INOUCEO MAL.OPERATIONS HAY INDIRECTLY AFFECT HOT SHUTOO'l'N. THESE REPAIRS MUST BE ACHIEVABLE PRIOR TO THE MALOPERATIONS CAUSING AN UNRECOVERABLE PLANT CONDITION.

REPAIRS FOR COLO SHUTOOVN ARE ALLO'lfED BY SECTION 111.L.S OF APPENDIX R.

FOR COLD SHUTDOWN CAPABILITY REPAIRS.

THE REHOVAL OF FUSES FOR ISOLATION AND THE REPLACEMENT OF CABLING IS PERMITTED. ALSO, SELECTED EQUIPMENT 3

REPLACEMENT, E.O., SUCH AS REPLACING A VALVE. PUMP, CONTROL ROCH CONTROLS

' ANO INSTRUMENTS. WILL SE REVIEWED ON A

__ ..'coMHON REOU IREHENT --- _,'COMMON REQUIREMENT CASE-BY-CASE BASIS TO VERIFY ITS PRACTICALITY WITHIN THE APPROPRIATE TIME CONSTRAINT

S. PROCEDURE

S FOR REPAIRING DAMAGED EQUIPMENT SHOULD BE PREPARED JN ADVANCE liITH REPLACEMENT ANO AND EQUIPMENT U. E., CABLES HAOE-UP VITH TERMINAL LUGS ATTACHEOJ STORED ONSITE.

ALL REPAIRS SMOULO BE OF SUFFICIENT QUALITY TO ASSURE SAFE OPERATION UNTIL RADIANT ENERGY SHIELD FIRE DETECTORS MEASURED HORIZONTAL SEPAAATION !SEE NOTE 6) FIRE DETE TORS MEASURED H RIZONTAL SEPARATION !SEE NOTE I 3-HOUR BARRIER THE PLANT IS RESTORED TO AN CABLES, EQUIPMENT ANO ASSOCIATED FIRE DETECTORS SHALL BE INSTALLED IN ALL CABLES, EQUIPMENT AND ASSOCIATED FIRE DETECTORS SHALL BE INSTALLED IN CABLES, EQUIPMENT AND ASSOCIATED CABLES, EQUIPMENT AND ASSOCIATED OPERATING CONDITION.

NON-SAFETY CIRCUITS OF (SEE NOTE I! THE FIRE AREA NON-SAFETY CIRCUITS OF (SEE NOTE II THE FIRE AREA NON-SAFETY CIRCUITS OF NON-SAFETY CIRCUITS OF 'REPAIRS NOT PERMITTED INCLUDE THE USE REDUNDANT TRAINS SHALL BE SEPARATED BY AUTHOR1 NRC REDUNDANT TRAIN '2' SHALL SE SEPARATED REDUNDANT TRAIN

  • 2' SHALL BE SEPERATEO REDUNDANT TRAIN '2' SHALL BE SEPARATED OF CLIP LEADS IN CONTROL PANELS Clr'HICH AUTHOR1 NRC A NONCOMBUSTIBLE RAD ANT NERGY SHIELD REF1APP R 111.G IE! BY A HORIZONTAL OISTANCE OF HORE THAN REF: APP R llI.G.2 !Cl BY A HORIZONTAL. DISTANCE OF MORE THAN FROH THE EQUIPMENT/CABLE OF CONCERN MEANS THAT HARO WIRED TERMINAL LUGS AUTHOR1 NRC ONL1 I 20 FEET FROM THE EQUIPMENT /CABLE OF 20 FEET FROM THE TRAIN 'I' WITH THE FOR TRAIN 'I' BY A FIRE BARRIER HAVING HUST BE USEDJ , ANO THE USE OF JUMPER REF1APP R 11.G.2 <Fl CONCERN FOR TRAIN 'I' WITH THE FOLLOWING CONDITIONS BEING HET; A 3-HOUR RATING CABLES OTHER THAN THOSE FASTENED VITH FOLLOWING CONDITIONS BEING MET1 AUTOMATIC FIRE SUPPRESION TERMINAL LUOS.
  • AN AUTOMATIC FIRE SUPPRESSION SYSTEM A. NO INTERVENING COMBUSTIBLES AUTHOR1 NRC

\IHEN REPAIRS ARE NECESSARY IN THE A. NO INTERVENING COMBUSTIBLES SHALL BE INSTALLED IN tSEE NOTE 1l THE B. NO INTERVENING FIRE HAZARDS REF1 APP R JII.0.2 (Al FIRE AREA, THE LICENSEE SHOULD B. NO INTERVENING FIRE HAZARDS FIRE AREA DEMONSTRATE THAT SUFFICIENT TIME IS AUTHOR: NRC AUTHDR1 NRC DNL= 1 STRUCTURAL STEEL AVAILABLE TO ALLOW THE AREA TO BE REF1APP R III ** REF1 APP R. 111.0.2 !OJ AUTHOR1 NRC REF1APPR 111.G.2 ICJ STRUCTURAL STEEL DOES NOT FORM A PART RE-ENTERED ANO THAT EXPECTED FIRE ANO 2 OF OR DOES NOT SUPPORT THE FIRE BARRIER FIRE SUPPRESSANT DAMAGE WILL NOT

\*HOUR FIR BARRIER AUTHOR1 NRC PREVENT THE REPAIR FROM TAKING PLACE CABLES, EOUIPMENT AND ASSOCIATED REF1APP R lII.0.2 !Al ANO THAT REPAIR PROCEOURE WILL NOT NON-SAFETY CIRCUITS OF THE ENDANGER OPERATING SYSTEMS. IN ADDITION, TRAIN 1 I' EQUIPMENT OF CONCERN SHALL BE WRITTEN PROCEOURES MUST EXIST FOR THE PRC STRUCTURAL STEEL ENCLOSED IN A FIRE BARRIER HAVING A ORDERLY TRANSFER OF CONTROL FROM THE STRUCTURAL STEEL FORMING A PART OF OR I-HOUR RATING CONTROL ROOM AND THE REMOTE SHUTDOWN SLJPPORT(NO SUCH FIRE BARRIERS SHALL BE STATIONS ANO VICE VERSA. THE REPAIRS AUTHOA1 NRC DNL1 I PROTECTED TO PROVIOE FIRE RESISTANCE TO COLD SHUTDOWN SYSTEMS ARE CONSIDERED REF< APP R I l.G. 2 IC) EQUIVALENT TO THAT REQUIRED OF THE APERTURE TO BE AN UPPER LIMIT. THE LICENSEE BARRIER HAY DESIGN THE PL.ANT SO THAT COLO I-HOUR FIRE BARRIER AUTHOR1 NRC CNL1 I SHUTDOWN CAN BE ACHIEVED WITHOUT CABLES, EQUIPMENT AND ASSOCIATED CIRCUITS REF1APP R 11r.o.2 REPAIR.'

OF ALL TRAIN '2' EQUIPMENT IN FIRE AREA OUALIFIEO BY NOTE I <REFERENCE ITEM B OF ATTACHMENT C OF CONCERN SHALL BE ENCLOSED IN A FIRE { ON LRDC-002-GEN. SH. 2 TO NRt INTERNAL CORRESPONDENCE.

BARRIER HAVING A !*HOUR RATING SECY-83-26q, JlJL.Y 5, lqij31 CARD APPEND IX A TO BTP ASS 9. 5* I AUTHOR1 NRC ONLr I CABLES, EQUIPMENT ANO ASSOCIATEO REF1 APP R I J. G. 2 <Cl 6. 'PLASTIC JACKETS ANO INSULATION OF NON-SAFETY CIRCUITS OF REDUNDANT GROUPED ELECTRICAL CABLES. INCLUDING TRAIN '2' SHALL BE SEPARTEO FROM THE THOSE VHICH ARE COATED, SHOULD BE EOUIPHENT/CABLE OF CONCERN FOR TRAIN 'I' CONSIDERED AS INTERVENING COJoUlUSTTBLES. 1 BY A FIRE BARRIER HAVING A RATING <REFERENCE GENERIC LETTER B3-33 CONSISTENT WITH THE GUIDANCE PROVIDED OCTOBER 1q, l'l83J IN APPENDIX A TO BTP ASS 'l. 5- J ANO ACCEPTED BY NRC AUTHOR1 NRC DNL* 1 REF1 APP R 111.G.2 <Al

~" NUCL[ AR POWER PLANT R. R.H. SATTERELLI 10*7-S 0<. L W, BAUER

~!:CllO'I "'""

ArP. N. L. HASKELL 12* 12-B3 12-28-B3 CONSUMERS POWER co L!CENS ING REQUIREMENTS AND DESIGN CRITERIA 10 CFR 50. 48 &. APPENDIX R P OT CTION ORIGINAL ISSUE JACKSON, MICHIGAN SHEET REV, NONE REFERENCE ORAWIMGS DESCRIPTION BY DESCR!PT!ON

[40. J00lSKl210BJ. 005 5 0 DF4122B83 J I I H G F E D c B A 8401250249-0G,

f

  • . 7 I I I I I I

~*

~

  • DIHCAm CCllRD.ATIDN iETMElll Dl'LIJBTATION S0G&LE. ACTIVITY m:SCSUPTIQll MCI SPiClr:'lC SiCTICIN OS:

~

L SCHEtu.E AS FOLLOWS.

BEFORE STAATt.P AFTER THE EARLIEST f1F TIE FCl.LOVING DATES AFTER 1M7~11 A) nE FIRST REFtELIHG OUTAGE BJ A PLAYED OUTACiE THAT LASTS AT LEAST 60 DAYS C> AN lH'LQHNED OUTAGE THAT LASTS AT LEAST 129 DAYS

2. SCHEDULE AS FOLLCIWS.

BEFORE STARTuP AF'TEA THE EARLIEST OF Tt£ Fu.LOWING OATES AFTER ll-26*B3i AJ TtE FIRST REFUELlNG DUTACE 8> A PL/HIED OUTAfiE THAT l.ASTS AT LEAST 60 DAYS Cl m UfiF'l..INED OUTAGE TtMT LASTS AT LEAST l2S DAYS

3. SOEDU.E AS FOLLOWS.

6EFORE SHRTUP AFTER THE EARLIEST OF n£ FOLLOWING DATES AFTER Ci*B-931 A> TNE FtRST REFl.ELING OUTAGE B> A PUIMED OUTACiE TKAT LASTS AT LEAST Giii DAYS 0 AN lltPLANNED OUTAGE THAT LASTS AT LEAST WI DAYS 10 CFR 50.48, FIRE PROTECTION 4. FPSER-FIRE PROTECTIOO TY SCHEDULE REQUIREMENTS EVALUATION REPOATCSI M>PENDIX CAI TO BNKH POSITltlt QTP APCSS Cl.5-1 IPU3LI IN AUGUST 1*761 1e CFR 5il.48 IPALISADES 2*17-81 3*17*81 3*17*81 3-17-81 11-17*81 SEE NOTE I 5-26-83 CSEE REF. un 11*26*83 SEE NOTE 2 SEE REFEREKCES 2.:1.4. PIG 9 SCHEDULE IBI~orrfrCK 2*17-81 3*17*81 3-17-81 3*17-81 11-17-81 SEE NOTE I 3--8*83 lSEE REF. II q.a-e3 SEE NOTE 3 SEE REFERENCES Z.S.,7.0.At<<J q EFFECTlVE DATE OF COMPLET FIRE SUBMIT PL.ANS ANO EXEP.PTION REQU£STS- COMPLETE MODIFICATIONS COMPLETE HOOIFICATICl6 fflC CONCLUSION THAT THE COMPLETE 6\LL MODIFICAT10NS COMPLETE ALL MIXllFICATIOHS COMPLETE ALL MODIFICATIONS 10 CFR '50.46 AMJ PROTEC THAT SCt£DULES FOR f'E'.ETING IN EVENT THAT AN THAT DO NOT REQUIRE THAT REQUIRE Al.T£RMA TllOllN THAT DO rcn REQUIRE THAT REQUIRE ASSOCIATED VITH TfE 10 CFR 50 APPENDIX R INV Tl£ PROVISIONS OF E TION REQUEST TO PLANT SHUTDOWN PLANT SfflJTDOWN DESIGN I PLANT SHUTDOWN Pl.ANT SHUTOOWN FIRE PROTECTION PLAN

s. APPEfl:llX R I

TS SAFE MEETS T TS AND FPSER lSEE N'lTE 41 ACTIVITY TRAIN!

CE OF SECTIDN 111.G.3 OF fll'P.R TO"' CFR 50.

REQUIREMENTS SHALL BE TOLLED UNTIL. FINAL COMMISSION ACTION ON Tl£ EXEMPTION REQUEST 10 CFR 50; APP. R.

III.G.2

!SAFE SHUTDOWN> * * * * *

III.G.3,III.L

!AL TERNA TIVE/DED.

SHUTDOWN>

<SCHEDLIL.E NOT REO'OI * * * * '

L. LETTER. NRC TO CPCO 3-8-Bl. DOCKET *50-155

2. 10 CFR 5'1.48 SECTION Id>

3- LETTER. NRC TO CPCO Q-1*78 0 DOCK£T 50*255 10 CFR Sil. APP. R.

III.J

!EMERGENCY LIGHTING>

  • * * * *
  • 4. LETTER. NRC TO CPCO 3-IQ-88, DOCKET 5'!1*25S
5. LETTER. NRC TD CPCO 2*10*81. DOCKET 50-255 S.. LETTER. NRC TO CPCO 10 CFR 50. APP. R. 4-4-7<1, DOCKET 50-15!5 III.0

<OIL COLLECTION SYSTEM> * * * * * * \ 7. L.ETTER. NRC TO CPCO 3*11*80, DOCKET 50*155

8. L.ETTER. NRC TO CPCO 3-27-80, DOCKET 50-155 10 CFR 50.48 Cl. LETTER. NRC TO CPCO FIRE PROTECTION PLAN, ANO FPSER !SEE NOTE 41 *
  • 11-14*80, DOCKET SMSS If!. LETTER. NRC TO CPCO 5*26-BJ, DOCKET 59-255

.Als@ Available On Aperture Card p Rc 1,*~;.

Ap ERTuRB cARD I I "" J.L. STERRETT 10-§~83 NUCLEAR POWER PLANT CONSUMERS POWER* co LICENSING REQUIREMENTS cK. L.W. BAUER 12*12*83 ANO DESIGN CRITERIA su;ttOt<>£40 i0 CFR 50.4 8 ANO APPENDIX R APP. N. I.. HASKELL 12-28-83 FIRE PROTECTION 0 ~"-lsJ ORIGINAL ISSUE DLF LWB JACKSON, MICHIGAN 1