ISHAM, LINCOLN & BEALE

  • coUNSELORS AT LAW ONE FIRST NATIONAL PLAZA F'ORTY-SECO"ID FLOOR CHICAGO, ILLINOIS 60603 TELEPHONE 312-558-7500 TELEX: 2-5288 WASHINGTON OFFICE:

1120 CONNE:CTICUT AVENUE:. N. W.

SUITE: 32S WASHINGTON. D. C. 20036 202-633-9730 April 3, 1980 Charles Bechhoefer, Esq.

Atomic Safety and Licensing Board U.S. Nuclear Regulatory Commission Washington, D.C.

20555 Dr. George C. Anderson Department of Oceanography University of Washington Seattle, Washington 98195 Gentlemen:

Dr. M. Stanley Livingston 1005 Calle Largo Sante Fe, New.Mexico 87501 Re:

Consumers Power Company (Palisades Plant)

Docket.No. 50-255-SP cccKEiED USi.. l?iC Enclosed please find a copy of a document "Environmental Assessment - Palisades Plant - Steam Generator Replacement."

This report was prepared by Consumers Power Company as part of its request for approval from the Michigan Department of Natural Resources and the Army Corps of Engineers to construct a barge slip at Palisades.

The barge slip would be used in connection with the delivery of the replace-ment steam generators to the plant.

The assessment addresses the environmental effects of the proposed barge slip.

MEG:cem Enclosure cc:. Service List w/ Enclosures

~:;u4/"

Martha E. G~

ce.,.

j

consumers Power company BEU.TED GORRESP0~1JE.i.VCB General Offices: 212 West Michigan Avenue, Jackson, Michigan 49201

  • Area Code 517 788-0550 March 31, 1980 Director, Nuclear R~actor Regulation Att Mr Dennis L Ziemann, Chief Opera.ting Reactors Branch No 2 US Nuclear Regulatory Commission Washington, DC 20555 DOCKET 50-255 - LICENSE DPR PALISADES PLANT - STEAM GENERATOR REPAIR PROJECT:

TRANSMITTAL OF ENVIRONMENTAL ASSESSMENT REGARDING PROPOSED BARGE SLIP Consumers Power Company letter dated January 3, 1980, submitted a document

entitled, 11Palisades Plant - Steam Genera.tor Repair Report".

Several revis-ions to the report h~ve subsequently been transmitted.

The report describes a potential repair program.for the Palisades steam genera.tors based on com-plete replacement of the existing units.

The report identifies that the re-placement steam generators would be delivered to the plant using a newly

  • constructed barge slip.

Construction of the proposed barge slip at *Palisades requires approval of the Michigan Department of Natural Resources and the US Army Corps of Engineers.

Consumers Power Company has requested such approval.

In support of our request, an Environmental Assessment, addressing the effects of the proposed barge slip, has been prepared.

Transmitted herewith for your information a.re 40 copies of the assessment discussed above entitled, 11Environmental Assessment - Palisades Plant Steam Generator Replacement" dated December, 1979.

David P Hoffman (Signed)

David P Ho ff'man Nuclear Licensing Administrator CC:

JGKeppler, USNRC 8 pages

CONSUMERS POWER COMPANY Palisades Plant STEAM GENERATOR REPAIR PROJECT Docket No 50-255 License Mo DPR-20 At the request of the Commission and pursuant to the Atomic EnereY Act of 1954, and the Energy Reorganization Act of 1974, as amended and the Commission's Rules and Regulations thereunder, Consumers Power Company submits a. report entitled, "Environmental Assessment -

Palisades Plant Steam Generator Replacement" dated December, 1979.

This report discusses the environmental effects associated with a proposed barge slip which would be constructed as part of the potential repair program bs.sed on complete replacement of the existing steam generators if major repairs become necessary.

CONSUMERS POWER COMP.ANY By R B DeWitt (Signed)

R B DeWitt, Vice President Nuclear Operations Sworn and subscribed before me this 31 day of March, 1980.

  • By Linda K Carstens (Signed)

Linda K Carstens, Notary Public Jackson County, Michigan My commission expires Jl.llle 10, 1981.

ENVIRONMENTAL ASSESSMENT PALISADES PLANT STEAM GENERATOR REPLACEMENT CONSUMERS POWER COMPANY December 1979

PALISADES SGR-EA 1

SUMMARY

Consumers Power Company has applied for an Act 247 Permit to deliver two replacement steam generators to the Palisades Plant.

From both an economic and a technical viewpoint, barge delivery is preferred with the replacement generators unloaded at a docking facility at the Plant.

This facility includes offshore and onshore components.

In this Environmental Assessment Report, general littoral drift characteristics and chemical analysis of bottom sediments are discussed as a description of the existing environment in the affected offshore area.

Impacts associated with the temporary barge slip facility are related to construction, dredge spoil disposal, shoreline and visual aspects.

While adverse, all such impacts are temporary and minimal.

Secondary impacts associated with the steam generator repair project are also addressed in this Report.

Monitoring activities include an observation program for beach erosion and analysis of dredged material.

Appropriate State agencies would b.e consulted prior to taking mitigative measures that would

'involve additions to or changes in movement of beach material.

Various alternatives to the preferred barge delivery method were considered.

Truck transport from the fabricating shop. is not feasible due to the massive size of the generators.

Short haul trucking from harbors in the Plant vicinity is impractical and it is unlikely that necessary permits could be obtained due to the excessive size and weight of the steam generators.

Rail transport is impossible due to unavailability of rail equipment for such a massive load and to obstructions along the route.

Onsite assembly of the steam generators is not a practical alternative due to the massive onsite facilities required and the manufacturing status of the replacement 1-1

PALISADES SGR-EA generators.

Not having the steam generators on site and available for installation could add over $50 million in replacement power costs to the cost of the potential repair.

If the repair project is necessary, the Palisades Plant could be shut down for one to two years to replace the steam generators.

Costs for replacement power from the Consumers Power system are estimated to be $8-$10 million more per month over generation costs from Palisades.

In addition, the direct costs associated with the repair are estimated to be $80 million.

There are no known controv.ersies which have not been addressed and the major uncertainty is receipt of the Permit under Act 247 on a timely basis to complete planning and engineering for the barge slip facility prior to receipt

(

of the replacement steam generators.

Timely receipt pf the necessary governmental permits and approvals will contribute substantially to the success of the steam generator replacement contingency plan and will also minimize the costs of the repair.

1-2

Section 1

2 3

3.1 3.2 4

4.1 4.2 4.3 4.4 5

5.1 5.2 5.3 6

6.1 6.2 6.2.1 6.2.2 7

8 9

10 APP A PALISADES SGR-EA TABLE OF CONTENTS Title

SUMMARY

TABLE OF CONTENTS DESCRIPTION OF EXISTING ENVIRONMENT Littoral Drift Characteristics..

Bottom Sediment Analysis...

ALTERNATIVES TO THE PROPOSED ACTION No Action Onsite Assembly Truck Transport Rail Transport.

DESCRIPTION OF THE PROPOSED ACTION Need for the Project.

Purpose of the Project Schedule IMPACTS Primary Impacts Secondary Impacts Physical Impacts.

Economic Impacts of Plant Shutdown UNAVOIDABLE ADVERSE IMPACTS PROPOSED MITIGATION UNRESOLVED CONTROVERSIES REFERENCES EXCERPTS FROM PALISADES STEAM GENERATOR REPAIR REPORT 2-1 Page No 1-1 2-1 3-1 3-1 3-2 4-1 4-1 4-2 4-2 4-3 5-1 5-1 5-2 5-4 6-1 6-1 6-3 6-3 6-3 7-1 8-1 9-1 10-1

PALISADES SGR-EA LIST OF TABLES Table Description 3-1 Sediment Sample Analysis - Proposed Barge Slip Area 2-2

\\.

Figure 3-1 5-1 5-2 5-3 PALISADES SGR-EA LIST OF FIGURES Description Sediment Sample Locations - Proposed Barge Slip Area Site Plan General Arrangement - Section A-A General Arrangement - Section B-B 2-3

PALISADES SGR-EA 3 DESCRIPTION OF EXISTING ENVIRONMENT 3.1 Littoral Drift Characteristics Littoral drift, or the movement of sand along the shore, is due to wave action and a longshore current.

The sand movement is predominantly toward the south, with occasional flow reversals.

The sand movement occurs in the region near the shore where wave action is sufficient to carry the sand.

This region is expected to extend offshore about 2,000 feet, which is the Corps of Engineers estimate for another location on the southeast shore of Lake Michigan (3).

The flow of sand varies greatly on a daily basis, is more substantial during storms and rough weather, and is not significant during ice-bound periods.

The annual net volume southward of the drift has been stated to be not more than 100,000 cubic yards along the southeast shore of Lake Michigan (3).

Shore erosion is related to changes in littoral drift and to wind waves and water erosion.

Storms, particularly during periods of high water level, have severely eroded the shore at times.

The shore areas with bluffs in reach of the waves are particularly susceptible to damage.

The coarser eroded materials join the longshore drift while the finer are carried offshore.

Structures built into the Lake from the shore may alter littoral drift.

The signifi~ance of this alteration depends upon the length, design and duration of the protrusion from shore.

The presence of such a structure will trap some sand along its sides, as limited by the physical size of the structure.

The littoral drift must flow around the protrusion, and the sand flow will be 3-1

PALISADES SGR-EA effectively blocked only if the flow is diverted into deeper water beyond the littoral drift zone, as a result of the length of the structure or by offshore currents.

3.2 Bottom Sediment Analysis In October 1979, Lake Michigan bottom sediment samples were collected by diver from the proposed barge slip area at the Palisades Plant.

Collections were taken at the shoreline and at 100 ft, 200 ft and 300 ft from shore (see Figure 3-1). All samples appeared to be entirely clean sand with no visible contaminants or obvious odors.

Samples were preserved and analyzed according to the methods established by the American Public Health Association (1) and the US Environmental Protection Agency*(EPA) (5).

Results of these analyses

/

are given in Table 3-1.

According to the EPA guideline for the Pollutional Classification of Great Lakes Harbor Sediments (4), the sampled sediment material has been found to be nonpolluted.

3-2

w I w Parameter Volatile Solids Chemical Oxygen Demand Oil and Grease (Hexane Total Phosphorus - P Total Kjeldahl Nitrogen Ammonia Cadmium Cyanide Chromium Barium Copper Iron Lead Manganese Mercury Nickel Zinc Arsenic PCB Shoreline.

100 ft offshore.

200 ft offshore.

300 ft offshore.

Sol)

TABLE 3-1 SEDIMENT SAMPLE ANALYSIS PROPOSED BARGE SLIP AREA (mg/Kg)

Samele Locations A(a)

B (b)

C (c) 0.30 0.25 0.24 2,065 1,886 2,442 192 113 173 41.6 40.8 51.0 27 34 47 1.6 1.5 1.5

< 0.14

< 0.14

< 0.14

< 0.018

< 0.016

< 0. 017 2.47 2.20 2.40 3.23

< 2. 75

< 3.01 1.28 1.02 0.95 1,861 1,351 1,440 1.15 1.19

1. 75 28.2 24.2 25.8 0.013 0.013 0.008 1.98 1.66 1.37 5.84 5.33 5.80 0.37 0.24 0.32 (g)

(g)

(g)

(a)

(b)

(c)

(d)

(e)

(f)

(g)

Great Lakes Harbor Sediment Classification (EPA 1977).

Limits not established.

No detectable amounts (< 0.06 mg/Kg).

D(d)

Nonpolluted (e) 0.26

< 5 1, 777

< 40,000 131

< 1,000 33.0

< 420 58

< 1,000 1.5

< 75 1-d

< 0.14 (f)

~

< 0.016

< 0.10 H

Cl) 1.89

< 25

~

2.89

< 20 trJ en 0.76

< 25 Cl) 1,450

< 17,ooo C)

~

1.42

< 40

~

24.4

< 300 0~014

< 1 1.33

< 20 4.35

< 90 0.39

< 3 (g)

< 10

I I

\\

r

.. ~,.* ~-,:::;_7~*

_. '"!~f~*r!!~ !*

l lr~':....

  • . _p-;~: 1..- -,-_;i-I,,. ~,.. J,~

11'

~*

£3:'

. p____

-l I.

i +J 1,,,.,,,...~~

I~~,

~a'T4!

r I

I I

~.. ~.,,,. n.s* o.o c I

I. k1~,r. lf!M/1#.

PALISADES PLANT CONSUMEIS POWEi COMPANY SEOlllEIT SAMPLE LOClTIOllS PIOPDSEO ll!GE SLIP AllEA FIGURE S-1.

(NVIRONMlNTAl ASSlSSM(NT l'Tit11 l'rurannft *rn1 ll'rurur

PALISADES SGR-EA 4

ALTERNATIVES TO THE PROPOSED ACTION 4.1 No Action The barge slip is the preferred means of delivering the replacement steam generators to the site. Presently, the date for the outage to repair the steam generators cannot be predicted with a reasonable degree of certainty.

However, the length of the outage and the associated cost of replacement power during 1the outage are of paramount importance.

Those measures that serve to minimize the length of the outage also serve to minimize the total cost of steam generator repair project.

Therefore, not having the replacement steam generators available at the site in advance of the outage would be the penalty to be paid for the additional replacement power required while the Plant is

/

I

\\

idle awaiting delivery of the replacement steam generators.

Although such risk is unavoidable during the period that the replacement generators are being manufactured, such risk essentially can be eliminated if the replacement generators are delivered to the s.ite immediately following completion of fabrication.

The shipping season on Lake Michigan generally precludes barge shipment between mid-October and mid-April. If it becomes necessary to commence steam generator repairs after the shipping season is closed and the replacement steam generators are not in storage at the. site, there is the potential to add in excess of $50 million in replacement power to the cost of the outage.

This estimate assumes that the barge slip would be constructed and the units delivered to the Plant at the earliest opportunity, once Lake shipping could be resumed.

4-1

PALISADES SGR-EA 4.2 Onsite Assembly Onsite assembly of the steam generators is not a viable option due to the need for special facilities to assemble such equipment.

Even though planning would limit the scope of onsite work, the assembly of the steam generators requires a massive facility with specialized equipment.

Large cranes, lifting devices, machining capability, extensive testing equipment and welding systems similar to those *currently employed in the equipment's manufacture would be needed.

Additionally, the steam generators currently under fabrication would require disassembly, as the shells (outer boundary) of the steam generators have been assembled.

4.3 Truck Transport Large transport vehicles have been used to haul complete steam generators, and this option was investigated assuming the availability of such vehicles for Palisades.

This approach is completely impractical for the total trip from Chattanooga, Tennessee to the Plant site due to the size and weight of the loaded vehicle.

To address the practicality of short-range trucking, barge unloading in the existing harbors at South Haven and St Joseph was considered.

At either harbor, an unloading facility would have to be constructed, as neither harbor is prepared to receive. such heavy equipment.

Specialized lifting *equipment would be needed to place each steam generator on the transport vehicle.

Presuming issuance of proper permits from the local agencies, the load would 4-2

PALISADES SGR-EA proceed through city streets to the Blue Star Highway.

Special supporting measures would be taken at bridges, underground pipes and ducts.

Throughout the trip, residents would be inconvenienced because the movement requires an extremely slow speed, the removal of essentially all overhead wires, obstructions and branches, and the utilization of two lanes of roadway by the special 200-foot long "truck."

Based upon contacts with highway departments, Consumers Power believes that it is highly improbable that permits would be issued for highway use, because the expected loads present weight and dimensional requirements which are far in excess of those previously considered.

During the.construction of the Palisades Plant, highway departments urged Consumers Power to utilize the waterways for the delivery of heavy equipment.

Additionally, a cost estimate shows that transportation costs associated with this approach, about $500,000, would significantly add to the cost of delivering the steam generators.

4.4 Rail Transport The option of utilizing the railroads to deliver the assembled steam generators was investigated, considering shipment directly to the Palisades Plant from Chattanooga, Tennessee or from a barge offloading facility in

. 7 either St Joseph/Benton Harbor or South Haven.

The Chessie system, the railroad company operating the rails in the area, informed Consumers Power that such a movement is a "physical impossibility,"

4-3

PALISADES SGR-EA f"

I due t.o the unavailability of rail equipment that could accommodate a steam generator and to obstructions along the route.

4-4

PALISADES SGR-EA i

\\.

5 DESCRIPTION OF THE PROPOSED ACTION 5.1 Need for the Project During the 7-year operation of the Palisades Plant, the steam generators have been afflicted by a number of corrosion related-phenomena.

Consequently, a substantial portion of the extra heat transfer capacity of the steam generators has been removed as a result of plugging affected tubes.

Major progress has been made toward arresting or retarding the various corrosion mechanisms through changes in Plant equipment, secondary chemistry and operating procedures.

However, steam generator tube denting (local constrictions of tubes) remains an unresolved issue and threatens to result in additional steam generator problems.

With the uncertainty that exists with regard to future plugging requirements and the expected useful lives of the existing steam generators, Consumers Power Company has evaluated practical major repair alternatives that are available to restore the steam generators to their original condition and regain the initial heat transfer capability.

Complete replacement of the steam generators is the preferred method of repair.

Recognizing the length of the procurement lead times associated with obtaining components for the steam generator repair project, Consumers Power Company has embarked upon a contingency planning effort designed to mitigate possible adverse consequences of continued tube corrosion.

To conduct this repair, the major elements of this contingency plan include:

procurement of replacement steam generators and other long lead time materials, preparation of engineering studies and detailed engineering necessary to support the 5-1

1-*.

\\

(

\\

e*

PALISADES SGR-EA construction aspects of repair; preparation of work plans associated with repair activities; and, preparation of applications for permits needed from various regulatory agencies.

Work proceeds on all elements of this plan and although Nuclear Regulatory Commission (NRC) approval of the repair program will be required prior to the commencement of the actual repair work, it is reasonable to expect that the replacement generators will be finished and ready for shipment to the site before replacement is necessary.

NRC approval by June 1979 was requested.

A Consumers Power Company Application for a Permit under the Great Lakes Submerged Lands Act, Act 247, PA 1955, as amended,* and Section 10, Navigable Waters, US Rivers and Harbors Act of 1899, was transmitted to the Michigan Department of Natural Resources (MDNR) and the US Army Corps of Engineers (COE) on January 10, 1979 (joint application) for installation of the barge slip.

This Permit is a long lead time item which is needed to finalize planning, to have the barge Slip approved before work starts, and to minimize the outage time and costs if it is necessary to replace the steam generators.

5.2 Purpose of the Project The project for which Application for an Act 247 Permit was submitted is the construction of a temporary barge slip in Lake Michigan to d~liver two replacement steam generators to Consumers Power's Palisades Plant.

Application has also been made to the NRC for approval of a program to replace the steam generators when and if such a repair is necessary.

The details of 5-2

r-.

i

\\

\\

\\

PALISADES SGR~EA the proposed repair program were presented to the NRC in January 1979 in a document entitled "Palisades Plant Steam Generator Repair Report."(2)

It is planned that replacement generators will be shipped by barge and unloaded at a temporary barge slip at the Plant-site (see Figure 5-1). It should be noted that the proposed barge facility has been designed to accommodate the largest barge considered and the facility may be smaller if a smaller barge is utilized.

However, interstate Commerce Commission regulations prohibit the contracting of a barge more than 40 days in advance of its use, so the barge facility must be designed at this time to accommodate the larger barge.

A portion of the reactor containment building will be detensioned and a.

construction opening cut in the containment to allow access of men, components and materials.

The old steam generators will be cut free from connecting

~iping, rigged vertically from their cavities, lowered to a horizontal position, and removed through the construction opening in the containment.

The installation will then follow in reverse order using the replacement

~enerators (see Figures 5-2 and 5-3).

The "Repair Report" included an assessment of alternatives for disposal of the old steam generators.

(Sections 4.4 and 9.3 from that report are included as Appendix A to this Environmental Assessment.)

In addition to possible site storage in a suitably shielded facility, consideration was given to offsite disposal methods, with shipment from the site by means of either rail, truck, or barge.

Offsite disposal with shipment from the Palisades Plant via barge 5-3

l i

\\

PALISADES SGR-EA is the most desirable method of disposal from both an economic and an occupational dose standpoint.

No date has been established for commencing the repair project, and availability of offsite disposal facilities at the time of the repair is uncertain. Therefore, it is premature at this time to include shipment of the old steam generators from the site as a definite use for which the Application for an Act 247 permit is submitted. If the repair project schedule and availability of offsite disposal facilities are compatible with receipt of the replacement generators, then Consumers Power Company may ask for an extension of the Act 247 Perniit for shipment of the old steam generators.

However, a real and urgent need exists to have suitable facilities available at the site for the receipt of the replacement generators, and the approval of the proposed barge slip is sought now.

The replacement generators are being I

assembled on schedule at a vendor shop and are expected to be ready for shipment to the Plant site by August 1981.

5.3 Schedule The following schedule milestones must be met in order to permit barge delivery of the replacement steam generators to the Palisades Plant site in August 1981:

a.

Complete Soil Investigation and Test Piles, December 1979

b.

Complete Design of Barge Slip, June 1980

c.

Award Sheet Piling Contract, December 1980 5-4

(

PALISADES SGR-EA

d.

Deliver Sheet Piling, March 1981

e.

Drive Sheet Piling, Start April 1981, Finish July 1981

f.

Dredge Channel, July 1981 Federal (COE) and State (MDNR) approval of the Application for an Act 247 Permit for the repair project is sought by January 1980 (one year after Application date) to avoid an adverse impact on this schedule.

The offshore sheet piling or sunken ship hulls that may be required temporarily (approximately eight months) in the Lake will be removed as soon as practicable after operations are completed.

The decision on the ultimate disposition of the onshore facilities above the Ordinary High-Water Level of the Lake has not been finalized; however, their removal will be at Consumers Power's option.

5-5

...... *~._,..,.i!*Pi.¥44ffi3!!!!1JJCSi~;f£ntZ!iSZ t


:-:-:-:~::=====~~;;~

' ' -dk*i::;t=

...* RtS!'!'t".~~*~;:;;.*

~

~~~--~~-

  • m=Pf4¥S~=*~~'""-*~-~-*

mi.. *.... ~~

.............. ~. '""

    • +~~~

...,.:-:.,1*,...*

SITE YIClf<llY !!AP U.u.lr-111111,.,.,...0ll.

!~~----***-*-* -

\\

\\

. /';~-':.,~~.-,. G*""


'lib

-* ~--=~

i Si

~I

      • ~*--

PALISAD CONSUMERS P SITE

IL

\\1,

~

~

-- ~--.-- T--

I

~:

PALISADES PLA CONSUMERS POWER COMP GENERAL ARRANGEME SECTION A-A FIGURE 5-2

0

  • g-**- - --*--*

t-SEC.TION e.-e. (*""".... 4.1*7 )

L___ ___

JI

.., GG

- ** 4 ~J*~!Wlo'!NT PALISADES PLAP CONSUMERS POWER COMPAi OE"ERAL ARRAHOEMEll SECTION B-8 FIGURE 5-3

\\.....

I_

PALISADES SGR-EA 6

IMPACTS 6.1 Primary Impacts The primary impacts are those impacts associated with the temporary barge facility.

This facility is discussed in Section 5 and shown in Figure 5-1.

The impacts are categorized as construction impacts, dredge disposal impacts, shoreline impacts, and visual impacts.

The construction impacts would be those temporary impacts of construction, and are addressed in Appendix A, Sections 7.0 through 7.6.3.

Within that Appendix, Section 7.2.3 discusses the effects *on water resources.

Other construction impacts, including noise and dust, are discussed in Section 7.4 of that Appendix.

Because the dredged material was shown to be nonpolluted (see Section 3.2),

the relocation of this material will not have a significant impact.

The offshore dredge material would be distributed on the sides of the dredge channel.

The onshore excavated material would also be placed on the sides of the work area and remain onshore.

Material* from either source may be transported to a disposal area on site if they interfere with construction activities, or if it is found to be polluted at the ti~e of dredging.

Natural wave action will return the Lake bottom to its original contour; the disposition of the onshore sand piles will be determined at a later date.

The shoreline concerns are:

(a) restricted access, and (b) erosion.

The temporary offshore installation, due to its physical limits, will preempt approximately 0.6 acre of the Lake surface and bottom.

This portion of Lake 6-1

(

i

\\ ;...... _,

PALISADES SGR-EA Michigan would be preempted from public recreational and fishing use, but the impact is minimal because of its small size relative to similar water of the Lake.

The offshore portions would pose a temporary obstacle to boats, and appropriate markers and/or lights will be installed.

The onshore sheet piling will extend about 100 feet along the shore, making that section unsuitable for beaching small water craft. This area, however, is not generally used for such activities.

Access to the beach by walkers is already hampered by natural and other Plant interferences.

As described in Section 3.1, protrusions into the Lake may alter the littoral drift and, thereby, aggravate beach erosion.

However, because this facility extends only about 240 feet into the Lake, the flow of the sand near the.shore will be deflected into the Lake, but will remain close enough to shore to be carried to nearby beaches by wave action.

This flow pattern would also occur during storms, when major shore erosion would be most likely.

Most important, the offshore facilities will be present for only a brief period and removed promptly upon completion of equipment delivery.

Therefore, the contribution of the barge facility to shore erosion from natural effects is expected to be minimal.

The barge facility will be visible to the public from the Lake, beach, and air. It will appear like portions of other marine* *facilities in harbors or pleasure boat marinas.

The offshore installations will be removed after use, leaving only the onshore barge slip which will be inobtrusive because of its size relative to the Palisades Plant.

6-2

PALISADES SGR-EA 6.2 Secondary Impacts 6.2.1 Physical Impacts The construction activities associated with the steam generator replacement are similar to those of any heavy construction work, but with the additio~ of

  • radiological considerations. Radiological impacts are within the scope of the jurisdiction of the U.S. Nuclear Regulatory Commission.

This topic was addressed in the Steam Generator Repair Report (2) and portions of that report are included here as Appendix A.

Sections 4.4 and 9.3 of Appendix A discuss the disposition and the impacts of steam generator storage.

Sections 4.37 and 6.2.2 of the Appendix address radiological aspects while

(..

Section 7.0 considers other environmental aspects of the repair program.

Only references within those sections that are relevant to the topic are included in the Appendix.

6.2.2 Economic Impacts of Plant Shutdown The replacement of the Palisades steam generators requires that the Plant.be shut down for some period of time (expected to range from one to two years).

During that time, the generation deficit caused by the loss of the Palisades Plant from the electrical system will be m~de up at other Consumers Power Company generating facilities or from external sources. If system reserves are adequate and replacement power is available within the Consumers Power Company system, such power is estimated to cost from 8 to. 10 million dollars more per month to produce than if it were generated at Palisades.

(Estimated costs are based on an outage which might occur in the early 1980s.) The 6-3

PALISADES SGR-EA estimated cost of the steam generator replacement project, exclusive of replacement power, is 80 million dollars.

This estimate is also based on the repair outage occurring in the early 1980s.

The impact upon rate payers will depend upon treatment by the Michigan Public Service Commission.

It should be noted, however, that to minimize the economic impact.of the steam generator repair program, Consumers Power Company has proceeded on the contingency plan described in Section 5.1.

The success of that plan and the ability to minimize the cost of the repair will, to a large extent, depend upon the ability to obtain the necessary governmental permits and approvals on a timely basis.

(

\\ __

6-4

PALISADES SGR-EA 7

UNAVOIDABLE ADVERSE IMPACTS The impacts discussed in Section 6 must be incurred to accomplish the repair of the Palisades steam generators in a practical manner.

Unnecessary impacts have been eliminated by controlling the scope of activities.

The impacts discussed in Section 6 are tabulated below:

- Construction Impacts of Barge Slip and Replacement Effort

- Dredge Disposal Impacts

- Shoreline Access Limitations

- Shoreline Erosion

- Visual Impacts

- Radioactive Releases

- Radiation Exposure of Workers

- Resource Commitments These impacts, however, are minor in that they do not significantly alter any ecological system or massively disrupt natural settings.

With the exception of some onshore structures which will not be removed, the impacts of the steam generator repair effort will be temporary.

7-1

PALISADES SGR-EA 8 PROPOSED MITIGATION With spe_cific regard to the proposed barge slip, several items have been identified that warrant continued appraisal and may result in the need for mitigative action to reduce adverse environmental impacts.

These are identified separately below.

In addition, construction activity will be controlled to mitigate, to the extent feasible, impacts associated with noise, dust,* aesthetic intrusions and related activities that may be cause for local complaint.*

A program of shoreline monitoring will be in effect during the period when offshore facilities may affect littoral drift, although the Company believes the project will have no significant impact on littoral drift. Visual inspection procedures, as well as land-based photography, will form.the basis for identifying erosion patterns.

Upon identification of adverse effects, if any, quantitative estimates of material displacement would be developed and a program of corrective beach nourishment would be implemented after concurrence by the appropriate agencies and property owners.

Representative samples of dredged material will be obtained to ensure that the material is disposed of in accordance with regulations which limit chemical constituents and particle size characteristics. Mitigative action may be necessary should the tests indicate an unexpected variance from anticipated characteristics.

The Michigan Department of Natural Resources will be notified immediately if any significant variance is found.

8-1

PALISADEs*saR-EA 9 UNRESOLVED CONTROVERSIES It is hoped that the information contained herein will resolve any controversies with individuals and groups who have filed objections to the proposed a.ctions.

The primary interest of most obj ect9rs is in connection with shoreline erosion, which has been recognized, but should not be significantly affected by this activity.

Some uncertainty remains with respect to the need for and extent of mitigative activity, as identified in Section 8, and with regard to the schedule of various activities.

Necessary adjustments in either of these categories are not expected to significantly affect the nature and extent of environmental impacts.

9-.1

PALISADES SGR-EA 10 REFERENCES

1.

American Public Health Association, Standards Methods for the Examination of Water and Waste Water, 14th Edition, APHA.

Washington, DC, 1975.

2.

Consumers Power Company (Compiler), Palisades Plant Steam Generator Repair Report (as revised) (January 3, 1979), Consumers Power Company.

3. Tillinghast, John, (Senior Executive Vice President, American Electric Power Service Corp.), statement before the US Corps of Engineers at a

'Hearing-in-Br-idgman-,-Michigan~_April_l9_, 1=9~7~3~*--------------------

(

\\

4.

US Environmental Protection Agency, Guidelines for the Pollutional Classification of Great Lakes Harbor Sediments (1977), USEPA Region V.

Chicago, Illinois.

S.

US Environmental Protection Agency, Methods for Chemical Analysis of Water and Waste (1979), Environmental Monitoring and Support Laboratory, Office of Research and Development, USEPA.

Cincinnati, Ohio.

10-1

PALISmHI..*.

Palisades Steam :Gia Repair Report.

Section 4.3.7 Man-Rem Assessment 4.4 Disposition of Old Steam Gent:a:

6.2.2 Offsite Radioactive Releases jia.Asses:sment

7. 0 Environmental Aspects of the ljtrogram-

(

PALISADES PLANT SGRR

\\ *..

/ (

\\.... _

  • 4*. 3 ;7 MAN-REM ASSESSMENT 4.3.7.l Man-Rem Assessment for Continuing Operation Assuming that the replacement steam generator tubes maintain their integrity during the remaining operating lifetime of the plant, radiation exposure attributed to steam generator work will be reduced.

It is not expected to exceed 25 to so man-rem per year for a tube inspection operation in accordance with Regulatory Guide l.83.

It has been estimated that approximately 250 man-rem could be saved each year following the steam generator repair.

4.3.7.2 Man-Rem Assessment for the Repair Effort Health physics survey data have been reviewed for the period from November 1976 through March 1978 at various times ~fter shutdown to determine trends in dose rates and radionuclide contributors that affect operations in the vicinity of the steam generators. (Typical survey results and data are shown in Figures 4.3-3 through 4.3-5.) It is believed that this plant survey data is representative of conditions expected at the. start of the repair activity, provided that appropriate dose rate increases due to activity buildup within the steam.generators are considered (Reference 3).

Survey data in the vicinity of the steam generators and primary coolant piping were averaged and used to project general field and dose rate estimates at various times after shutdown (see Figures 4.3-6 and 4.3-7).

The man-rem assessment for the repair effort is shown in Table 4.3-2.*

4.3.7.2.1 Radiation Field Uncertainties

a.

Radiation fields were taken from actual Palisades Plant surveys and adjusted for activity increase as a function of time before steam generator removal.

In developing the man-rem predictions, it was assumed that the radiation fields would not decay throughout the repair effort.

Actual radiation fields will decrease with time.

Therefore, the actual total job man-rem are expected to be lower than the calculated values.

b.

The effectiveness of temporary shielding or local decontamination will be further defined as dose rate survey data and primary system samples are gathered during future outages.

Reduction factors as now estimated are ihdicated in Table 4.3-2.*

  • This table has been revised and is now labeled Table C-1-5.

4-31

PALISADES PLANT SGRR 4.3.7.2.2 Assumptions Used to Estimate Manhours by Area for Dose Calculations

a.

Nonwelding Operations in Radiation Area

l.

50% of manhours in radiation area

. 2.

30% of manhours checking in and out through Health Physics and Security

3.

20% of manhours in lower radiation area of containment

b.

Welding Operations in Radiation Area

. Welding operations in the radiation area are based on rotating welder and helper between work area and lower radiation area, as work operations dictate, to minimize welders' exposure.

l.

35% of manhours in radiation area

2.
3.

30% of manhours checking in and out through Health Physics and Security 35% of manhours in lower radiation area of containment

c.

Outside Work All manhours are outside of the containment.

d.

Welding of Primary Coolant Pipe The following is based on rotating welder and welder.' s helper between work area and lower radiation area as work operations dictate to minimize welders' exposure.

4-32

)

_,*.~

)

_)

PALISADES PLANT SGRR

l.

35% of manhours at primary coolant pipe broken down as follows:

Outside pipe 35% X 68% = 24%

Inside pipe* 35% X 32% = 11%

Total in place

= 35%

  • Inside pipe manhours required to grind and clad inside of primary coolant pipe by conventional manual methods
2.

35% of manhours in low radiation area of containment

3.

30% of manhours checking in and out through Health Physics and Security

e.

Stress Relieving of Primary Coolant Pipe

l.

10% of manhours inside pipe

2.

30% of manhours. within 6 feet of pipe

3.

30% of manhours in lower radiation area of containment

4.

30% of manhours checking'in and out through Health Physics and Security

f.

X-Ray and NDT of Primary Coolant Pipe A total of 2,600 hours0.00694 days <br />0.167 hours <br />9.920635e-4 weeks <br />2.283e-4 months <br /> is allowed to x-ray the primary coolant pipe.

This is based on 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> availability per day for x-raying inside containment.

l.

37% of manhours checking in and out through Health Physics and Security

2.

20% of manhours inside of pipe

3.

30% of manhours within 6 feet of outside pipe

4.

13% of manhours in lower radiation area of containment 4-33

g.

PALISADES PLANT SGRR Approximately 780 additional hours of time for x-ray technicians are included to x-ray the main steam and feedwater lines.

h.

Rigging

1.

The following work operations were considered to be outside of the power plant building but inside of the security fence:

(a)

Set up equipment to handle the new steam generators from the barge slip to the containment (b)

Set up equipment external to the containment to handle the new and existing steam generators (c)

Offload, move to storage, and later transport steam generators to containment (d)

Remove all external rigging equipment from the site (e)

Decontaminate and remove all internal rigging from the site (f}

21% of manhours allowed to install new steam generators

2.

The following work.operations were considered to be at the containment operating floor level or higher:

(a)

Install rigging equipment inside containment (b}

Decontaminate and remove rigging equipment 'from inside of containment (c) 60% of the manhours allowed to install new steam generators

3.

Seventy percent of the manhours associated with 2. above were considered to be at the operating floor while 30% were required for checking in and out through Health Physics and Security.

4-34

_\\

I,

)

I

_)

(.

i.

PALISADES PLANT SGRR

4.

Forty-nine percent of the manhours associated with removing the existing steam generators from the containment were considered to be within 6 feet of the primary coolant pipe or

  • bottom of the steam generator, 21% were required to check in and out through Health Physics and Security, and 30% were next to the existing steam generators outside of the containment.
5.

The manhours associated with moving the existing steam generators to storage were considered to be adjacent to the existing steam generators but outside of the containment.

An assumption was made that 50% of the manhours required to cut the primary coolant pipe would be spent within 6 feet of the outside of the primary coolant pipe or bottom of the steam generators, with partial exposure to the inside of the primary coolant pipe before the steam generator removal.

Thirty percent of the remainder would be spent checking in and out through Health Physics. and Security, and 20% would be spent in an area of low radiation.

j.

It was also assumed that 50% of the manhours required to level, line up, and tack the primary coolant pipe would be spent within 6 feet of the outside of the primary coolant pipe, with partial exposure to the inside of the primary coolant pipe after steam generator removal.

Thirty percent of the remainder would be spent checking in and out through Health Physics and Security, and 20% would be spent in an area of low radiation.

k.

The manhours associated with miscellaneous piping operations were spread in accordance with the piping hours spent in each area.

l.

Oistributables

1.

Welder tests and miscellaneous services were considered to be outside the plant buildings but inside the security fence.

4-35

/

/

/

2.

PALISADES PLANT SGRR Startup, cleanup, and scaffolding distributables were prorated on the basis of total manual manhours at each location, excluding the outside work.

m.

Nom:anual Labor The following assumptions were made on the nonmanual labor manhours:

1.

All manhours, except for superintendents and engineers, would be expended outside plant buildings but inside the plant security fence (office work).

2.

Fifty percent of the superintendents' and engineers' manhours for piping, electrical, civil, rigging, and safety would be outside the plant building but inside the security fence (office work).

3.

The remaining 50% of the superintendents' and engineers' manhours were prorated to each of the work areas based on the total manual hours spent in each area by discipline.

For instance, the piping superintendents' and engineers' manhours were prorated on the basis of the total of manual hours spent in performing the piping operations in each area.

4.3.7.2.3 Technique for Estimating Radiation Dose The total dose is dependent on the following factors:

a.

Dose rates (rem/hr) before shielding or decontamination

b.

Shielding or decontamination effectiveness

c.

Duration of tasks (hours)

d.

Manhours required to complete tasks

e.

Fraction of time the task is in radiation interest field The entire repair program has been divided into discrete areas.

The total personnel exposure in an area is the 4-36 of j

.J

_)

/

    • ~.

PALISADES Pt.ANT SGRR product of the dose rate and the manhours required to complete all tasks involved.

The total exposure for the entire job is a summation of the exposure for all areas.

Therefore:

Ei = Di (rem/hr) x Mi (manhours)

E

= L: Ei (man-rem) where:

Ei Di Mi E

=

=

=

=

Total personnel exposure for area i (man-rem)

Average dose rate in area i (rem/hr)

Manhours to complete all tasks in area i (manhour)

Total personnel exposure for all areas (man-rem) 4.3.7.2.4 Confirmation of Man-Rem Estimate Daily radiation dose logs will be maintained for each worker stationed within the higher dose rate (~10 mrem/hr) areas of the containment.

Weekly, monthly, or quarterly records will be maintained for those working outside the containment and in other specially designated low dose rate areas.

These actual doses will be tabulated by task category for confirmation of estimated doses provided in this ~eport.

4-37

(I) l'Al.lliAlllm l'l.ANT St:RB

'l"ABl.E c:-1-5 (SUEf.1' I)

HAN -lltll f.S'l"ltlA'l"F.

Work Art*<I (l.nr111 Ion)

Aver1111e R1ulJ11llu11 Field (re**/hr) t:1;1* llo11ted H1mho11r11 (tln111111I Ucldlug)

--_, ___ !._1 __,_

I. Oult1l1le nf 1111wor 11lanc ln1ll1ll1111 11111. within occur I l y (t~1u:u.

l. Chedduc 111 mul uut Llu*u1111h um:nr It y 1111tl heallh 11hy1dce *ltl Wt!ll 110 Lliuu s1nml uulLlni:

up, cl*~anlnu "I' and 111ovl1111 In mul hum wol"k Rrt!llU 1111" t*Cl"llUIUlt-l workl1111 In n11ll1uu:llvo u1*cu:1.

1. lueltle **nutaluumnl nl'ar H&.!W t!OIUlll"Ut~l..... opculua.

'** llllhln,, *.,, m1lt1l1ll! or rl!nctor 1:uol;111l 1*1110 cu*

l10Llu1n ur HltH111a G"'u!rntur au* lur In JUlllUVil I u( steaua GClh!JUl01"8.

~. Within 6' out 11l1le 111 n*ul"lur 11rnolnnl 1*l1u-ullt~I° Ut**mM t;,t'!tll!Ci&lnr 1 H rt*muual.

(1. Within (o' o( uutttlolo* 111* re11ctur 1:onlan1 1*l1u~ ur lutl I UUI ul*

t1lt~11m G*UU!l'itlon1 wl lh.. art IHI CICpOHUl"I! tu luuld.. nl 1*ua1*1or conlnnl l'll*l!' 1*1*1,11*

to ult:nm get!t~nunr'u a t*umv;1I.

1. Within 6' of 1111lt1lol0! of ruac:tor 1:u1tl*111C 1*lpu with 1o;11t l11I t!KIUUIUCC lu hu1l1lf! u( l"fl'iU:tur t*tmlunl pip~ a(lt'I ul t.*am 1~1!1mrdl11r*n n~111nval.

I

-5

.5 x 10

.01125

.001

.010 -

.050

.OIO -

.010

.050 - o. 1110

.050 -

.100 211659

'J"i14 6216 1"678 501 "iMB In llJ11llnt Ion l'leld (tlad1lne u... 1o11t111)


*-*---~L---

211619 521118 12111 5111 (1.)

Areu tlan-11<*111 llooc (H*111-ll1*1n)

(Hnnuol Ueltllng)

(tlad1l11e \\lclcllng)

I.I

1. l 110.J 1 *111 J.S 1.5 188.J - lll.R 1*.n.1 - ]2l.l 196.8 - SIJll.1 UI.1 -

"JM.II 2'i.4 -

')() *.,

l~.1. -

50. J 281
  • 111.H - 615.5

...,. ___ )

Z"lll -

1 *I *1 l "l.ll -,.,.,

  • 1111 11 l"'ll l "'11 lllll

'1"9 l'l'l'I l"O t"O 6lL fi"l 6"[

II"" -

c.;*,,.,

l"86 -

("6'1 11066

(

  • 11 z*11 l'll 11 u* 11 0*11 O!;ll l"Oll 961 Oto9'1 l *c.;

z*c.;

oc.;1 o*e11z -

'Ill ll"lll -

9CI

'II. I

'l"OS - B"Lt

.,., !i - L"UC l "'I (H111r1an '"'l'l'"'H)

(ll111r1a1t JBntmH)


l~-** --- --*--*

(n1;tl1-llUff)

(Bo11*1"1t ""l'l*"'H)

OHOC1 **Jlf-tll?ff "".JV l'l"'ld lllllltrll>llll U(

(l) r

  • 9111 '1 0(0" - 010*
  • ("'""" "I) R.IO)U.Jttoan "ll!il lfl t\\;IU Jo l I "'I "'" 11 "'I '"I' J",., "1'1111\\ "l l lClll c.;oo*

0.illOIJ,...... '""J 111mls..,,

11011*1 100*

. """l Ol'l<>r*"'l'I Jmm lln11111m1 AJl!J I pmy *c.;1 6ll IOO" l91tl.

IOO" l911f1 om* - c.;oo-lllll IOO" c.;9cz suo*

I 861fJI:

c.;oo*

8'11 uo*

9Cl o*z

- 11* 1 C"'I o*u

- 0"6


,-¥--*---

(ft111r1an '""""10 B.JllUlllll!H l'i111JlllJ1!1ll ll.l.Vlfl.l.S-11 lfllll-NVH (l.1.:m11s) 1t-1-a :n11v.1.

r1au 1111:.IS J.NY'IJ SilllVS I '!Vol

(.l*lf*ia.1)

OOJlllJllllll alfo.131\\V (I)

.Jtllt?r\\ ~h111uo:. pun """l lllll"J tl1till:l.llJilU !11111*11*111 Aiu111xny..,,

  • ""I 1l!Aapl aUUJ~l

.1u1ml 111

  • 1natuHIU:JUO;l "l'JRlll *u
  • 1um11111 u1una.10 *"'"1 J lln111r.1mlo *z1
  • ( """ 1t1

.., l"'l l'flHlll)

~.1n1c.1au.,fl 01na1Y fttJH JU Jll!lf ""'

JO I 9 11 Jiil I H

  • 11

. ("""' "' l"'l l1!1911J)

RJOll!l.1U;.19 NIHl IA 1uu1llpo JO JIUll 1ln1 JO

,9 ""'""

  • 111 llliJIHHI l!lUO;J

""' 11'1Jlr

...., llrJl*l!.I l'llrj "6

  • uni 111n1um1nn:tap JilJJll.,.11d

.1uu100~* Ju1.11~a.1 )" ;-11*111111 ("

  • uo11uu1nm1uo:-tap iUllJ"'I Ol'l""I aJnnudxn 1u11.rn<I/"' 0<11<1 Jn a1*101110 (*I "OCll ll!lllOllllllO:'Jill' il.UIJll<I adJ

lfilll!lo:'I' l) tlAN**ltt:tl l*:STIHAl'E Aver11gc llrullatlnn t"lcl1I (n.. /hl')

t:N1* lm11te1I tl1111hm11'8 (tla111111l Welding)

  • -- -*-. __ 11_1 ___._
18. Wllhln,, *.. r lbe 11111*sl1lt* nf tho reactor YllH8t'I.

.IOO ltO

19. Ill' Kr l:U I he l!11 l11t Ing 11tt!i11M H,L'IH?l'Uluru cnil11l1h: uf 1lae cu11-tulmm*nt

.020 -.OIO 1111

20. lnsl"l lnt* lou "'

11hl**lillnc..... 1 local 1l1*,:unl:e1u1lnul Ion.

(1)

(1)

(I) ltl!1hu*1 Inn r111*tlll"ll all'rllmtcd to 11hleldlng 111111/ul' dec:n11tmoh1nl 11111 huve been h11*oq111ri111*1I 111111 1 l11Hu' Uel1I e11t lruate11 a111I wl 11 not l*e 1*rllNC'nted here 1111 a Ht!pnrate 1*ulmun.

(2) t"url11m* u"luct Inn In 11n*11 1um-rcia doNc *:uni.I nc:t:UI' nt1 wurk 1m1*k1111cs onil Al.AHA ul111l le11 *~nnt 11111**.

'l'hl! l!11l l11111te11 111*., l111oe1I 1111 1:011Bl!l'Ylll lvl! 11u1111na1*t lunu.

0) 1'hc 1o;111huul' l!llt l111a1 e11 for ploc:e11e11t of ehlt!ldh*K 111111 ltll"111 cl1,.*m1tomh111l ln11 arc lmlliltlVI! dm* 111 1111* o:nnllnm11'11111 of Al.111111 annlyuln m11I wnrk p111'kn1;e 1luvu lo1*uu,nt.

"l'h** uuml11*rH 11rt*au11l*'*' here aru an e111* 1m,1l**

~11111 1*n1-.rc:eent u 1mrcuu1anc~ ur llm lotal 1mu1-rcm.

~-/*

In llmllnr 1011 Field (Had1l11t! \\.l**ldlng)

  • ----~1 ____ _

1,0 l1'J1 (1)

(l) 1\\1'1!11 tl1111**lh*m l1118l' (lla11-R1*m)

(H11111111l lleld lnK)

(tli1d1lne lleld Ing) 4.II lt.O 14.7 -

'>2.1 v *. 1 -

52.1 J!i~! - ]!1!!*"

!.'~~'?. -

?l!~!J 1541 28111.6 l~H U162.9

... ___ )

. (

PALISADES PLANT SGRR 4.4 DISPOSITION OF.OLD STEAM GENERATORS The disposal effort is independent of the repair and is evaluated on that basis.

Because of the uncertainty of the timing of the repair and the availability of the offsite disposal facilities, the ultimate disposition of the old units cannot be finalized at this time; however, a variety of disposition alternatives has been investigated.

The steam generators to be removed represent the single largest source of solid radioactive waste to be disposed of during the repair effort.

The primary side internal surfaces of the steam generators are contaminated by a tenacious film of deposited radioactive corrosion products made up primarily of cobalt, manganese, and iron isotopes.

Isotopic analyses obtained from uncleaned 2-inch long sections of steam generator tubing indicate that at the time the steam generators are removed, each will contain approximately 30 curies of deposited gamma activity (see Table 4.4.l and References 2 and 3).

The activity will decrease to approximately 2.8 curies per steam generator 2 years after shutdown, then continue to decay with the 5.6 year half-life of Cobalt-60.

4-37

PALISADES PLANT SGRR 4.4.l OBJECTIVES OF HANDLING/DISPOSAL OPERATIONS The objectives of handling/disposal operations are as follows:

a.

To dispose of the steam generators safely and economically

b.

To provide the means to handle/dispose of the steam generators so that radiation exposures to plant and contract personnel are as low as is reasonably achievable

c.

To minimize the release of radioactivity to the environment so as to keep radiation exposure to the public as low as is reasonably achievable and within the limitations of 10 CFR 20 4.4.2 ONSITE STORAGE If it is decided that the old steam generators will be stored onsite, a storage facility will be necessary (see section 4.1.1.2.2).

Before removal from the containment, the openings in the steam generators will be sealed to prevent the release of radioactivity during transfer and subsequent onsite storage (see Section 4.3.5.2).

Sealing will pe performed by welding plates of steel over each pipe opening.

The steel plates will be thick enough or supplemented by lead shielding, if required, so that external dose rates at the sealed opening are not higher than adjacent surface areas.

The only significant radiological consideration associated with storage is the direct radiation from the steam

  • generators (see Section 4.4.6).

Shielding will be provided to ensure acceptable radiation levels external to the storage facility.

Section 4.4.7 demonstrates that there are no credible accident considerations associated with onsite storage of the sealed steam generators that result in the release of radioactivity from the steam generators.

4-38 J

-~--*.

(

PALISADES Pt.ANT SGRR Based on the above considerations, the required storage facility design criteria are:

a.

Appropriate shielding for direct dose

b.

Access for periodic surveillance of steam generator seal integrity using portable monitors

c.

Environniental protection in a weathertight and restricted-entry shelter 4.4.3 OFFSITE DISPOSAL The following three methods were investigated as alternative means of shipping the removed steam generators* to a licensed land burial site:

a.

Shipment by barge in one piece

b.

Shipment by truck cut up

c.

Shipment by rail cut up 4.4.3.l Pre;Earation for Shipment b;L Barge.*

Barge shipment of the *old ste*am generators is determined to be the most acceptable method from both environmental and occupational dose standpoints provided that routing and

  • handling capabilities remain available at the time of shipment.

The steam generators will be sealed before removal from the containment so that the radioactivity will be contained within a strong, tight package as required by 49 CFR 173.

When the steam generators are to be shipped to a licensed land burial site, each one will be transported to the barge facility intact and shipped as low specific activity (LSA) material in accordance with applicable state and federal regulations.

4.4.3.2 Preparation for Shipment by Rail and/or Truck In preparation for shipment of the steam generators by rail or truck to a licensed land burial site, the generators would be cut into sections suitably sized for shipment.

The cutup sections would then be packaged in strong, tight packages and shipped with appropriate shielding in accordance with applicable state and federal regulations.

4-39

.e PALISADES PLANT SGRR Cutting operations on the steam generators would be performed in enclosure envelopes, as required, to minimize the spread of airborne radioactivity.

The enclosure envelopes will be provided with a HEPA filtration system to reduce the potential release of radioactivity to the environment and will be designed to allow the ~se of remote cutting techniques to reduce personnel exposure to radiation during cutting.

Temporary shielding will also be provided, as required, to further reduce personnel radiation exposure.

Rad~ation detection and measurement during cutting operations will be in accordance with the Palisades Plant Health Physics Procedures.

4.4.3.3 Shipment If shipped by truck, potential disposal sites would be Sheffield, Illinois; Morehead, Kentucky; Barnwell, south Carolina; Beatty, Nevada; and Richland, Washington if in service at the time.

Further, if shipped by truck, 14-foot maximum width dimension limits exist, and then only for escorted shipments.

This width includes shielding and overpack material.

Hence, the net width would be around 12 feet, with maximum length limited to about trailer length, or 38 feet, without special hauling permits.

Shipment by rail or barge limits disposal to Richland, Washington, as this is the only site with rail and ship offloading facilities.

For rail, the maximum width, including shielding and overpack, is 10 feet, producing an effective maximum net width of the cutup material of about 8 feet.

These maximum dimensions apply for rail and truck shipments only if additional large shields are constructed and receive U.S.

Department of Transportation approval permits.

Utilizing existing shielded casks, 'dimensions.of the cutup material would be considerably smaller--on the order of 10 feet by 6 feet by 3 feet.

If the steam generators were shipped by truck, with a net payload of l0,000 pounds per shipment, approximately 90 shipments would be required for each of the 450-ton steam generators.

Conceivably, a single shipment of both steam generators by barge can be made to Richland, Washington, through either the Illinois - Mississippi River

  • Panama Canal route or the St. Lawrence Seaway - Panama canal route.

The offloading facilities at Richland, Washington, can easily acconunodate a single.steam generator at 450 tons.

4-40

.).,

_)

PALISADES PLANT SGRR 4.4.4 MAN-REM ASSESSMENTS If the steam generators are shipped by rail and/or truck, they must be cut into suitably-sized sections before shipment.

The man-rem associated with this operation.will vary depending on the length of time the steam generators are in storage before the actual cutting operation.

If barge transport is employed, cutting is not required and handling of the steam generators would be minimized.

Based on radiation survey data and analogous manhour estimates established in Section 4.3.7, the man-rem associated with barge transport (1 to 5) is a small fraction of the man-rem associated with rail and/or truck shipments (575 to 750)

(see Table 4.4.-2).

4.4.5 RADIOACTIVE RELEASES AND DOSE ASSESSMENT ASSOCIATED WITH OFFSITE DISPOSAL The openings in the steam generators will be sealed before the steam generator is removed from the containment building (see Section 4.3.5.2}.

Since the steam generators will be sealed during storage and eventual shipment by barge, no airborne or liquid radioactive releases are associated with offsite disposal.

4.4.6 RADIOACTIVE RELEASES AND DOSE ASSESSMENT ASSOCIATED WITH ONSITE STORAGE If onsite storage is necessary, a suitable storage facility would be constructed before the removal of the old steam generators (see Section 4.1.1.2).

Since all openings in the steam generators will be sealed before removal from the containment, no airborne or liquid radioactive releases are expected as a result of onsite storage.

As discussed in Section 4.4.7, the radioactivity within the steam generators is immobile.

Thus, if seal integrity was lost, releases to the environment would not be likely.

Nonetheless, a surveillance program will be implemented comprised of periodic visual inspection of the external surfaces of the lower* assemblies, area radiation surveys, and random swipes of the welds sealing the covered openings in the lower assemblies.

This surveillance program will provide further assurance that there are no unanticipated releases of radioactivity to the environment.

4-41

PALISADES PLANT SGRR The only contribution, therefore, to the annual dose equivalent to any member of the public is from direct radiation emanating from the storage facility.

The storage facility would be shielded, as required, in order to limit the dose rate at the outside of the storage facility to l.O mR/hr.

The resulting dose equivalent to an individual at the NNE site boundary (@ 2,200 feet) for a full year would be approximately 1. 9. x io*3 mrem, which is considered an insignificant contribution to the offsite dose.

Furthermore, it is highly unlikely that an individual would be continuously exposed for a period of 1 year at the site boundary; therefore, the actual annual dose equivalent to any individual at this location will be lower than that given above.

4.4.7 ACCIDENT CONSIDERATIONS.ASSOCIATED WITH ONSITE STORAGE The primary concern associated with accidents involving the onsite storage of the old steam generator is the remote possibility for the release of radioactivity to the environment.

The majority of this radioactivity is on the primary side surfaces of the lower assembly in the form of a protective corrosive film of metal oxides which is very adherent and refractory.

As di~cussed in Section 4.4.6, an additional measure of

._)

radioactivity confinement will be attained by welding cover plates over all pipe connection openings in the old steam generators.

Radioactivity could conceivably be released to the environment only if both of the conditions below occurred:

a.

Radioactivity is dislodged from the primary side surfaces.

b.

The lower assembly primary side boundary is breeched.

There are three mechanisms which could potentially dislodge the corrosion film:

a.

Thermal shock

b.

Chemical/corrosive attack

c.

Mechanical shock 4-42

PALISADES PLANT SGRR The old steam generator storage facility would provide a weathertight environment and minimize temperature extremes so that dislodging of corrosion by thermal shock is considered unlikely.

Because the. steam generators will be drained and sealed against moisture, chemical and corrosive attack is not likely to occur.

The possibility of mechanical shock during storage is not great since the storage building wou.ld be an engineered structure and not subjected to general use.

Even if thermal or mechanical shock is assumed, the tenacious nature of the corrosive film is such that it would not dislodge a significant amount of radioactivity.

In addition to the fact that it is highly unlikely for a significant amount of radioactivity to become dislodged from a primary side internal surface, breeching the lower assembly primary side boundary is considered an extremely remote possibility because of the minimum steel thickness of approximately 4 inches.

Based on the above, it is concludeq that there are no realistic accident scenarios which would result in the release of radioactivity from the generators during the onsite storage interval.

4.

4.8 CONCLUSION

S The steam generators will ultimately be disposed of in a licensed land burial site or decommissioned with the plant.

ALARA considerations, economics, and burial site availability will be the factors determining the storage, handling, and shipping techniques employed.

4-43

PALI SADES -PLANT SGRR TABLE 4.4-1 ACTIVATED CORROSION PRODUCTS AFTER SBU'l'DOWN ACTIVITY IN (CURIES x 10-6 )/(2 11 SAMPLE )'11 <2>

  • IsotoEe O da::z:s 42 da::z:s 140 da::z:s 200 da::z:s 470 da::z:s cr-51 s.0s 2.06 0.807 0.04 0.0 Mn-54 1.33 1.23 1.00 0.86 0.47 co-57 0.60 0.54 0.428 0.36 0.18 Co-58 341.10 228.50 117.18 48.95 3.5*6 Fe-59 3.08 1.70 0.733 0.14 o.o Co-60 6.16 6.06 5.85 5.73 5.18 Nb-95 0.31 0.14 0.0594 0.01 0.0 zr-95 0.37 0.24 0.116 0.04 o.o Total 358.8 240.*47 126.24 56.13 9.39 Notes 111 The activities established are an approximation which assumes that the majority of the activity is concentrated in the tubesheet.

121 The following technique was used to find approximate activity per steam generator at the time of removal c-200 days):

3.5 x 105 inches of tube/tube sheet (3.5 x 105 inches of tube)(SG.13 x 10~ Ci/2 inches of tube) = 9.82 curries/steam genrator at 200 days This should increase by a factor of 2-3 for additional operation of from 3 to 5 effective full power year (Reference 3).

Therefore: (9.82 curies) x 3 ~29.5 Ci/steam generator at

-200 days

)

-""'< r

)

)

(-~..

PALISADES PLANT SGRR

\\

/

6.2.2 OFFSITE RADIOACTIVE RELEASES AND DOSE ASSESSMENT Radioactive airborne and liquid offsi~e releases have been evaluated for the repair effort using conservative bounding parameters,and assumptions.

6.2.2.l Airborne.Releases*

Radioactive airborne effluent releases to the environment resulting from the repair effort have been estimated using the following assumptions and parameters:

a.

Airborne releases are assumed to occur during the cutting operations.

b.

The reactor coolant pipes and the steam generators are expected to be contaminated primarily by deposited corrosion products.

Typical corrosion product activities expected on the primary side surfaces of the steam generators are given in Table 6.2-1.

These activities have been increased by a factor of 3 for approximately 5 effective full power years (Reference 3) of additional reactor operation.

c.

It is conservatively assumed that all the activity present in the vicinity of each cut will become 6-2

PALISADES PLANT SGRR airborne and be available for release to the environment.

d.

One hundred forty days of radioisotope decay were assumed before cutting operations, on the basis of the earliest reasonable time as dictated by the repair effort.

No credit was taken for radioisotope decay during cutting operations.

e.

All primary coolant piping cuts are assumed to be made in specially-designed contamination control enclosures which will provide high efficiency filtration.

The enclosures are assumed to be 90% efficient for capturing particulates.

An additional 99% efficiency is assumed for the stack filter (HEPA) through which all plant ventilation flows.

Further reductions in airborne radioactivity will occur through use of the two internal recirculation filters which are discussed in Section 4.3.3; however, no additional environmental release credit is assumed for these filters since their primary purpose is to reduce occupational doses and minimize personal respiratory protection devices.

Radioactive airborne effluent releases to the environment based on the above assumptions are approximately

5. 9 x 10.s Ci.

Details of the airborne effluent release by isotopes are given in Table 6~2-1.

6.2.2.2 Comparison with Observed Gaseous Releases and Estimated Doses During Normal Operation The estimated releases of radioactive airborne effluents during the repair effort are found to be much smaller than the observed effluent releases at the Palisades Plant during 1977.

Observed airborne effluent releases.during 1977 are compared with estimated releases during the repair effort in Table 6.2-2.

The estimated critical organ dose for the repair program was found to be less than*l.0% of the calculated critical organ dose for 1977.

6.2.2.3 Liquid Effluent Releases Liquid effluent releases resulting fr.om the repair effort were estimated using analogous data from previous refueling and steam generator inspection outages.

The total radioactive effluent release estimated for the repair activity is shown in Table 6.2-4.

The total incluqes 6-3

  • -.)

)

1' I

\\

r

.., I r*:~..,..

PALISADES PLANT SGRR laundry waste effluents expected during repair activities and the small amount of liquid waste generated as a result of local decontamination.

The estimated specific activities of laundry wastewater are shown in Table 6.2-3.

A description of the laundry waste treatment system is included in Section 4.3.6.3.

A comparison of the average release for the repair effort is shown on Table 6.2-5.

6.2.2.4 Comparison with Observed Liguid Releases during Normal Operation.

Observed liquid effluent releases during 1977 are compared with the estimated releases for the repair effort in Table 6.2-5.

The total body and significant organ doses for the repair effort were roughly equivalent to the dose from liquid effluents during the year 1977.

6.2.2.5 Conclusion The combined effect to the offsite dose from gaseous and liquid releases is less than that expected for a year of normal operation.

The estimated dose to an individual in an unrestricted area from all pathways of exposure is much less than the limits specified in 10 CFR Part 50 (Appendix I).

6-4

PALISADES PLANT SGRR TABLE 6.2-1 ESTIMATES OF AIRBORNE RELEASES TO ENVIRONMENT DURING STEAM GENERATOR REPAIR EFFORT Activity of Corrosion Products I 11 Total Release 121 Isotope at 140 days (l.1Ci/in2)

(l.1 Ci)

Cr-51 0.589 0.378 Mn-54 0.730 0.468 Co-57 0.312 0.200 co-58 85.5 54.8 Fe-59 0.535 0.343 Co-60 4.27 2.74 Nl:>-95 0.040 0.026 Zr-95 0.085 0.054 TOTAL 92.2 59.l NOTES:

(1) These are the activities presented in Table 4.4-l.

converted to l.1Ci/in2.

The activities were increased by a factor of 3 to account for the expected activity build'!""up.

(2) The following technique was used to estimate the activity from each isotope released during cutting operations:

Airborne Activity Near cut (lJ Ci)

= Area x

of cut

(.5 in2 )

Activity of x Nwnber x Corrosion of cuts (l.1Ci/in2)

(No.)

Enclosure and Stack Filter Penetration

(.1) (. 01)

The total number of cuts on primary coolant piping which were assumed to total 12 where:

4 cuts (42-inch ID pipe) 8 cuts (30-inc.h ID pipe)

~

t 'r*

-1

)

r

.)

_._,/

\\ ;

y

.\\, I

~

~

(

(_

e e

PALISADES PLANT SGRR TABLE 6.2-2 COMPARISON OF GASEOUS EFFLUENT RELEASES Isotol2.e Noble Gases Iodines l

111 Particu ates Tritium NOTES:

Average 1977 Release (Ci) 59.89

1. s1 x 10*2 i.1 x io*3 2.21 Estimated Release During SG Repair Effort (Ci}

Negligible Negli.gible

  • 059 x io:3 Negligible 111 Approximately 29.0 and 26% of the total particulate release during the year.. 1977 are co-58 and Co-60, respectively.

PALISADES PLANT SGRR TABLE 6.2-3 ES'l'IMA1'ED SPECIFIC ACTIVITY OF _LAUNDRY WASTEWA'IER ISO'roPE SPECIFIC ACTIVITY Ci/cc< t>

co~sr 8.96 x 10-7 Cs-134

4. 6L& x 10-s Cs-137 1.0J x 10-*

Co-58 3.85 x 10-*

Mn-54 2.63 x 10-s c~-60 1.22 x 10-s Fe-59 3.27 x 10-*

zn-65 4.09 x 10-7 zr-95

4. 15 x 10-6 Nb-95
7. 2 x 10-*

sr-90

3. 66 x 10-s Ni-63 2.65 x 10-s NOTE:

<1>

Time averaged specific activity during a period of 365 days.

1'

'( l

_)

\\

../

(~

\\.

/

I '

\\ ' -

PALISADES PLANT SGRR TABLE 6.2-4 ESTIMATED RADIOACTIVE LIQUID EFFLUENT RELEASED DURING

'1'BE STEAM GENERATOR REPAIR ISOTOPE RELEASE Ci co-57 6.85 x 10-4 cs-134 3.54 x io*2 cs-137 7.85 x 10*2 Co-58 2.95 x 10 *1 Mn-54 2.01 x io-2 Co-60 c 5.5 x 10 *2 Fe-59 2.5 x 10 *3 zn-65 3.12 x 10 -4 zr-95 3.17 x 10 *3 Nb-95 5.5 x 10 *3 Sr-90 2.79 x 10 *2 Ni-63 2.02 x 10 *2 TOTAL

.544 H-3 1.91

PALISADES PLANT SGRR TABLE 6.2-5 COMPARISON OF RADIOACTIVE LIQUID EFFLUENT RELEASES ISOTOPE AVERAGE 1977 RELEASE (Ci)

Fission

.093 and acti-vation products Tritium 55.8 Total 55.9 ESTIMATED RELEASE DURING SG REPAIR EFFORT (Ci)

.544 1.91 2.45

'1

).*

j

\\

( fl

/,.... --

/

\\.~.... -.

PALISADES PLANT SGRR 7.0 ENVIRONMENTAL ASPECTS OF THE REPAIR PROGRAM 7.1 GENERAL The following sections present information and the assessment of environmental impact of the proposed steam generator repair program.

The estimated environmental impact of the repair activity and disposal of the removed steam generators is expected to be negligible and temporary.

The proposed activity will cause little additional environmental impact over that of normal plant operation.

Construction activities, particularly the barge slip preparation, will-be carried out in conformance with local, state, and federal regulations.

When the facility is returned to service after the repair, water use, occupational exposures, and radiological releases are expected to be less than those associated with current facility operation.

It may be necessary to store the old steam generators onsite in an engineered storage facility that will provide shielding for the direct radiation.

The steam generators will be sealed to contain any airborne radionuclides.

The steam generators may be shipped offsite to a federally licensed storage facility, if available.

If shipped offsite, all local, state, and federal regulations pertaining to the shipment of radiological materials will be followed.

7.2 RESOURCES COMMITTED 7.2.1 NONRECYCLABLE BUILDING MATERIALS The steam generator repair program at the Palisades Plant.

will require the commitment of various irretrievable building materials.

The quantitative estimates for the nonrecyclable building materials are as follows:

Concrete Structural steel Alloy or stainless steel Tendons (53)

Cable (copper)

Inconel Pipe Wood 7-1 l,000,000 pounds 50,000 pounds 1,594,000 pounds 150,000 pounds 400 pounds 280,000 pounds 5,000 pounds 15,000 board feet

PALISADES PLANT SGRR 7.2.2 LAND RESOURCES The steam generator repair program will have minimal impact on the existing site in terms of land use.

The construction of facilities (see Section 4.1.l.2) to store the steam generators will require some excavation, leveling, and foundation work.

If necessary, a building will be located near the temporary barge slip (see Figure 4.l-1).

The extent of the disturbance will be temporary, negligible, and of minor impact.

This area had been previously excavated during plant construction.

7.2.3 WA'.I'ER RESOURCES During the repair effort, construction water will be supplied from existing Palisades Plant water sources.

No requirements for commitments of new water sources have been identified for the repair effort.

Since water consumption during the extended shutdown is expected to be less than during plant operation, water consumption during the repair effort will result.in a reduction in plant water usage.

A temporary barge slip will be constructed just north of the existing Palisades Plant (see Figure 4.1-2) to receive and offload two replacement steam generators.

The temporary barge slip will be approximately 110 feet long, SO feet wide, and 18 feet deep.

The total dredged quantities are anticipated to be approximately 12,000 cubic yards based upon a lake elevation of 579'-0" (USGS).

The dredged material will be disposed of according to Guidelines for the Pollution Classification of Great Lakes Harbor Sediments, U.S. EPA Region V.

The dredging will be conducted according to specifications of the U.S. Coi:ps of Engineers permit.

Steel sheet piles or sunken ship hulls may be used to provide wave and scour protection for the barge.

Depending on lake conditions, the barge slip may have to be periodically redredged to specifications if suspended materials (sand) are deposited there before delivery of the generators.

The dredging activity will temporarily increase turbidity in the site vicinity and remove a small number of benthic organisms with the spoils.

The piling or sunken hulls, if used, will provide substrate suitable for attachment of periphyton and filamentous algae, but large growths are not expected.

The impacts of the dredging will only have a temporary impact upon the aquatic biota in the immediate plant vicinity.

Removal of the temporary barge slip 7-2 r

(J l

\\

-~

/

../

/

i

\\

PALISADES PLANT SGRR facility will result only in some temporary increase in turbidity along the shore line.

7.3 WASTEWATER 7.3.1 SANITARY FACILITIES Since the repair activities will take place in locations near which permanent sanitary facilities are not readily accessible (e.g., the containment and laydown area),

portable units w:i.ll be used.

There will be no modification to existing sanitary facilities as a result of the repair activity.

7.3.2 LAUNDERING OPERATIONS Laundry wastewater generated during the repair activities will be produced in the existing facility.

A description of the laundry waste processing scheme is included in Section 4.3.6.3.

7.4 CONSTRUCTION Construction activities at the time of the repair effort will satisfy applicable laws that are in force at that time.

These activities will have a negligible effect on noise levels, dust, or smoke.

7.4.1 NOISE Values and calculation methods described in Reference 6 have been used to examine the maximum sound pressure level (SPL) expected at the site boundary (0.4 miles) because of construction noise.

The maximum source SPL is expected to be less than 94 dBA at 50 feet, which will attenuate to less than 62 dBA at the site boundary.

The site boundary maximum expected SPL is within the acceptable limits for permissible outdoor noise levels for sleeping with open windows.

Moreover, the site is located in a low population area.

On the basis of these facts, it is concluded that the additional noise resulting from the repair program for the steam generators is expected to have negligible impact on the local area.

To protect personnel located on the site, Occupational Safety and Health Administration standards (state and federal) will be followed.

7-3

PALISADES PLANT SGRR 7.4.2 DUST Dust, if any, will be abated by periodically spraying with water or other dust control measures.

The frequency of spraying and the quantity of water sprayed will be determined by vi~ual inspection of the areas and will vary with the weather conditions.

7.4.3 OPEN BURNING Open burning is not anticipated during the steam generator repair effort.

However, should the necessity arise, applicable county and state regulations for open burning will be followed.

7.5 RADIOLOGICAL MONITORING Radioactive effluent release points during steam generator repair activities will be the same as during normal plant operations; therefore, the plant radioactive process monitors will not be affected.

Since releases of radioactive effluents during the repair program will be similar to those from the operating plant, and their potential exposure pathway will be the same as for existing plant operations, these effluents will be monitored in accordance with the existing environmental monitoring program at Palisades Plant.

7.6 RETURN TO OPERATION 7.6.1 WATER USE Water consumption during post repair plant outages is expected to be appreciably less than is currently required as a result of repairs to degraded tubing.

Periodic plant shutdown for steam generator inspection consumes large quantities of pure water.

During shutdown, the steam generator water level is controlled on the low side {between 20 to 40% of operating band) to aid in chemical layup.

Approximately 10,000 gallons of water are required to place the two steam generators into wet chemical layup.

If a steam generator requires draining (for tube plugging, tube sleevingJ or tube removal) during the inspection, it would require an additional 24,000 gallons to refill.

Other plant requirements for pure water include 70,000 to*as,ooo 7-4 (t

f'I

PALISADES PI.ANT SGRR gallons for heater train, condensate polishers, and hotwell.

This is the amount necessary to refill the systems if maintenance had been performed that required draining the systems.

Approximately 75,000 gallons would be required for primary system dilutions to return to power.

Depending on various chemical parameters, as much as 50% of this water could be recovered through the plant recovery systems, such as clean radwaste system, boric acid recycle system, and steam generator blowdown ~ecovery system.

Following replacement of the steam generators, it is expected that forced outages associated with steam generator tube plugging and/or tube sleeving will be essentially eliminated; however, it is not anticipated that the water consumption associated with the current inspection program will be significantly ~educed because of the continuing requirement to inspect (eddy current test) the steam generator tubing at regular intervals.

7.6.2 OPERATIONAL EXPOSURES Section 4.3.7 discusses the future reduction in man-rem exposure as a consequence of the repair program.

A potential savings of 250 man-rem/yr may be realized because of the ex;pected elimination of the necessity to plug tubes in the repaired steam generators and the decrease in the nl;Unber of inspections required (Regulatory Guide 1.83).

7.6.3 RADIOLOGICAL RELEASES Although the Palisades Plant has experienced only one primary to secondary leak from tube failure (1974), the repair of the steam generators should reduce the probability of future secondary releases as a consequence of the same tube failure mechanism.

/

7-5

(',

PALISADES PLANT SGRR 9.3 STEAM. GENERATOR STORAGE AND DISPOSAL The old steam generators may be stored onsite, at least temporarily, before eventual disposal.

The alternatives associated with the storage and disposal are addressed below.

9.3.1 LONG-TERM STEAM GENERATOR STORAGE ONSI~

As discussed in Section 4.4.6, the steam generators would be sealed before storage to ensure complete encapsulation of residual contamination and placed in a storage facility.

The storage facility would provide adequate shielding around the steam generators.

Access control and monitoring measures would be implemented during the storage period.

At.

the end of the plant lifetime, disposition of the steam generators will be accomplished in conjunction with plant decommissioning.

9.3.2 IMMEDIATE SHIPMENT BY BARGE The immediate shipment of the steam generators in one piece by barge as discussed in Section 4.4.3.3 is curre~tly considered to be a viable method of disposal.

Immediately upon removal from the containment, the steam generators would be loaded on barges and shipped to a licensed depository.

9-2 I

I

PALISADES PLANT SGRR 9.3.3 SHORT-TERM STORAGE ONSITE WHILE UNITS ARE CUT UP FOR SHIPMENT (WITHOUT DECONTAMINATION)

If the steam generators are to be cut up for shipment, additional contamination control measures, as well as shielding, would have to be employed as discussed in Subsection 4.4.3.2.

For this option, an enclosure with appropriate controls for airborne and liquid effluents will be required in addition to the requirements set forth in Section 4.4.2.

Techniques for cutting and packaging are not well established, making cost and dose calculations uncertain.

9.

3.4 CONCLUSION

S The present-day conceptual cost and man-rem estimate for each method of steam generator stor-age and disposal are summarized below.

a.
b.
c.

Immediate shipment by barge Long-term storage with disposition during decommissioning cut up and disposal near term with no decontamination

- Approximate Cost Man-Rem

$353,000 1-5

$2,560,000 s-10

$1,756,000 575-750 It is apparent that immediate shipment by barge would be beneficial from the standpoint of both man-rem exposure and cost.

9-3 r

\\

,_}