ML18044A376

From kanterella
Jump to navigation Jump to search
Const Specs for Inside Containment Portion of Pressurizer Relief Valve Position Indication Sys
ML18044A376
Person / Time
Site: Palisades 
Issue date: 11/13/1979
From: Didesch T, Green W, Trohkimoinen G
ENERGY, INC.
To:
Shared Package
ML18044A372 List:
References
CPO-001, CPO-1, NUDOCS 7912310501
Download: ML18044A376 (23)


Text

ATTA~_

5- ________ _

c:;:;

ENERGY INCOR?GRATE:D

/

~ '

~~

CONSTRUCTION S?ECIFI CATION OESCR!?TION

?REPAREO SY 40-2 REVISION NO.

0 CONSTRUCTION SPECIFICATIONS FOR INSIDE CONTAINMENT PORTION OF PRESSURIZER RELIEF VALVE POSITION INDICATION SYSTEM AT PALISADES NUCLEAR PLANT.

~'--./~,._,.~.......... ~"""""'--

G. R. Trohkimoinen REVISIONS DATE

!!}3/-u1 I

'4~/77 u,d$hr 11/13/7'1 C-SPEC NO.

CP0-001 CONTRACT NO. 13052-000 REL.EASE OATE l l /l 3/79 PREPARED FOR Consumers Power Company G.W.O. 6972 JOB CODE-S/N PAGE: l.

CF _11_

  • -*-----*-------------~---~c "~7 912310 ~~'.

FORM E:-0?0 REV. 0,10/79

40-2 TABLE OF CONiENTS

1. O GENERAL **** ********************************************************* 5 2.0 TRANSDUCER MOUNTING ****.*..****************************.***********. 7 2.1 Reference Drawings *..***..*..**.*.*************.*....*. ~*******7 2.2 r1aterial List......,..........*.........*............... *........ 7
2. 3 Tool Li st........**...*......**....**...*.*.......*..*......*.. 7 2.4 Valve Flange Modification **************** ~ ********************* 8 2.5 Transducer Installation *************************************** 11 3.0 MECHANICAL INSTALLATION INSIDE CONTAINMENT ************************* 12 3.1 Reference Drawings ************.****.************************** 12 3.2 Material List.*..**.*.*...*****....******.**.*...* ~***********12 3.3 Tool List *********.*..*********.********.**.*..**.*********.*. 13 3.4 Expansion Fastener Installation Instructions ****************** 14 3.5 Charge Amplifiers *********** ~ ********************************* 14 3.6 Junction Box.***..*****.*.****.*********.***.*********.****..* 15
3. 7 Conduit *..*.*.******.*.*...**...*..****..****.******.***.***** 15 3.7.1 3.7.2 Conduit Inside Pressurizer Room ************************ 15 Conduit Outside Pressurizer Room *********************** 17 4.0 CABLE INSTALLATION INSIDE CONTAINMENT ****************************** 18 4.1 Reference Drawings-.**.**...****************.***************..* 18 4.2 Material List *******.************************.**************** 18 4.3 Tool List ****************************~***********************19 4.4 Transducer to Charge Amplifiers ******************************* 19
4. 3.1 Ha rdl i ne/ Softl i ne Cab 1 e Connect i ng Procedure *********** 19 4.3.2 Hardline/Softline Cable Installation ******************* 21
4. s Char~e-An1pJifi ~f -to El ectri caT.Penetrafi on-;.--;*~-~-=;-;:-::-:-~.*:-.. 22 REVISION NO.

0

-SPEC NO.

CP0-001 JOB CODE-SIN PA-GE.LoF.1L FORM E:-Q34 REV. 0, 10/79

40-2 LIST OF FIGURES Page 2-1.

Power Operated Relief Valve Outlet Flange ************************** 9 2-2.

Safety Relief Valve Outlet Flange ********************************* 10 3-1.

Junction Box Knockout Details **************************** * *****.**** 16 REVISION NO.

0

-SPEC NO.

CP0-001 JOB CODE-SIN PAGE LOF 23 FORM E-Q34 REV.0,10/79

40-2 9033 9037 9201 9311 9351 9381 9418 9419 9420 9610 REVISION NO.

0 Rev. 0 Rev. O Rev. 0 Rev. O Rev. 0 Rev. 0 Rev. 0 Rev. 0 Rev. 0 Rev. 0 DRAWING LIST Electrical Circuit Schedule, Sheet 1 Electrical Raceway Schedule, Sheets 1 through 6 P&ID Primary Coolant Systems Instrument Index Conduit and Tray Pl an, Canta i nment h'ea 1 El. 607' -0" Conduit and Tray Sections Installation Details Pressurizer PRV/RV Position Indication Schematic Diagram, Pressurizer PRV/RF Position Indication, Sheet 1 Charge Amplifier Junction Box Detail Pressurizer PRV/RV Position Indication Connection Diagram Containment Canisters, Sheets 156 through 160

- SPEC NO.

CPo-001


~~~~~~

JOB CODE-SIN PAGE _LoF 1L FORM E-Q!4

~EV. 0, 10179

40-2 CONSTRUCTION SPECIFICATIONS FOR PRESSURIZER RELIEF VALVE POSITION INDICATION SYSTEM AT PALISADES NUCLEAR PLANT

1. 0 GENERAL The Valve Position Indication System to be installed to monitor the pressurizer relief valves at Palisades Nuclear Plant is a Babcock and Wilcox Valve Monitoring System.

The system functions by *measuring fl ow noise in each valve and converting the signals to meaningful outputs, specifically, visual indication, audio monitoring, audible al ann annunciation, and visual alann annunciation.

A piezoelectric accelerometer is to be mounted on each of five pressurizer relief valves.

This device produces an electric charge pro port ion al to the noise caused by fluid flowing through the valve.

Each accelerorreter is connected, via special coaxial cable, to one of five charge amplifiers mounted outside the pressurizer room.. The charge amplifier converts the coulomb charge signal to a voltage.

This 0 to 10 volt signal is conducted through a shielded~ twisted pair cable to the panel-mounted signal conditioner and monitor/alann unit.

The signal conditioners and monitor/al ann unit are to be 1 ocated. in the plant control room.

Each signal conditioner provides power to a remotely-1 ocated charge amplifier; filters and conditions the incaning voltage signal for the roonitor/alann unit; displays the signal level on a rreter which is part of the signal conditioner; provides an al ann signal to the monitor/alarm unit; and indicates alann condition on the signal conditioner panel front.

A common monitor/al arm unit serves all five signal conditioners.

It provides a canroon alann bus with audible annunciator and retransmitting contact output.

The dual monitor section allows the operator to select any of the five channels for *audio rronitoring.

REVISION NO.

0

-SPEC NO.

CP0-001 JOB CODE-SIN PA'GE LOF -'L.

FORM E-Q'34 REV.O,i0/79

40-2 ihe retransmitting contacts are wired into the plant annunciator system in Cl2/Cl3 panel to flag the "PORV/SRV" alann.

REVISION NO.

0

-SPEC NO.

CP0-001 JOB CODE-SIN PAt;E LOF.2.l.

FORM E-Q:34 REV. 0, 10/ 79

40-2

2. 0 TRANSDUCER MOUNTING 2.1 Reference Drawings Drawing No.

9201 Rev. 0 P&ID Primary Coolant System 9418 Rev. 0 Installation Details Pressurizer PRV/RV Position Indication 2.2 Mlterial List The following materials are required to install the transducers on five pressure relief valves:

Quantity 5

5 Description Acceleraneter, Endevco Model 2273AM20 Mounting stud, Endevco Model 2981-3 Adhesive, Pyrogel (or equal acoustical coupling compound) 2.3 Tool Li st The following tools, as a minimum, are required to install accelerometers on the pressure relief valves:

Magnetic Base Drill, 1/2-inch chuck Multiple Flute Center Cutting End Mill, 7/8-inch or 1-inch diameter, 1/2-inch shank Carbon Steel Dril 1, #21 (.1590" - tap dril 1 for 10-32)

Plug Tap, #10-32 Bottom Tap, #10-3 2 Tap Drive Wrench REVISION NO.

0

-SPEC NO.

CP0-001 JOB CODE-SIN PAGEL.OF 1L FORM E-Q34 REV.0,10/79

40-2 Miscellaneous Clamps,* Angles, and Plates to fonn a base for Magnetic Drill Flat Blade Screw Driver Torque Wrench, 25 inch-lb range, 3/8-inch square drive Socket, 5/8-inch hexagonal, 3/8-inch square drive, Delrin Ma*teri al, Endevco No. 2940 2.4 Valve Flange Modification To mount the transducer, a flat surface on the circumference of the valve flange is required.

Figure 2-1 depicts the required mounting surface to be prepared on the outlet flange of valves PRV-10428 and PRV-10438.

Figure 2-2 shows the same for valves RV-1039, RV-1040, and RV-1041.

The mounting locations shown on Drawing 9418 are only suggested locations; the transducer may be mounted at any of a number of points on the circumference of the flange.

The only requirement is that the transducer be installed in the center of the region betineen two bolt holes.

To machine the flange of a valve in place on the pressurizer will require a magnetic base electric drill, a center-cutting end mill, and several clamps, plates, and brackets to support the drill.

The drill is to be set up over the area to be machined.

With the end mill in the drill chuck, start the dril 1 and 1 ower the mil 1 until it just contacts the flange.

Continue to feed the mil 1 into the flange Lmt i1 the outer edges of the mill are about to enter the work.

If a 7 /8-inch diameter center-cutting end mill is used, the machined area should now be sufficient to mount the transducer.

Without moving the drill base, retract the drill motor and mill, and stop the motor.

Remove the *mill arid install a #21 drill.

Drill a hole in the center of the machined area to a depth of 3/8 inch.

This hole must be drilled within +/-6 minutes of perpendicular with the machined surface.

Tap 110-32 threads using the plug tap to start and the bottom tap to finish the task.

REVISION NO.

0

-SPEC NO~

CP0-001 JOB CODE-SIN PA~E -LoF 1L FORM E-034 REV.0,10/79

REV IS ION NO.

0

-SPEC NO.

CP0-001 JOB CODE-SIN

...I

-=

Q

...I I ""

N

= ~

6

...I c::

Q

.=:; =

c..

Q

=

§

~

PAGE...i.OF.il_

FORM E-034 RE'l.0,10/79

0

~

0 iij c...

0 m 0

0 0

Pl I

(/)

~

z 0 z z p I

(/)

"1J ITI 0

z p n

"'O 0

I 0

0 _.

@/

//*-1

. 9,7~. r~*~t: ~

\\ J__=-___

?=~---

-n.

l.J

~----


t::)

A-\\)

v---.

/*. ----

/

FIGURE 2-2 SAFETY RELIEF VALVE OUTLET FLAJIGE

  • J b~- 300 # IJ/JlZET IZAAl6ES 5f.4L E: FLIL l

40-2 For the safety relief vaives, RV-1039, RV-1040, and RV-1041, it is sug-gested that the surface be machined and the mounting hole drilled and tapped before the va*1 ves are re-insta.1 led on the pressurizer.

The machinist should remove material to* provide a surface in accordance with Drawing 9418.

Having milled a flat surface on the flange, the machinist should drill and tap a #10-32 hole in the center of the machined area.

Transducer mounting requires that this hole be 3/8-inch deep, and not more than !6 minutes off perpendicular with the machined surface.

2.5 Transducer Installation Do not install the transducer until the valve is in place in the pres-surizer piping system.

Screw the mounting stud, Endevco No. 2981-3, into the fl0-32 hole in the flange.

Tighten with a screw driver.

Apply the Pryogel acoustical coupling canpound to the base of the transducer, and twist the transducer onto the stud by hand.

Tighten the transducer with a Del rin socket and torque wrench to a torque of 18 inch-pounds.

REVISION NO.

0

- s P"E c NO.

CP0-001.

JOB COOE-S/N PAGE~OF~

FORM E-034 REV.0,10/79

40~2 3.0 MECHANICAL INSTALLATION INSIDE CONTAINMENT 3.1 Reference Drawings Drawing No.

9037 Rev. 0 9311 Rev. 0 9418 Rev. 0 9420 Rev. 0 Title Electrical Raceway Schedule, Sheets 1 thnlugh 6.

Instrument Index Installation Details Pressurizer PRV/RV Position Indication Charge Amplifier Junction Box Detail Pressurizer PRV /RV Position Indication 3.2 r.Eterial List The following materials wJll be required to complete the installation of valve position indicating system components within the containment.

Palisades Plant-approved equals may be substituted if the materials s peci fi ed are not ava i1ab1 e.

Quantity 5

5 1

25 ft.

250 ft.

10 ft.

5 ft.

8 2

REVISION NO.

0 Description Charge Amplifier, B&W Part No. LPVMS IC 229 Hole Seal, Hoffman A-S075SS, *if required Wiring Trough (Junction Box), 4 11 x4" x 30 11

, Hoffman F-4430 Uni strut P-1000 channel, 1-5/8 11 x 1-5/8" Conduit, 3/4" rigid galvanized steel Conduit, 1-1/4" rigid galvanized steel Conduit, 3/4" liquidtight flexible, non-PVC jacket Connector, straight, for 3/4" liquidtight flexible conduit Connector, 90°, for 3/4" liquidtight flexible conduit

-SPEC NO.

CP0-001 JOB COOE-S/N PA~E JLOF.11.

FORM C:-Q34 REV. 0I10/79

40-2 Bushing, galvanized steel, for 3/4" conduit Bushing, g.alvanized steel, for 1-1/4" conduit Locknut, galvanized steel, for 1-1/4 11 conduit 20 4

4 2

Pipe Clamp, galvanized steel, for 1-1/4" conduit, Unistrut P-2914 40 5

25 50 3 ft.

4 Pipe Clamp, galvanized steel, for 3/4" conduit, Uni strut P-2912 "C" Condulet, 3/4", galvanized cast iron, with cover Coupling, 3/4" conduit, galvanized steel Anchor Bolt, 1/4 x.2-1/4, Phillips Redhead No. WW-1422 Al lthread, 3/8-16 Hex Nut, 3/8-16 2 ft.

Galvanized Fl at Steel Stock, 1/4" x 1-1/2" 2

Beam Clamp, galvanized cast iron, 1/4-20 tapped hole 2

Machine Screw, 1/4-20 x 1 3.3 Tool Li st The following tools, as a* minimum, will be required to complete the installation of valve position indicating hardware within the containment.

Dri11 Motor Masonry Dril 1, 1/4" Carbon Steel Drill, 9/32", 13/32" Tape ~asure Level Hammer 3/4 11 Conduit Knockout Punch 1-1/4" Conduit Knockout Punch 12" Adjustable Wrench Socket Wrench Set,

Fl at Blade Screw Driver 10" Slip Joint Pliers Hacksaw 3/4" Rigid Conduit Bender REVISION NO.

0

-SPEC NO.

CP0-001 JOB CODE-SIN PA~E~OF~

FORM E-034 REV.O,l0/79

40-2 1-1/4" Rigid Conduit Bender 3/4" Rigid Conduit Threader 1-1/4" Rigid Conduit Threader 3.4 Expansion Fastener Installation Instructions The expansion fasteners approved for use at Palisades Nuclear Plant are wedge-type non-bottom bearing expansion anchors.

The hole required for the anchor is the *same diameter as the anchor.

It should be drilled 1/2 inch deeper than the length of the anchor.

Excess concrete dust should be removed from the hole as much as is practical, either by repeated insertion and withdrawal of a rotating drill, or by blowing into the base of the hole through a small tube.

To install the anchor, back off the nut unt'il the tapered end of the anchor just protrudes _above it.

Set the device to be fastened over the hole drilled for the fastener, and start the anchor into the hole.

Drive the*

anchor in with a hammer until the nut and washer bottom against the device being fastened.

Tighten the nut with a wrench to set the anchor and secure the fastened device.

Normally this requires 3 to 5 turns.

Holes for this type of*anchor may be drilled through hales in the device being fastened.

3.5 Charge Amolifiers Punch a hole for a 3/4-inch conduit in the bottom end of each of the five charge amplifier enclosures.

See Drawing 9420 for the location of this hole.

(The enclosures may have been pre-punched for a smaller size conduit.

If so, it wil 1 be necessary to use a hole seal to close the REVISION NO.

0

-SPEC NO.

CP0-001 JOB CODE-SIN PAGE~OF~

FORM E-034 REV.0,10/79

40-2 opening at the top of the box.)

It is suggested that the holes be punched prior to entering the containment.

Use caution (possibly remove the sub-panel) to avoid damaging the charge amplifier when punching the holes.

Lay out the mounting bolt hole patterns on the outer wall of the pressurizer room and dril 1.

Refer to Drawing 9418 for the 1 ayout and dimensions for mounting the charge amplifiers.

Mount the charge amplifiers on the wal 1 using four 1/4-inch diameter expansion fasteners for each amplifier.

3.6 Junction Box Punch five 3/4-inch conduit holes and two 1-1/4-inch conduit holes in the junction box as shown in Figure 3-1.

It is suggested that these holes be punched prior to*entering the containment.

Lay out mounting bolt hole pattern on the wall beneath the charge amplifiers and drill.

Refer to Drawing 94ULfor layout and dimensions for mounting the junction box.

Mount the junction box to the wal 1 using six 1/4-inch diameter expansion fasteners.

3.7 Conduit Conduits are required for routing cables where cable trays are not available.

3.7.1 Conduit Inside Pressurizer Room Install Uni strut channel brackets to the wa11 s of the pressurizer room in the approximate positions shown on Drawing 9418.

Use two 1/4-inch diameter expansion fasteners for each bracket.

REVISION NO.

0

-SPEC NO.

CP0-001 JOB COOE-S/N PA-GE.J.§OF.ll_

FORM EeQ34 REV.0,10/79

---2*

t:n-j

µ--r 2".

REVISION NO.

0

\\

?"

\\

' \\

L..!/4' &JtJC~- Jt/TS 5,=t,A{'~

I

/

I --.::;-*-.

L9"~

FIGURE 3-1 JUNCTIOH BOX _KNOCKOUT DETAILS

-SPEC NO.

CP0-001 JOB CODE-SIN PA~Eli.OF ~

FORM E-(\\34 REV.0,10(79

40-2 Two additional brackets should be clamped to structural members er catwalk supports using a full-circle cl amp or beam cl amps as required.

Install five 3/4-i nch conduits as shown on Drawing 9418.

Each ::ondui t is to run fran near a relief valve to the opening of the cable penetration at elevation 635'-8" on the southwest wa11 inside the pressurizer roam.

The end of each conduit near the valve is to be 12 inches

-:=ran the transducer.

Eight feet fran the valve end of each conduit there ;;iust be a "C"

condulet in which two cable sections will later be joined.

The conduits are to be secured to the Uni strut mounting brackets using a pipe cl amp.

Install bushings on both ends of each conduit.

Identify each end of each conduit with a pennanent raceway identification marker in accordance with plant practices.

3. 7.2 Conduit Outside Pressurizer Roan Install a Unistrut channel bracket beneath the junction box on the outer wall of the pressurizer roan as shown on Drawing 9418.

Use two 1/4-inch diameter expansion fasteners to attach the bracket.

Install two 1-1/4-inch conduits fran the junction box to the vicinity of cable tray CV605.

Secure conduits to the box with a locknut ins~de and a 1 ocknut outside the box.

Use a pipe cl amp to cl amp each conduit to the Unistrut bracket.

Refer to Drawing 9418 for details of the installation.

Install a

3/4-inch flexible liquidtight conduit between each charge amplifier and the junction box.

Install a bushing on the end cf each conduit connector.

Drawing 9418 shows details of the five conduits.

Identify each conduit with a pennanent raceway identification marker in

\\

accordance with pl ant pr act ices.

R ~VISION NO~

0

-SPEC NO.

CP0-001

  • JOB CODE-SIN FORM E-Q34 REV. 0, J0/79

40-2

4. 0 CABLE INSTALlJl.TTON INSIDE CONTAINMENT 4.1 Reference Drawings Drawing No.

9033 Rev. 0 9037 Rev. 0 9351 Rev. 0 9381 Rev. O 9419 Rev. O 9610 Rev. O Title Electrical Circuit Schedule Sheet 1 Electrical Raceway Schedule, Sheets 1 through 6 Conduit and Tray Plan, Contairment Area 1 El. 607'-0" Conduit and Tray Sections Schematic Diagram Pressurizer PRV/RV Position Indication, Sheet 1 Connection Diagram Containment Canisters, Sheets 156 through 160 4.2 M3ter1 al Li st The following materials will be required to ccrnplete the installation of cable inside the containment.

Quantity 5

5 5

1 10 250 ft.

125 REVISION NO.

0 Description Hardline Cable, 10-foot length, Endevco No. 3075M6 Softline Cable, 40-foot length, Endevco No. 3090B Softline Cable, 25-foot length, Endevco No. 30908.

Softline Cable,. 10-foot length, Endevco No. 30908 Coaxial Cable Connector, Endevco EJ34 Cable, 16 ga. twisted, shielded *pair, Dekoron No. 1952-68310 Cable Ties

-SPEC NO.

CP0-001 JOB COOE-S/N PA13E~OF E_

FORM E-o_34 RSV. 0, 10/79

40-2 15 Ring Tenninar, uninsulated, crimp type, #8 screw 16 Safety Tie Wire, if required by plant Dow-Corning RTV Silicone, Type 96-081 5

Connector for Containment E1 ectrical Penetration Scotch 23 Electrical Tape Scotch 33+ Vinyl Plastic Tape 4.3 Tool List The following.tools, as a minimum, will be required to install the cables within.the containment.

Wire Pulling Fish Tape Flat 81 ade Screw Driver Tenninal Crimping Tool Wire Cutter Heating-Type Wire Stripper Connector Plug Crimping Tool Ohm Meter Pliers 8" Adjustable Wrench 4.4 Transducers to Charge.Amplifiers The cables to connect the transducers to the charge amplifiers are special 1 ow-noise, high-temperature coaxial cables.

They have been cut to length, and connectors have been installed by the vendor.

Under no circumstances are these cables to be altered during installation.

The minimum bending radius for hardline cable is 2 inches and 1 inch for softline cable.

Care must be exercised not to damage the cable sheaths.

4. 4.1 Hardl ine/Softl ine Cable Connecting Procedure Each transducer will require one hardline cable piece, one or two softline cable pieces, and one or two EJ34 connectors.

R EVlSION NO.

0

-SPEC NO.

CP0-001 JOB CODE-SIN PAGE 22..oF.B._

FORM E-034 REV.0,10/79

40-2 ihe hardline and softline cables are to be connected together prior to installation in their respective conduits.

One end connector of each cable is screwed onto the EJ34 connector.

.Before proceeding with sealing the connection, the resistance of the spliced cable should be tested with an ohm meter.

If the total cab 1 e resistance exceeds 18 ohms, then the con-nect ion should be checked by disconnecting one cable and testing the resi s~

tance from one end through the EJ34 connector.

Check the other cable in the same fashion, an~r disconnecting th~ tested cable fran the connector and reconnecting the remaining one.

if the resistance of a cable piece and connector is too high, check the cable piece alone.

If it checks

properly, substitute another EJ34 connector and* recheck.

If any cable or connector fails to check out properly, then it must be replaced with a new item fr-an the vendor.

When the resistance checks -are completed, then the connection may be seal ed.

If the plant requires that connectors be secured with. safety wire, it should be installed prior to sealing.

Sealing is accomplished by first wrapping the connection with Scotch Z3 electrical tape and then overwrapping with Scotch 33+ vinyl plastic tape.

The Scotch 23 base tape is applied with moderate tension, beginning at the splice and 1/2 lapping to a point 2 inches back on the cable.

Take one full lap turn, and then 1/2 lap back across the splice to a point 2 inches on the other side of the splice.

Full 1 ap one turn, then 1/2 -1 ap back to the* splice.

The last wrap should be full lap applled at*zero tension.

Begin wrapping the Scotch 33+_. vinyl plastic cover tape where the base tape ended.

Using moderate tension, 1/2 lap to a point 1 inch past the base tape and take one turn with full lap. 1/2 lap back across the splice to a point 1. inch past the end of the base tape.

Take one turn with full lap, and then 1/2 lap back to the splice.

Continue 1/2 lapping 2 inches past the splice, and then full lap one turn at zero tension and cut the tape.

REVISION NO.

0

-SPEC NO.

CP0-001 JOB CODE-SIN PA~E 20 OF.E._

FORM E-0!4 AEV.0,10(79

  • 1*

40-2 The same checkout and sealing procedures. apply for softl i ne to softl i ne cable connections.

4.4.2 Hardline/Softline Cable Installation The following table lists the.valves, cable identifications, and 1 engths.

Valve Cable No.

Hardl ine Length Softl ine Length PORV-10428 FE1042B-FM1042B/4 10 ft.

65 ft.

PORV-10438 FE1043B-FM1043B/5 10 ft.

65 ft.

RV-1039 FEl 039-FMl 039 /1 10 ft.

65 ft.

RV-1040 FE1040-FM1040/2 10 ft.

65 ft.

RV-1041 FE1041-FM1041/3 10 ft.

65 ft.

The cables are to be pulled into their respective conduits using a fish tape.

Inside the pressurizer room the cable should be fed in from the valve end of the conduit and pul 1 ed frcm the ertd near the cable penetra-t ion.

The cab 1 e is to be pul 1 ed into the conduit until the connection of the hardl ine and softline cables is in the 11C 11 condulet.

If there is another connection in a cable, it should be positioned outside the 3/4-inch conduit, either in the penetration, the 1-1/4-inch conduit, or the junction box.

The cab 1 es then are fed through the penetration at elevation 634 1 -6;..

They are instal 1 ed in conduit XXXX to t.he junction box, where they fan out and go to the charge amplifiers.

Each cable is to be screwed onto the charge amplifier connector within the 8

11 x 6 11 x 4 11 enclosure and safety wired, if the plant requires.

At the transducer, the hardline cable should be looped in a 4-to 6-inch diameter coil and screwed onto the transducer connector.

Install safety wire if pl ant requirements call for it.

REVISION NO.

0

- SPEC NO.

cPo-001

~

JOB CODE-S/N PA~E~OF~

FORM E-<:134 REV.0,10/79

40-2 Identify each cable with a pennanent marker at each end in accordance with pl ant pr act ice.

4.5 Charge Amplifiers to Electrical Penetration The route for the five 16-gauge twisted shielded pair cables from the charge amplifiers to the electrical penetration canister is as follows:

Charge Amplifier Junction Box Conduit XXXX (Number to be supplied by plant)

Tray CV605 Tray CV600 T.ray CV500 Penetration Canister Z142 Install connectors on the ends of the cables at the electrical penetra-tions.

The cable must be cut off squarely so that all conductors are of equal length.

Strip off 1 inch of the cable sheath, and strip 1/4 inch of insulation fran the black and white conductors.

Slip the connector hood onto the cable. and slide it along the cable out of the way.

Crimp connector pins onto the black, white, and drain conductors using a plant-approved crimping tool.

Push the pins into the connector body as follows:

Black - Pin B White.. Pin C Drain - Pin A Attach the hood to the connector body and connect the cable connector half to the corresponding penetration connector half.

Safety wire the connectors if required by the plant.

REVISION NO.

0

-SPEC NO.

CP0-001 J08 CODE-SIN PA-GE 22 OF.:fl..

FORM E-Q34 REV.0,10/79

40-2 Charge Amplifier Cable No.

Penetration No.

Connector No.

FM1039 FM1039-Zl42/1 Zl42 4

FM1040 FM1040-Z142/2 Zl42 5

FM1041 FM1041-Z142/3 Z142 6

FM1042B FM1042B-Zl42/4 Zl42 7

FM1043B FM1043B-Zl42/5 Z142 8

Lay the cables in the trays back to the vicinity of the charge ampli*

fiers.

Insert the cables into the 1-1/4-inch conduit.to the junction box.

Spread the cables and route each to its respective charge ampli-fier.

Cut the excess length from the cable, and remove two inches of the sheath.

Strip the leads 1/4 inch, and install ring tenninals using a plant-approved crimping tool.

Be sure to put a tenninal on the shield drain wire.

Tenni nate the three conductors as follows:

Black - S (signal - corresponds to the center conductor of coax)

White - C (common)

Drain - Sh (shield)

Refer to schematic Drawing 9419 for connections of cables i.n the charge amplifiers and at the contairunent electrical penetration.

After the cables are laid i.n the cable trays, they must be secured using cable ties spaced not more than 18 inches apart on vertical runs and not more than 48 inches apart on horizontal runs.

Cables and conductors are to be identified with pennanent mar!<ers on each end in accordance with plant practice.

Seal the fl ex conduits between the charge amplifiers and junction box with Dow-Corning RTV Silicone at the charge amplifier ends.

REVISION NO.

0

-SPEC NO.

CP0-001 JOB COOE-S/N PAGE JloF _g_

FORM E-Q34 REV.O,J0/79