INTERIM REPORT LECTR ICAL EQUIPMENT (jUALIFIC N

POTENTIAL REPORTABLE 50.55 e

DEFICIENCY I. Description of'eficienc The potential-reportable deficiency was discovered during an audit of our nuclear steam supply system Vendor during the week of March 24, 1980.

The'potential deficiency concerns the. qualification of electrical equipment supplied by the. nuclear steam supply system Vendor.

Three components.- had. inadequate or no documentation to show that they met envir onmental and seismic qualification The Nuclear Regulatory Commission was notified of the potential reportable deficiency because the significance of the deficiency was undetermined and because of the generic implications of a breakdown in the nuclear steam supply system Vendor' equality Assurance Program II.. Descri tion of Findin s and Corrective Action A

Corrective Action Request.

0042 Corrective Action Request 0042 resulting from the audit indicated that: documentation was missing to show full qualification of Rosemount Model 1151 differential pressure transmitter.

Following the-audit'n additional search of the qualification records was performed The qualification documentation for the Rosemount Model 1151 differential pressure transmitter was found in another record file The-adequacy of the qualification records. will be verified during-a. subsequent audit..

To prevent the recurrence of not being able to retrieve documentation in a, timely manner, the nuclear steam supply system Vendor's guality Assurance Program is being modified to cross-reference qualification records and vendor-supplied documentation.

B.

Corrective Action Request 0041 Corrective Action Request 0041 resulting from the audit indicated that no environmental or seismic qualification documentation was found for a conductivity element and level transmitter.

This item is still under investigation.