PRELIMINARY DATA SHEET FOR NUREG4737 S/RV TEST

~ LABS, HUNTSVILLE, ALA.

DATE TESTED 3-25-81 S/RV MODEL NP HB-65-BP-FN S/RV SERIAL NO N63580-00-0019 RUN/TEST NO.

406 S/RV MANUFACTURFR CROSBY 6R10 TYPE OF TEST STEAM, SATURATED LOADS I

SUPPORTS TEST RESULTS S/RV OPENED ON COMMAND S/RV CLOSED ON COMMAND S/RV FLUID TEST CONDITIONS

'LUID TEMPERATURE INLET PRESSURE S/RV FLOW RATE S/RV OPENING TIME (MAIN DISK LIFT TINE)

YES YES 555 F

1080 PSIG LATER 24mSec VALVE INTEGRITY DEMONSTRATED BY:

VISUAL INSPECTION POST-TEST HYDRO+

~ POST-TEST DISASSEMBLY INSPECTION FACILITY INTEGRITY DEMONSTRATED YES H/A*

N/A

+ ONLY ONCE PER VALVE AT ENO OF TEST SEQUENCE

~ NOT APPLICABLE 81070h0221 81 PDR ADOCK 050 7