PRELIMINARY DATA SHEET FOR NUREG4737 S/RV TEST WLE LABS> HUNTSVILLE'LA>>

DATE TESTED 3-24-81 MODEL NP HB-65-BP-FN S/RV SERIAL NO RUN/TEST NO.

404 S/Ry MANUFACTURER CROSBY 6R10 TYPE OF TEST

STEAM, SATURATED LOADS I

SUPPORTS TEST RESULTS S/RV OPENED ON COMMAND S/RV CLOSED ON COMMAND S/RV FLUID TEST CONDITIONS FLUID TEMPERATURE INLET PRESSURE S/RV FLOW RATE S/RV OPENING TIME (MAIN DISK LIFT TIME)

YES YES 5550F 1080 PSIG LATER 25mSec VALVE INTEGRITY DEMONSTRATED BY:

VISUAL INSPECTION POST-TEST HYDRO+

POST-TEST DISASSEMBLY INSPECTION+

FACILITY INTEGRITY DEMONSTRATED YES N/A*

N/A YES

+ ONLY ONCE PER VALVE AT ENO OF TEST SEQUENCE

  • NOT APPLICABLE 8107060217 810 PDR,ADOCK 0500g3 7