Forwards Preliminary Results of NRC Review of Environ Qualification of safety-related Electrical Equipment at Facility.Identified Deficiencies & Ramifications Should Be Reviewed & Overall Findings Submitted
ML18025B406
Person / Time
Site: Browns Ferry  
Issue date: 03/16/1981
From: Novak T
Office of Nuclear Reactor Regulation
To: Parris H
TENNESSEE VALLEY AUTHORITY
References
NUDOCS 8103260083
Download: ML18025B406 (100)


Text

PARTIAL REVIEW EQUIPMENT EVALUATION REPORT BY THE OFFICE OF NUCLEAR REACTOR REGULATION FOR TENNESSEE VALLEY AUTHORITY BROWNS FERRY UNITS 1, 2, AND 3 DOCKET NO. 50-259/260/296 3

STAFF EQUIPMENT EVALUATION The staff evaluation of the licensee's response included an onsite inspection of selected Class IE equipment and an examination of the licensee's report for completeness and acceptability.

The criteria described in the DOR guidelines, and in NUREG-0588, in part, were used as a basis for the staff evaluation of

'he adequacy of the licensee's qualification program.

The NRC Office of Inspection and Enforcement performed (1) a preliminary evaluation of the licensee's

response, documented in a technical evaluation report (TER) and (2) an onsite verification inspection (November 17-21, 1980).

of selected safety"related electrical equipment.

The core spray, primary containment, reactor fwedwater, sampling and water quality, emergency equipment cooling, water and standby gas treatment, systems were inspected at Unit l.

The reactor core isolation cooling, primary containment, residual heat removal'ervice water, fuel pool cooling and demineralizing, and the standby liquid control systems were inspected at Unit 2.

The residual heat removal, residual heat removal service water, primary containment, containment atmospheric dilution, reactor feedwater, fuel pool cooling and demineralizing, auxiliary

power, and emergency equipment cooling water systems were inspected at Unit 3.

The inspection at the three units verified proper installation of equipment, overall interface integrity, and manufacturers'ameplate data.

The manufacturer's name and model number from the nameplate data were compared to information given in the Component Evaluation Work Sheets (CES) of the licensee's report.

The site inspection is documented for Units 1, 2, and 3 in reports IE 50-259/80-41, 260/8-38, and 296/80-36, respectively.

No deficiencies were noted.

For this review, the documents referenced above have been factored into the overall staff evaluation.

3. 1 Com leteness of Safet -Related E ui ment

'n accordance with IEB 79-01B, the licensee was directed to (1) establish a

list of systems and equipment that are required to mitigate a

LOCA and an HELB and (2) identify components needed to perform the function of safety-related display information, post-accident sampling and monitoring, and radiation monitoring.

The staff developed a generic master list based upon a review of plant safety analyses and emergency procedures.

The instrumentation selected includes par ameter s to monitor overall plant performance as well as to monitor the per-formance of the systems on the list.

The systems list was established on the basis of the functions that must be performed for accident mitigation (without

1 P ~

1 ~

P

0 regard to location of equipment relative to hostile environments).

The list of safety-related systems provided by the licensee was reviewed against the staff-developed master list.

Based upon information in the licensee s submittal, the equipment location references, and in some cases subsequent conversations with the licensee, the staff has verified and determined that the systems included in the licensee's submittal are those required to achieve or support:

(1) emergency reactor

shutdown, (2) containment isolation, (3) reactor core cooling, (4) containment heat removal, (5) core residual heat removal, and (6) prevention of signifi-cant release of radioactive material to the environment.

The staff therefore concludes that the systems identified by the licensee.(listed in Appendix D) are acceptable, with the exception of those items discussed in Section 5 of this report.

Display instrumentation which provides information for the reactor operators to aid them in the safe handling of the plant was not specifically identified by the licensee.

A complete list of all display instrumentation mentioned in the LOCA and HELB emergency procedures must be provided.

Equipment qualifi-cation information in the form of summary sheets should be provided for all components of the display instrumentation exposed to harsh environments.

Instrumentation which is not considered to be safety related but which is mentioned in the emergency procedure should appear on the list.

For these instruments, (1) justification should be provided for not considering the instrument safety related and (2) assurance should be provided that its sub-sequent fai lure will not mislead the operator or adversely affect the mitiga-tion of the consequences of the accident.

The environmental qualification of post-accident sampling and monitoring and radiation monitoring equipment is closely related to the review of the TMI Lessons-Learned modifications and will be performed in conjunction with that review.

The licensee identified 415 items of equipment which were assessed by the staff.

3.2 Service Conditions Commission Memorandum and Order CLI-80-21 requires that the DOR guidelines and the "For Comment" NUREG-0588 are to be used as the criteria for establishing the adequacy of the safety-related electrical equipment environmental quali-fication program.

These documents provide the option of establishing a bounding pressure and temperature cohdition based on plant-specific analysis identified in the licensee's Final Safety Analysis Report (FSAR) or based on generic profiles using the methods identified in these documents.

On this basis, the staff has

assumed, unless otherwise noted, that the analysis

'for developing the environmental envelopes for Browns Ferry Units 1, 2, and 3, relative to the temperature,

pressure, and the containment spray caustics, has been performed in accordance with the requirements stated above.

The staff has reviewed the qualification documentation to ensure that the qualification specifications envelope the conditions established by the licensee.

During

~

=

I-ItI'

0 this review, the staff assumed that for plants designed and equipped with an automatic containment spray system which satisfies the single-failure cri-terion, the main-steam-line-break (MSLB) environmental conditions are enveloped by the large-break-LOCA environmental conditions.

The staff assumed, and requires the licensee to verify, that the containment spray system is not subjected to a disabling single-component failure and therefore satisfies the requirements of Section 4.2. 1 of the OOR guidelines.

Equipment submergence has also been addressed where the possibility exists that flooding of equipment may result from HELBs.

3.3 Tem er ature Pressure and Humidit Conditions Inside Containment The licensee has provided the results of accident analyses as follows:

Max Tem

'F Max Press si Humidit LOCA/MSLB 325 55 100 The staff has concluded that the minimum temperature profile for equipment qualification purposes should include a margin to account for analytical uncertainties in the calculated temperature profiles for postulated accidents.

A margin of 20'F above steam saturation temperature is considered to be appro-priate for either a pos'tulated LOCA or MSLB, whichever is controlling as to potential adverse environmental effects on equipment.

The licensee's minimum temperature profile for qualification purposes includes a margin at least as large as would result from the staff's recommendation.

Therefore, the staff concludes that the specified temperature profile is accept-able.

3.4 Tem erature Pressure and Humidit Conditions Outside Containment The licensee has provided the temperature,

pressure, humidity and applicable environment associated with an HELB outside containment.

The following areas outside containment have been addressed:

(1)

HPCI room (2)

SW pump room

'3)-

NW pump room (4)

NE ppmp room (5)

SE pump room (6)

Pressure suppression chamber (7)

Main steam valve vault (8)

General floor areas (9)

Reactor water cleanup pump rooms

'(10) Heat exchanger room (11)

RWCU BW receiving tank room (12)

RWCU Oemineralizer A and B

(13) Cleanup demineralizer valve room The staff has verified that the parameters identified by the licensee for the MSLB are acceptable.

0 0

The maximum submergence levels have been established and assessed by the licensee.

Unless otherwise

noted, the staff assumed for this review that the methodology employed by the licensee is in accordance with the appropriate

'riteria as established by Commission Memorandum and Order CLI-80-21.

The licensee's value for maximum submergence is 33 ft.

No equipment below this level has been identified by the licensee.

~hi S

No chemical spray is used at Browns Ferry Units 1, 2, and 3.

3. 7 Arran Section 7 of the DOR guidelines does not require a qualified life to be estab-lished for all safety-related electrical equipment.

However, the following actions are required:

(1)

Hake a detailed compariso'n of existing equipment and the materials identi-fied in Appendix C of the DOR guidelines.

The first supplement to IEB-79-01B requires licensees to utilize the table in Appendix C and identify any additional materials as the result of their effort.

'0 (2)

Establish an ongoing program to review surveillance and maintenance records to identify potential age-related degradations.

(3)

Establish component maintenance and replacement schedul.es which include considerations of aging characteristics of the installed components.

The licensee identified a number of equipment items for which a specified qualified life was established (for examples, 5 years, 15 years, or 40 years).

In its assessment of these submittals, the staff did not review the adequacy of the methodology nor the basis used to arrive at these values; the staff has

'ssumed that the established values are based on state-of-the-art technology and are acceptable.

For this review, however, the staff requires that the licensee submit supple-mental information to verify and identify the degree of conformance to the above requirements.

The response should include all the equipment identified as. required to maintain functional operability in harsh environments.

The licensee indicated that this phase of the response is outstanding and that the review is in progress.

The staff will review the licensee's response when it is submitted and discuss its evaluation in a supplemental report.

'.8 Radiation Inside and Outside Containment)

'he licensee has provided values for the radiation levels postulated to exist, following a LOCA.

The application and methodology employed to determine these.

values were presented to the licensee as part of the NRC staff criter ia contained

0 0

4, ~ l

)

~

0 in the 00R guidelines, in NUREG-0588, and in the guidance provided in IEB-79-01B, Supplement 2.

Therefore, for this review, the staff has assumed that, unless otherwise noted, the values provided have been determined in accordance with the prescribed criteria.

The staff review determined that the values to which equipment was qualified enveloped the requirements identified by the licensee.

The value required by the licensee inside containment is an integrated dose of 2 x 10'ads.

This value envelopes the OOR guideline requirements and is therefore acceptable.

A required value outside containment of greater than 3 x 10~ rads has been used by the licensee to specify limiting radiation levels within the SW pump room of the reactor building.

This value appears to consider the radiation levels influenced by the source term methodology associated with post-LOCA recirculation fluid lines and is therefore acceptable.

4 QUALIFICATION OF E(UIPMENT The following subsections present the staff's assessment, based on the licensee's submittal, of the qualification status of safety-related electrical equipment.

The staff has separated.

the safety-related equipment into three categories:

(1) equipment requiring immediate corrective action, (2) equipment requiring additional qualification information and/or corrective action, and (3) equip-ment considered acceptable if the staff's concern identified in Section 3.7 is satisfactorily resolved.

In its assessment of the licensee's submittal, the NRC staff did not review the methodology employed to determine the values established by the licensee.

However, in reviewing the data sheets, the staff made a determination as to the stated conditions presented by the licensee.

Additionally, the staff has not completed its review of supporting documentation referenced by the licen-

, see (for example, test reports).

It is expected that when the review of test reports is complete, the environmental qualification data bank established y

the staff will provide the means to cross reference each supporting document to,the referencing licensee.

If supporting documents are found to be unacceptable, the licensee will be required to take additional corrective actions to either establish qualifi-

'ation or replace the item(s) of concern.

This effort will begin in early 1981.

An appendix for each subsection of this report provides a list of equipment for which additional information and/or corrective action is required.

Where appropriate, a reference is provided in the appendices to identify deficiencies..

It should be noted, as in the Commission Hemorandum and Order, that the deficiencies identified do not necessarily mean that equipment is unqualified.

However, they are cause for concern and may require further case-by-case evaluation.

J'

l 4 4. 1 Equi ment Re uirin Immediate Corrective Action 4.2 E ui ment Re uirin Additional Information and/or Corrective Action Appendix 8 identifies equipment in this category, including a tabulation of deficiencies.

The deficiencies are noted by a letter relating to the legend (identified below), indicating that the information provided is not sufficient for the qualification parameter or condition.

~Le end R

- radiation T

- temperature QT qualification time RT - required time P

pressure H

- humidity CS

- chemical spray A

- material-aging evaluation; replacement schedule; ongoing equipment surveillance S

- submergence M

- margin I

- HELB evaluation outside containment not completed gM - qualification method RPH - equipment relocation or replacement; adequate schedule not provided ENH - exempted equipment justi'fication inadequate SEH - separate-effects qualification justification inadequate "6-

gI - qualification information being developed RPS - equipment relocation or replacement schedule provided As noted in Section 4, these deficiencies do not necessarily mean that the equipment is unqualified.

However, the deficiencies are cause for concern and require further case-by-case evaluation.

The staff has determined that an acceptable basis to exempt equipment from qualification, in whole or part, can be established provided the following can be established and verified by the licensee:

(1)

Equipment does not perform essential safety functions in the harsh environ-

ment, and equipment failure in the harsh environment will not impact safety-related functions or mislead an operator.

(2a) Equipment performs its function before its exposure to the harsh environ-

ment, and the adequacy for the time margin provided is adequately justified, and (2b) Subsequent failure of the equipment as a result of the harsh environment does not degrade other safety functions or mislead the operator.

(3)

The safety-related, function can be accomplished by some other designated

'equipment that has been adequately qualified and satisfies the single-failure criterion.'

(4)

Equipment will not be subjected to a harsh environment as a result of the postulated accident.

The licensee is, therefore, required to supplement the information presented by providing resolutions to the deficiencies identified; these resolutions should include a description of the corrective action, schedules for its completion (as applicable),

and so forth. The staff will review the licensee'

response, when it is submitted, and discuss the resolution in a supplemental repor t.

It.should be noted that in cases where testing is being conducted, a condition may arise which results in a determination by the licensee that the equipment does not satisfy the qualification test requirements.

For that equipment, the licensee will be required to provide the proposed corrective action, on a timely basis, to ensure that qualification can be established by June 30, 1982.

4.3 E ui ment Considered Acce table or Conditional.l Acce table Hased on the staff review of the licensee's submittal, the staff identified the equipment in Appendix C as (1) acceptable on the basis that the qualifi-

.cation program adequately enveloped the specific environmental plant parameters, or (2) conditionally acceptable subject to the satisfactory resolution of the staff concern identified in Section 3.7.

0 For the equipment identified as conditionally acceptable, the staff determined, that the licensee did not clearly'7-

(1) state that an equipment material evaluation was conducted to ensure that no known materials susceptible to degradation because of aging have been.

used, (2) establish an ongoing program to review the plant surveillance and main-tenance records in order to identify equipment degradation which may be age related, and/or (3) propose a maintenance program and replacement schedule for equipment identified in item 1 or equipment that is qualified for less than the life of the plant.

The licensee is, therefore, required to supplement the information presented for equipment in this category before full acceptance of this equipment can be.

established.

The staff will review the licensee's response when it is sub-mitted and discuss the resolution in a supplemental report.

5 DEFERRED REQUIREMENTS IEB 79-01B, Supplement 3 has relaxed the time constraints for the submission of the information associated with cold shutdown equipment and THI lessons-learned modifications.

~ The staff has required that this information be provided by February 1, 1981.

The staff will provide a supplemental safety evaluation addressing these concer'ns.

0

~ $f)

I

  • I~l

e APPENDIX B

Equipment Requiring Additional Information and/or Corrective Action (Category 4.2)

~

LEG=ND:

Des

. nation for Deficienc R - Radiation T - Temperature QT - Qualification time RT - Required time P - Pressure H - Humidity CS -. Chemical spray A - Material aging evaluation, replacement

schedule, ongoing equipment surveillance S - Submergence M - Margin I - KELB evaluation outside containment not completed QM - Qualification method RPN - Equipment relocation or replacement, adequate schedule not provided EXN - Exempted equipment justification inadequate SEN - Separate effects qualification justification inadequate OI - Qualification information being developed RPS - Equipment relocation or placement schedule provided Equipment Descri tion Manufacturer Com onent No.

Deficienc GE-7-104 Transformer Transformer Transformer General Electric Valve Assembly General Electric TS3A (4160-480V)

General Electric TS3E (4160-480Y)

General Electric, TS3B (4160-480V)

R,T,QT,RT,P,H)A, QI R,T,QT,RT,P,H,A, QI R,T,QT,RT,P,H,A, QI R,T,QT,RT,P,H,A)

QI 48OV MCC 480V MCC General Electric General Electric Louis Allis Co.

480V Reactor MOV BD 3C 480V Reactor MOV 3D Motor-Gener ator Set 3DN R,T,QT,RT,P,H,A, QI R,T,QT,RT,P,H,A, QI R,T,RT,P,H,QM,A B-1

Appendix B (Continued)

Equipment Descri tion M"G Set Louis Allis Co.

Motor-Generator Set 30A R,T,RT,P,H,QM,A Manufacturer Com onent No.

Deficienc

/

M-G Set Louis Allis Co.

Motor-Generator Set 3EN R,T,RT,P,H,QM,A Transformer Trans former Transformer General Electric TSlA (4160-480V)

General Electri c TS1E (4160-480V)

General Electric TSlB (4160-480V)

R,T,QT,RT,P,H,A, QI R,T,QT,RT,P,H.,A, qI R,T,QT,RT,P,H,A, qI 480Y MCC 480Y MCC M-G Set M-G Set M-G Set M-G Set General Electric General Electric Louis Allis Co.

Louis Allis Co.

Louis Allis Co.

Louis Allis Co.

480V Reactor MOV BD lc 480V Reactor MOV BD 10 Motor-Generator Set 10N Motor-Generator Set 1DA Motor-Generator Set lEN Motor-Generator Set lEA R,T,QT,RT,P,H,A, QI P.,T,QT,RT,P,H,A, R,T,RT,P,H,QM,A R,T,RT,P,H,QM,A R,T,RT,P,H,QM,A R,T,RT,P;H,QM,A Transformer Transformer Transformer General Electric TS2A (4160-480V)

/

General Electric TSZE (4160-480V)

General Electric TS2B (4160-480V)

R, T,QT,RT, P,H,A, QI R,T,QT,RT,P,H,A, QI R,T,QT,RT,P,H,A, QI

- 480Y MCC 480Y MCC

/

General Electric General Electric 480V Reactor MOV BOZC 480V Reactor MOV BDZO R,T,QT,RT,P,H,A, QI R,T,QT,RT,P,H,A, QI B-2

I,

Appendix B

(Continued)

Equipment Descri tion M-G Set M-G Set M-G Set M"G Set Manufacturer Louis Allis Co.

Louis Allis Co.

Louis Allis Co.

Louis Allis Co.

Com onent No.

Motor-Generator Set 2DN Motor-Generator Set 2DA Motor-Generator Set 2EN Motor-Generator Set.2EA Deficienc R,T,RT,P,H,QM,A R,T,RT,P,H,QM,A R,T,RT,P,H,QM,A R,T,RT,P,H,QM,A M-G Set Louis Allis Co.

Flow Solenoid Va'Ive RSCO Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO

. Flow Solenoid Valve ASCO Motor-Generator Set 3EA FSV-1"15A FSV-1"15B FSV-1-15C FSV-1-27A FSV-1-27B FSV"'1-27C FSV"1"38A FSV-1-38B FSV-1" 38C FSV-1-52A FSV-1-52B R,T,RT,P,H,QM,A RT,QT, RT,P,H,A, QI,RPN RT,QT,RT,P,H,A, QI,RPN RT,QT,RT,P,H,A, QI,RPN RT,QT,RT,P,H,A, QI, RPN RT,QT,RT,P,H,A, QI,RPN RT,QT,RT,P,H,A, QI, RPN RT,QT,RT,P,H,A, QI,RPM RT,QT,RT,P,H,A, QI,RPN RT,QT,RT,P,H,A, QI,RPN RT,QT,RT,P,H,A, QI,RPN RT,QT,RT,P,H,A, QI, RPN B"3

Appendix B

(Continued)

Equipment Descri tion Manufacturer Com onent No.

Deficienc Flow Control Valve Temperature Switch Temperature Switch Temperature Switch Temperature Switch Pressure Solenoid Val ve Limitorque Fenwal Fenwal Fenwal Fenwal Target Rock Flow Solenoid Valve ASCO FSV"1-52C FCV-1-56 TS"1-17A TS"1-17B TS-1" 17C TS"1"17D PSV"1-4 RT,QT,RT,P,H,A, QI,RPN QT,RT,H,A,QI QI, RPN,R,A QI,RPN,R,A QI,RPN,R,A QI,RPN,R,A R,T,QR,RT,P,H,A QI 0

Pressure Solenoid Valve Pressure Valve Solenoid Pressure Solenoid Valve Pressure Solenoid Valve J

ASCO ASCO ASCO ASCO PSV"1"5 PSV-1-18 PSV-1-19 PSV-1-22 R,T,RT,P,H,QT,A, QI QT,R,T,A,QI,RPN R,T,QT,A,QI R,T,QT,A,QI Pressure

,Valve Pressure

.Valve Solenoid Solenoid ASCO ASCO PSV-1-23 PSV"1-30 R,T,QT,A,QI R,T,QI,RPN,QT,A Pressure Solenoid Valve P r es sure Solenoid Valve Pressure Sol'enoid Valve Pressure Solenoid Val ve ASCO ASCO ASCO ASCO PSV-1-31 PSV-1" 34 PSV-1-41 PSV"1"42 R,T,QT,A,QI R, T,QT,A,QI R,T,QT,A,QI R, T,QT,A,QI

Appendix 8 (Continued)

Equipment Descri tion Pressure Solenoid Valve Pressure Solenoid Yal ve Manufacturer Target Rock Target Rock Com onent No.

PSV"1-179 PSV-1" 180 Deficienc R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO Fl ow -Sol enoid Val ve ASCO Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO Pressure Switch Pressure Switch Unknown

. Unknown Flow Solenoid Valve Limitorque FSV-1-14A FSV"1-148 FSV-1-14C FSV-1-26A FSV"1-268 FSV-1-26C FSV"1"37A FSV-1-378 FSV-'1-37C FSV-1-51A FSV"1-518 FSV-1-51C FCV-1-55 PS-1-4 PS-1-5 R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI.,RPN R,T,QT,RT,P,H,A, QI,RPN QT,RT,H,A,QI R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A 8-5

Appendix B

(Continued)

~

Equipment Descri tion Pressure Switch Pressure Switch Pressure Switch Pressure Switch Pressure Switch Pressure Switch Pressure Switch Pressure Switch Pressure Switch Pressure Switch Pressure Switch Pressure Differential Indicator Switch Pressure Differential Indicator Switch Pressure Differential Indicator Switch Pressure Differential Indicator Switch Pressure Differential Indicator Switch Pressure Differential Indicator Switch Pressure Differential Indicator Switch Pressure Differential Indicator Switch Manufacturer Unknown Unknown Unknown Unknown Unknown Unknown Unknown Unknown Unknown Unknown Unknown Barton Barton Barton Barton Barton Barton Barton Barton Com onent No.

PS-1" 18 PS-1-19 PS-1-22 PS-1-23 PS-1" 30 PS-1-31 PS-1-34 PS-1"41 PS-1-42 PS" 1"179 PS-1" 180 PDIS"1-13A PD IS-1"13B PDIS"1"13C PDIS"1"130 PD IS"1-25A PD IS-1-25B POIS-1-25C POIS-1-25D Oeticienc R T,QT,RT,P,H,A R,T,QT,RT,P,H,A R, T,QT, RT, P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R',7,QT,RT,P,H,A R,V,QT,RT,P,H,A R,;T~,QT,RT)P)H,A R,'T,QT,RT,P,H,A R,:i,QT,RT,P,H,A R,. l,QT, RT, P,H,A, QI'RPN R,T,QT,RT,P,H,A, QI,RPN R, T',QT,RT,P,H,A, QI, RPN R,T-,QT,RT,P,H,A, QI, RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN B-6

0 0

0 Appendix 8

(Continued)

Equipment Descri tion Pressure Differential Indicator Switch Pressure Differential Indicator Switch Pressure Differential Indicator Switch Pressure Di'fferential Indicator Switch Pressure Differential Indicator Switch Pressure Differential Indicator Switch Pressure Differential Indicator Switch Pressure Differential Indicator S~itch Zone Switch Zone Switch Pressure Solenoid Val ve Pressure Switch Pressure Switch Pressure Switch Pressure Switch Pressure Switch Pressure Switch Pressure Switch Manufacturer Barton Barton Barton Barton Barton Barton Barton Barton NAMCO NAMCO Unknown Barksdal e Barksdale Barksdale Barksdale Barksda1 e Barksdale Barksdale Com onent No.

PDIS"1-36A PD IS-1-368 PDIS"1-36C POIS"1-36D PDIS-1-50A PDIS-1"50B PD IS-1-50C PDIS-1-50D ZS-1-14 ZS-1" 15 PSV"1-34 PS-3"22A PS"3-228 PS"3-22C PS"3"22D PS-3-57A PS-3-57B PS-3-57C Deficienc R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI, RPN R,T,RT,QT,P,H,A, QI,RPN R,T,RT,QT,P)H,A, QI,RPN R,T,RT,QT,P,H,A R,T,QT,RT,A R,T,QT,RT,A R,T,QT,RT,A R,T,QT,RT,A R,T,QT,RT,A R,T,QT,RT,A R,T,QT)RT,A B"7

0

0 Appendix B

(Continued)

Equipment Descri tion Pressure Switch Level Indicator Switch Level Indicator Switch Level Indicator Switch Level Indicator Switch Level Indicator Switch Level Indicator Switch Level Indicator Switch Level Indicator Switch Level Indicator Switch Level Indicator Switch

, Level Indicator Switch

- Level Indicator Switch Level-Indicator Switch Level Indicator Temperature Switch Level Indicator Switch Manufacturer Barksdal e Barton Barton Barton Barton Barton Barton Barton Barton Yarway Yarway Yarway Yarway Yarway Yarway Yarway Com onent No.

PS-3-57D LIS-3-203A LIS-3"203B LIS-3-203C LIS-3-2030 LIS"3-208A LIS-3-208B L IS-3-208C LIS-3-208D LIS-3"58C L IS"3-56A L IS"3"56B LIS-3"56C LIS"3"56D LITS-3"46B L IS-3-184 Deficienc R,T,QT,RT,A R,T,QT,RT,A R,T,QT,RT,A R,T,QT,RT,A R,T,QT,RT,A R,T,QT,RT,A R,T,QT,RT,A R,T,QT,RT,A T,QT,RT,R,A R,T,QT,RT,A,P,QM R,T,QT,RT,P,A,QM R,T,QT,RT,P,A,QM R,T,QT,RT,P,A,QM R,T,QT,RT,P,A)QM R,T,QT,RT,P,A,QM R,T,QT;RT,P,A,QM

'B-8

Appendix B

(Continued)

Equipment Oescri tion Level Indicator Switch Level Indicator Switch Level Indicator Temperature Switch Level Indicator Temperature Switch Level Indicator Temperature Switch Pressure Switch Pressure Switch Temperature Element Flow Control Valve Manufacturer Yarway Yarway Yarway Yarway Unknown Barksdale Barton Calimatic Limitorque Com onent No.

LIS" 3-185 L IS-3-58A LITS-3-46A LITS-3-58B LITS-.3"580 PS"3"74A PS-3"74B TE-23"32 FCV-23"34 Deficienc R,T,QT,RT,P,A,QM R,T,QT,RT,P,A,QM R,T,QT,RT,P,A,QM R,T,QT,RT,P,A,QM R,T,QT,RT,P,H,A T,QT,A T,QT,A R,T,QT,RT,P,H,A, QI,RPN QT,A Temperature El ement Cal imati c TE-23-35 R,T,QT,RT,P,H,A, QI,RPN Flow Transmitter GEMAC FT-23"36 R,T,QT,RT,P,H,A.

QI,RPN Temperature El ement Cal imati c Flow Control Valve Limitorque Temperature Element Calimatic TE-23-38 FCV"23-40 TE-23"41 R,T,QT,RT,P,H,A, QI, RPN QT,A R,T,QT',RT,P,H,A, QI,RPN Flow Transmitter GEMAC FT"23"42 R,T,QT,RT,P,H,A, QI,RPN Temperature Element Calimatic Flow Control Valve Limitorque TE"23"44 FCV-23"46 R,T,QT,RT,P,H,A, QI,RPN

'T,A B-9

~ I

~II

, I e

0 Appendix B

(Continued)

Equipment Oescri tion Manufacturer Com onent No.

Oeficienc Temperature Element Calimatic TE-23"47 R,T,QT,RT,P,H,A, QI,RPN Flow Transmitter GEMAC FT-23-48 R,T,QT,RT,P,H,A, QI,RPN Temperature Element Calimatic Flow Control Valve Limitorque Temperature El ement Cal imati c TE"23-50 FCV"23-52 TE-23-53 R,T,QT,RT,P.,H,A, QI, RPN QT,A R, T,QT,RT,P,H,A, QI, RPN Flow Tr ansmitter.

GEMAC

,FT-23-54 R,T,QT,RT,P,H,A, QI,RPN Flow Solenoid Valve Atkomatic FSV-23"56 (1,2)

R,T,QT,RT,P,H,A, QI,RPN Power Supply Power Supply Power Supply Power Supply Solenoid Valve Solenoid Valve Limitorque Unknown Unknown Unknown Unknown AAA AAA FCV"23-57 (1,2)

PX-23-58 PX"23-60 PX-23-59 PS"23-61 FSV"32-62 FSV"32"63 QT,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A,.

QI,RPN R,T,QT,RT,P,H,A, QI, RPN Flow Solenoid Valve ASCO Pressure Switch Unknown FSV-43-14 PS"24-133A(3)

F'low Indicator Switch Fischer 5 Porkier FIS-43-13B Pressure Switch Unknown PS-24"133B(3)

Flow Indicator Switch Fischer 8 Porter FIS-43-13A R,RT,QM,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A,

- QI;RPN

0

Appendix B

(Continued)

Equipment Oescri tion Manufacturer Com onent No.

Deficienc 0

Flow Solenoid Valve ASCO Flow Control Valve Micro Switch Temperature Element Fenwal Flow Control Valve GEMAC Flow Control Valve Conax Flow Indicator Switch Unknown Temperature Indicator Fenwal Control Pump Motor General Electric Flow Control Valve Micro Switch FSY"43-13 FCV-43-13 (1,2)

FCV-43"14 (1,2)

TE-63-2 FCV-63-8A FCV-63-8B FIS-63"11 TIC"63-2 SLC Pump Motor A T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,A, QI,RPN R,T,QT,RT,P,A,

.QI,RPN R;T,RT,P,A,QT.,H, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,A R,T,QT,RT,P,H,A R,T,RT,P,H,A,QI, RPN,QT R,T,RT,P,H,A,QT, QI Pump Motor General Electric SLC Pump Motor B

R,T,RT,P,H,A,QT, QI Temperature Control Honeywell Flow Solenoid Valve Unknown Flow Solenoid Valve Unknown Flow Solenoid Valve ASCO Flow Solenoid Valve Flow Solenoid Valve Flow Solenoid Valve ASCO ASCO ASCO Pressure Indication Unknown Temperature Control Honeywell PI-63-7A TC-63"5A TC"63"5B FSV"64-9 FSV-64-10 FSV-64-17 FSV-64-18 FSV-64-19 FSV-64-20, R,T,QT,RT,P,A R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A QT,A,R,QM QT,A,R,QM QT,A,R,QM QT,A,R,QM

Appendix 8

(Continued) quipment Descriotion Manufacturer Com onent No.

Deficienc Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO Flow Solenoid Val ve Unknown Flow Solenoid Valve Unknown Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO FSV-64-21 FSV"64-29 FSV"64-30 FSV-64-31 FSY"64-32 FSV-64-33 FSV-64-34 FSV-64"36 FSV-64-40 FSV"64-41 FSV-64-42 FSV-64-43 FSV"64"44 (1)

FSV-64.-45 (1)

QT,A,R,QM QT,R,A,QM QT,R,A,QM QT,R,A,QM A,R,T,RT,P,H,RPS A,R,T,RT,P,H,RPS A,R,T,RT,P,H,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI, RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A,

.,QI,RPN R,T,QT,RT,P,H,A, QI, RPN

'hermocouple Meed TE"64-52B R, T,QT, RT, P,H,A, QI, RPN Level Transmitter Rosemount LT-64-54 Temperature Element American Standard TE-64-55A Temperature Element American Standard TE-64-558 Temperature Element American Standard TE-64-55C A,QT,R,RPN,QI R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI, RPN R,T,QT,RT,P,H,A.,

QI,RPN 8-12

-0 Appendix 8

(Continued)

Equipment Descri tion Manufacturer Com onent No.

Oeficienc Temperature Element American Standard TE-64-550 1

Temperature Element American Standar d TE-64-55E Temperature Element American Standard TE-64-55F R,T,QT,RT,P,H,A, QI, RPN R, T,QT,RT,P,H,A, QI, RPN R,T,QT,RT,P,H,A, QI,RPN Flow Control Operator Honeywell Flow Control Operator Honeywell Flow Control Operator Honeywell Flow Control Operator Honeywell r

Level Transmitter Temperature Sensor'osemount Honeywell Temperature Sensor

. Honeywell Temperature Sensor Honeywell Temperature Sensor Honeywell Flow Solenoid Valve ASCO

.Temperature Sensor Honeywell FCO-64-60A (1,3)

FCO-64-608 (1,3)

FCO-64-60C (1,3)

FCO-64-60O (1)

LT-64-66 TS"64-68 TS-64"69 TS"64"70 TS-64"71 TS"64-72 FSV-64-139 R, T,QT,RT,P,H.,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R, T,QT, RT, P,H,A, QI,RPN QT)RjQI)A R,T,QT,RT,P,H,A, RPS R,T,QT,RT,P,H,A, RPS R,T,QT,RT,P,H,A, RPS R,T,QT,RT,P,H,A, RPS R,T,QT,RT,P,H,A, RPS R,T,QT,RT,P,H,A, RPS 0

Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO FSV-64-140 FSV-64-141 R,T,QT,RT,P,H,A, RPS R,T,QT,RT,P,H,A; RPS 8"13

Appendix B

(Continued)

Equipment Descri tion Manufacturer Com onent No.

Defscsenc Power Supply General Electric PX-64-51 R,T,QT,RT,P,H,A, RPN,QI Pressure Differential Indicator Switch Pressure Differential Indicator Switch Pressure Switch Pressure Switch Pressure Switch Pressure Switch Pressure Differential Switch Pressure Differential Switch Pressure Differential Indication Switch Barton Barton Static-0-Ring Stati c-0-Ri ng Stati c-0-Ring Static-0-Ring Owyer Honeywell Fischer

& Porter P 9IS-64-20 PDIS-64-21 PS-64-570 PS"64-58A PS-64-58B PS-64-58C PDS-64"15 P DM"64"16 POIC-64-16 QT,A QT,A T,QT,QI,RPN,R.,A T,QT,QI,RPN,R,A T,QT,QI,RPN,R,A T,QT,QI,RPN,R,A R, T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN Pressure Differential Transmitter Fischer

& Porter POT-64-16 R, T,QT,RT, P,H,A, QI,RPN Temperature Element Meed Temperature Element Meed TE-64.-52A TE-64"52C R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI, RPN Pressure Differential Swi-ch Owyer PDS-64-62A R, T,QT, RT, P,H,A, QI, RPN Pressure Differential Dwyer Switch POS-64-62C R,T,QT,RT,P,H,A, QI,RPN Flow Control Valve Flow Control Valve Flow Control Valve Unknown Unknown Unknown FCV-64-20 FCV-64-21 FCV-64-19 R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A

Appendix B

(Continued) 0 Equipment Oescri tion Flow Control Valve Flow Control Valve Pressure Oifferential Switch Pressure Differential Switch Temperature Switch Pressure Differential Sw'itch Pressure Differential Switch Pressure Differential Switch Pressure Differential Switch Pressure Differential Switch

'I Manufacturer Unknown Unknown Dwyer Owyer Honeywell Owyer r

Owyer Fischer 8 Porter Honeywell Com onent No.

FCV-64-18 FCO-64-43 PDS-64"62B PDS-64-620 TS-64-63 PDS-64-63 (1)

POS"64"61A (1)

PDS-64-61C (1)

PDT-64-64 (1)

POM-64-64 (1)

Deficienc R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A, QI, RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI, RPN R,T,QT,RT,P,H,A, QI, RPN R,T,QT,RT)P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI, RPN Pressure Differential Switch Fischer 8 Porter POT-64-8 (1)

R,T,QT,RT,P,H,A, QI,RPN Pressure Oifferential Monitor Honeywell PDM-64-8 (1)

R,T,QT,RT,P,H,A, QI,RPN Pressure Oifferenti al Indicator Control Fischer 8 Porter PDIC-64-8 (1)

R,T,QT,RT,P,H,A, QI, RPN 0

Pressure Differential Switch Pressure Differential Switch Pres sure Oifferenti al Switch Unknown Owyer Owyer PDS"64-61B (1)

POS"64-61D (1)

PDS" 64-7 (1)

R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI, RPN

Appendix 8

(Continued)

Equipment Descri tion Manufacturer Com onent No.

Deficienc Pressure Switch.

Pressure Switch Pressure Switch Pressure Switch Pressure Switch Static-0-Ring Static-0-Ring Static-0-Ring Static-0-Ring Static-0-Ring Fl ow Control Operator Honeywel l Flow Control Operator Honeywel 1 PS-64-56A PS-64-568 PS-64"56C PS-64"56D PS-64-58D FCO-64"65D FCO-64" 65A (1)

QT,R,QM,A T,QT,R,QM,A T,QT,R,QM,A T,QT,R,QM,A T,QT, R,QI, RPN,A R,T,QT,RT,P,H,A, RPS R, T,QT,RT,P,H,A, RPS Flow Control Operator Honeywell FCO"64-658 (1)

R,T,QT,RT,P,H,A, RPS Flow Control Operator Pressure Switch

\\

Pressure Switch Pressure Switch Honeywell Static-0-Ring Static-0-Ring Static-0-Ring I

FCO-64-65C (1)

PS-64-57A PS-64-578 PS-64-57C R,T,QT,RT,P,H,A, RPS T,QT,QI, RPN, R,A T,QT,QI,RPN,R,A T,RT,P,H,RPN,QI Pressure Differential Fischer 8 Porter PDIC-64-64 (1)

R,T,RT,P,H,A,QI RPN,QT Flow Control Operator Unknown Flow Control Operator Unknown Flow Control Operator Unknown Flow Control Operator Unknown Flow Control Operator Unknown Flow Control Operator Unknown Flow Control Operator Unknown Flow Control Operator Unknown FCO-64-40 FCO-64" 41 FCO-64-44 FC0-64-45.

FCO-64-36 FVO-64-29 FVO"64-30 FVO-64-31 R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,'QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A',T,QT,RT,P,H,A R,T,QT,RT,P,H,A 8-16

0 Appendix B

(Continued)

Equipment Oescri tion Manufacturer Com onent No.

Deficienc Flow Control Operator Unknown Flow Control Operator Unknown Flow Control Operator Unknown Flow Control Operator Unknown Flow Control Operator Unknown Flow Control Operator Unknown Flow Control Operator Unknown Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO FYO"64"32 FVO-64"33 FVO-64"34 FVO-64"139 FVO-64-140 FVO-64"141 PX-64-54 FSV-64-139 (1,2)

FSV-64-14O (1,2)

FSV-64-141 (3)

R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN RT,QT,RT,P,H,A, QI,RPN Pressure Differential Swi ch Dwyer PDS-64-62A/C R,T,QT,RT,P,H,A, QI,RPN Pressure Swi ch Differential Owyer PDS"64-62B/0 R,T,QT,RT,P,H,A, QI, RPN Pressure Switch Differential Owyer Owyer Pressure Oifferential Switch PDS-64-61B/D (1)

PDS-64-61B (1)

R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI, RPN Pressure Differential Switch Dwyer PDS" 64-64A/C (1)

R,T,QT,RT,P,H,A, QI, RPN Pressure Transmitter GEl<AC Pressure Transmitter GEHAC Flow Control Valve NAHCO PT-64-51 PT-64-50 (2,3)

FCY"64-3.8 R,T,QT,RT,P,H,A, QI,RPN R,T,QT)RT,P,H,A QI,RPN R,T,QT,RT,P,H,A; QI,RPN B-17

Appendix 8

(Continued)

Equ'.pment Oescri tion Flow Control Valve Flow Control Valve Flow Control Valve Flow Control Valve Flow Control Valve Flow Control Valve Flow Control Valve Flow Transmitter Manufacturer HAMCO HAMCO NAMCO NAMCO NAMCO HAMCO NAMCO HAMCO Com onent Ho.

FCV-64"19 FCV-64"29 FCV-64-30 FCV"64-31 FCV-64-32 FCV-64-33 FCV-64"34 FT-65-1 Oeficienc R,T,QT,RT,P,H,A, QI, RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H.,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H)A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN Pressure Transmitter Bailey Pressure Transmitter Bailey PT"67"15 (1)

PT-67" 16 (1)

R,T,QT,RT,P,H,A, QI,RPH R,T,QT,RT,P,H,A, QI,RPN Flow Control Valve Flow Control Valve Power Supply Solenoid Valve Limitorque Limitorque Unknown ASCO FCV-67-17 (1)

FCV-67-1S (1)

PX-67-12B (1)

FSV-67-53 QT,A R,T,QT,QI,RPN,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A, QI,RPN Control Valve Unknown Flow Solenoid Valve

. ASCO Flow Solenoid Valve ASCO FCV-67-53 (1)

FSV-67-50 FSV-67-51 R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A; QI,RPN B-18

~ ~

Appendix B

(Continued)

Equipment Oescri tion Signal Modifier Power Supply Flow Transmitter Flow Transmitter Flow Modifier Flow Modifier Flow Modifier Power Supply Power Supply I

Flow Switch Flow Transmitter Flow Transmitter Flow Control Valve Flow Control Valve Flow Control Valve Flow Control Valve Pressure Switch Pressure Switch Flow Control Valve Flow Control Valve Pressure Switch Pressure Switch Manufacturer Unknown Unknown GEMAC Unknown Unknown Unknown Unknown Unknown Unknown Unknown Unknown Unknown Unknown Unknown'imitorque Limitorque Unknown Unknown Limitorque Limitorque Unknown Barton

" Limitorque Com onent No.

FM"67-3B (1)

PX-67-3B (1)

FT"67-9A (1)

FT"67-9B (1)

FM-67-12B (1)

FM"67-9B (1)

FM-67-6B (1)

, PX-67-6B (1)

PX-67" 9B (1)

FS-67-12B FT-67-12A FT-67"12B FCV-67-50 FCV-67"51 FCY-68"1 FCV-68-3 PS-68-93 (1,2)-

PS-68-94 FCY"68-77 FCV-68"79 PS-68-95 PS-68"96 FCV"69-2 Oeficienc R'T,QT,RT,P,H,A R T,QT,RT,P,H,A RT,QT,RT,P,H,A, QJ,RPN RT,QT,RT,P,H,A R, T,QT,RT,P,H,A R,'T,QT,RT,P,H,A R, T,QT,RT,P,H,A R, T,QT,RT,P,H,A R,'T',QT,RT,P,H,A R,:I,QT,RT,P,H,A R,T.',QT,RT,P,H,A R,Y,QT,RT,P,H,A R,l'.,QT,RT,P,H,A R,T',QT,RT,P,H,A T,A,QT,QI T,A,QT,QI R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A

.T,A,QT,QI T,A,QT,QI R,T,QT,RT,P,H,A QT,R,QI,RPN,A QT,A 8-19

0 Appendix 8

(Continued)

J Equipment Descri tion Manufacturer

.Com onent No.

Deficienc Temperature Element Scam Temperature Element Scam Temperature Element Scam Temperature Element Scam Temperature Element Scam Temperature Elem'ent Scam Temperature Element Scam TE-69-29A TE-69"298 TE-69-29C TE-69-29D TE-69-29E TE-69-29F TE-69-29G R,T,QT,RT,P)H, QI,RPN,A R,T,QT,RT,P,H, QI,RPN,A R,T,QT,RT,P,H, QI,RPN,A R,T,QT,RT,P,H, QI,RPN,A R,T,QT,RT,P,H, QI,RPN,A R,T,QT,RT,P,H, QI,RPN,A R,T,QT,RT,P,H, QI,RPN,A Temperature Element Temperature Sensor Scam Fenwal TE-69-39H TS-69-30A R,T,QT,RT,P,H, QI,RPN,A R,T,QT,RT,P,H,A, QI,RPN Temperatur e Sensor Fenwal Temperature Sensor Fenwal Temperature Sensor Fenwal P

Temperature Sensor Fenwal Temperature Sensor Fenwal Temperature Sensor Fenwal Temperature Sensor Fenwal.

TS"69-308 TS-69"30C TS-69-30D TS-69" 30E TS-69-30F TS-69-30G TS"69-30H R,T,QT,RT,P,H,A, QI,RPN

',T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI, RPN R,T,QT,RT)P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN 8-20

l

0 Appendix B

(Continued)

Speed Sensor Temperature Sensor Temperature Sensor Temperature Sensor Temperature Temperature Sensor Sensor Temperature Sensor Temperature Sensor Temperature Sensor Temperature Sensor Temperature Sensor Equipment Oescri tion Zone Switch Temperature Switch Temperature Switch Temperature Switch Temperature Switch Flow Control Valve Flow Control Valve Flow Control Valve Pressure Switch Pressure Switch Flow Control Valve Speed Sensor Manufacturer Unknown Fenwal Fenwal Fenwal Fenwal Limitorque Limitorque Limitorque r

Barksdal e Barksdal e Limitorque Terry Turbine Terry Turbine Fenwal Fenwal Fenwal Fenwal Fenwal r

Fenwal Fenwal Fenwal Fenwal Fenwal Com onent No.

ZS"69-1 TS-69-29J TS-69-29K TS-69-29L TS-69-29M FCV-69-1 FCV-70-47 FCV-71-2 PS-71-11C PS" 71"110 FCV-71-25 S E"71"42A SE-71-42B TS"71-2A TS"71" 2B TS-71" 2C TS-71-2O TS-71-2E TS-71-2F TS-71-26 TS-71" 2H TS-71-2J TS-71-2K Oeficienc R,T,QT,RT,P,H,A R,A,RPN,QI R,A,RPN,QI R,A,RPN,QI R,A,RPN,QI T,QT,A,QI QT,A T,QT,A,QI QT, T,R,A,QI,RPN QT, T, R, A,QI ) RPN R,T,QT,A, R,T,QT,RT,P,H,A, QI R,T,QT,RT,P,H,A, QI A,R A,R A,R A,R A,R A,R A,R A,R A,R A,R

, I I

Appendix B

(Continued) qulpment Oescri tion Manufacturer Com onent No.

Oeficienc Teriaerature Sensor Temperature Sensor Temperature Sensor Temoerature Sensor Temperature Sensor Temperature Sensor Flow Control Valve Pressure Transmitter Flow Control Valve Fenwal Fenwal Fenwal Fenwal Fenwal Fenwal Limitorque Unknown

.Limitorque Flow Control Valve Terry Turbine Flow Control Valve Terry Turbine TS-71-2L TS-71-2H TS-71-2N TS-71-2P TS"71-2R TS-71"2S FCV"71-3 PT-71-4 FCV-71-8 FCV"71-9 FCV"71-10 A,R A,R A,R A',R A,R T,QT,A,QI R,T,QT,RT,P,H,A T,QT,A,QI R,T,QT,RT,P,H,A, QE.

R,,T,QT,RT,P,H,A, QI.'peed Control Terry Turbine SC-71-10 R,T,QT, RT,P,H,A, QI Pressure Transmitter GEHAC PT"71-12 R, T,QT,RT,P,H,A, QI,RPN Pressure Switch Pressure Switch Her coid Hercoid PS-71-13A PS-71-13B R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI, RPN Flow Control. Valve

.imitorque flow Control Valve Limitorque Flow Control Valve Limitorque Pressure Transmitter GEHAC Barksdale FCV-71"17 FCV"71-18 FCV-71-19 PT-71-20 PS-71-21 T,A,QT,QI T,A,QT,QI A,T,QT,QI R,T,QT,RT,P,H,A, QI,RPN QT,T,R,A,QI,RPN B"22

0

0 Appendix B

(Continued)

Equipment Descri tion Manufacturer Com onent No.

Deficienc Pressure Switch Flow Control Valve Static-0-Ring Limitorque Flow Transmitter GEMAC Flow Control Valve Flow Control Valve Flow Control Valve Limitorque Limitorque Limitorque Temperature Element Scam Temperature Element Scam Temperature Element

-Scam Pressure Transmitter Unknown Flow Switch Barton PS-71-21"1 PT-71-34 PT"71-35 FS"71"36 FT-71-36 FCV"71-37 FCV"71-38 FCV-71-39 TE"71-41A TE"71"41C TE-71"41D QT,T,R,A,QI,RPN R,T,QT,A,QI,RPN R,T,QT,RT,P,H,A T,QT,QI,RPN,R,A R,T,QT,RT,P,g,A, QI,RPN T,A,QT,QI T,A,QT,QI T,A,QT,QI R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A,

. QI,RPN Pressure Switch Terry Turbine PS-71-44 R,T,QT,RT,P,H,A,

.-QI Temperature Indicator Terry Turbine Switch Temperature Indicator Terry Turbine Switch Flow Solenoid Valve ASCO TIS-71-45 T IS"71-46 FSV-71-6B R,T,QT,RT,P,H,A, QI R,T,QT,RT,P,H,A, QI R,T,QT,RT,P,H,A, QI,RPN Pressure Switch Pressure Switch Pressure Switch Bar ksdal e Barksdale, Barksdal e Barks dal e PS-71-1A PS-71-1B PS-71-1C

'S-71-1D T, R, QT, A,QI, RPN T,R,QT,A,QI,RPN T,QT,R,A,QI,RPN T,QT,R,A,QI,RPN 8-23

0

Appendix B

(Continued)

Equipment Descri tion Manufactur er Com onent No.

Deficienc Pressure Differential Barton Indicator Switch PDIS"71-1A R,T,A Pr essure Differential Bar ton Indicator Switch PDIS-71-18 (1,3)

R, T,A Pressure Switch Pressur e Switch Si gnal t 1odifier Power Supply Barksdale Barksdale PS"71-llA (1,3)

PS-71-118 (1,3)

General Electr ic PX-71-4 Gener al Electri c Ftl-71-36 QT,R,T,A,QI,RPN QT,R,T,A,QI,RPN R,T,QT,RT,P,H,A, QI, RPN R,T,QT,RT,P,H,A, QI,RPN Flow Transmitter Flow Transmitter Power Supply Power'upply Power Supply Flow Recorder Flow, Control Valve Flow Control Valve Flow Control Valve Flow Control Valve Pressure Transmitter Speed Sensor Speed Control Unknown Unknown Unknown

-Unknown Unknown Unknown Limitorque Limitorque Limitorque Limitorque Unknown Terry Turbine Terry Turbine FT"71" 1A FT-71-18 PX-71-35 PX-71-36A PX"71-12 FR-71-36 FCV-73-3 FCV-73-2 FCV-71-59 (2,3)

FCY-73-27 PT-.73-4 SE-73-5 SC-73-19 R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A QI,A A,T,QT,QI QT,A T,RT,P,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A, QI R,T,QT,RT,P,H,A, QI Pressure Transmitter GEMAC PT-73-21 R,T,QT,RT,P,H,A,

'I,RPN B"24

0 t.

0

Appendix B

(Continued}

quspment Descri tion Manufacturer Com onent No.

Deficienc Flow Switch Barton Pressure Transmitter GEMAC Flow Solenoid Valve ASCO Termper ature Switch Terry Turbine FS-73-33 PT-71-48 (3)

TS-71-9 (3)

FSV-71-6A T,QT,A R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI R,T,QT,RT,P,H,A, QI, RPN Pressure Switch Pressure Switch

'Pressure Switch Pressure Switch 4

Barksdale Barksdale Bar ksdal e Barksdale PS"73"20B PS-73-22A (2,3)

PS-73-20C PS-73-22B (2,3)

R,T,QT,RT,P,H,A, QI, RPN R,T,QT,RT,P,H,A, QI,RPN R,RT,P,H,QI;RPN R,T,QT,RT,P,H,A, QI, RPN Pres'sure Switch Pressure Switch Pump Motor Bar ksdal e Barksdale Unknown Temperature Indicator Terry Turbine Switch PS"73-20D PS-73-20A HPCI Aux Oil Pump Mtr TIS-73-52 R, RT, P,H,QI, RPN R,T,QT,QI,RPN,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A, QI Pressure Switch Pressure Switch Pressure Switch Pressure Switch Pressure Differential Indicator Switch Barksdale Barksdale Barksdale Barksdale Barton PS" 73-lA (1,2}

PS"73-1B PS-73"1C PS-73-1D PD IS-73-lA T,A,QT,R T,A,QT,R T,A,QT,R

'T,A,QT,R T,A,R Pressure Differential Barton PDIS-73"1B T,A,R B-25

0 Appendix B

(Continued)

Equipment Descri tion Flow Transmitter Manufacturer GEMAC Com onent No.

FT-73"33 Deficienc R,T,QT,RT,P,H,A, QI,RPN Temperature Sensor Fenwal Temperature Sensor Fenwal TS-73-2C TS-73-2E (2,3)

R,A T,QT,RT,P,H,QI, RPN,A Temperature Sensor Temperature Sensor Fenwal Fenwal TS"73-2D TS-73"2F (2,3)

R,A T,QT,RT,P,H,A,QI,

RPN, Temperature Sensor Fenwal Temperature Sensor Fenwal Temperature Sensor Fenwal Temperature Sensor Fenwal

~

Temper atur e Sensor Fenwal TS-73-2J TS"73"2G (2,3)

TS"73-2K TS-73-2H (2,3)

TS"73-2L T,QT,RT,P,H,A,QI, RPN T,QT,RT,P,H,A,QI RPN T,QT,RT,P,H,A,QI, RPN T, QT, RT, P, H,A,QI RPN T,QT, RT, P, H,A,QI RPN Temperature Sensor

'I Fenwal TS"73-2M T,QT,RT,P,H,A,QI RPN Temperature Sensor Fenwal Temperature Sensor Temperature Sensor Temper'ature Sensor Terperature Sensor Fenwal Fenwal Fenwal Fenwal Unknown

. Temperature Sensor Fenwal TS"73"2N TS"73-2P TS"73"2R TS-73-2S TS-73"2A TS-73-2B FCV-73"16 T,QT,RT,P,H,A,QI RPN T,QT,RT,P;HA,QI RPN T,QT, RT,P,H,A,QI T,QT,RT,P,H,A,QI T,QT,RT,P,H,A,QI T,QT, RT, P, H,A,QI R,T,QT,RT,P,H,A 8-26

0

Appendix 8

(Continued)

Equipment Oescri tion Manufacturer Com onent No.

Deficienc Flow Control Valve Flow Control Valve Flow Control Valve Flow Control Valve Flow Control Valve Flow Control Valve Flow Control Valve Temperature Element Limitorque Limitorque

'Limitorque Limitorque Limitorque Limitorque Limitorque Scam FCY-73-26 (1,2)

FCV-73-30 (1)

FCV-73-34 FCV"73-35 FCY"73"36 (1)

FCV-73"40 FCY-73-44 TE-73-55A T,A,QT,QI T,QT,A T,A,QT,QI T,,A,QT,QI A,QT T,A,QT,QI T,A,QT,QI R,T,QT,RT,P,H, A,QI,RPN Temperature Element Scam Temperature Element Scam Temperature Element Scam TE-73-558 TE-73-55C TE"73"550 R,T,QT,RT,P,H, A,QI,RPN R,T,QT,RT,P,H, A,QI,RPN R,T,QT,RT,P,H,A, QI,RPN Levels Switch Level Switch Level Switch Level Switch Robertshaw Robertshaw Robertshaw Robertshaw LS-73"57A LS"73"56A (2)

LS-73-578 LS-73-568 (2)

R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,'RT,P,H,A, QI,RPN Flow Control Valve Terry Turbine Pressure Transmitter Unknown PT-73-65 FCV-73-18 FCV-73-64 (2,3)

R,T,QT,RTiP,H,A R,T,QT,RT,P,H,A, QI QT,A 8-27

0 Appendix 8 (Continued)

Equipment Descri tion Manufacturer Flow Control Valve Terry Turbine Pressure Differential Terry Turbine Com onent No.

FCV-73-19 PDS-73"53 Deficienc R,T,QT,RT,P,H,A, QI R,T,QT,RT,P,H,A, QI Power Supply Pressure Switch Pressure Switch Unknown Terry Turbine Terry Turbine PX"73-65 PS"73-47A PS-73-47B R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A, QI R,T,QT,RT,P,H,A, QI Pressure Transmitter Terry Turbine Pr essure Switch Static-0-Ring Temperature Sensor Fenwal Temperature Sensor Fenwal Flow Control Valve Terry Turbine PT-73-31 PS"73"29-1 TS-73-2F (1)

TS"73-2H (1)

FCV-73"18 R,T,QT,RT,P,H,A, QI R,QT,T,QM,A S,A R,A R, T,QT, RT, P,H,A, QI Flow Control Valve Flow Control Valve Limitorque Terry Turbine FCV-73-26 (3)

FCV-73-19 QT,A R,T,QT,RT,P,H,A, QI Flow Control Valve Flow Control Valve Limitorque Limitorque Flow Control Valve Pressure Switch Limitorque Static-0-Ring Temperature Element Scam Flow Control Valve Flow Control Valve Limitorque Limitorque Flow Control Valve Limitorque FCV-73"36 (2,3)

FCV-74"1 FCV-74-2 FCV-74-7 PS-74-8A TE-74-9 FCV-74"12 FCV-74-13 QT,A T,A,QT,QI

,T,A,QT,QI T,A,QT,QI R,T,QT,A,QI,RPN R,T,QT,A,QI,Rr N T,A,QI,QT

. T,A,QT 8-28

Appendix B

(Continued)

Equipment Descri tion Manufacturer Com onent No.

Oeficienc Pr essure Switch Pressure Switch Flow Control Valve Flow Control Valve Flow Control Valve Pressure Switch Static-0-Ring Static-0-Ring Limitorque Limitorque Limitorque Static-0-Ring Temperature Element Scam PS-74-19A TE"74-21 FCV-74-24 FCV-74-25 FCV-74-30 PS-74-31A TE-74-32 R, T,QT,A,QI,RPN R, T,QT,A,QI, RPN T,A,QI,QT T,A,QT A,T,QT R, T,QT,A,QI,RPN R, T,QT, RT, P,H,QI, A,RPN Flow Contr ol Val ve Flow Control Valve f

-Pressure Switch Temperature Element Flow Control Valve Flow Transmitter Limitorque Limitorque Static-0-Ring Scam Limitorque GEMAC FCV-74-35 FCY-74"36 PS-74"42A TE-74-43 FCV-74-47 FT-74-50 T,A,QT,QI T,A,QT RT, P, H,A,QI,RPN R,T,QT,RT,P,H,A, QI,RPN T,A,QT,QI R,T,QT,RT,P,H,A, RPS Pressure Transmitter GEMAC PT-74-51 R,T,QT,RT,P,A, QI,RPN Flow Control Valve Flow Control Valve Flow Control Valve Flow Control Valve Flow Transmitter Limitorque Limitorque Limitorque Limitorque GEMAC FCV"74"52 FCV-74-53 FCY"74-60 (1,3)

FCV"74-61 FT-74-64 T,QT,A,QI QT,QI,A QT,A QT,A R,T,QT,RT,P,H,A, QI,RPN Pressure Transmitter GEMAC PT-74-65 R,T,QT,RT,P,A,H; QI,RPN B-29

0'

Appendix B

(Continued)

Equipment Descri tion Flow Control Valve Flow Control Valve Flow Transmitter Manufacturer Limitorque Limitorque GEMAC Com onent No.

FCV-74-66 FCV-74-67 FT-74"07 Deficienc T,QT,A,QI T,QT,A,QI R,T,QT,RT,P,H,A, QI,RPN Flow Control Valve Flow Control Valve Flow Control Valve Temperature Element Limitorque Limitorque Limitorque Calimatic Temperature Element Cal imatic Temperature Element Calimatic Pressure Transmitter GEMAC Temperature Element Calimatic FCV-74-74 FCV"74-75 FCV-74-77 TE-74-81 TE-74-82

'TE"74"83 TE"74"84 PT-74-94 T,A,QT T,A,QT T,A,QT R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T',QT,RT,P,H,A, QI,RPN Flow Control Valve Flow Control Valve Limitorque Limitorque FCV-74-98 (1,2)

FCV"74-99 (1,2)

T,QT,A T,QT,A Flow Solenoid Valve Flow Solenoid Valve Flow Solenoid Valve Moisture Element

'oi'sture Element ASCO ASCO ASCO Unknown Unknown Flow Control Valve

'imitorque Flow Solenoid Valve ASCO FSV-74"102 FSV"74-103 FSV-74-119 FSV-74-120 ME-74-137A ME-74-137B R,T,QT,RT,P,H;A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T;QT,RT,P,H,A FCV-74"101 (1,2)

T,QT,A B-'30

0'

Appendix 8

(Continued)

Equipment Oescri tion Moisture Indicator Switch Manufacturer Unknown Com onent No.

MIS-74" 137A Deficienc R,T,QT,RT,P,H,A Moisture Indicator Unknown Switch Pump Motor General Electric Pump Motor General Electric Pump Motor General Electric Pump Aotor General Electric Flow Indicator Switch Barton t

v Flow Indicator Switch Barton MIS-74-1378 RHR Pump Motor 1A (1)

RHR Pump Motor 1B (1)

RHR Pump Motor 1C (1)

RHR Pump Motor 10 (1)

FIS-74"50 FIS-74-64 R,T,QT,RT,P,H,A QT,A,M,QI QT,A,M,QI QT,A,M,QI QT,A,M,QI T,QT,A)QI,RPN R,T,QT,RT,P,H,A, QI,RPN Flow Control Valve Flow Control Valve Flow Control Valve Flow Control Valve Flow Control Valve Flow Control Valve

.Flow Control Valve Flow Control Valve Flow Control Valve Flow Control Valve Flow Control Valve Limitorque Limitorque Limitorque Limitorque Limitorque Limitorque Limitorque Limitorque Limitorque Limitorque Unknown FCV"74-100 FCV-74-96 (2)

FCV-74-48 FCV-74-97(2)

FCV-74-57 FCV-74-58 FCV-74"59 FCV"74-71 FCV-74"72 FCV-74"73 FCY"74-78 QT,A QT,T,A T,QT,A,QI QT,T,A QT,A QT,A QT,A QT,A QT,A QT,A R,T,QT,RT,P,H,A B-31

1

Appendix 8

(Continued)

Equipment Descri tion Flow Transmitter Temperature Transmitter Switch Temperature Transmitter Switch Flow Control Valve Flow Control Valve Flow Control Val ve Flow Control Val ve Temperature Element Manufacturer GEMAC Unknown Unknown Unknown Unknown Unknown Unknown Scam Com onent No.

FT"74-56 TTS-74-136A TTS-74-1368 FCV-74"102 FCV-74-103

'CV-74" 119 FCV-74-120 TE-74-95A Oeficienc R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A, RPN,QI Temperature Element Scam Temperature Element Scam Temperatyre Element Scam Temperature Element Scam Temperature Element Scam Temperature Element Scam

=Temperature Element Scam TE-74-958 TE-74-95C TE"74-95D TE-74-95E TE-74-95F TE-74-95G TE-74-95H R,T,QT,RT,P,H,A, RPN,QI R,T,QT,RT,P,H,A, RPN,QI R,T,QT,RT,P,H,A, RPN,QI R,T,QT,RT,P,H,A, RPN,QI R,T,QT,RT,P,H,A; RPN,QI R,T,QT,RT,P,H,A, RPN,QI R,T,QT,RT,P)H,A, RPN,QI Pressure Switch Pressure Switch Pressure Switch Static-0-Ring Static-0-Ring Static-0-Ring'S-74-88 PS-74-198 PS-,74-318 R,T,QT,A,RPN,QI R, T,QT,A, RPN,QI

~

R, T,QT,A,RPN,QI'-32

0 Appendix B

(Continued)

Equ',pment Descri tion Pressure Switch Flow Control Valve Flow Control Valve Pressure Switch Flow Control Valve Flow Control Valve Flow Indicator Valve Flow Control Valve Flow Contr ol Valve Pressure Switch Flow Control Valve Pressure Differential Indicator Switch Flow Control Valve Pressure Switch Manufacturer Static-0-Ring Limitorque Limitorque Mercoid Limitorque Limitorque Barton Limitorque Limitorque Unknown Limitorque Barton Limitorque Mercoid Com onent No.

PS-74-428 FCV"75-2 FCV-74-60 (2)

PS"75-7 FCV-75-9 FCV"75-11 FIS-75-21 (1,3)

FCV"75-22 FCY"75-23 PS-75-24 FCV"75-25 PDIS-75-28 FCV-75-30 PS-75-35 Deficienc R,QT,T,A,RPN,QI T,A,QT,QI QT,A',T,QT,RT,P,H,A, QI,RPN T,A,QT,QI T,A,QT,QI T,QT,A,RPS T,A,QT,QI QT,A R,T,QT,RT,P,H,A T,A,QT R,A,QT,QI QT,A R,T,QT,RT,P,H,A, QI,RPN Flow Control Valve Pressure Switch Limitorque Mercoid Pressure Transmitter Unknown Flow Transmitter GEMAC Flow Indicator Switch Barton Flow Control Valve Limitorque FCV-75-37 FCV-75"39 PS-75-44 PT-75-48 FT"75-49 (1,3)

F IS-75-49 T,A,QT T,A,QT R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN B-33

0

APPENDIX 8 (Continued)

Equipment Descri tion Flow Control Valve Flow Control Valve Pressure Switch Flow Control Valve Pr essure Differential Indicato~ Switch Manufacturer Limitorque Limitorque Unknown Limitorque Barton FCV-75-50 FCV-75-51 PS-75-52 (1,3)

FCV-75-53 R,A,QT R,A,QT R,T,QT,RT,P,H,A QT,A PDIS"75"56 (1,3)

R,A,QT,QI Com onent No.

Deficienc Flow Solenoid Valve ASCO FSY"75-57 R,T,QT,RT,P,H,A, QI,RPN Flow Solenoid Va'1ve ASCO FSV-75"58 (1,2)

."".,T,QT,RT,P,H,A, "I,RPN Moisture Indicator f

Switch t

Moisture Element Moisture Indicator Switch Moisture Element Pressure Switch Unknown Unknown Unknown Unknown Mercoid MIS-75-70A ME-75-70A MIS-75-708 ME-75-70B PS-75-16

-',T,QT,RT,P,H,A r",T,QT,RT,P,H,A R,T,QT,RT,P,H,A R.,T,QT,RT,P,H,A R,T,QT,RT,P,H,A, QI, RPN Pressure Transmitter Unknown Flow Transmitter GEMAC PT"75-20 (1,3)

FT-75-21 (1,3)

R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A, RPS Pump Motor Pump Motor Pump Motor General Electric General Electric General Electric Core Spray Pump Motor 1A (1)

Core Spray Pump Motor 1B (1)

Core Spray Pump Motor 1C (1)

QT,A QT,A QT,A General Electric Core Spray Pump Motor 1D (1)

QT;A 8-34

Appendix B

(Continued)

Equipment Oescri tion Temperature Transmitter Switch l1anufacturer Unknown Com onent No.

TTS-75-69A Oeficienc R,T;QT,RT,P,H,A Temperature Transmitter Switch Unknown Flow Solenoid Valve ASCO Hydrogen Analyzer Hydrogen Analyzer

~

Hydrogen Analyzer Hydrogen Analyzer Hydrogen Analyzer Hydrogen Analyzer Hydrogen Analyzer General Electric General Electric General Electric General Electric General Electric General Electric General Electric Flow Solenoid Valve ASCO Flow Solenoid Valve Unknown Flow Solenoid Valve Unknown Flow Solenoid Valve ASCO TTS-75-69B FSV-75-71 FSV-75" 72 FSV-75-58 (3)

FSV-75-57 (3)

H E-76-37 2

H E-76-37A 2

H E"76-38 2

H E-76"38A 2

H E"76-39 2

H E-76-39A 2

H E-76-40 2

FS"76-37A (1,3)

R, T,QT,RT,P,H,A R,T,QT,RT,P,H,A R, T,QT, RT, P,H,A R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A R,T)QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A, RPS Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO FSV-76"37B (1,3)

FSV-76-39A (1,2)

FSV"76-39B (1,2)

FSV-76-40A (1,2)

FSV-76-40B (1,2)

R, T,QT, RT, P,H,A, RPS R,T,QT,RT,P,H,A, RPS R,T,QT,RT,P,H,A, RPS R,T,QT,RT)P)H,A, RPS R,T,QT,RT,P,H,A, RPS B-35

0 0

Appendix B

(Continued)

Equipment Descriotion Manufacturer Com onent No.

Deficienc Flow Solenoid Valve Unknown Flow Solenoid Valve Unknown Flow Solenoid Yalve Unknown Flow Solenoid Valve Unknown Flow Solenoid Valve Unknown Flow Solenoid Valve ASCO FSV"76-41A (1,3)

FSV-76-41B (1,3)

R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A FSV"76-3SA (1)

FSV"76-3SB (1)

FSV-76-42A (1)

R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A

',T,QT,RT,P,H,A, RPS FSV-76-43A (1,2)

R, T, QT, RT, P, H, A Flow Solenoid Valve ASCO r

Flow Solenoid Valve ASCO Flow Control Valve NAMCO Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO Flow Solenoid Flow Solenoid Flow Solenoid Valve Unknown Valve Unknown Valve Unknown Flow Solenoid Valve Unknown Flow Solenoid Valve Unknown Flow Solenoid Yalve NAMCO Flow Control Val ve NAMCO Flow Control Yalve NAMCO Flow Solenoid Valve Unknown FSV"76-42B (1)

FSV-76-17 FCV-76-17 (1,2)

FSV-76-18 FSV"76-19 FSV-76"24 FSY-76-44A FSV-76-44B FSV-76-50 FSV-76-61 FSV"76-52 FSV-76-62 FSY-76-aS FSV-76-19 FCV"76-24 R,T,QT,RT,P,H,A, RPS

,QT,A R,T,QT,RT,P,H,A, QI,RPN QT,A QT,A QT,A R,T,RT,P,H,A,QT R,T,QT,RT,P,H)A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI, RPN R,T,QT,RT,P)H,A, QI,RPN 8-36

0

Appendix B

(Continued)

Equipment Descri tion Level Indicator Switch Level Indicator Switch Level Switch Level Switch Level Indicator Switch Level Indicator Switch Flow Control Valve Flow Control Valve Flow Control Valve Level Switch Level Switch Manufacturer Gems Gems Auto Con Auto Con Gems Gems Unknown Unknown Unknown Auto Con Auto Con Com onent No.

LI5-77-1A L IS-77" 1B LS-77-BA LS-77-88 LIS-77-14A LIS-77-14B FCV-77"17B FCV-77-178 LS-77-17A LS-77-17A LS-77-178 Oeficienc R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI, RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,,A, QI, RPN R,T,QT,RT,P,H,A, QI, RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A, RPN,QI R;T,QT,RT,P,H,A, RPN,QI Temperature Element Thermo Elect Temperature Indicator Unknown Switch TE-77-17 TIS"77-17 R,T,QT,RT,P,H,A, RPN,QI R,T,QT,RT,P,H,A l'evel Switch Lovel Switch

~

l.evel Switch Pump Motor Unknown Unknown Unknown General Electric LS-77-25A LS-77-25E LS-77-25F R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A Reactor Building R,T,QT,RT,P,H,A, Equipment. Drain RPS Sump Pump A (1)

B-37

Appendix 8

(Continued)

Equipment Descri tion Level Transmitter Level Transmitter Level Transmitter Level Transmitter Manufacturer Gems Gems Gems Gems Com onent No.

LT-77-1A LT-77-18 LT-77-14A LT-77-148 Deficienc R,T,QT,R,P,H,A, RPN,QI R, T,QT,R,P,H,A, RPN,QI R,T,QT,R,P,H,A, RPN,QI R,T,QT,RT,P,H.,A, QI,RPN Temperature Element Thermo Elect Flow Solenoid Valve Versa Flow Solenoid Valve Versa I'

Flow Solenoid Valve Versa Flow Solenoid Valve Versa TE-77-14 FSV"77"2A FSV-77" 28 FSV-77-15A FSV"77"158 R,Q,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI, RPN R,T,QT,RT,P,H,A, QI, RPN Level Switch Level Switch Level Switch Level Switch Level Switch Flow Control Valve Unknown Unknown ASCO ASCO ASCO Micro Switch LS-77-258 LS-77-25C FSV-77-17 (1)

FSV-77-17 (2)

FSV-77"17 (3)

FCV-77-2A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A:

R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A, QI,RPN

'Flow Control Valve Micro Switch FCV-77-28 R,Q,QT,RT,P,H,A, QI,RPN Level Switch Unknown LS-77-250 FCV;77-15A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A, QI,RPN 8-38

0

0 Appendix B

(Continued)

Equipment Descri tion Manufacturer Com onent No.

Deficienc Flew Control Valve Micro Switch FCV-77-15B R,T,QT,RT,P,H,A, QI,RPN Level Switch Level Switch Level Switch Meletron Meletron Meletron LS-78-1 LS"78-1B LS-78-1C R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A.

QI,RPN R,T,QT,RT,P,H,A, QI,RPN Level Switch Level Switch Level Switch Level Switch Level Switch Level Switch F',ow Control Valve Flow Control Valve Flow Control Valve Flow Control Valve Flow Control Valve Flow Control Valve Barksdale Bar ksdale r

Barksdale Barksdale Unknown Unknown Rotork Rotork Rotork Rotor k Rotork Rotor k Flow Control Valve

'Rotork Flow Control Valve Flow Control Valve Rotork Target Rock Flow Solenoid Valve Target Rock Flow Solenoid Valve Target Rock Target Rock LS-78" 1D LS-78-1E LS-78-1F LS-78-1G LS-78-2A LS-78"2B FCV-78-61 FCV"78-62 FCV-78-63 FCV-78"64 FCV"78-65 FCV-78-66 FCV-78-67 FCV-78-68 FSV-84-BA (1,2)

FSV-84-8B FSV"84-BC FSV"84-8D R,QT,QM,A R,QT,QM,A" R,QT,QM,A R,QT,QM,A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A A,QT,T A,QT,T A,QT,T A,QT,T A,QT,T A,QT,T A,QT,T A,QT,T QT,A QT,A QT,A QT,A B-39

Appendix B

(Continued)

Equipment Oescri tion Flow Transmitter Flow Transmitter Manufacturer GEMAC Com onent No.

FT-84-19 FT-84-20 Deficienc R,T,QT,RT,P,H,A, RPS R,T,QT,Rr,P,H,A, QI,RPN Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO FSV"84-20 FSY-84"19 (2,3)

R,T,QT,RT,P,H,A,

gI, RPN R,T,QT,RT,P,H,A,

<QI, RPN Flow Modifier Pressure Switch'ressure Switch Flow Modifier Y

Fischer Controls FM-84-20B Custom Components PS-84-21 Custom Components PS-84-22 Fischer Controls FM-84-19B B,T,QT,RT,P,H,A) qI,RPN B,T,QT,RT,P,H,A, (QI, RPN R,T,QT,RT,P,H,A, qI,RPN R, T,QT, RT, P,H, A)

QI,RPN Flow Control Valve Unknown Flow Solenoid Valve Unknown FCV-84-19 FCV-84-20 B,T,QT,RT,P,H,A R,T,QT,RT,P,H,A Flow Modifier Flow Control Valve Flow Control Valve Unknown Unknown Flow Solenoid Valve ASCO FCV-84-19 FCV-84-20 FSV-84-20 Fischer Controls FM-84-19B R,T,QT,RT,P,H,A, QI, RPN R,T,QT,RT,P,H,A R, T,QT, RT, P,H,A R,T,QT,RT;P,H,A, QI,RPN Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO FS-84-20 FS-85-39A R, T,QT, RT, P,H,A, QI,RPN R, T,QT, RT, P,H,A, QI,RPN B-40

Appendix B

(Continued) quipment Descri tion Manufacturer Com onent No.

Oeficienc Flow Solenoid Valve ASCO FS"85"39B R,T,QT,RT,P,H,A, QI,RPN Level Switch Level Switch Level Switch Level Switch Level Switch Robertshaw Robertshaw Robertshaw Robertshaw Robertshaw LS-85-45A LS"85-45B LS-85-45C LS-85-450 LS-85-45E R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI, RPN R, T,QT, RT, P,H,A, QI, RPN Flow Control Valve NAMCO Flow Control Valve NAMCO Flow Control Valve NAMCO Flow Control Valve Micro Switch Flow Control Valve Micro Switch FCV-85"37C FCV-85-37A.

FCV"85-37B FCV-85-39A FCV-85-39B R,T,QT,RT,P,H,A, QI, RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R, T,QT, RT, P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN Primary El'ement Primary El ement Radiation Monitor Radiation Monitor Radiation Monitor Unknown Unknown Nuclear Measure-ments Corp.

Nuclear Measure-ments Corp.

Nuclear Measure-ments Cor p.

RE-90-133 RE-90-134

,RE-90-134A (1)

RE-90-133A (2)

RE-90-131A R,T,QT,RT,P,H,A R,T,QT,RT,P,H,A A,QT,T,H,R,QI A,QT,T,H,R,QI A,QT,T,H,R,RPN, QI B-41

'4 ~

jj

Appendix 8 (Continued)

Equipment Oescri tion Ion Chamber Ion Chamber Ion Chamber Ion Chamber Manufacturer Com onent No.

General Electric RE-90-136 General El ectric RE-90-137 General Electric RE-90-138 General Electric RE-90-139 Deficienc R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN',T,QT,RT,P,H.,A, QI,RPN Sensor 8 Converter General Electric RE-90-140 R,T,QT,RT,P)H,A, QI,RPN Sensor 8 Converter Sensor 5, Converter

'I

)

Sensor 8 Converter General Electri c RE-90-141 General Electric RE-90-142 General Electric RE-90-143 R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN Flo~'ontrol Valve Flow Control Valve Flow Control Valve Flow Control Valve Flow Control Valve Radiation Monitor Unknown Unknown Unknown Unknown Unknown Nuclear Heasure-ments Corp.

FCV-90-254A FCV-90-2548 R,Q,QT,RT,P,H,A R,Q,QT,RT,P,M,A FCV-90"2578 RE-90-133A R,T,QT,RT,P,M,A A,QT,T,H,R,QI, RPN FCV-90"255 (1,2)

R,T,QT,RT,P)H,A FCY-'90-257A (1,2)

R,T,QT,RT,P,H,A Fission Product Monitor Fission Product Nonitor General Electric RE-90-273A General Electric RE-90-2738 R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN 8-42

Appendix 8 (Continued) qu)pment Descri tion Reactor Building Equ.'pment Drain Sump Pump A

Reactor Building Floor Drain Sump Pump A

Reactor Building Floor Drain Sump Pump 8

Terminal Blocks Penetrations Penetrations Con"rol Switches Ic Cable

'(COAX, TRIAX, signal XLPE)

General Electric Pump Motor General Electric Pump Motor General Electric (Numerous}

Physical Science Cor p.

(Numerous)

General Electric (Numerous}

General Electric 8 Cutler Hammer (Numerous)

Times Wire 8

Cable, Brand
Rex, Gray Bar, Boston Insulated Wire, Okonite,

Dearborn Wire,

Alpha Wire,

Belden, Consolidated, Rockbestos, Annconda (Numerous)

Manufacturer Com onent No.

General Electric Pump Motor Deficienc R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, RPS R,T,QT,RT,P,H,A, RPS T,QT,RT,P,H,A R,T,QT,P,H,A R,T,QT,RT,P,H,A R,T,QT,P,H,A T,QT,P,H,A Cable (silicone rubber insulation)

Annaconda (Numerous)

P,QM,A 8-43

II

0 Appendix B

(Continued) quipment Descri tion Cable (CP,CPO,CPJS,PXJ)

Cable (PNN, PJJ, PN, PJ)

Manufacturer Sumitomo Shoji, Plastic Wire 8 Cable, Collyer,

Okonite, Triangle Conduit
Cable, Rome,
Essex, PWC,
Simplex, General
Cable, Rockbestos Plastic Wire 8 Cable, Brand Rex,
Rome, Cyprus, American Insulated
Wire, General
Cable, Tamaqua, PWC Com onent No.

(Numerous)

PT"67-19 (2)

Deficienc P,R,QM,A T,P,R,A,QM R, T,QT,RT,P,H,A, RPN,QI Pressure Transmitter Bailey F 1 ow Contr ol Val ve Limitorque Flow Control Val ve Limitorque Pressure Transmitter Bailey

'ressure Transmitter Bailey PT-67-21 (2)

FCV-67-22 (2)

FCV"67-23 (2)

PT-67-2C (3)

PT-67-25 (3)

R,T,QT,RT,P,H,A, RPN,QI QT,A R, T,RT,P,H,QI,RPN R,T,QT,RT,P,H,A, QI,RPN R,T,QT,RT,P,H,A, QI,RPN Flow Control Valve Flow Control Valve Limitorque Limitorque FCV"67-26 (3)

QT,A FCV-67-27 (3) ', T,RT,P,A,QI,RPN

'Pump Motor General Electric RHR Pump Motor 2A QT,A,M,QI

0 Appendix B

(Con'tinued)

~quspment Oescriation Pump Motor Pump Motor Pump Motor Pump Motor Pump Motor Pump Motor Pump Motor Pump Motor General Electric RHR Pump Motor 3A QT,A,H,QI General Electric RHR Pump Motor 3B QT,A,M,QI General Electric RHR Pump Motor 3C QT,A,M,QI General Electric RHR Pump Motor 30 QT,A,M,QI General Electric QT,A Core Spray Pump Motor 2A Core Spray Pump Motor 2B Core Spray Pump Motor 2C Core Spray Pump Motor 2D Core Spray Pump Motor 3A Core Spray Pump Motor 3B Core Spray Pump Motor 3C Core Spray Pump Motor 3D.

FSV-85-35A (1,2)

'General Electric QT,A Pump Motor Pump Motor General Electric QT,A QT,A General Electric Pump Motor General Electric Pump Motor QT,A QT,A General Electric Pu'p Hotor General Electric Pump Motor QT,A General Electric Pua;p Motor QT,A R,T,QT,RT,P,H,A,

'PN,QI Flow Solenoid Valve ASCO Manufactur er Com onent No.

Oeficienc General Electric RHR Pump Motor 2B QT,A,M,QI GeneraI Electric RHR Pump Motor 2C QT,A,M,QI General Electric RHR Pump Motor 20 QT,A,M,QI Flow Solenoid Valve ASCO Flow Solenoid Valve ASCO FSV"85-35B (1,2)

FSV-85-37A (1,2)

R,T,QT,RT)P,H,A, RPN,QI R,T,QT,RT,P,H,A, RPN,QI

0 LEGEND:

APPENDIX C

Equipment Considered Acceptable or Conditionally Acceptable (Category 4.3)

Designation for Deficienc R-T-

QT-RT "

p-H-

CS-A-

S" M"I-QM-EXN "

r SEN-QI-RPS-Radiation Temperature Qualification time Required time Pressure Humidity Chemical spray Material aging evaluation, replacement

schedule, ongoing equipment surveillance Submergence Margin HELB evaluation outside containment not completed Qualification method RPN Equipment relocation or replac~.ent, adequate schedule not provided Exempted equipment justification inadequate Separate effects qualification justification inadequate Qualification information being developed Equipment relocation or replacement schedule provided Equipment Descri tion Manufacturer Com onent No.

Deficienc Penetrations

, Physical Science Corp.

(Numerous)

Penetrations Junction Boxes Zone Switch Zone Switch Zone Switch Zone Switch Zone Switch

~Unknown NAMCO NAMCO.

NAMCO NAMCO NAMCO NAMCO (Numerous)

AT-1-26(QTY6)

AT-1-27(QTY6)

AT-1-37(QTY6)

AT-1-38(QTY6)

AT-1-51(QTY6)

AT-1-52(QTY6)

General Electric (Numerous)

0

~!

Appendix C

(Continued) quipment Descri tion Manufacturer Com onent No.

Deficienc Flow Solenoid Valve Valcor Flow Solenoid Valve Valcor Flow Solenoid Valve Flow Solenoid Valve Flow Solenoid Valve Valcor Valcor Valcor Flow Flow Flow Solenoid Valve Valcor Solenoid Valve Valcor Solenoid Valve Valcor Flow Solenoid Valve Val cor Flow Solenoid Valve Yalcor Flow Solenoid Valve Valcor Flow Solenoid Valve Valcor Flow Solenoid Valve Valcor FSV-76"56 FSV-76-58 FSV-76-60 FSV-76"66 FSV-76-68 FSY-76-49 FSV-76"51 FSV-76-55 FSV"76-57 FSV-76-59 FSV-76-63 FSV-76-65 FSV-76"67 A

A C-2

I

APPENOIX 0 Safety-Related Systems List~

Function System Emergency Reactor Shutdown Engineered Safeguards Actuation Reactor Protection Standby Liquid Control Control Rod Orive Containment. Isol ation Main Steam Feedwater Control Air Sampling Reactor Recirculation Reactor Water Cleanup Reactor Building Closed Cooling Water Reactor Core Isolation Cooling Residual Heat Removal Core Spray Containment Inerting Radwaste Containment Air Oilution Primary Containment Reactor Core Cooling High Pressure Coolant Injection Low Pressure Coolant Injection (RHR)

Core Spray Automatic Oepressurization.

Reactor Core Isolation Cooling Containment Heat Removal Residual Heat Removal Emergency Equipment Cooling Water Core Residual Heat Removal'ain Steam Residual Heat Removal Reactor Core Isolation Cooling Residual Heat Removal Cooling Water

'The NRC staff recognized that there are differences in nomenclature of

.systems because of plant vintage and engineering design; consequently,

~ some systems performing identical or similar functions may have different names.

In tnose instances it was necessary to verify the system(s) function w",.h the responsible IE regional reviewer and/or the Licensee.

0-1

APPENDIX D (Continued)

Function System Core Residual Heat Removal Reactor Building Closed Cooling Water Raw Cooling Water Prevention of Significant Release of Radioactive Material to Environment Standby Gas Treatment Containment Air Dilution Radwaste Reactor Water Cleanup Radiation Monitoring Neutron Monitoring Containment Inerting Sampling Supoorting Systems Auxiliary Power Air Conditioning Ventilating Fuel Oil 0-2

gag '44 l981