EBASCO S:.RWiCM INCORPORA~i-SPECI."aCA-ION EBASCO 202 73 KLZCiRICAL COhiML SYSicM, BOARDS

& CABINETS PART OF SPECIFICATION EBASCO 216-73Th DGScL KNGRi. - <KhcRATOR UN T AND COhTROLIP~c FOR NUCLEAR PO~

PLAh S

PRO~iCT IDENTFRICATION NO.

CAR Sn K-ll egQgQ4Q QgQQQ4 PQR ADOG~

PDR 8

M@0 S Q4'Q j+CQg SPRATQ C'PICA IQg E"-ASC0 202 E PiRluQ. CGb"iiOL SYSs 5, BOARDS

& CAZIhc.iS COh

.VZS Scope I

S tandards Ex"epticas By Se~z 44~4 et De =

oas General Construct" oa Features Control Board Construction Control Cabinets Control Board Cable Entrance Coatrol Cab'aet Cable Entrance Addit'oaal Physical Design Details Lighting, Heat" ng Aad Veatila ica Requirements Geaezal Control Philosophy Con zol C'rcu'ts

-Control Buses

& Circuit Protection Electrical Control Vir'ng La@ Level Signal (Electronic) QiMg Ground Bus I.mic Buses Namep lates Electrical Iadicat'ag And Recording Inst~ats Relays Integratiag dieters Aad Analog Traasducezs Control Switches And Pushbut oas Indicating Lamps Annunciator Electronic Eau'pmear Pcver Circuits Earthquake Loads Painting Clean'ng Factory Assembly Aad Tests Contract Info~ ion

& Dza~ ags By Seller Specific Requirements P aran" ash 1

2 3

4 5

6.7 8

e 9

10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 Pa e

1 1

1 1

3 4

5 6

6

~ 6 7

8 9

U.

11

~

.14 16 16 16 17 17 18 20 21 25 26 29 30 30 31 32 37 Figure 1 - Typical Miring Diagram

Spe='.'ca

'on ~asco 202-73 Electrical Control Systems, Soards

& Cabinets Pro)ect Identification Ho.

1.

S COPX This Spec fication covers the structural, electrica'nd elect-o"..'c requ'-e-ments for controllina si.ste~

such as coal and ash hanc"ng, soot bl~int

<<J de ne ali=ers, vater treatment, rad'catt ve waste treatment, e ".

Spec'1 prospect requireants are ind'cated in Section 32.

~

~

01 The control assembly shall include all featu"es

."nd devices reauired to provide a complete, coordinated, se'conta'ned svstem except as spec'.1-cally limited by the ma)or equipment Specificatio".

.02 h11 components shall faction in a satisfactory manner ~~thin the'r rated capacitv unde" the spec'fied se~ce conditions.

'.03 Xt is not the intent to snec'fy details of design and constwction except vhere necessary to establ'ish perfo~

ance requ'remen s, nor is it intended to set zorth those pe" or ance requirements vhich are adequately specified bv applicable standards.

2 SYAÃDA~SS Unless otherwise specified, this eou'pment shall meet the reauirerants of applicable published OSHA, NKC, hNSI, Zi~, KA and ISA Stancards vith preference in order oz list~mg.

3 KXC~ XONS SY S~r.

~R Whenever equipment proposed by Seller does not conform to th's Specifica-tion in any respect, such exceptions r~t be clearly stated bv Seller in his proposal.

'.fo exceptions are allcMed unless spec'fically granted by Purchaser in ~ting.

.01 Any materials, ecuipment, or methods Mhich Seller considers sune.

or oz'referable to those soecif'ed herein for the purposes in ended, may be offered for Purchaser's consideration.

4 ~

D~"NI.TONS guipznt cove ed by this Specifica ion is defined as rollvsz 1

Spec'cat'on Ebasco 202-73 Elec rical Control System, Boards

& Cabinets

~

~ 1 Project Identification No.

4 ~

D:"ZNITIONS (Conc')

. 01.

C and ma.".

~

on ro oazd is a

ee-stand'n sheet outdoor construction v"'-x may be e'".

1 ce, an=

.m e ".er adooz or e

e tne aua or d.plex.

a - h dual control board sh~l have the rear narel hinaed for access to the inte or u."Bess Purchaser s soace l'-'ra-tions requ're fzont access only.

b - h duplex control board shall have access doors a-both ends u"less Purchaser's space Limitations require access ac one end only.

~

~

.02 h Control Cabinet is a vali-mounted cabinet vi h front ac ave n wearing a"c or manual control devices m-=.ted there-on, or is a free standinp cabinet vith rear access doors.

ei~

.03 Ins Instruments, controls and pzotec ive devices are def-'ned as ~ollovs, a - hn insolvent is any device used to measu=e, indicate or record a physical quar.tity.

b - h control any device ~dually oz autowtically actuated~

and used foz ope ation of plant equipment.

h pro ective device is one used to automa icallr d'sconnect sto oz limi P

m t ope ation of plant equipment to li 'uaae 4

under fault con i" ons or vhen operating parameters exceed pzeset limits.

An annunciator is a device vhich vill ind'cate a source of trouble bv ill&natw~g one of the group of vindevs, equ=pped vith approx mate word"ng, and by s -ultaneously enezgitinc a

common audible device.

h control system is a system of elec

'carcuits contain~me instruments, controls, protective devices and @nunc atozs, or any combination of these, supp~'ed from Purchaser's pmer andlor control sources and involved in th'e operat'on of a pa.t or al'f the major equioment or system of Paragraph l.

Spe ification Ebasco 202-73 Electrical Control System, Scares 6 Cabinets Project identification Hoi 5

Kh~~~

CQ'lSTRUCT ION 7~ ~7ZS It is intended that Se>>er utiL'ze standardi=ed units anc standari=ed asse-"es of equipment ~afar as these vill~et the rec. 'reme=ts o=

pover pL~

use.

The nature of such se~

ce re" -'res heavy d'y co ponents requiring en = - or no a='ntenance during forty years of pro-jected L~fe.

.01 The control boards anc/or cabine s sha'1 prov'de en'onmental protec-tion for equipment mounted in or on them.

Protection sha

be a=for"e" age+ ns t e a.~ Dust b - Dripping vater (re i~ outdoor) c - H~dity, condensation d - Insects, rodents e - High and/or lov temperatu=es as specified f - Vibration of suppor ing structure g '- Earthquake vhen specified (usually nuclear requirement)

.02 Control board md cab'net enclosures shall be constructed o

spec'a"v

selected, smooth f'nished sheet steel, vith suffic'ent struc-ural re'n=crcemen to insure 'a plane surface, to L' t vibrat'on and,to provide ~[id'w.

03 Control board and cabinet enclosures shall con orm to the fol s:in@

flatness tolerances.

Panel flatness tolerance is defined as the ~mm allovable deflection of a steel panel from a plane surface

='n cne cirection but no" both. It is furthe, required that the surface shall slope un=fo='y from the edge of the panel tcvard a point of max='~ deflection, to ra~e out vavy or vrinkled sur ace vhich does not exceed allowable deflection.

a - 'Vithin he above definition the follcr ing tolerances shall be alloved on steel panels~

Vidth Tole. ance Up to 24 In.

24 In. to 32 In.

32 In. and Up 1/16 In.

3/32 In.

1/8 In.

Spec'f'ation Ebasco 202-73 Electrical Co"trol Syst~,

Board b Cabw Pro)ect Identification Ho.

5 ~

CRURAL COYSTRU~ICN F:-~::.S (Cont'd)

~

Des g, na erial select'on, a.".d ~et~ship sha'1 be such as to result in a nea appearance outside a"d inside,

=th no velds, r'vers b'

ds

~

~

~

~

0 1

r bo t heads apparent fro-outside, and with a exter or sur aces true and snooth.

5 The completed boards and cabinets shall have ~le s-ength Oc stand, vLthou da=age, all stresses incidental o shipping, inszallat'o" c4' a

a a

~

a

~

~

s J Jat o

seismic (shen spec'ed) and short circuit forces during operation.

.06 L1 pa.s of the netal struc ure shal1 be effec ively g.ounded to the p'ound bus herein spec'f'ed, except for sw11 cabinets where deletion is autho='zed by Purchaser.

ei o

.07 The arrangene"t of ecLuipment shall in no case prevent satisfac o~

performance, and shall allcv suff"'c'ent space for prope" naintenance cr1thin the structure 'ncluding access to ter='nal block.for in ernal and ex:ernal connections.

6 C04iROL BOA%) CQ'ASTRUCT ION Control Board height shall not exceed 90 in. bless spec'ed

'n Pa:a~ann 3.8.

The Length and ~wdth shalL tjeet Purchaser's Li&tations for sh pping and installation space.

The enclosure shall be of sheet steel not less than 1/S in. thick.

.01 Indoor con rol boards shall be of KJL 12 construe ion, bless othe-Mse spec'f'ed in Paragraph-32.08

.02 Outdoor control boards shall be of K% 4 const action (-ate ight).

Front panels containing control devices shall be pr'otected by.-eatherproof access doors unless such panels are greater than three ft '" length, vhen a salk-in type of construction shall be used.

Rear panels, reeuired for access only, shall be veatherproofed.

~ 03 Outdoor control boards shall be designed so chat dr.'v'rg ra'n

sncv, sand, or other naterials shall not inter ere w=t'a'ts

~ successful ope at-'on.

The hous'ng shall be constructed and ventilated so thar, the heating effects or solar radiation viLL not produce totaL temperatures and te.Perature mes in the equipnent oeyond those alla+ed by the, app'='cab'e standards.

Spec'icati Ebasco 202-73 Electrical Control Syst~,

Eoards fi Cabinets Project Identification Ho.

8.03 CO~mOL Spi=-Z CONS~C:ION (Cont'd) 4 5

<<.S>>

Vent at ng cpe"'ngs, vhen reouired, sha'1 be prov'ded at the op ot>>o~ oc>>L

<<1 a

e

<<.OD an>>

bot om of.he enc'osure, scree"ed and ba="ed to prevent entrance of These ope"'ngs m~o sha'1 be so arranged and located as to prevent d~

to or malfu"ction of the control c" rcuits, and other condone=

s fro eater dr'pping fron above o. splashing frcnn the floor.

No openings shall be placed in the top cover of the e.clcsure bless its construction prevents the ent a"ce of dust, vater and othe". foreign a-te

.04 Heaters and/or fa.".s shall be fu...ished in indoo and outdoor enclosures.

See Paragraph lg2 and 1343 for detail recuirenents.

.05 Doors on outdoor weatherproof enc'osu>>es shall be fuU, he ght, eru'pped vith a 3 point latch and device to hold the door in fu'1 open posit.'on a@a.'nst

,06 Dust filters and filtered air pressure tvpe or sel conta'ned re-circulat'ng tvpe cooling systet: shall be provided "n dusty environment such as coal handling areas.

.07 The unde.sur ace of outdoor housings shall be cove.ed by a heavy, scaling undercoating.

.08.

Vibration insulators shall be provided chen environmental cond'tions reouire then (Paragranh 3ZN).

?CONTROL CAB h:.TS Mall mounted control cabinet he ght shall not exceed 48 in. I g.eater height is necessarv, they shall be designed for free standing floor mounting.

Indoor cont.ol cab'nets shall be of l~A 12 construct'on unless otherM'se spec'fied 'n Paragraph 32.08

.Ol Outdoor control cab'nets shall be of h~A 4 (vatertight) construction.

Paragraphs QQ through 608 also aoply.

.02 Comrcially ava'lable cabinets (eg Boff:.ann, %~A 4 nclosure) neet" ng the intent of this Specificat'on wy be used for control cab'nets.

5

Specif ication Ebasco 202-73 K cosmical Can rol System, oaards 4 Cabinets Progec Ident'ication Ho.

CO4.ROL SOAP3 C'ZLE E.'.MK Control boards shall be designed These open'ngs sha'1 Lave eas 'ly shipment prowl cong tne sana ~ie itself does.

for both top and bo:to= access a= ca'es.

removable screved on covers aske- -'"-

of envlrormen a'rotect'c" as

-he boa""

.01 u'ch open nts shall be in stric" confo~ ce m.=.

Se 'e.

s dra'=n s

Sn the locations requ'red bv Purchaser-I~

ca le open'ngs shall be sa ar.anged as to proi de the ~-~ clear f'oor and cei~ng area in the est direct path to the cabl blocks.

.02 Seller shall provide vi evavs of 0.06 sq ~"

sq ". area or each ex-equal cabinet

~

con~ect on te.'nalpoint (including spares) in both o

top and bottom of

.03 he openings shall provide d'rect path to 8e te bl shall be rou ed e

e~na

ocks, and level e groupe scca.d'ng to cable functions (paver cont-1 d 1 sig a3.) ~SO?'~.

5 (Cont'd)

.03 Outdoor boa.ds a"d cabine s sha'1 have s"a=e heate s mounted in "".e enc osure to pre'ent condensation, and to "rovice heatinz to ensure sa= s-facto..- mient te=erat e

or the operation o.

b "th electro-.~..e-'"a""

solid state components, ass=ng

-30 C tempera ure and 30 t-h w='nd.

Indoor boards and cabinets shall also be equipped ~-'. space heaters to prevent condensation du. 'ng nm-operating conditions except

@here de'e-tion is author'red bv Pv"chaser.

Space heate s shall be thermostatica'ly controlled and shal'e

~='red for connec "on to a supplv branch circuit separate from t.'iose of the Lpi:a and of the fans (if supplied)

~

These space heaters shall be ene gi ed at

~ "0 volt single phase a-c

~~

rated 1500 hyatt or less and at 208 volt three phase a-c for ratinas between U00 ed 3000 matt.

Large heaters shall be energized through a

Contactor (120 volt a-c coil) at 208 volt three phase, four v're a-c.

The heaters shall be located so that u.'ring, buses, equ.'pment and control devices ui.ll not be overheated.

Alarm thermostats for low and h'gh temperature shall be provided, except

@here delet'on is author'ted by Purchaser.

.04 Wiring for 1'bahts, receptacles,

switches, snace heaters and ans shall be run between standard outlet. boxes in electrical netallic tu"i and shall ter.enate in a )unction box for Purchase

's incon'ng cable conne ions.

.05 Lighting and heatinp shall be supplied from a Selle fu~hed 480:20&/120 vol three phase, d~ tvpe trans orner if the an end space heater load exceeds 5 kva, or direct'y at dis ribut on vol age from a built-in 120 volt distr'but on or lighting panel if total load is less than 5 kva.

Separate feeds shall be provided for L'ghts and space heaters.

.06 Seller shall provide nonautomatic molded case circuit breakers as separate master disconnec" devices for Purchaser's incorxng L'Rht'".g and heater placer supply - one for each if remotely sucplied at using vo'cage, or one in SV side of local transfonaer supplv (Paragraoh 1LQS).

12 GE?P'RAL COh sROL PHILOSOPPv Control system shall be desi+ed to operate ~~thout d'sturba..ce to controi1ed equipment during no=al and other cmditions encou.".tered nor~1'y - but infrequen ly - ir. plant operation as folio-.s:

Spec fication Ebasco 202-73 Elec=. cal Control Systems, Boa cs and Cabinets Project Identific~tion No.

Gc..i=PAL CONTROL pHILCSOp~ (Cont')

a - h-c syste voltage dip 15 percen voltage Qp caused by starting a 1azge motor fc 10 25 se cones

~

his +

1 a..ec~

the outout of other already jh4 ey4 1 0 CC motors and also w~ L>

~ ifes w tselc dip in a-c c'rcuits delved from the affected bus.

b - High and lour vcltage a-c oozier system sho.

c'rcu'ts and subseouent fault endearing causing loss of a-c pmer for 0.5 seconds.

c Hlackout start-up from limited i"-oint paver source (Diesel generator or gas turb-ne) vhich may cause 30-40 percent voltage reduc ion for 10-30 seconds.

d - Short circuits in a-c or d-c control c'rcu's reducing the source bus voltage to zero for 0.02 seconds breake or fuse clearing time.

,01 hll circuits shall be engineered to be productio cont'".uous, ie:

loss of circuit voltage shall not result in plant shutdoMn unless per-sonnel safety or irreparable eauipment damage vould resu't.

Such loss shall othe=aise leave controlled eeuipment in an "as is" oz "stay-put" condition.

Such occurrences shall be alar ed from a souzce not. re'ated to the a fected circuits.

13.

CON.ROL CIR~iTS The following three control voltage sources shall be used:

a - 125 Volt d-c 2 vize, ungrounded unless othe. vase specified.

b - 120 Volt single phase, 2 size (one leg g ounded) 60 Hertz i"te. ~tible a-c.

(Intezzuptible:

@hen no.alpcMez sou-'ces are lost, a-c contro'ave is lost. It mav be restored in about 30 seconds

o. co"..ven-'coal a-d in 10 seconcs foz nuclear e'ts.

These ci.cui p

are usually combination star:ez ccn=z":" -'-s

Spec fica 'on Ebasco 202-73 Elect. 'al Ccntro1 Sys tea, 3oards b Cabinets Prospect dent'f'cation Ho.

13., COB:ROL CIRC ITS (Cont'd) c - Same rat ng as

'b except the svste=. wv be grounded or I~

~ I u grounded but <<.='".term" 'b'.

(0".='nrem:ntible: a-c ava'1able at all tiws bv i"verter fed.rcm a ba" e

Fe a..e

- a.ter plant loss of a>>c, usuallv ava'lahle for abou 30 Mnutes).

.01 Aoplication of sources:

control c'rcuit voltage causes or indirectlv, da=.age to major "a and c" shall be used

<<Ihen the loss o

shut-dna of tNe generating wit, direc 'r enu'pment o" enda.".acts nerso""el safem.

~I~ II b

alte,ate source may be used when continuiry is not reouired and vhen

+ 10-L5 percent voltage va" at'on is acceptable.

.02 The. individual control circuit supnlies sha11 be arranged to fo11o<<I the paver supplv division of controlled eouioment (ie:

fa a f d ~"om ev diffferent hid% voltage r~itc'".gears sha'1 have the'= separate control logics supplied from the corresponding smitch@ear control sources).

.03 System Voltage, frequency spread and required inter~ting capac'ties villbe as follows:.

The cononen s (relavs, indicatins lights I cortacts to operate properlv, without overheating du-.'ng the vithout limiting the t'me or above

o. be3.o<<I nor-.@l The interrupt'ng devices shall be able to interruot themselves the short c" rcuit currents listed belm:

etc) shall be selected condi 'ons L'sted bela:

status of ooerat'on.

<<- thout da=age to a - 125 volt nominal d<<c 90-140 Volts Short circuit: ~~

amperes b - 120 volt nominal a-c 105-135 Volts 60 bert

+ 2 Bert@

Short circuit:

5000 (inte~ptib3e) amoeres rm sym c - 120 volt nominal a-c 115-125 Volts 60 Rer-z +.5 He z

Shor" circuit:

5000 (1t1in te mp tible) at=eres.w svm 10

Specificat'on Eh asco 202-73 Electzica Ccv t c

SvstM h Boards

& Cabinets Pro]ect identif'cation Ho.

13.

CON ?O'. RC S (Cont')

izansient voltages -.he co<<.ol c'zcuits of fu=..ished ecui-~nt s."a '

\\

not generate a-c oz d-c volta"e surges ~re tie<<1000 v"'ts (.=s for a-c)

"= o"e taiczosecond duration.

The control c'rc. its and components sha'1 be a'"'e accept voltage su=yes of 4000 volts

( m for a-c) of one microsecond curat'on froQl any source

~

14.

CO'.

ROL BUSES

& CTBCU T PRO ECTION The control pave supply buses shall extend throughout he lenrnh of the struc u=e and shall be metal enc3osed in conduit oz bv neans of duct o.

ba~ers in ozder to isolate the= fz"m all other volta

"ts.

.01 One two pole 600 volt s tch or non-autorztic disco".".ecting air circuit bzeake" shall be prov'ded foz connec ing Purchaser's a-c oz d-c control supp3y to contzol bus.

.02 The control branch circuits shall be protected bv caanetic trip only, two pole air c"rcuit bzeakezs (single pole is needed vhen one leg is g ounded) rated 240 volt a-c and 250 volt d-c for a-c and d-c apnlications zesnec ively.

The inte~pting capac'y shall be in accordance Wth Paragraph

~~

The circu't breakers shall be eas'ly anc safely access'ble.

Each arcuit breaker shall be fully identified for equip~nt supnlied.

The trip zatints of the breakers shall be tvice the inrush of al1 devices in the circ'hen energi"ed simultaneously at the specified m mm vol arne in Paragraph Q"3.

These breakers shal3. provide short circuit protection o=ly.

.03 Potential circu-'ts, for inst@mentation, and for nete='ng, shall each be protected by 250 volt, 6 anoere fuses loca ed 'n such a posit'on -".at thev are easily and safely accessible.

Each fuse and each set of fuses shall be fully identified foz potent'al o~gin and eau.'p en" supp3ded.

15.

EL CTRZCAl CO'i"i'ROL VZRZHG Seller shall provide control ~ring and ter='nation facilities '" accordance vith the follav~wg requirements:

.Oh Witted shall be 600 volt st=ended ooooer sv'-:thboatd v':a.

T>pe 5 d, odth hear,eoast

=a and.front tasmtant insniataon.

.02 V'~ng sha'1 be free of abrasions a~8 tooK nazks M"im= bend ng radius of 1j4 in.

dell i='-.'np shall be to preven sagrin" and breakage ca sed bv vib-ation d

vires

<<~v be '" a bund e to fac'=a=e t:a"inc cf v'zes and shal'ave a

a"e""a o'v s"""ce~

S pe at'n Gas co 202-73 Electrica'cn. cl System Boards 6 Cabinets aroj ect Identic'ation Ho.

15.

V'=~URIAH. COb.ROL 4 P BC'Cont'd)

.03 size shall. be of adecuate rating for the extent to be ca.

d.

All.

vires vithin a panel or wwit shall be cont auous, ie:

no soliciae is er-Mtted.

A 1 current trans or er and circu breaker tz o c'-'ts sra'~

use noth

".g, seller than ho.

14 Avg v're.

On other c'remits vhere ~~

cur.ent does not exceed 5 amperes, such as a"nunc'ator or indicatiao Lm circu ts, Ho.

15 Avg v're may be used.

Mire sine md ~ula-ion selectica shall conform vith the folloving:.no overheating os the concuctoz itsel~

or of Wulation doge to adjacent conductor shall occu vhea current tra"s-fozmez secondary conduc. ors ca~

one hundred awczes for one second Fo-4 I~

~

vires assoc ated vith d<<c and a-c con rol circuits, the c treat value is 10,000 amperes and 5000 amperes rm sym respect'vely and the t'mc internal is 0.025 second.

.04 Mheze cables must be ca~ed across hinges to devices momted on

doors, ex=ra flexible, 19 strand conductors shall be used..hc vire bundle s all be carried betveea a cia~

on the door and one on the fixed port'oa of the board or cabinet.

These shall be adjaceat to the hinee aad shall oe at least one ft apart vith door in full open position. If the clos are 2 ft.

further apaw than 2 ft, a suppor for the cable shall be provided eve e ezy

.05 Terminal boards shall be provided for all controls, inst=meats, aanunciato s, meters and relays rcouiring exteznal coanec ion.

They shalL be rated aot less than 25 adheres, 600 volts.

They sha'1 be provided vith barrier, marking strins and te=~aal screvs.

Each te

-nal poia-shall be marked vith the desig ations shcwn on Seller's viriag d'agzams.

The preferred ternal block is General Elect c Catalog Ho. CR-15lB2.

Each ternal board shall have aot less than

~elve points.

Tvo poiats out of each tvelve shall be spares.

.06 Seller s a~ring shall be term='natcd oa tez-'nal boa ds or equin.eat I

vith flanged spade, or indented spade type iasulatioa trip'ng insulated tezmiaals equivaleat to Aircraft-Ferin Produc s pre-insulated Diamond Grip or Thomas and 'Betts self-insulated Sta-Ron vith insulaticn g in.

Ring type tez='nals of approved type v 11 be acceptable.

Box cl~ or saddle clamp ter='nals are aot acceptable.

Ho solder or "push-on" oz'quick" type conaec ors shall be used in conaec-tioa vith any vi 'ng, except soldez type v'll be acceptable for indica-ng Light zcsistom, Parag.aph 24CQ.

0 Specificatioa Ebasco 202-?3 Elect. ca'ontrol Systems,

'Boards 6 Cabinets Progec-Idea 'fication Ho.

15.

E.:-~iiRIC~~ CQhiV PP 3C'Con 'd)

<<t

.07 Purchaser s control ~~~ay vill be '.lo.

12 or Sc.

16 Avg straac c

co oer cab'es copper cables te."aated vi"" te.='mals s'-'lzr to those described above

~

~

CZ secoadav ca"le vill be 10 Avg.

Purchaser v='U, fu..ish all '"-

connect rg control ca'"les except those desc='bed

'". Paragraph 16,E.

Termiaa~a fo" Purchaser's ex=canal coaaections sha'1 be arra"ged fo.

consecutive connection of conductors vith'a oae cable.

Oae ex=canal vire vill be connected to each outgoing te.'aal point.

.08 In Seller's 'ateraal veering, not more than oae vi.c shaQ be conncc ed o oae terminal block point except vne e ~~~er vires a"e

necaed, in vh'ch case tvo vires mav be coaacc ed for '"=e=..al v'rin

.09 I accidental short ci cuitiag of ce a'n vires ca" resu't ia ~l-functioa of e~uipmcat, such as closing or tr'pping o.

a breaker, these vires shall aot be te.'mated oa adjacent te='aal board points.

'.10 Provision shall be made for conveniently estabUshiaa the contiaui~

of all control circuits.

Mire ma kers oa both ends of a vire vi ", desiraa-tions in accordance c-,'th Seller's viriag diagrza shall be proviced if spec'fied (Paragraph 3~&8}.

.11 Each instrLwat transformer (CT or PT} circui shall be a..aaged as a four vire circui vith Phases ly 2y 3)

N from top to bottom, le t to right aad front to back.

Required groundiag of each circUt shall be bv connect'oa to the gr uad

bus, as sham on Figure 3o. 1.

The inst-.meat t ansforme circuits shall be vired fro= the 'neo=.'ag te='a board through a current or potent'al or current and pote.. ial test device such as General Electric Company Taupe PK-2 or Vestiaghouse Corpora ioa;>~

or approved equal.

Test plugs for each type of test svitch sha" 1 be fu..shed.

The tes svitches shall be v'red to fac'litatc ia se~ce testing, a"d ca'ibrat-ing of inst~meats only.

Rhea circuits are associated v'th dravout ~e relays or vatthour meters Meir integral test devices satisfy the above reouiremeat.

.12 icz~aal boards shall be momted verticallv be

~e a racevays eac'"siar Seller's aad Pure.'".aser's

~bring.

Selle,.'s viriaz shall be co<<netted to oa side of the te.'aa'oard, the other side shall be reserved for P -"-.aser's ex".e..al connectiors

~

~

~

~

Specat'o-..

Ebasco 202-73 ELec.ical Control Systcas, Boards a" d Cabinets Project Identification No.

15.12 KE~::.~ COB.."-3L 4~iRL~G (Coat'd) hdequate space shall be prodded on both s" des of thc te='aa'onnecting vires ad for v're

.-burke s.

To allov for strippiat of inco='ag cables, te.'aa'

=as sha

be loca:ed a r "'-.-

avay fro= cable cx-raaces e'.er at the top or bottom.

bio ass

~or beaw 'a

~

ar

.13 The raccvavs for elec rical control ~%ring and lov level s" r.".aL vi shall not coa a=n vires assoc'aced vith internal coatrol pr er dist Duticn w~ 4 ~

lighting and heaten, and pover vi 'ag for any voltage.

Separate racevavs shall be provided for above systems, and for Pu-chaser's viriag o

.14 Future instruaent or reLay positions, or unused inst-.zen space oa the front or rear of the panels shall be kept clea of i='=ag to faci'-'tate addition of devices vithout rev ~ag.

.L5 Xf aaay u"ifo= nodules east, it is prefe..ed to use round or rectangular plug connectors properly polarixed md meting the folloviag requirements:

a - Electrical characteristics (voltage, insu1atioa resistance, flashovcr, cu. eat caroling capac" ty) shaL>> be eauaL to or better than the cable connec ed to it.

b - Contacts shall 'be gold plated copper alloys, the vires shall be attached by cr'ming.

c - The, bodv of conaector shall seal against the e trance of anisture (rain) and dust, and also shall resist the corrosive agents found in eavirons.

d - The connectors shall be vibrat'oa and shock proof.

e - The ~ge of connectors proposed requires Purchaser's approval.

.16 For control vi ag requirer~ats on prefabricated assmb" es rcfe to Paragraph 26.19.

16.

IAK L~~

SACRAL (E =C %0ÃZC) ViRMG Seller shall provide the required electrostatic aa8 ragaetic sh'elfin'to reduce noise for Lov level signal c='rcui w.

Both vi-.'na and inst~-.eats Soec' ca."=.. Ebasco 20~-73 Electrical Co"..tzol Systems, Boards a".d Ca"'nets Project Identification No.

16.

L(ÃfL~ STG':-:-

R HTC)

'4 R~G (Cont'd)

(Coat pliers) assoc ated ~~-4 lc level sig.".a'o provide suc'.". shieldiag.

Selle sha'1 ass~

"se "-

~

~ -

-~e presence o

3~~v everest 60 oe=z a-c three f" above the board.

~ 01 Shielded, tais ed, 300 volt rated Inst-.~ea at oa, C

=..icatioa and Ccaputer Transducer cable shall be used as descz'3e" h

shall be 7

s. a be strand copper of 'a'=..~ No.

18 Avt, '-adulated vith heat moisture zesis ant insulation.

Shi'eldiag to be provided by 1.7 t"'1 coa<<

tinuous cooper mylar tape aad No.

18 Avg uncoated co"pez drain ~ ze in coatact vith shield.

To insula e the sh'eld from groped, 30 t='1 min'pproved f'ze-resistant jacket shall be provided.

The lay of t +st sha" not exceed tvo iaches.

~ 02 Po~~

C ~+al, t. ar al cables aad other maeci~- ed saecia'b' es s.,a'eet Seller s requirements, and operate satisfactorily ia

<<".e s

y ia

.e spec ied

.03 Mirin 'n circuits foz povez suoply to transducezs aad awlifiers for signal transmission shall be su'tably fused or other-~me ciesiaaed to Limit short circui currents and ~ employ vire havina su'table voltage ratiag and of a size consistent vith the reouiremeat o

th vhich itt is installed.

An approved means for detect-oa of blrz oz ope"..-

circuited fuses must be provided.

,04 TXnterconaec.ioas

'betveea electronic modules shall be made vith co'oz-on a tor " "le ha'g te.inalconnectors su"ject to approval by the Puzchasez.

.05

%heen aay of the cable types desc=bed ia foregoing Paragraphs 1<C1 and 16D2 aze r

'" d eaui.ed to in ercoanect the board or cabinet jz=h remote assemblies, Seller shall supply these cables in lengths de e.'ned bv Pur-

chaser, together vith all connector-plug assu&lies.

The above cables shall be suitable for above and underground insta'lat" oa in dry or vet environment and ia cable trays.

,06 Zf circui grounding is at the board, or cab'aet,

<<he drain v'ze (shiel ) shall be vired to a ter nal point adjacent to othe s ia the same cable.

Gromding of the shield shall be similar to inst.ament tzar-forme ground'ng (See Paraeraph 15.11) if required in th's location.

Specification Ebasco 202-73 Zlectri=a'-..tro'ystems,.

Boards 6 Cabinets Prospect Identif'at'on No.

ll.

GROVE) BCS A copper gromd bus shal'e prov'ded excel for small cab'nets uhere de'e-t'on is authori ed by Pur".aser.

The ~xi=.dinensio".s, shall no.

be 'ess than 1/4 x 1 in.

Ground bus features sha

~corporate the following,:

.OL BoI.ted )oints, splices, and taps (except control and inst-.=ent circ'-

ground connections) to Ne ground bus shall be made ~=5 not less than r~o bolts each.

.02 The g.ound bus shall ex=end throughout the structu.e and shalI. be bolted, brazed, or fielded to the framework of each uc'nd of each panel, side sheet etc.

-tD Buddy YA or approved ecual compression type te

.'"a's shall be pro-vided at each end of the ground bus for connection to Purchase

's No.

2 or 2/0 Aug ground cable.

.04 For grounding of inst~ent transformer secondaries refer to Paragraph I5.11, for lou level signal v'rmg to Paragraph 1Q6 05 120 Volt a-c control c'rcuits, orirLnating (tra"sfoaer-supplied) within the board or cabinet, shall have one leg (neutra')

g ounded a

one point only.

Can ol circuits originatina outside the board or cabinet, shall not be grounded by Seller.

.06 Lighting and space heater circu'ts shall. be g.ounded as described above.

18

~C BCSM Y~c buses, if reauired, shall be of smooth edged mate al approved bv Purchaser.

Attachment shall be bv concealed scr~s o

studs e ess alte=ate method of attachment has been approved by Purchaser.

All bus angeles shal'e mitered.

~~c devices shall be of a thickness matchi g that of the mi-'c buses

~

19 ~

HA~~M; S Each board and devices cm and in it shall have a na.e""ate encraved uith vording in acccrcance vi h Seller's ice='-ed lists.

':~~e" lares shall aao be furnished for all re'ays, control s~itches, controrcuit fuses and

Spec' cat'n

"=bas co 202-73

~

Electrical Control Svstems, Poa".ds 4 Cabinets Pro)ect Identification No.

19.

5':M.- S (Cont'd) aux'"ary prier ACS's.

Na=~plates shall be black laminated plastic v.'th vhite lettering fastened v'th rust resmtant steel sel'-ta"."ing sere.-s.

SeLer sha 1 proi"'de a Mt of insc='ptions for such nameoiates cor P "-

chase s approval.

20.

~:-C RTC'~

'RTC'..TNG A.'D %~ORB NG TNS:RL~.S Zlectrical indicat'ng and recording instments sh~~l confo to the follov-ing requiremenv:

.01 Seller supplied electrical ind'"ating inst~ents, unless spec ~ied othervise, shall be flush mounted vith a f}ange on the front of name} 4-1/4 in.

square (270 degree scale) and/or 2-1/4 x 6 in. hor son al/vert ca'dg vise

.~nts vith accuracy of 1 pe cent and 1.5 percent respec -'ve'y sh'ould be used.

Parallax free vhite backaround, black numeral dials sha'1 be pr~

vide d.

.02 A-c instruments and recorders shall, unless othe.~se soecif'ed, be fox'oeration from instrument transformers ha~'ng nominal 5 amoere or 120 volt secondaries.

.03 Suitable tvpes of inst~nts are General Electric Tvoes Q-40, AD-40, and 180, and these shall be funished vhenever poss-'ble, or cor.espond'=g Vest~~ghouse or I~= Tvnes.

21.

P~MYS LN~GRA F< ~~S AND ANALOG TR.'RSDUCK..S Relavs Integrating meters and analog transducers sha'1 confo.

to the fo"ov-ing requirements:

01'rotect"ve relays, vatthour meters and varhour mete s shall be rectangular in shape, and seW-flush mounted in d avout tvoe. cases vi h self-contained test'nE facilities.

Reauired surface-mounted re'ays shall have dust-t'ht covers.

.02 Vatt-hour and varhour meters shall be of the induc ion disc tvpe, equipped vith potent'al indicating l~s and, unless othervise speci ed, shall be for one ation from instrument t ansformers hzv'ng no-.'nal 5 ~ere or 120 volt secondaries.

.03 All protec ve relays shall, unless othe-.-'se spec'fied, be fo ope at'cn from inst~mt trans

o. ers having nominal 5 ampere or 120 vc't secondaries z".8 fro= stancard 60-ce.'tat'on bat re~.

Specif'ca ion Ebasco 202-73 Electrical Control Sys

ems, Boards 6 Cabinets Pro) e ct !den ' ication Ho, 21.

R MYS !b~~~~. ~TWG iF

.6 A.iD 4%ALOC.~~.SDQC:..9 (Cont'd) 1

.04 All vol age relays shall have suf icient the al capacity tinuous energi=ation.

D-c voltage relays nv'wlcy economy'c-"g res.'s:"rs if necessa~.

All d-c relays non'nally rated 125 vc'-s she'1 be

".e=-

capable of continuous ene giaation at, L40 volts.

.05 Protect ve relavs shall action, opera.'an indicators.

con ac s of protect"ve relays other.

be equipped with ezte=aLLy rese" pos't've The time delzv and instantaneous shall be electrically isolated fro each

.06 Tsnere Pu=chaser's space H=~tations do not pe. 't the use of a s'cele board or cab'net Large enough to contain all the necessary re'ays, a re cte

cabinet, confo.'ng to this Specification, may be furnished to contain -"e additional reLays.

.07 Analog transducers for remote use or indiciation of values of press e,

flow, position, etc.

as requ'red for Purchaser's cowuter and/or control

systems, shall be offset zero type, if possible, and ~~M be sub]ect to Purchaser's approval.

.08 Suitable ~~es of aux'Liary relavs are as follows, md these ~es shall be used whenever possible'.

General Electric Tvpes HCA and iD'A, CR: Westinghouse Type SG and HQ:

Agastat Tyoes

2412, 2422, 2414 and 2424, ALLe S:adley i3uLLe in 70A H,

,700 '.i and 700 M~; Square D Class 8501, Types G0-40, CN-80 and GO-40-GD and Cutler-B~r Type B.

22~

CONTROL S~I Q'.vM A%) PCS~L~iiONS Control scCtches shall conform to the foLLowing requirements:

~ 01 Switches shall be, of rotary ~e, having mclosed contacts vhich are accessible by the removal of cover or covers.

.02 Ymufacturer's switch escutcheon o1ates shall be clearly marked to show operating position.

Positive actions causing flow o merge or fl."d, increasing level of action, shall be clockvise (as seen from fron ) 'ppcs'te actions shall be counterclodcvise.

03 Control switches shall be rated 600 vol=s and 20 amperes cont.'nucus current.

The recuired nurse" o

positio~a, maintained ~d mc~ntary ccn:act requ're=ents shaLL be dere.'ned by Seer.

Se ler sha

a'sc dere=.'ne

-'-.e

Speci~tea ion Ebasco 202-73 Elcctrica1 Cont ro Sys tens Soards L Cabinets Pro< ec Identification Ho.

22.03 CD'....ROL 5-ITC".-.ES Peg PUSHY;:.F.:5 (C t'd) recuircd seri c '

ries cod

..a

'on o

con ac s

o provicc r. ".ches ope-a" e" at

~ a S'a e"

o he pe 's 'hie n.emptying. acing.

Continuous cur-e-~

ca.ried by con.act shall be less

".an SO pe cent o

rated value.

Control tches shall be Genera'1ect~c Co a"y Type 53. or Purchaser's aw proved alternately Control s-itches shaQ have pistol p'p ha"d3.es; irstwwnt and con rol circuit selector switches shall have round, knurled handles.

.04 Synchroniaing svitchcs shall have naincained con acts and shall be operated bv means of a keyed removable oval handle co~n to a'1 synchro"..'"-

ing s'tches on the control board.

.05 In lieu of contro'atches, heavy duty oil tight pushbutton co"tact blocks vith gloved hand opera ors nay be used, prov'ded they eeet the 600 vol-continuous and in e upt'ng current requirements.

Such mitches shall be,General Elect c Company Type W2940 Q, or Pur-chaser approved alternate.

.06 Pushbuttors shall be selec cd to natch the indicating lights v"th

~hich thev " b he vi be assoc a.ed.

~ccrever this recuirenent does not apply, heavy duty oil tight buttons shall bc, used.

.07 Pushbuttons, se1ector sr'tchcs ud control s-~ "ches shall be as follcars or Purchaser approved alternate'.

a>> Pushbuttons:

General Electric - Types CR2940V Cenco Elec r c - Coact Type 404 b - IllmInatcd Pushbuttons (When Specified):

Minneapolis Honeyve& 2C200 or Purchaser approved.

c <<Control and Selec or Stitches:

Ceneral Elec ric - Types 53'.f, CR29400 Cenco Electric - Compact Type 404

Spec'f'cation Ebasco 202-73 lect cal Control System Boards k Cabinets Prospect Ident'~icaticn No.

23.

WDICATING LA'.PS Indicating 3'ghts shall be of the lm'vat age, lm voltage w. es, vith se" ara=e'y mounted res 'ster for use on both 320 volt a-c a.d '25 v"I d-c c'-"u'ts.

L'ghts sha 1 co-or to the follaving recuire=ents:

.01 Indicat~wg L~gha shall be su'table for single hole panel mo~ting and shall have lenses or caps of approp-.'ate color and of dc=ad shape for mac.mum visabiL'ty.

Lenses and lans shalL be front removable v'shout the use o

tools.

.02 Resistors shall be. rated 2500 ohm, 55 vatt (free ai ) and shaM be stacked horizontally, not more than four-deep, preferably on a ver 'cal su race.

Conductors soldered to the. resistor lugs shall have ~wulatina s eeves Mhich securely g ip the insulation and co=lete3y cover the solde ed )oint.

.03 Ind'cating light shall be made up of the follwi.ng compone..ts.

No others Wll be aoproved.

a - Indicating Light Socket:

C~neral Elec ric - Type ~03HC or CR104C116 Dialco - Type 134-5030 b - Lamp:

Ho. 387, 28 Volt, SC midget flanged base c - Resistor:

Ohmite - Catalog No. F523 Dale, - Catalog No. HL-55 Vard Leonard - Catalog Ho. PÃ-22 IRC - Catalog No.

FR>t-22 Clarostat - Catalog No. V14ZT

.04 Application of lens colors:

(Lights "On" for)

+ Red:

Elmer of energy, process fluid, (full open valve), etc

  • Green.

No flar of ene gy, process flu"'d, ( u 1y closed valve) etc t

White'.

Control c'rcu't per-er available, or relav co1 supe

.isory 'L'ght ASe.:

D sagreement v th prei~ously se ec:ed and abno.ml co"..d' o-a"-a'e" C

~ ~ 4 4

a Spec'f'cat on z.fiasco 202-73 Elec:-.'a'ontrol System, Soazds

& Cab'nets Pro5ect Identification No.

23.

VEDIC'T&C LA~S (Cont')

.05 Locatio" of Lifts (Front Vitv):

a - Creen ad Red light assoc'ate8

~~th a circ.': break z

control svitch shall be above the s.-'t""., gree" o" the left, red on Mght s'de.

If an ~ez L'.ght is spec'f'ed it shall be between green and zed lighm.

b - When associa ed c:ith star.-stop (ooen-shut foz valve) pushbuttons, the az=~".gement shaLL be s~'laz to above Paragraph 2305~ foz ho~-ontal conf'uzation.

Foz vertical configuration from top to bottom the prefe=ed arrangement is either of the follos~ng:

Red Light Creen Light, Start (Open Valve) Pushbutton Stop (Shu Valve) Pushbutton Red Light Start (Open Valve) Pushbut" on Stop (Shut Valve) Pushbutton Green Li@t When integ al nameplates identi y contro'evices, no separate nameplates are needed for associated lights.

24.

hk>uNCIATOR When speci ied, Seller shall furnish and mow-..

electro-me haical or soL'd state annunciator system(s):

they shall be complete arith tzoub'e contacts if Seller

~w required to furnish remote devices.

Pure'.".asez <="'u>h cabling beveen annuciatoz and trouble contacts.

The svstem shall consist of'he foll+ ng:

Eouioment Description Pazaazaoh No.

a - Leap cab~met b - Power supplies *.

c - Log1c cabinet

  • d - Flasher *

~01

.02

.03

~ 04

~ ~

Purchaser s pze ezence is to ha=e these svste=~

mou.".ted '" 'a cab ne

Specation

~ozsco 202-73 Electrical Control System Boards S Cabinets Project Identification Ho.

Eouioment Des c. iption Paraoraoh

~'o.

e - Horn

.05 f Set of operating and testing pushb ut"cns

.06 g - Crowd detection, ala~ng and testing system *

.07 h - Requ'red g.omding to board or cabinet i - Viring from annmciator te ~nels to board or cabinet ternal boa.d for Purchaser's external connections

.58 5 - Cooling equ"'pment if needed

-'bsence or it is preferred

.10

.01 The lamp cabinet shall co..s's of an arrav of one in. by 1-1/2 in. or 3/4 in. translucent

~andovs iCth approor'ate enaravina.

Too lights in paraU.el shall be used -n each Wndmr:

The bulb shall be the same as descried in Paragraph 2&3.

Location ident' ca on of annunc'a or uindoMs on drawings is to be alpha-numeric in tMo charac em.

The f'"is a let er Mhich ind'ates the column:

"A" is at the le t, end, in front view.

The second character is a neer uhich indicates the roe:

"1" is on top.

The arrangement of related alarms shall be from too to botto.=.

The arrange-ment requires Purchaser's approval.

The ~ndm:s shall pe.'tsuffit'ent light diffusion to observe a "steady" lit vindou by one 1'Rht from 30 f-aith external imping ng illt-'nation of approx mately 100 ft-candles.

.02 Each annunciator system shall operate at 125 volts d-c or 120 vol s a<<c, supplied fro= its ot:n inverters from Purchaser's u" grounded 125 volt d-c pcxrer supply; th's arrangement is requ'd to prov.oe electrical isolation from Purchaser's d-c supply.

  • Purchaser's preference is to have these syste~

motored in lamp cab inct.

Spec'ficacion Kbasco 202-73 Electrical Control Systems, Boards E Cabinets Prospect Ideati ication No.

2<.02 u>UNCThTOR (Cont'd)

Each sQcty point main system(s) v'll have one separate 1"5 volt (nominal) d-c supply from Purchase s d-c d'stribut" on syst=..he aaa'=.c=ator shall opera e vichou overheating or diaaished functions bccveea 90-140 volts for inde n'tc time.

Sellers viriag vhic" is clcctrica"y aa ex-tension of this 125 v d-c system shall be ungrounded.

Each tveaty point subsystem shall have an isolated (elec rically iadepeaocnt) pover supply for its logic, lamps etc.

This unit sha'1 be the plug-ia,~ie solid state inverter.

he output side. of the irve. er sha'1 be u"grounded.

The systems shall contain su=Re protection against 4000 volt, 1 r'crosecond surges generated by Purchaser's devices on the d-c svs em, aad shall not generate extraneous frequencies.

The pove supplies of each subsystem shall be fused separately to peart de-eaergi"a ion of a subsystem for trouble shootiag or ma'acena" ~.

.03 The logic cabinet shall con ain all elec romechaaical relays aad/or sol" d state cards needed for 'the operation of the system vithin the voltage boundaries listed ia tMs Paragraph.

Solid state devices shall be ope able in the a%icnt cond'tions of this cabinet.

The cards shall aot varp because, of hcac or hucidi~.

Like cards shall be iasc.

able ia like slots only.

Slots shall be ar.anged to prcc'ude contac" vith adjacent cards during card movement.

The concac s shall be ao fer=ous, gold plated and provide contact pressure needed for satis=ac ory operation during shocks and vibration.

hnnmciacor system operating sequence is to be:

No.

Seouence Trouble Contact Lm. s Somme 1

Normal hlarm hcknovledge Trouble Clears Reset Normal hbnorma1 hbaozmal

~

Nor~

Normal Off Flash Steady Steady 0cc Off On Ofc Off Off 2

Normal hlarm Clears Before hckaovlcdge hcknovledgc Reset Normal hbnozmal Normal Normal Nor~1 Off Flash Steadv Steady 0cc Off On On Ofc Occ 3

Test Prov'des Lam Test 23

Spe&fication Ebasco 202-73 Electrical Con rol Systems, Boards

& Cab'nets Prop ect Identification No.

24.03 Ah>GNCXATOR (Cont'd)

The log' shall provide 125 volt (no nal) d-c or 120 vo'-c across trouble contacts.

The trouble contac s shall be no m'ly open or closed.

Convezsio to accept the opposite type shall be s >le, - such as i".se ion o

a screw..

Each alarm poin" shall be equ'pped w

h cne electrically isclated

~~"

volt d-c, 0.05 amoezes rated alarm retrans-'ssion contact Mh'ch w'1} be closed from the incept'on of trouble until the ann~aciatoz is reset by the reset pushbutton.

'These contacts (zoo wires per con act) shall be wired to terminal boards for Purchase

's ex:ernal ccnmections.

.04 One flasher shall be provided for each ma='n system.

ne f'ashe shall be supplied from the incom'ng annunciator ~in syste d-c supplv.

.05 One horn of different sold shall be prov ded for each ma"'n syste One electrically isolated contact, closed when alarm 's sodded shall be prov ded for Purchase

's exceznal connec ion.

Power supply shall be the same as in Paragraph

.04.

The horn shall be eauipped with a cu -out switch co"..nected in series

~Cth the Acicnowledge pushbut ton.

.06 Seller shall furnish the following pushbuttons (Refer to Pa.agzaph 22fPa).

Acknowledge Reset Test Ground Test These'buttons shall be mounted in a convenient location on the board between four and five ft above the opera ing floor or on the bench board sec ion if board of such design is employed.

The buttons shall operate all subsystems simultaneously by electrically isolated contact.

.07 Each subsystem shall have a ground detection syste which covers the logic and wiring to and including the trouble contacts.

Any ground sensed on the system shall be ala~d on the 20th windar.

The ground test pushbutton shall simulate failure in the trouble contact wiringa Specifica '"

basco 202-73 Electrical Coatrol Systems, Boards 6 Cabinets Prospect Identification So.

24 ~

NWCIATOR (Con 'd)

.08 Seller sha'1 prov'de electrically indepeadea g.ouad connect'oas aeeded to the groped bus of the boazd.

.09 Wiring from the eneciator cabinet to te.=malb'ocks for Pa-1 chaser s external connec ioas sha~~

co" for= to Paragraph 15 ~

Tvo tery:iaal board points shall be prov'ded

~or each iaco"'ag trouble contact.

This is also required for alaa retzaas

'ssion contacts a

d in addition these contacts shall be separately' red vith tvo v'res each from ann~c'ator to ter 'nal board.

Internal viring vithin thc aanmciator shall utiL' pressu e type coaaectors as descrbed in Pa"agzaph 15.06.

The asulat'on sha'1 be sui able ~or amb eat temperatures in the aaamc'a ozs (hiaher te=peratuze e c, - tef'oa insulation).

~ 10 If cooling fa" (s) are required, they shall be su"pLed rom a separate d-c branch c'zcu't originating fzo= the boazd d-c control bus.

Two full capacizv Sans shall be supplied vith automa ic t~ delaved start-up of the standby vhen the zming fan fails to deL~ver aiz.

The air inlet may be taken from the board, bu the hot air shall be discharged d'rect'y to the outside.

The system shall be designed to generate Ma~-

amount of heat aad shall be so insulated as not to radiate heat into the board.

.11 Alarm philosopny., All troubles leadiag to shutdovn of eouipmeat a=d ultimately to shutdovn on the tu"bo-generator siial3. be ala ec iadividua"y.

Method of annunciation shall be that. of aanunciatiaa spec'c causes of troubles such as "Generator Differential Trip" rarhez thar. a"..a~ciat' operations of certa" a pieces of equipment. such as "Generator Bzeake Ope"."

25

~c, ~~OhEC EOl~T Where electronic assemblics are utili-ed, the comooaeats provided shall be selected to be trouble-free and perform the funct'on i"tended duz'ag the

~

40 year estimated life of the plant ia vhich they are to be installed,

Fcviar, due consideration ro enviroamntal cond'tioas desc-.'bed ia Paragraph 5

vhich they must operate.

The ope.at'ng cycle of the equipment of vh."'.".

'".ese components are a part, may veil require 1oag periods of continuous opera=

loag periods v'out operation or both.

25

0 Specification Ebasco 202-73 Elect. ca'ontrol System Boards I Cabinets Project Ident'f'ca ion Ho.

25 ~

P'C"RORIC EOUIP.

hT (Cont')

.01 Equipment pr-ered from no='nal plat operatinr.

buses

-<<LL be sub-jec ed to supply voltage var'at'ons described i" Paragraphs 4" and U.

Special considerations shall be given to the selection of se=-

conductors, capacitors ad res'stors so they vill perfow satisfac orily-under the above conditions.

Engineering of c'rc'ts and selection of equipmen" shall prevent "cascade" rype failures.

ff

~

ff

.03

~inhere cards are used to mount electronic equ "ment they sha'1 be selec ed to be rugged and free from ~arping, sve11'ng vr cracking ~der normal handling in the environment in which they <<='ll operate.

In

assembly, the cards shall be spaced and/or supported to prevent accidental contac.

between adjacent cards or the components moeted thereon shen be' vithdrze or inserted.

Vi ng or printed c" remits on ca ds shall be de-signed and installec for trouble-free serv'ce throughout the 4'fe o

the plant shen sub'ected to the flexing assoc.'ated vi h no.~lope.at'on and maintenance.

Plug;in cards shall have gold plated floating contact connectors unless an alternate is approved by the Purchaser.

1

.04 For extensive or very important electronic control sys. m, con-tinuously energized circuits which control the positions of va'ves,

dampers, etc, are unacceptable unless safeguards are aoded to prevent, malfmction upon loss of control voltage or failure of sc=e elec ronic device.

Details of such control systems must be incluced in the Selle.'s quotation and the final design must be approved by the Pu"chaser.

26.

PO'~:R CIRCGT"S Although ANSI Standa d C37-20 defines.a control scratchboard as one from vhich poser (pr'mary) c'rcuits a"'e absent, this Speccation provides for such circuits under the foll~ing conditions:

.01 Paver circt ~t voltages shall not exceed 480 volt a-c ot'50 volt d-c.

.02 Control circuits associated vith pouer circuits shall be 120 volt a<<c or 125 volt d-c, except for control c'rcuits of d-c motors starters for 250 volt service vhich shalL use 250 volt control supply from the starter.

Some a-c peered equipment may require d-c controls if lao voltage conditions prevent contactor pickup or cause inadver:ent dropout.

D-c powered circuits shall have d-c control c'rcu's.

<<25-

Specification Ebasco 202-73 Electrical Control System, Soards 6 Cabinets Propre Identification Hoi 26 PO'w. R CIRCUV'S (Cont')

l

~03 The pover circuits may cubist of the folie, a - Air c'zcuit breakers manually or elect='c~ly operated supplying various loads.

b - Combination starters cc=tzol~'ng motors, heate s, dzy type tra"sfozmers etc.

the

.04 Eac.. air c.rcuit bzeake sha'1 act as a cire'- <<zotec iv circuit controlled.

The breaker shal'fro"d b th z.".:

c rcuit protection for cable, motors and other equinment.

.05 Cizcuit breaker.s shall be manually operated, t~p-free and f tted vLQ thermal-magnetic or adjustable magnetic non-intercha..geable tr'p e'emerts, as spec'fied in Paragraph 3256 and cal.'brated on the bas's of 40'C mugient temperature outside of the control enclosure.

.06 Circuit breakezs shall have 14 000 amperes ~

in capacity at 480 volt unless listed othezvise in Paragraph 3206.

.07 Each combination starter shall ac as a short c'rcuit a d o

c rcu " an motor p o-a short circuit prctec.

ve dev.'ce its air circuit breaker shall safely remove faults occurring daestrear.

of the breaker terminals.

As a moto locked ro r z protec.ive dev'ce it shall'provide ove curre t d

to protection vhen the motor operates vith'n Ne range of 110 to an 90 percent of its rated voltage and under other abnormal cond'tions as speci ied in Paragraph 32.

.08 The air c'uit breakers shall be as desc.'bed in Paragraph 26.04.

The circuit bzeakezs may have ad)ustable magnetic tr'p or the~1 ragnetic tr'p as specif'ed in Pazagraph 3209.

.09 Each combination starter shall consist of one multipole air-c rcuit

breaker, one multipole magnetic starter vith three the

..a3. over'oad devices, bl one contzol transformer vith 120 volt secondary and d

f ocks for Puzchasez's ex-eznal connect'on, and p~ez md control viring.

( n cez ain cases vhere d-c coils are specified fo each such stazte, and for 120/208 volt systems, no control trans ozmez shall be provided)

.10 The magnetic contactozs shall be the electrically operated and held (non latching) type.

The rated voltage of the operating col.l shall be 110 volts except as noted ir. Paragraph 26.02.

The coil shall pick-up and hold cont nuously vi bout overheatiag v't'ai" the

~o variations.

(~here contac:ors are control'ed bv -e'ays

-~e have the s~e characte-.atics)

Specificat'an E'oasco 202-73 Electrical Control Systems, Boards 6 Cabinets Prospect Identifica ion No.

26.10 P04:-L C 'RCi S (Cant'd)

Ra ed P-.'~~ Supply Vol ace Volts Pr'--~

Sup ly Va'cage Pa"ee Vo' Alternating Cu=ent 120 240 480 93.5 - 126 187 - 252 374 - 504 Direc Cur. ent 125 250 9Q - 140 200 - 280

.11 D-c coils shall be desi~ed to v'thstand the 140 or 280 volt ecualiz~mg load voltage that is period'cally applied to the station batteg. M coi.l rated voltage shall be 115 or 23Q volts

.12 The dropout voltage of contac ors shall not be more than 60 percen of the rated voltage.

.13 The over'oad devices shall be the manually reset type and shaL'e selected on basis of motor data g ven in Part One of ~a)or Equipment Spec'-

ficatian (Paragraph 1).

.14 The primarv of control t-.mfozme s shall be connected vithout fusing to the load side of the air circuit breaker.

The minimum size shall be 150 volt-~eres.

One leg of the secondary shall be g ounded independently to the grand bus to facil'tate individual testing af one starte ae other 1eg sha

be fused vt,th a 250 volt rated fuse.

.15 Minimum size starte s shall be ?M SS.ze 1.

.16 Starter a&liary contacts shall be readily convertible from "a" to "b" and vice versa.

.17 Paver viring shall be capper vire rated at 600 volts vith heat, moisture and flame resistant insulat'on, Type SXS, 90'C conductor rating.

Si ing of the pceer viring shall be based on 60'C conduc o. ra ing '" ac-cordance vith Table 310-12 of the National Elec"='cal Code and in addi io-..

conside='-g de"a-~g f-c o-s co-g ouo'"g and a="'>>n- -e~e-a"u-e 2B-

<<pec "a

<<asco 2O2 73 Electrical Control Systems, Bcar~m

& Ca'='e,ts Projec Ideatificatiaa Ho.

26.17 PO'w. q CIRCVITS (Cont'd)

Pcver

~~ ring aad control sC.mg shall be ia separate racevays.

P rchaser's ex=e,.al pave blocks s..al'rovice ample Burady YA lugs.

cables vi~~ be connected d'rec lv to s arte aad te =-.als.

ihe race:ays leaching to these te="aal space for bead'ng and temnaciag these vires vith

.1B Equ'pmeat operating at more thaa 120 volt a-c or 125 vol d-c sha3~

either be designed to have no live parts exposed in service or shall be guarded by re ova" le, grounded, shee" steel barriem.

Equ'pmeat mouated in V-4 Type 1 or 12 enclosures vithin the board meets the above recuiremeat.

.29 Control and pover racevay requ'remacs for pref-bricated assemblies shall be as he.ein desc-.3ed.

On prefabricated assecml'es of vired pose.

and coa rol devices such as motors, solenoid valves, control sv'tches ex-ternal e'the to the control board or cabinet, che viring shall be in-stalled in heavy vali, rigid steel galvanized candu't.

he number of v'res in a condu't aad derzt'ng factors shall be in accordance vith the National Electrical Code.

Pledble conduit or armored cable shall not-be used.

PVC 'acketed flexile conduit may be used in lengths not ex-ceeding 3> ia.

The conduit shall be suppored on. the prefab.icated assembly and shall present a neat and vorkmaalike appearance.

27~

EAP..HOU~ LOhDS If seis'c (eaz=hauake-proof) design is specified ia Soecific ~equiremencs as Class I, Selle shall provide test data to demonstrate the adequacy of his product, to vithscand the effects of the speci ied seisc='c forces.

A product vnich comolies vith the intent of this requirement shall during aad after exposure co speci ied seismic forces:

.Ql Exhibit no undue de lect'on vhich vould preveat any co=poneac specified ia this Spec'fication from per.orang normal uninte~pted operac" on.

.02 Rave no components d~mlocated, vhich vould prevent mincerupced no.~~

operatioa (ie, fuse thrcarn out of fuse holde

', bolt to mount coatrol trans-former sheared, etc).

Maintain all components in the same operat'ng posit-'on du~ng the disturbance as they vere pr'or to it.

.04 PezU proper opera" oa of all components during the disturbance

('e if a breake" is requ'red to be closed or tripped d~ring the d'sturbance it vi13. operate as required) and noc per=~ t false ope"ation.

- 29

Specificatioa Ebasco 202-73 Elec ~~wl Control Sysieu, Boards 6 Cabinets P

og e ct Ident'cation Ho.

I 27.

EAM~HOVAR:. LOADS (Cont')

.05 All devices vhich aze ope.a-ed by elec zomechaaical forces aaaiast mec..a" cal restraiaiag forces (sp-.ag tens'on) shal'e tested vith restrair'ag force and the tests snail ve='y zequ'rements coata'aed

-" fore-go'ng Paragraohs.02,.03 and.04.

In testiag, the horizontal and vertical accelerations sha'1 be app" ed simultaneously.

The application of the combination of these tvo forces shall be repeated to s mulate horizontal acceie at'on ia as many d'rec-tiov as necessary to demons"rate adeouacy o

equipment due to i s as'~

metrv.

Floor response spectra repzesentiag earthquake iaput funct'on vill be paz= of this Specification.

These spect a cu~es are deve'oped at the equ'pmeat base levels and represent varia ioa o

accelerat'on ia mult pies of "g" v'th the natural pe

'od of vioration of the suppo

..wg stzuctureo

.06 If seisMc design is specified in Specific Requirements as Class IZ, Seller shall design equipment for the coeffic'eats indicated ia Paragraph 32 ~ 7 0 2S.

PALPATING The pa'nt shall be applied ia accordance vith Steel Structures Painting Council - Paint Application Specification No.

1 Shop, Field aad Y~ ate ance Painting.

All steel vork shall be cleaned by remov'ng all oil, dirt aad grease.

All steel vork shall then rece've a phosphatiag or Pu=chaser's approved trea ment.

Folloviag this sur ace treatment, a coat of rust-resistant primer paint shall be applied to all steel surfaces.

The dzv fi~~

thickness of the pr me coat shall be 1.0 to 2.0 Mls.

The exterior and interior oz S~=t"".-

gear Compar ~ats shall thea be given. a baked-on coat of ANSI No. 61>> Light Gray acrylic or mel~a mod'fied'alkyd paiat of 1.0 to 2.0 m'ls th ckaess.

For outdoor'nclosures exter'or f~h shall be ANSI 24 enamel.

interaa1 surfaces shall be ANSI No. 61 - Liaht Gray.

The tota'inimum drv film thickaess of prime coat plus finishing coats shall be 4-5 mils.

In 1'eu of the foregoiag paints aad thicknesses, 2 coa s of Naaufacturer's Standard paint finish may be acceptable after detailed procedure is submitted for approval and approval given.

29'LUING A tez fabrication, all manufac ur ag vaste shall be removed rom the iate='or of the unit.

All g ease, chalk, crayon, paint ma:lw and other de'e e-.'ous material shall be removed from inte='or and ex=er'or surfaces.

At t'-..e cf sh'paeat, equ'pmeat shall be clear. ias'de md out.

Specifica ion &zsco 202-73 Electrical Control Systems, Boards 6 Cabinets Prospect Identification Ho.

30.

FACTO%I ASSAY AND TESTS The cont ol beard, or cabinet shall be assail d

-Li c

Cprac-cable vith respect to shioo~wg except f s ze o~ esse&led ~its vh'ch ~ be two d f h d" ose or an

'ng pr=b-~ at the construction si e; any such L'='rations v'll be se foh

'ents of this S

~~i e se

o. 'n Spec ~ic Require-

.. s peci icat'on.

Factory tests shall be ap~l'ed to all t".

ment being furnished as follovs:

p e

0 r ae equip JNSZ l~ Standa"ds

..01 Electrical tests shall be made in accordan vi 5 li ab ce t.

app c

le current

02 Rcnstine electrical shop tests shall be made on all tests sh e on eq print ~

Thes e tests to dern s all include high potential tests on pover equi me t d

pmen't an ope at&R o

emonstrate that the equipment vill function correc ly and in accordance vith the intent of the Specificat'on.

.03 The control vir'ng tests shall include those vhich are necessary to determine that all instruments, mete s, relays, synchroscooes inst-

, etc, are correctly vired and func ion correc ly vhen ene g'ze"

.04 The control viring shall be factory tested as follovs:

a - Each circuit shall be given a continuity test.

b - Each circuit* shaM~

be given an insulation resistance test vith equipment connected, using a 1000 volt megge The insulation resistance shall be no less than 25 megohms.

c - A simulated operating test shall be conducted on each systemo

  • Except circuit cont~4ing.electronic'omponents.

and shall bea

.05 The Seller shall provide equipment, instruments tool d

oo s an pe sonnel an s all bear all expenses incidental to the foregoing tests, inclurLng replacement of damaged par s and material.

.06 Earthquake load tests shall be performed according to Para ra h 27 vhen a seeismic design is called for in Specific Requirements.

In lieu of ng o

aragrap test, certified test results for identical equ'pment and sz~ or more stringent requirements are acceptable.

h

Specification E".asco 202-73 E1ectrical Control Systems, Boa"ds

& Cab'nets Prospect Zdentification So.

31 COh RACT P.:OP~ATT03 6 DRA4DGS BY SPZ-R Seller's drawings shall c=fo.

to the foll+ ng zecuizemenrs:

01 Dzavings saic'"ted fo-Pu c."ase rs e ~et s"a'e o< sacr'c'e acope and detail to pe='t control of des'z by Purchaser.

.02 Dz~<ngs shall be to full, haL~, qua=et oz eighth scale wherever practicable.

Dimensioned or mdimemioned deta'ls no to sca'e shall be clearly identi 'ed as such.

.03 Draw&xgs to scale shall include the follmrmg:

a - Layouts of front panel and bench and rear panel, complete vith ident'f'cat'on mark'ngs fo.

M~

mounted devices and nameplate 1'st.

b - General Construe 'on sha~ng section views, detaih, sills and framing.

"a" and "b" shaLl include the follcxring:

Pcver and control systems

raceways, separation of paver equinnent from control.

The dimensioned size and location of cutou s for Puzchasez's control and pcvez cable entrances shall be identified by specif'c usage such as paver, control, low level signal, etc.

Outline, including dimensions for maintenance and operatina c1eazances.

Purchaser's

pads, surfaces needed foz mounting.

Mounting holes, foundation detaiLs.

P Suffic'ent details to demonstrate'ccessibility of ecuipment and details to assess framework construction and peel design (rig'city, accessibilig).

c - Details of eah1ems, escutcheons and nameplates (vith exact lettez ng).

d - Panel cutouts.

e - Total, ~eight of each board oz cabinet.

f - Si"e and location of ground bus.

g - Location and s""e of 'nteznal L'ghts, heate s etc (max'mum load (her)).

32

Spec'ficatioa Ebasco 2C2-73 Elec =ical Control Systems, Boards 6 Cabinets Prospect Ho.

Xdentification 31.

CP..K(C. Rr0?v~TIOH 6 DiK~. SCS P-SV.:=R (Coat'd)

.04 Electrical Dza-~ags:

%4%1 C <<

~ pA 1

l -~<

Bi o

a s,.

co.e a

e compoaea=s to o

=

ae dra!.-ants aac'iagzm.

Components mav be ideati 'ed bv Mzaufacturer and h's catalog nunbe s. If the catalog referzed does aot coataia all opezat'aF character~at cs such as in case of aa aux'lia~ relay, the, folloc~ng shall be supp&ed:

hominal voltag<<

Qperating, vo3.taRe range Hislimum nick up voltage Drop-out voltage Pick-up time at mini~ nick-uo voltage Iarush VA and pf if a-c at m5.aimxa pick-uo voltage Coat'nuous VA a-c, coil resis ance - d-c Nmbez and kind of coatacts Contac ratings:

making, continuous, iatewpting Since all na".aneters for all devices caa not be listed in this Specification, the above shall be considered as aa illustzat've example of data realized to enable Pur-chaser to aaalvse circuits !a!der va. 'ous conditions.

The 8/M shall include all electrical eauipmen

- iaclud'ng vize tvpes (no le"..g hs) mounted oa the board, aad also shall list vhether equipneat is fu..ished bv Purchase.

or Seller..

- E1eneatazv Diatzam The elementary diagrm shall contain the follerfaa".

Each device desigaatioa correlated to outline and siring diagrams.

Contac" development diagrams of control, selector, etc

itches, pushbuttons.

Each tvpe of device internal m.ring diagram:

Control poser suaplv circu't voltage, aad source requirement for u.".inter-.~atible or intermotible a-c, or d-c.

Each coa"zol c'zcuit breaker s' and trip zatiaF.

Con zol suppLy one lire diagr~

(d-c, a-c aad i=ter. otible a-c)

Spe"'f'cat'on Ebasco 202-73 Zlectrica'ontrol Systems, Boards

& Cabi Prospect Identification So.

3lo COh.PAC" 5-0=='Ã

& D.X -'.lPsS Z.

S:-

=R (C

'd)

.04 Electr'al Dra-brags:

(Coat'd)

E:e cata~ Diarrm (Cont'd)

Each a-c (d-c) coa rol branch circ '

load:

h-c inrush VA and pf, a-c cont"auous VA a-d pf (d-c amoeres) vhea no

.wily ooerat g a"d o" standby.

The above vlaues shall be calculated for the conditiom resultiag in max-'-um values (h'ghes pc,='ss ble volt-

age, max'mum n~e of dev'ces eaergised).

Total of control circuit loads for:

Idle, normal and emergency operatiar cond'om.

0 Device terminals, and ternal block po'nts to uhich devices are aired shall be shcrw and the loca ioa of these sha" be deaoted (board, cab=net re ote, etc).

The elemen ary diagram shall indicate maxi=~ pe~s-sible external conacction resistance to per'ret correct opera ioa of eouipmeat at minimum voltage Mhen such resistance is less than 403 ohms (1000 t No.

16 Aug copper cont ol cable).

If spec'al cables are.ccu'rcd for external conaec ioas (co~Mal, ewsted pairs, tu stcd and shielded),

they shall be identified.

Schc=a ic Cabl' ciao.res These diag ams shall indicate the cables to iaterconnec

boards, cabinets, etc to each othe=,

as to number of conduc ors, kind of cable etc.

The cables shall be cor.elated to the elementary diag am as noted above.

Part of this diagram shall be Seller's cable specifica-tions for shielded, tv'sted, and special copper control and thermocouple cables.

The spe,ci ications shall also consider the non-elec rical environs (temoeratu e

humidi~, above or uade g ound installat'on, presence of corrosive agcats, etc).

Lou level signal system ground'ag requirements shall also be included.

These shall be coordinated Mith other svstems (vhea not pro-vided by Seller, iafor at'oa ~11 be suoplied bv Pu=>>

chase")

as to result ia an installat-'on where the control syste= vf.ll be unaffected by external "noise" from pcxser sources defied belol-.

Purchase

's stan"ard

~

~

Snec---c --

-caste 20 -73 Elec. cal Control Syst~

Boards 6 Ca" inca Pro5ect Identification No.

31 COL aRAC4 TbrOP~JTZON 8 DKV'Nt:S F.

Sc

~

R (Cont'd)

04 Electzica'zw ngs:

(Cont'd) c - Sc.".e=.a='=

Ca.'". inz Dia"ra=a (Cont'd) low sig,al wiring consists of. No.

16 Awg leis ed pai shielded coppe oz thezmocouple cable, w'th 2 in. lay,.

coppe or alu='nu nacred mylar tape wi"4 No.

18 Awg dzain wire (grounded a" one noint only).

These cables a e in a fully enclosec solid alu;.inurn or galvanixed steal sable t-.av ror. parallelfo,r a aea'aoo 200 f to 480 vela eod 4, or

? kv cable t=avs, tvo aod cb"ee ft away, respect'velv.

These travs mav ca~

up to

,4000 rms. st azfpe es under nor~1 condit ons ano up to 60,000 rms si= amperes for one second.

d - Instrumentation, p.ocess and lopic diatzm shall indicate. the location of sensors, transducers, in-struments relative to the process, and their inter-action to serve as a basis for developing elementary diagrams.

c Board, cabinet internal ccnnection wirins diat-.ams should show icent'cat'on of devices, te.'nals and connecting wires.

The system used for designation of con zol wiz~ag shall show device identificat'on with identified ter~dais arranged in substantially correct phvsical relationship, and shall provide sufficient inforz~-

tion at each ware termination to locate the othe" termination without zecourse to routine, supple-mentary tabulations,

'or to'nfor~tion on function of wire.

Seller is solely responsible for correct-ness of the internal wiring and for proper function-ing of the equipment being furnished.

Panel wirine, drawings with identifications of devices, terminals and connecting wires shall be in accordance with Paragraph 31,04 and as illustrated in Figure l.

Diagram shall indicate wire sixes.

4 Spec'fica ion Ebasco 202-73 E 'ctrical Con<<<<ol Syst~'

Boards

& Cab'nets Prospect Identifica=~on No.

31 ~

CO%:FACT W:-OPM'-'XOh

& DRA ~GS SY SE~ZR (Con 'd)

.04 Electrical Dzavings:. (Cont'd) f ante -co,...ec

.. md exte=..al connec-icrc v'~-c d'aEza=

The diaRza sha11 s'hov clea 'y any connections to be made in field (because of shipp'zg sectional'zmg),

Seller shall shov all ex eznal cabling irfoz~tion conta'ned in Pu=chaser's Control Viring Diagrams, (funished after 'n't'al subssion of Seller' draving and diagr~)

ard space shall be resezved for additional exte=..al vi~ng infoz.action.

g - One Line Diagrams of pove c'zc -'ts and control povez circuits shall be fu=~hed.

h - Diagr~ shall be prepared in such a vay as to pro-vide for photographic reduction vithout loss of clarity.

Space betveen panel outline and dravina

margin, and betveen dw<<ices and the panel outMne shall be kept to a min='nu.

Letter'ng shall be its i. high min~.

lf

.05 T'hen Purchaser so specifies, Seller shall fuzn~mh six front ~ev and six rear viev 8 in. x 10 in. photographs of the fin'shed control board and tvo sets of 8 in. x 10 in. photographs clearly sha~-'ng inter'or i~='"g and piping as conpletely as poss-ble.

Front and rear photographs shall be made at a d'stance of approximately tvice:the length of a panel, from a point directly in zont, of its center.

a Specification impasto 202-73 Electrical Control Systems, Boards 6 Cahiaets Pro)ect Ideatification No.

a

~

32e SPECK'IC 1KQUIR~S The following spec'f ic requirnats apply to the prospect:

Equipaen Identification

.Ol Shipping L~tatioas Leag.h (in.)

hone Width (in.)

Height (in.)

.Op Cable Entrances Later Pcver Control Bus Incoming Supply Coatrol 6 Instrumentation Bt-. 'oo t

3.

1 Lm Level Signal

.03 Ambient Temperature Indoor - If Nad.arm is more than 40 C

0'utdoor (Different from Paragraph U. -03)

Maximum, F
Minimum, P

Vind.'fph at Hiaiaaxm etLperature

.04 Control 'Sou".ce Voltages 105 a - Rated Voltages Othe Than the Ones Listed ia Paragraph 13.

D-C Volts h-C Iate~t'hie Volts A-C Uniate

-. pti"'e Vcltsj GroL~Ce C-Uc.o.aced

/

~

I I

Spe c ' 'a ti.. =~as co 202-73 Kleczrica'o"trol Systems, hoards

& Cabinets Prospect Identification Ho.

32.

SPECIPIC R:OUIR~iS (Cont'd)

Equ peen Ice t ~ication

.04 Control Sov ce Vol ages (Cont'd) b>> Varia ions Other Than.

Listed in Parag aph 13.03 U-C Volts h& Inte~pt~&le Volts h-C Interruptible He~a k.-C Un'nterruptible Vol s h& Uninterruptible Hertz 05 Annunc at,oz Required on:

Voltage Supply, 125 or 250 V, d-c

~ 06 P~er Circuits

~

~

-Nord.nal Voltage Interrupting Capacity

-- System Grounded

~

~

System Ungrounded Supply Voltage Range Other than in Paragraph 26.10 Had.mum Continuous Volts Minima Continuous Volts b-hW Voltage Other Than 480 Volt

- Frequency Other Than 60 Hx Interrupt'ng Capacity 0 he Than 14,000 Azys ~ S~ at 480 Volt (26.06)

~ ~

1 Speci re ~a~c a

< as

~ ~0~ l3 Electrical Cont.al System, Boards

& Cabinets Prospect Identificat'on Noi 32.

SPECIFIC REOUIRZ~iiS (Cont 'd)

Equ'peen Ide" cat'on

.06 Pave" C'r u'ts (Cont'd) b - h-C (Cont'd)

Othe Supply Vol ace Range Than in Paragraph 26.3.0 Kudn~ Continuous Volts M~mn Continuous Volts h-C Systole:

Ung. ounded Crounded Mesa Res stance Feeder her Circuit Breakers (Paragraph 26.05)

Thermal'.-Magnetic Trip Ad)us table Magnetic Tr'p Yes Co6hination Sta..ers:

Thermal Magnetic Tr'p hCB hdgustable Magnetic Trip hCB Yes l

The folloving Starters Requi e D-C Controls:

Voltage Listing of Sta ers:

y ~

Specif'a:'oc

~=asco 202-73 Boards

& Cabinets Pro) ec Identification

, Ho.

0 32.

S. ECI:.IC R:-OK%~.~S (Cont'd)

Equipment Identification r

~

~< Seis~ c {Eanhcuaice-proof)

Requirements hpply:

Yes y Ho Class I, IX*

If Yes hpplicable Coefficients:

(Ti~ g)

Vertical Horison'tal,

.10

.08 Other Specific and Specia1 Requ'enents:

Interconnecting Cables Other Than Paragraph 16.05 Insulation - Type Insulation - Y~

Jac3cet - Type Jacket - Nils Device Ãa=.eplates Required Other Than Paragraph 39:

Standhy Ventilating Fan Pe Paragraph 1~a Requ'red:

No Mire Markers Reouired on Both Ends Paragraph l5.10

  • If Class',

resp'orle spectra curves are attached to th's Spec'ficat.'on.

S~e ici c>

2's o 20 73 Boards

& Cab'nets Progec Identificarion No.

32 ~

SPECZFEC RZOULR~TS (Cont'd)

Eq 'p~nt identification

.08 0=".er Spec'c and Spec'al Requirements:

(Cont'd)

Special Cables Required Different From Pa agraph 16.Q6 Illuminated Pushbur tons Requ red Per Paragraph 22.07b Photographs Recui.ed Per Paragraph 31.05 Control Board Height (Zi Over 90 In. - Parag aph 6)

Vibration insulators Required (Paragraph 6.08)

'hnnunciator Required (Paragraph 24)

F 09 Eaithquake Load Znfomation: w nufacturer Yes List of attachrents cover ng deta'led Seisnd.c data for equipment design and/oi test:

See Specification 216 for seismic qualification require=ents vhich supersede those requirements stated in this specification.

g 4

~

~

l Speci ficat'n Ebasco 202-7 3 Klectrical Con -o 1 Sys ms, Boa Ycs 6 Cabinets 10 2

AA 1-CA1 2-CQ 1

2 0

0

'AC S<"'ZC 2&%

ISEK NOTE 5) 1~82 I

N WBGZ t RES I5TORS )

1C ZC 2

'O 3

3C NC N

~

0 0

0 1

AS S&1 ZC A2 3

C$3C 881C~

So R

I Zr~ Zo I

o No CA 1(

C A

0 0

3 3C NC

. 0 S~AAS SC-AS 2 AAZ 2C A6 3C AT

( IND ~

1 0

0 3C 0

0 5C

'Ej 0

0 0

0 0

0 0

~

S &9 BAS 2-C5 2C RS ZC CT 3C-883 RS WSZC G:~

GZ-SAN LANP5 )

EE TC 9-SOC 1 1C 10 1-20 AC1 2 l 3-88 7

89 QQSO

~ C 611 uzc~

~3r~II I I 0

DA 08 0"5~(

CC'i So Pht Tc'-1 8

PS -Z I

So-SOo I 8

So AL ao AL 3c Ch gl 5Q C3 g

~

6~ CX Sa I CS CZ ~

qh I

1 alo 7c<

C So 20 DA 5

1 6

2 0

0 1-081 2&82

~85 6-85 DS 50 0

6 2

0 0

1-0 AS S~OCS 2-0AZ 2WCZ 5

DAS

$4N 6 84 5

1 0

0 6

2 0

0 S&BS 1-CS 2&82 2~

~85 5-86 6-83 CS-To T

8 9o S.

sa:"

CSZ DC1 o

~IDE A

GROUND SllS NOTES:

OES IGNlTIONS OR COLOP.

COOING AS ASSIGNED SY SKLI.ER

[SKE NOTE N)

CABLE XUHSER5 AS ASSI ONED EE EE'EEII EE"IIP T.. IxaIE TO CD(EN FO'R EACH CABLE.

[SEK NOTE A)

~gr rr EL X At ~

g

~ ca(ra APT l

A THE VI RING Dll iRAP( SHALL SE Ik SUFFI CI EH T SETA II. BOTH AS TO PHYSICAL ARRANC sENT OF EQJ I P..

N T lXO TQ ROUTING OF VI RE TO SERVE AS A RKCORD ORAVINC OF VIR ING OF F IN I Sr(KD SVI TCHBOARO SKCT IOl 2

TH I5 VI R'E DESI GN ATICli St STEH SHALL SE FOLLOVKD UNI.ESS ALTERH1 TI YE SY STK.'I P PO Y I0 E 5 SU FF IC I QIT I N FOR HATI CN AT E ACH TKRH I 8ll.

OF KACH VINE TO LOC

~ TK OTHL'R ~~INAL VITHOUT DK. rENOEXCE UPCN ROUTING CR FUNCTI ON OF V I RES,

3. THIS ORlvINC IS IN Tc VOKD TO IL'STRATE A HETHOO OF RKPRE SEX TATI5 CXIY ~

IT IS NOT INTL~O'O 0 IC;A K OE ~ A I LS CF DE-SI CÃ VH I CH HAY HAVE BKrEN USED FOR Ti(K PURPOSK OF I LLVSTRATI CN ~

8 ~

PJgrHASKR HiY i551G'(

CABLE XUEEerRS ANO.QO'P C"

. ".0.CF VIRES

~ ano Spa' COnCVC CO YS Vr1".n St ail Oe aC er tO h YaVirg bV Sel e.

be 0

e 51(b i55io 0

ai e'vis or~ 0

'C al' 0Y Ycviev ~

FIG I:Hr hag

( r I ~

g

~ +

~ (%A L

~ I

~

~ ~

EBASCO SERVICES INCORPORA~i'D SPECIFICATION EBASCO 300-70 BEARING METAL THERMOCOUPLES

~

~

COPYRIGHT 1970 EBASCO SERVICES INCORPORATED T'40 R:CTOR S.REE

~

h:.P YOP 8502040368 850i25 PDR

@DOCK 05000400 S

PDR

EEASCO SERVICES Ihf SPECIFICATION EBASCO 300-l0 BEARING METAL THERN3COUPLES

. Pazazzaoh SCOPE STANDARDS GBKRAL REQUIREMENTS CONSTiUJCTION FEATURES DiUGGNtK LABELS 5

6

Specification Ebasco 300-70 Bearing Metal in~ocouples I.

This specification covers the appl'cation and the instal-lation features of thermocouples for measuring bearing metal temp-era'turee 1 It is not the intent to specify aLL details of design and installation; nevertheless, equipment shall conform in all respects h

to high standards of engineering, design and cwork'anship-SCOPE 2

Material covered in this specification shall comply erich all currently approved standards, safety codes, and test codes of:

STANDARDS ANSI - American National Standards Institute (Formerly USASI)

ASME - American Society of Mechanical Engineers ISA - Instrument Society of America IEEE - Institute of Electrical and Electronic Engineers (Formerly hIEE)

ASSAM - American Society of Testing Materials 3

Thermocouples are required for measuring bearing metal temperatures;-Anti-friction bearings (ball or roller) are not re-quired to have bearing thermocouples.

Bearing metal thermocouples

'are required for:

a - Horizontal sleeve bearings b - Nngsbury Type thrust bearings (both loading faces) c - Thrust or plate bearings in vertical rotating equip-ment (both loading facts)'

1 Thermocouple assemblies for enclosed bearings shall be accessible and replaceable from the outside of the machine.

~ 2 Bearings insulated from equipment frames must have the thermocouple hot junction ungrounded from the sheath.

(i.e. mag-nesium oxide packed tip). It shall be the motor Manufacturer's responsibility not to destroy the electrical insulation barrier and CWERAL REQUIR~VZS

Specification Ebasco 900<<70 Bearing Hetal Thezmocouples to maintain insulation betveen the bearing and ground.

All other thermocouples must be gzounded.

~ 3 ALL thezmocouples shall be spring loaded.

(See 4,5-.6 on Pages 2 and 3}.

GD ERAL REQUIR".~g (Cont'd) 4 Each assem>1y sila1L consist of:

~ 1 A 3/16 in. OD, type 316 stainless steel sheath, spring loaded for good metal to metal contact CONSTRUCTli PEA'ZURKS Chromel-Constaatan the~+couple elements of not less than No. 20 AMG vire, packed in magnesium oxide.

Thermocouple to lead wire )unction shall be in a universal

'weatherproof head as shovn in ISA RP L.L Conduit connection to be 3/4 in NPT, extension nipple connection to be 1/2 in. NPT

~ 2 Color coding, terminology, vire, sire Limits of error, fab-rication and emf values shall conform to ISA RP 1.1 -.7.

~ 3 The measuring tip of the thermocouple should be bzought as close as possible to the bearing surface tempezature to be measured HorizontaL motor and equipment bearings shall be drilled radially to

'ithin L/8 in. from the internal surface of the babbit metal.

The hole shall be drilled at some angle from the lower verticaL zadius in the direction of shaft rotation, vhere thg "hot spot" is known to ex-ist, If this position is not practical, from casting design consid-

eration, an alternate position close to this point may be used.

~4 Installation of thermocoupLe at bearing shall be through 1/2 in.

NPT SS nipple having the thermocouple assembly head screwed on to one end and the other sczeved into the bearing housing. If this method of installation cannot be used due to inaccessibilit vibration or Eor saEety reasons, the specific installation shall be referred to the Purchaser for review.

.eC wl e gled 5~

J1 s

sp

..g.

d

-..E must be app ied at the bearing housing.

Specification Ebasco 30l)-70 Bearing Hetal Thermocouples 4.5 (Cont'd)

If an oil seal is used for )acketed bearings the spzing must be strong enough to ovezcome the seal friction as well, CQBSTiZC FEATUiKS (Cont'd)

,6 Sufficient clearance foz the thermocouple sheath shall be provided to allow free movement of the sheath in the bearing metal boring by the force of spzing loading.

However, design should be such as to preclude entrance of foreign matter between the thermocouple and the bearing bore.

Provision shall be made, wheze necessary, to prevent leakage of lube oil or cooling ~ater into the thermocouple head.

~7 Vertical motor plate beazing shall be drilled as close to the underside of the plate as possible.

5 Seller's dimensional drawings showing thermocouple loca-tion and installation are required.

Seller's details.of thezmocouple construction are also required.

Design is sub)ect to Purchaser's review prior to manufactuze.

DRAVIAQS 6

h corrosion resistant durable metal label tag which will serve to identify the thermocouple shall be firmly affQced to the equipment involved before packing.