TABLE 3.7-6 AREA TEMPERATURE MONITORING MAXIMUM TEMPERATURE LIMIT ('F)

REACTOR AUXILIARYBUILDING 1.

Control Room Envelope (El 305')

2.

Process I&C, Room (El 305')

3.

Rod Control Cabinets Area (El 305')

4.

A&B Battery Rooms (El 286')

5.

A&B Switchgear Rooms (El 286')

6.

Main Steam, Feedwater Pipe Tunnel (El 286' 261')

7.

SA&SB Electrical Penetration Areas (El 261' 286')

8.

Area with MCC 1A35SA and 1B35SB (El 261')

9.

HVAC Chillers, Auxiliary FW Piping

& Valve Area (El 261')

CCW Pumps,.

CCW Hx, Auxiliary FW Pumps Area (El 236')

1A-SA, 1B-SB, and 1C-SAB Charging Pump Rooms (El 236')

Service Water Booster Pump 1B-SB (El 236')

Mechanical and Electrical Penetration Areas (El 236')

Containment Spray Additive Tank, and H&V Equipment Area (El 216')

15.

Trains A&B Containment Spray

Pump, RHR Pump, H&V Equipment Areas (El 190')

FUEL HANDLING BUILDING 85 85 104 85 90 116 104 104 104 104 104 104 104 104 104 16.

Trains A&B Emergency Exhaust System Areas (El 261')

17.

Deleted 104 WASTE PROCESSING BUILDING 18.

H&V Equipment Room (El 236')

MISCELLANEOUS 19.

Tank Area (El 236')

20.

Diesel Fuel Oil Storage Building (El 242')

21.

Emergency Service Water Electrical Equipment Room 22.

Emergency Service Water Pump Room 23.

DELETED 24.

1A-SA & 1B-SB H&V Equipment Rooms (El 292')

25.

1A-SA & 1B-SB H&V Equipment Rooms (El 280')

26.

1A-SA & 1B-SB Electrical Rooms (El 261')

27.

1A-SA & 1B-SB Diesel Generator Rooms (El 261')

104 104 122 104 122 122 118 116 120 SHEARON HARRIS - UNIT 1 3/4 7-29 Amendment No.

9002020276 900122

)

~)

PDR ADOCK 05000400 P

PDC

s t

~