ML17348A376

From kanterella
Jump to navigation Jump to search
Proposed Tech Specs Re Enhancement of Emergency Power Sys
ML17348A376
Person / Time
Site: Turkey Point  NextEra Energy icon.png
Issue date: 07/02/1990
From:
FLORIDA POWER & LIGHT CO.
To:
Shared Package
ML17348A375 List:
References
NUDOCS 9007090038
Download: ML17348A376 (81)


Text

FLORIDA POWER

& LIGHT COMPANY TURKEY POINT UNITS 3 AND 4 EMERGENCY POWER SYSTEM ENHANCEMENT PROJECT TECHNICAL SPECIFICATIONS EPS Enhancement Report Supplement No.

3 Revision 0 Attachment 2

JULY, 1990

~s eO07o~

&DOCK pQC

TURKEY POINT UNITS 3 &4 PAGE

SUMMARY

FOR THE ENHANCED ELECTRICAL POWER TS Viil.

xi 3/4 1-11 3-26 3-27 3-47 3-48 3-49 5-3 5-4 5-5 5-6 5-7

'5-8 5-9 5-10 7-27 7-32 8-1 through 8-23 B3/4 1-3 8-1 through 8-8.

gag f 5 1990

0

INOEX LIMITING CONDITIONS FOR OPERATION AND SURVEILLANCE RE UIREMENTS FilNi. BRAFT SECTION 3/4. 4. 9 PRESSURE/TEMPERATURE LIMITS Reactor Coo'tant System.

FIGURE 3.4-2 TURKEY POINT UNITS 38L4 REACTOR COOLANT SYSTEM HEATUP LIMITATIONS (60 F/hr)

APPLICABLE UP TO 20 EFPY......................

FIGURE 3.4-3 TURKEY POINT UNITS 38L4 REACTOR COOLANT SYSTEM HEATUP LIMITATIONS (100 F/hr)

APPLICABLE UP TO 20 EFPY.................................

FIGURE 3.4-4 TURKEY POINT UNITS 38A REACTOR COOLANT SYSTEM COOLDOWN LIMITATION (100 F/hr)

APPLICABLE UP TO 20 EFPY.................................

PAGE 3/4 4-30 3/4 4-31 3/4 4-32

'3/4 4-33 TABLE 4.4-5 REACTOR. VESSEL MATERIAL SURVEILLANCE WITHDRAWAL SCHEDULE.....................

P r essur) zer...............

Oyerpressure Mitigating Systems.........

3/4.4. 10 STRUCTURAL INTEGRITY....................

3/4.4. 11 REACTOR COOLANT SYSTEM VENTS...........

PROGRAM-3/4 4-34 3/4 4-35 3/4 4-36 3/4 4"38 3/4 4"39 3/4.5 EMERGENCY CORE COOLING SYSTEMS 3/4.5. 1 ACCUMULATORS.............................................

3/4.5.2 ECCS SUBSYSTEMS - T GREATER THAN OR EQUAL TO 350 F....

3/4 5-1 3/4 5-3 FIGURE 3.5"1 RHR PUMP CURVE.......................................

3/4.5.3 ECCS SUBSYSTEMS " T LESS THAN 350 F...................

3/4 5-6 3/4 5-9 3/4.5.4 REFUELING WATER STORAGE TANK.............................

3/4 5-10 TURKEY POINT " UNITS 3 4 4 V111 AMENDMENT NOS.

AND JUN 1 5 19%

0

INOEX LIMITING CONDITIONS FOR OPERATION AND SURVEILLANCE RE UIREMENTS FlNAI. BRAFT SECTION 3/4. 7. 8 FIRE SUPPRESSION SYSTEMS Fire Suppression Water System........

Spray and/or Sprinkler Systems.......

Fire Hose Stations................

TABLE 3.7-4 FIRE HOSE STATIONS..............

Fire Hydrants and Hydrant Hose Houses TABLE 3.7"5 FIRE HYDRANTS....

3/4.7.9 FIRE RATED ASSEMBLIES....................................

PAGE 3/4 7"24 3/4 7-27 3/4 7-29 3/4 7-30 3/4 7"31 3/4 7"32 3/4 7-33 3/4.8 ELECTRICAL POWER SYSTEMS 3/4.8.2 D.C.

SOURCES t

0peratsng...................................

TABLE 4.8-2 BATTERY SURVEILLANCE REQUIREMENTS........

~ ~

~

~

~

~

~

hutdownt ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~

~ ~ ~ ~ ~ ~ ~ ~ ~ \\ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~

~

~

~

~

S 3/4.8. 3 ONSITE POWER DISTRIBUTION 0peratsng...................................

TABLE 3.8-1 UNIT 3 ALLOWABLE OUTAGE TIMES FOR UNIT 4 LC/MCC INOPERABILITY..........,...........

TABLE 3.8"2 UNIT 4 ALLOWABLE OUTAGE TIMES FOR UNIT 3 LC/MCC INOPERABILITY.....................

hutdownt ~ ~ ~ ~ ~ ~ ~ ~ ~ t ~ ~ ~ ~ ~ ~ ~ ~ ~

~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~

~

~

~

~

S 3/4. 8. 1 A. C.

SOURCES 0peratsng..........,.....................................

TABLE 4.8-1 DIESEL GENERATOR TEST SCHEDULE........................

hutdown.........................

S 3/4 8-1 3/4 8-10 3/4 8-11 3/4 8"13 3/4 8-16 3/4 8-17 3/4 8-18 3/4 8-21 3/4 8-22 3/4 8-23 TURKEY POINT "-UNITS 3 4 4 l

Xi AMENDMENT NOS.

AND gUN 1) 1990

REACTIVITY CONTROL SYSTEMS CHARGING PUMPS - OPERATING FINAL BRAFT LIMITING CONDITION FOR OPERATION

3. 1.2.3 At least two charging pumps shall be OPERABLE.

APPLICABILITY:

MODES 1, 2, 3, and 4.

ACTION:

With only one charging pump OPERABLE, restore at least two charging pumps to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY and borated to a SHUTDOWN MARGIN equivalent to at least 1X hk/k at 200'F within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />; restore at least two charging pumps to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in COLD SHUTDOWN within the next 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE RE UIREMENTS

~

~

~

~

~

~

~

~

~

~

~

~

~

~

~

4.1.2.3. 1 The required charging pumps shall be demonstrated OPERABLE by testing pursuant to Specification 4.0.5 The provisions of Specification 4.0.4 are not applicable for entry into MODES 3 and 4.

TURKEY POINT - UNITS 3 8c 4 3/4 1-11 AMENDMENT NOS.

AND gUN 1 5 1990

TABLE 3.3-3 (Continued)

ENGINEERED SAFETY FEATURE ACTUATION SYSTEM FUNCTIONAL UNIT 6.

Auxiliary Feedwater (Continued)

TRIP SETPOINT ALLOWABLE VALUEC d.

Bus Stripping See Item 7.

below for all Bus Stripping Setpoints and Allowable Values.

e.

Trip of All Main Feedwater Pump Breakers.

7.

Loss of Power a.

4.16 kV Busses A and B

(Loss of Voltage) b.

480V Load.Centers (Instantaneous Relays)

Degraded Voltage Load Center N.A.

N.A.

N.A.

N.A.

e 3A 3B 3C 3D 4A Coincident with:

Safety Injection and 418V15V (10 sec i 1 sec delay)

[

423ViSV (10 sec t 1 sec delay)

[

429Vi5V (10 sec k 1 sec delay)

[

429VRSV (10 sec t 1 sec delay)

[

407VX5V (10 sec t 1 sec delay) f 423Vi5V (10 sec t 1 sec delay)

[

419VR5V (10 sec a 1 sec delay)

[

404ViSV (10 sec a 1 sec delay)

[

See Item l. above for all Safety Injection Trip Setpoints and Allowable Values.

Diesel Generator Breaker Open N.A.

N.A.

TURKEY POINT - UNITS 3 4 4 3/4 3-26 AMENDMENT NOS.

AND ggg iS 19M

FiNL MAFI'ABLE 3.3-3 (Continued)

ENGINEERED SAFETY FEATURE ACTUATION SYSTEH FUNCTIONAL UNIT 7.

Loss of Power (Continued) c.

480V Load Centers (Inverse Time Relays)

Degraded Voltage Load Center 3A 3B 3C, 3D 4A'C 4D Coincident with:

Diesel Generator Breaker Open 8.

Engineering Safety Features Actuation System Interlocks a.

Pressurizer Pressure b.

T Low 9.

Control Room Ventilation Isol ation a.

Automatic Actuation Logic and Actuation Relays TRIP SETPOINT 416V%5V(60 sec delay) 426V+5V(60 sec delay) 436V+5V(60 sec delay) 437V25V(60 sec delay) 424V25V(60 sec delay) 422Vt5V(60 sec delay) 433Vi5V(60 sec delay) 432Vt5V(60 sec delay)

N.A.

<2000 psig

>531'F N.A.

ALLOWABLE VALUES sec i30

[

sec 230

[

sec 230 sec 230

[

sec

%30

[

sec 230

[

sec 130

[

sec i30

[

N.A.

<[

] psig L

3 N.A.

b.

Safety Injection See Item l. above for all Safety Injecti on Trip Setpoi nts and Allowable Values.

TURKEY POINT - UNITS 3 8c 4 3/4 3-27 AMENDMENT NOS.

AND JUN 1 5 1990

0

INSTRUMENTATION FIRE DETECTION INSTRUMENTATION LIMITING CONDITION FOR OPERATION

3. 3. 3. 4 As a minimum, the fire detection instrumentation for each fire detection zone shown in Table 3.3-6 shall be OPERABLE.

APPLICABILITY:

Whenever equipment protected by the fire detection instrument is IIPEIIPEIE.

ACTION:

b.

C.

d.

With any, but not more than one-half the total in any fire zone, Function A fire detection instruments shown in Table 3.3-6 inoperable, restore the inoperable instrument(s) to OPERABLE status within 14 days or within the next 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> establish a fire watch patrol to inspect the zone(s) with the inoperable instrument(s) at least once per hour, unless the instrument(s) is located inside the con$ ainment, then inspect that containment zone at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> (or monitor the containment air temperature at least once per hour at the locations listed in Specification 4.6. 1.5).

With more than one-half of the Function A fire detection instruments in any fire zone shown in Table 3.3-6 inoperable, or with any Function B fire detection instruments shown in Table 3.3-6 inoperable, or with any two or more adjacent fire detection instruments shown in Table 3.3-11 inoperable, within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> establish a fire watch patrol to inspect the zone(s) with the inoperable instrument(s) at least once per hour, unless the instrument(s) is located inside the containment, then inspect that containment zone at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> (or monitor the containment air temperature at least once per hour at the locations listed in Specification 4.6.1.5).

With the fire watch patrol not established at the 18 foot level of the turbine area, restore the fire watch patrol within one hour, or prepare and submit a Special Report to the Commission within 30 days.

The provisions of Specifications 3.0.3 are not applicable.

SURVEILLANCE RE UIREMENTS

4. 3. 3. 4. 1 Each of the above required fire detection instruments which are accessible during plant operation shall be demonstrated OPERABLE at least once per 6 months by performance of a TRIP ACTUATING DEVICE OPERATIONAL TEST.

Fire detectors which are not accessible during plant operation shall be demonstrated OPERABLE by the performance of a TRIP ACTUATING DEVICE OPERATIONAL TEST during each COLD SHUTDOWN exceeding 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> unless performed in the previous 6

months.

4. 3. 3.4. 2 The NFPA Standard 720 supervised circuits supervision associated t

with.the detector alarms of each of the above required fire detection instruments shall be demonstrated OPERABLE at least once per 6 months.

TURKEY POINT - UNITS 3 8L 4 '/4 3-47 AMENDMENT NOS.

AND JUN 1 5 1990

TABLE 3.3"6 FIRE DETECTION INSTRUMENTS INSTRUMENT LOCATION FIRE ZONE AREA 5

9 10 11 12 13 14 15 16 19 2021-22-25-26 27 30 40 47-54-55 "

58-59 "

60 61 "

62-63-67-68-70 "

71-72-73-74-75 "

76 "

79A" 81-82 "

Aux. Bldg. Corridor E.

10'hem.

Drain/Laundry/Shower Tank Room Laundry/Chemical Drain Tank Room Pipeway Unit 3 RHR Heat Exchanger Room RHR Pump 3A Room RHR Pump 3B Room Unit 4 RHR Heat Exchanger Room RHR Pump 4A Room RHR Pump 4B Room Unit 3 M Elect Penet Room Unit 3 S Elect Penet Room Instrument Shop Radioactive Laboratory Aux. Bldg. Elect.

Equipmt.

Room Unit 4 N Elect Penet Room Unit 4 W Elect Penet Room Unit 4 Piping and Valve Room Unit 3 Piping and Valve Room Unit 4 Charging Pump Room Unit 4 Component Cooling Mater Area Unit 3 Component Cooling Mater Area Unit 3 Charging Pump Room Aux Bldg Corridor, El.

18'nit 4 Containment Electrical Penet.

Area""

Unit 3 Containment Electrical Penet.

Area""

Reactor Control Rod Eqpmt Room - Unit 4 Computer Room Reactor Control Rod Eqpmt Room - Unit 3 4160V Switchgear 4B 4160V Switchgear 4A 4160V Switchgear 3B 4160V Switchgear 3A Diesel Generator 3B Diesel Generator 3A Day Tank Room 3B Day Tank Room 3A Unit 4 Turbine Lube Oil Reservoir North-South Breezeway Unit 4 Main Transformer Unit 4 Aux Transformer Area Unit 3 and 4 Aux Feedwater Pump Area (DC Enclosure Bldg.)

TOTAL NUMBER OF INSTRUMENTS

~xy)"

~x>~y (2/0)

(0/4)

(0/4)

(5/2)

(0/4)

(4/2)

(0/4)

(0/3)

(1/0)

(0/3)

(1/0)

(1/1)

(1/1)

(1/0)

(0/6)

(1/0)

(1/0)

~x]

yy'2/0)

(2/0)

(1/0)

(11/0)

(5/0)

(2/0)

(2/0)

(5/0)

(2/0)

(2/0)

(5/0)

(11/0)

(2/0)

(2/0)

(5/0)

(8/0)

(6/0)

(4/0)

(4/0)

(3/0)

(3/0)

(18/0)

(10/0)

(16/0)

(4/0)

(11/0)

(4/0)

(10/0)

(6/0)

(10/0)

(6/0)

(1/0)

(1/0)

(4/0)

(3/0)

TURKEY POINT - UNITS 3 4 4 3/4 3-48 AMENDMENT NOS.

AND dUN

> S 1990

FIINl. 98AFT TABLE 3.3-6 Continued FIRE DETECTION INSTRUMENTS INSTRUMENT LOCATION FIRE ZONE AREA 87 - Unit 3 Aux Transformer Area 93 - 480V Load Center 4A and 4B 94 - 480V Load Center 4C and 4D 95 - 480V Load Center 3A and 3B 96 - 480V Load Center 3C and 3D 97 - Mechanical Equipment Room 98 - Cable Spreading Room 101-RPI Inverter and MG Sets 102-Battery Rack 4B 103-Battery Rack 3A 104-RPI Inverter and MG Sets 106-Control Room 108A-Train A Inverters 108B-Train B Inverters 109-Battery Rack 4A 110- Battery Rack 3B 113-Unit 4 Feedwater Platform 116-Unit 3 Feedwater Platform 119-Unit 4 Intake Cooling Water Pump Area 120- Unit 3 Intake Cooling Water Pump Area 132-Control Room Electrical Chase 133-Diesel Generator 4B 134-4160V Switchgear 3D Room 135-: Diesel Generator 4B Control Panel Room 136-Diesel Generator 4B Fuel Transfer Pump 138-Diesel Generator 4A 139-4160V Switchgear 4D Room 140- Diesel Generator 4A Control Panel Room 141-Diesel Generator 4A Fuel Transfer Pump N/A - 18'evel of the Turbine Area TABLE NOTATIONS TOTAL NUMBER OF INSTRUMENTS

~xy)"

~x/yy'1/0)

(1/O)

(1/0)

(1/0)

(1/O)

(1/O)

(2/0)

(2/O)

(4/0)

(4/0)

(5/5)

(3/0)

(5/5)

(3/0)

(N/A)e (N/A)e

~xy (1/0)

(2/0)

(1/0)

(2/0)

(1/0)

(16/15)

.(1/0)

(2/0)

(17/0)

(3/4)

(4/4)

(1/0)

(5/0)

(2/0)

(2/0)

(2/0)-

(5/0)

(2/0)

(2/O)

(2/0)

(N/A)8

  • (x/y):

x is number of Function A (early warning fire dectection and notification only) instruments.

y is number of Function B (actuation of Fire Suppression Systems and early warning fire detection and notification) instruments.

The fire detection instruments located within the containment are not required to be operable during the performance of Type A Containment Leakage Rate Test.

A fire watch patrol shall be established to inspect the 18 foot level of the Turbine Area once each hour.

TURKEY POINT " UNITS 3 8E 4 3/4 3-49 AMENDMENT NOS.

AND JUN 15 1990

EMERGENCY CORE COOLING SYSTEMS

~

~

~

3/4.5.2 ECCS SUBSYSTEMS " T GREATER THAN OR EQUAL TO 3500F LIMITING CONDITION FOR OPERATION 3.5.2 The following Emergency Core Cooling System (ECCS) equipment and flow paths shall be OPERABLE:

a. 'our OPERABLE Safety Injection (SI) pumps, each capable of being powered from its associated OPERABLE diesel generator, with discharge aligned to the RCS cold legs,"

b.

Two OPERABLE RHR heat exchangers, D

c.

Two OPERABLE RHR pumps with discharge aligned to the RCS cold legs, d.

An OPERABLE flow path capable of taking suction from the refueling water storage tank as defined in Specification 3.5.4, and e.

Two OPERABLE flow paths capable of taking suction from the containment sump.

APPLICABILITY:

MODES 1, 2, and 3"".

ACTION:

a.

With any one of the required ECCS components or flow paths inoperable, except for inoperable Safety Injection Pump(s),

restore the inoperable component or flow path to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

b.

In the event the ECCS is actuated and injects water in the Reactor

~ Coolant System, a Special Report shall be prepared and submitted to the Commission pursuant to.Specification 6.9.2 within 90 days describing the circumstances of the actuation and the total accumulated

'ctuation cycles to date since January 1, 1990.

c.

Mith one of the four required Safety Injection pumps inoperable and the opposite unit in MODE 1, 2, or 3, restore the pump to OPERABLE within 30 days or be in at least HOT STANDBY within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in HOT SHUTDOWN within the f'ol hours. 44s~

AS%II

~

~

IIIIII)k

(+aaaU

<AS.OC.>aakCA

~a%h ~C

&AO'.M O~

the.

a pic O'c. Un i'9 "Only three OPERAB e y n ec on pump

, each c

of being powered from its associated OPERABLE diesel generator, with discharge aligned to the RCS cold leg are required if the opposite unit is in MODE 4, 5, or 6.

  • "The provisions of Specifications
3. 0.4 and 4. 0.4 are not applicable for entry into MODE 3 for the Safety Injection flow paths isolated pursuant to Specifica-tion 3.4.9.3 provided that the Safety Injection flow paths are restored to e

OPERABLE status prior to T exceeding 380'F.

Safety Injection flow paths may avg be isolated when T is less than 380'F.

avg

"""The provisions of Specifications

3. 0.4 and 4. 0. 4 are not applicable.

TURKEY POINT - UNITS 3 8( 4 3/4 5-3 AMENDMENT NOS.

AND

'XnSert l JUN 15 199D

r

~ t Il I

8Inoperability of the required EDG's does not constitute inoperability of the associated Safety Injection pumps.

Attachment to page 3/4 5-3

EMERGENCY CORE COOLING SYSTEMS 3/4 5 2ECCS SUBSYSTEMS TyGREATER THAN ORE(UALTO 350 F

LIMITING CONDITION FOR OPERATION d.

e.

I With two of the four required Safety Injection pumps inoperable and the opposite unit in MODE 1, 2, or 3, restore one of the two inoperable pumps to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

This ACTION applies to both units simultaneously.

With one of the three required Safety Injection pumps inoperable and the opposite unit in MODE 4, 5, or 6, restore the pump to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

f.

With a required safety injection pump OPERABLE but not capable of being powered from its associated OPERABLE diesel generator, restore the capability within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

TURKEY POINT - UNITS 3 8( 4 3/4 5-4 AMENDMENT NOS.

AND JUN 16 1990

e EMERGENCY CORE COOLING SYSTEMS SURVEILLANCE RE UIREMENTS FlNI. 9$lFT

4. 5. 2, Each ECCS component and flow path shall be demonstrated OPERABLE:

At least once pe'r 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> by verifying by control room indication that the following valves are in the indicated positions with power to the valve operators removed:

Valve Number Valve Function Valve Position 864A and B

Supply from RWST to ECCS Open 862A and B

RWST Supply to RHR pumps Open 863A and B

RHR Recirculation Closed 866A and B

H.H.S. I. to Hot Legs Closed HCV-758*

RHR HX Outlet Open To permit temporary operation of these valves for surveillance or maintenance

purposes, power may be restored to these valves for a period not to exceed 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

b.

At least once per 31 days by:

1)

Verifying that the ECCS piping is full of water by venting the ECCS pump casings and accessible discharge piping, 2)

Verifying that each valve (manual, power-operated, or automatic) in the flow path that is not locked, sealed, or otherwise secured in position, is in its correct position, and 3)

Verifying that each RHR Pump develops the indicated differential pressure applicable to the operating conditions in accordance with Figure 3. 5-1 when tested pursuant to Specification 4. 0. 5.

C.

At least once per 92 days by:

1)

Verifying that each SI pump develops the indicated differential pressure applicable to the operating conditions when tested pursuant to Specification 4.0.5.

SI pump

> 1126 psid at a metered flowrate > 300 gpm (normal alignment or Unit 4 SI pumps aligned to Unit 3 EST),

ot

> 1156 psid't a metered flowrate > 280 gpm 7Unit 3 SI pumps aligned to Unit 4 RWST).

"Air Supply to HCV-758 shall be verified shut off and sealed closed once per TURKEY POINT - UNITS 3 & 4 3/4 5"5 AMENDMENT NOS.

AND

290 SELECTED POINTS ON THE CURVE FLOW 280 270 260 0

250 500 1000 1500 2000 2500 3000 3500 3600 3750 277 277 277 275 270 265 251 233 213 208 200 CD 240 UNACCEPTABLE OPERATION ACCEPTA8LE OPERATION 210 1000 RHR PUMP FLOW (GPM)

Figure 3.5"1 RHR Pump Curve

'TURKEY POINT - UNITS 3 & 4 3/4 5-6 AMENOMENT NOS.

AND JUN 1 5 1990

FIINL 98AFT EMERGENCY CORE COOLING SYSTEMS SURVEILLANCE RE UIREMENTS d.

By a visual inspection which verifies that no loose debris (rags, trash, clothing, etc.) is present in the containment which could be transported to the containment sump and cause restriction of the pump suctions during LOCA conditions.

This visual inspection shall be performed:

1)

For all accessible areas of the containment prior to establish-ing CONTAINMENT INTEGRITY, and 2)

Of the areas affected within containment at the completion, of each containment entry when CONTAINMENT INTEGRITY is established.

e.

At least once per 18 months by:

Verifying automatic isolation and interlock action of the RHR system from the Reactor Coolant System by ensuring that with a simulated or actual Reactor Coolant System pressure signal greater than or equal to 525 psig the interlocks cause the valves to automatically close and prevent the valves from being

opened, and 2)

Verifying correct interlock action to ensure that the RWST is isolated from the RHR System during RHR System operation and to ensure that the RHR System cannot be pressurized from the Reactor Coolant System unless the above RWST Isolation Valves are closed.

3)

A visual inspection of the containment sump and verifying that the suction inlets are not restricted by debris and that the sump components (trash racks,

screens, etc.)

show no evidence of structural distress or abnormal corrosion.

f.

At least once per 18 months', during shutdown, by:

Verifying that each automatic valve in the flow path actuates to its correct position on Safety Injection actuation test

signal, and 2)

Verifying that each of the following pumps start automatically upon receipt of a Safety Injection actuation test signal:

a)

Safety Injection pump, and b)

RHR pump.

TURKEY POINT " UNITS 3 8L 4 3/4 5-7 AMENOMENT NOS.

AND JUN 15 1990

0

EHERGENCY CORE COOLING SYSTEHS SURVEILLANCE RE UIREHENTS g.

By verifying the correct position of each electrical and/or mechanical position stop for the following ECCS throttle valves:

1)

Mithin 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> following completion of each valve stroking operation or maintenance on the valve when the ECCS components are required to be OPERABLE, and 2)

At least once per 18 months.

RHR S stem a ve um er HCV-"'758 HOV-"-872 TURKEY POINT " UNITS 3 8( 4 3/4 5-8 AMENDMENT NOS.

AND

EMERGENCY CORE COOLING SYSTEMS 3/4.5.3 ECCS SUBSYSTEMS " T LESS THAN 350 F

LIMITING CONDITION FOR OPERATION 3.5.3 As.a minimum, the following ECCS components and flow path shall be OPERABLE:

a.

One OPERABLE RHR heat exchanger, b.

One OPERABLE RHR pump, and C.

An OPERABLE flow path capable of (1) taking suction from the refueling water storage tank upon being manually realigned and (2) transferring suction to the containment sump during the recirculation phase of operation.

APPLICABILITY:

MODE 4.

ACTION:

'a 0 b.

C.

With no OPERABLE ECCS flow path from the refueling water storage tank, restore at least one ECCS flow path to OPERABLE status within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or be in COLD SHUTDOWN within the next 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

With either the residual heat removal heat exchanger or RHR pump inoperable, restore the components to OPERABLE status or maintain the Reactor Coolant System T

less than 350'F by use of alternate heat removal methods.

In the event the ECCS is actuated and injects water into the Reactor Coolant System, a Special Report shall be prepared and submitted to the Commission pursuant to Specification 6.9.2 within 90 days describing the circumstances of the actuation and the total accumulated actuation cycles to date since January 1, 1990.

SURVEILLANCE RE UIREMENTS 4.5.3 The above ECCS components shall be demonstrated OPERABLE per the applicable requirements of Specification 4.5.2.

TURKEY POINT - UNITS 3 8( 4 3/4 5-9 AMENDMENT NOS.

AND JUN 1 i 1990.

EMERGENCY CORE COOLING SYSTEMS 3/4.5.4 REFUELING WATER STORAGE TANK

~

~

LIMITING CONDITION FOR OPERATION 3.5.4 For single Unit operation, one refueling water storge tank (RWST) shall be OPERABLE or for dual Unit operation two RWSTs shall be OPERABLE with:

a.

A minimum indicated borated water volume of 320,000 gallons per

RWST, b.

A minimum boron concentration of 1950 ppm of boron, c.

A minimum solution temperature of 39'F, and d.

A maximum solution temperature of 100'F.

APPLICABILITY:

MODES 1, 2, 3, and 4.

ACTION:

With less than the 'required 'number of RWST(s)

OPERABLE, restore the tank(s) to OPERABLE status within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or be in at least HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE RE UIREMENTS 4.5.4 The required RWST(s) shall be demonstrated OPERABLE:

a.

At least once per 7 days by:

1)

Verifying the indicated borated water volume in the tank, and 2)

Verifying the boron concentration of the water.

b.

By verifying the RWST temperature is within limits whenever the outside air temperature is less than 39 F or greater than 100'F at the following frequencies:

1)

Within one hour upon the outside temperature exceeding its limit for consecutive 23 hours2.662037e-4 days <br />0.00639 hours <br />3.80291e-5 weeks <br />8.7515e-6 months <br />, and 2)

At least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> while the outside temperature exceeds its limit.

TURKEY POINT - UNITS 3 8c 4 3/4 5-10 AMENDMENT NOS.

AND

PLANT SYSTEMS SPRAY AND/OR SPRINKLER SYSTEMS LIMITING CONDITION FOR OPERATION 3.7.8.2 The following Spray and/or Sprinkler Systems shall be OPERABLE:

a.

Fire Zones 47 and 54 - Component Cooling Water Areas b.

Fire Zones 45 and 55 - Charging Pump Rooms c.

Fire Zones 79A - North - South Breezeway C U ~It' EE cEd. UrEiE'A d.

Fire Zones 72, 73, 74 and 75 - Emergency Diesel Generator and Oay Tank Rooms (Unit 3) e.

Fire Zones 133, 136, 138 and 141-Emergency Diesel Generator and Fuel Transfer Pump Rooms (Unit 4)

APPLICABILITY: Whenever equipment protected by the Spray/Sprinkler System is IPE EEEII.

ACTION:

b.

With one or more of the above required Spray and/or Sprinkler Systems inoperable, within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> establish a continuous fire watch with backup fire suppression equipment.

This ACTION apply to both units simultaneousl

. f'r 3.7 S. 2. c.

LAJ 1 The provisions of Specification 3.0.3 are not app icable.

SURVEILLANCE RE UIREMENTS 4.7.8.2 Each of the above required Spray and/or Sprinkler Systems shall be demonstrated OPERABLE:

a.

At least once'er 31 days by verifying that each valve (manual, power-

operated, or automatic) in the flow path is in its correct position, b.

At least once per 12 months by cycling each testable valve in the flow path through at least one complete cycle of full travel, C.

At least once per 18 months:

1)

By performing a system functional test which includes simulated automatic actuation of the system, and:

a)

Verifying that the automatic valves in the flow path actuate to their correct positions on a test signal, and b)

Cycling each valve in the flow path that is not testable during plant operation through at least one complete cycle of full travel.

TURKEY POINT " UNITS'3 8E 4 3/4 7-27 AMENDMENT NOS.

AND JUN 15 1SSO

R k

TABLE 3.7-5 FIRE HYDRANTS FINAL DRAFT IDENTIFICATION FIRE ZONE LOCATION NUMBER OF HYDRANTS HY"01 HY-07 HY-08 HY-09 HY-10 HY"ll HY-12 HY-13 HY-17 HY-16 HY-18 HY-26 124 86 81 77 125 123 NA NE Corner of Unit 3 near Vehicle Gate into RCA Unit 3 Transformer Area Unit 4 Transformer Area Unit 4 Turbine-Generator Area Unit 4 Condensate Storage Tank Area SW Corner of Unit 4 near equipment hatch Unit 4 New Fuel Storage Area Refueling Water Storage Area Nuclear Dry Storage Area Steam Generator Storage Area Unit 3 Containment Access Ramp Area Unit 3 Diesel Generator Building Area TOTAL e

TURKEY POINT - UNITS 3 8, 4 3/4 7"32 AMENDMENT*NOS.

AND JUN 2 5 lS90

3/4. 8 ELECTRICAL POWER SYSTEMS 3/4.8.1 A.C.

SOURCES

~

~

~

~

OPERATING LIMITING CONDITION FOR OPERATION 3.8.1.1 As a minimum, the following A.C. electrical power sources shall be OPERABLE:

a.

Two startup transformers and their associated

circuits, and b.

Three separate and independent diesel generators including, 1)

For Unit 3, two (3A and 3B); for Unit 4, one (3A or 3B) each with:

a)

A.separate skid-mounted fuel tank and a separate day fuel tank with an OPERABLE solenoid valve to permit gravity flow from the day tank to the skid mounted tank, and with the two tanks together containing a minimum of 2000 gallons of

~ fuel oil.

b)

A common Fuel Storage System containing a minimum volume of 38,000 gallons of fuel, c)

A separate fuel transfer

pump, d)

Lubricating oil storage containing a minimum volume of 120 gallons of lubricating oil, e)

Capability to transfer lubricating oil from storage to the diesel generator unit, and Energized MCC bus (MCC 3A vital section for EDG 3A, MCC 3K for EDG 3B).

2)

For Unit 3, one (4A or 4B); for Unit 4, two (4A and 4B) each with:

a)

A separate day fuel tank containing a minimum volume of 230 gallons of fuel, b)

A separate Fuel Storage System containing a minimum volume of 34,700 gallons of fuel, c)

A separate fuel transfer

pump, and d)

Energized MCC bus (MCC 4J for EDG 4A, MCC 4K for EDG 4B).

Qhcacv cv'~e.

oc ~of 6 of W4 Woof

~OS 5 hS Ov~" 04 SRCVlC.Kq ensure eo~pliaece,.~ifh

+4< E~6 requ.ire.rn<n4s spec.s$ <t,d

>n Sqe.<if< c o,4t ops

3. 5'. 2. one 3.8.2.1

~

TURKEY POINT - UNITS 3 8 4 3/4 8-1 AMENDMENT NOS.

AND JUN ~5 19%

FIINL 98AFT ELECTRICAL POWER SYSTEMS g<~<w aWof is otic e.od.ii ope.c GCing LIMITING CONDITION FOR OPERATION Continued APPLICABILITY:

MODES 1, 2, 3, and 4.

ACTION:

a4 b.

C.

cuit tup trans-ance er 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> the trans-ors have not trate their 1.2.a.4, for If the transformer With one of two startup transformers or an associated ci inoperable, demonstrate the OPERABILITY of the other sta former and its associated circuits by performing Surveil Requirement 4.8. 1. 1. l. a within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once thereafter.

Notify the NRC within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> of declarin former inoperable.

If any of the required diesel gener t been successfully tested within the past 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, demo s

OPERABILITY by performing Surveillance Requirement 4.8.

each such diesel generator, separately, within 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> crab e

ta tu transformer is the associated startu snp l

s r

p p

and became inoperable while the unit is in MODE 1, reduce THERMAL POWER to < 3(C RATED THERMAL POWER within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, or restore the inoperable startup transformer and associated circuits to OPERABLE status within the next 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

If THERMAL POWER is reduced to < 30K RATED THERMAL POWER within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or if the inoperable startup transformer is associated with the opposite unit restore the startup transformer and its associated circuits to OPERABLE status within 30 days of the loss of OPERABILITY, or be in at least HOT STANDBY within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

If the inoperable startup transformer is the associated startup transformer and became inoperable while the unit was in MODE 2, 3, or 4 restore the startup transformer and its associated circuits to OPERABLE status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the.following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

This ACTION applies to both units simultaneously.

With one of the required diesel generators inoperable, demonstrate the OPERABILITY of the above required startup transformers and their associated circuits by performing Surveillance Requirement 4.8. l.l.l.a within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter.

If the diesel generator became inoperable due to any cause other than preplanned preventative maintenance

'or testing, demonstrate the OPERA-BILITYof the remaining required diesel generators by performing Surveillance Requirement 4.8.1. 1.2.a.4 within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />".

Restore the inoperable diesel generator to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

With one startup transformer and one of the required diesel generators inoperable, demonstrate the OPERABILITY of the remaining A.C. sources by performing Surveillance Requirement 4.8.1.1.1.a on the remaining

~Unless the diesel generator inoperability was due to preplanned preventative maintenance, or testing, this test is required to be completed regardless of when the inoperable diesel generator is restored to OPERABILITY.

TURKEY POINT - UNITS 3 4 4 3/4 8-2 AMENDMENT NOS.

AND JUN 15 1990

ANN. 88AFT ELECTRICAL POWER SYSTEMS y v,~ I <ss 44@

dry.sc.l gc nac a+os s 0 c'e w) c'e.why o pz.r~+ i>~

LIMITING CONDITION FOR OPERATION Continued ACTION (Continued startup transformer and associa ed circuits within one hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> there fter; and if the diesel generator became inoperable due to any c use other than preplanned preventative maintenance or testing, demons rate the OPERABILITY of the remaining required diesel generators by performing Surveillance Requirement 4.8. 1. 1.2.a.4 within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />", restore one of the inoperable sources to OPERABLE status in accordance with Action Statements a and b, as appropriate.

Notify the NRC within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> of declaring both a start-up transformer and diesel generator inoperable.

Restore the other A.C. power source (startup transformer or diesel generator) to OPERABLE status in accordance with the provisions of Section 3.8. 1. 1 Action Statement a or b, as appropriate, with the time requirement of that Action Statement based on the time of initial loss of the remain-ing inoperable A.C. power source.

d.

With one diesel generator inoperable, in addition to ACTION b. or c.

above, verify that:

1.

All required systems, subsystems,

trains, components, and devices (except safety injection pumps) that depend on the remaining required OPERABLE diesel generators as a source of emergency power are also OPERABLE.

If this condition is not satisfied within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />, be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

2.

At least two Safety Injection pumps are OPERABLE and capable of being powered from their associated OPERABLE diesel generators.

If this condition is not satisfied within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />, be in at least HOT STANDBY within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

This ACTION applies to both units simultaneously.

e.

With two.of the above required startup transformers or their associ-ated circuits inoperable notify the NRC within 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> s and demon-strate the OPERABILITY of the required diesel generators separately by performing the requirements of Specification 4.8. 1. 1.2a.4 within 8

hours, unless the diesel generators are already operating, and at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> thereafter; restore at least one of the inoperable startup transformers to OPERABLE status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least HOT STANDBY within the next.6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />"" and in COLD "Unless the diesel generator inoperability was due to preplanned preventative maintenance, or testing, this test is required to be completed regardless of when the inoperable diesel generator is restored to OPERABILITY.

t "*Ifthe opposite unit is shutdown first, this time can be extended to 42 hours4.861111e-4 days <br />0.0117 hours <br />6.944444e-5 weeks <br />1.5981e-5 months <br />.

TURKEY POINT - UNITS 3 4 4 3/4 8"3 AMENDMENT NOS.

AND JUN 1 5 1990

~. v

~

Jl

ANAL IlBAFT ELECTRICAL POWER SYSTEMS e

LIMITING CONDITION FOR OPERATION Continued ACTION Continued SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

This ACTION applies to both units simultaneously.

With only one startup transformer and associated circuits restored, perform Surveillance Requirement

4. 8. 1.1. 1. a on the OPERABLE Startup transformer at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />, and restore the other startup transformer and its associated circuits to OPERABLE status or shutdown in accordance with the provisions of Action Statement 3.8. l.la with time requirements of that Action Statement based on the time of initial loss of a startup transformer.

This ACTION applies to both units simultaneously.

With two of the above required diesel generators inoperable, demon-strate the OPERABILITY of two startup transformers and their associated circuits by performing the requirements of Specifica-tion 4.8. 1. 1. la. within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> there-after; restore at least one of the inoperable diesel generators to OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

Restore all required diesel generators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from time of initial loss or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

4.8. l. 1. 1 Each of the above required startup transformers and their associated circuits shall be:

a.

Determined OPERABLE at least once per 7 days by verifying correct breaker alignments, indicated power availability, and b.

Demonstrated OPERABLE at least once per 18 months while shutting down, by transferring manually unit power supply from the auxiliary transformer to the startup transformer.

E 4.8. 1.1.2 Each diesel generator shall be demonstrated OPERABLE":

aO In accordance with the frequency specified in Table 4. 8-1 with diesel generator surveillances performed nonconcurrently by:

2) 3)

Verifying the fuel volume in the day and skid-mounted fuel tanks (Unit 4 - day tank only),

Verifying the fuel volume in the fuel storage tank, Verifying the lubricating oil inventory in storage, e

"All'diesel generator starts for the purpose of these surveillances may be proceeded by a prelube period as recommended by the manufacturer.

TURKEY POINT - UNITS 3 8c 4

\\

3/4 8-4 AMENDMENT NOS.

AND JUN 1 5 1S90

ELECTRICAL POWER SYSTEMS SURVEILLANCE RE UIREMENTS Continued b.

C.

d.

e.

4)

Verifying the diesel starts and accelerates to reach a generator voltage and frequency of 4160 t420 volts and 60 k1.2 Hz.

Once per 184 days, these conditions shall be reached within 15 seconds after the start signal from normal conditions.

For all other

starts, warmup procedures, such as idling and gradual accelera-tion as recommended by the manufacturer may be used.

The diesel generator shall be started for this test by using one of the following signals:

a)

Manual, or b)

Simulated loss-of-offsite power by itself, or c)

Simulated loss-of-offsite power in conjunction with an ESF Actuation test signal, or d)

An ESF Actuation test signal by itself.

5)

Verifying the generator is synchronized loaded" to 2300-2500 kW (Unit 3), 2650-2850 kW (Unit 4)~", operates at this loaded condition for at least 60 minutes and for Unit 3 until automatic transfer of fuel from the day tank to the skid mounted tank is demonstrated, and the cooling system is demonstrated OPERABLE.

6)

Verifying the diesel generator is aligned to provide standby power to the associated emergency busses.

Demonstrating at least once per 92 days that a fuel transfer pump starts automatically and transfers fuel from the storage system to the day tank, At least once per 31 days and after each operation of the diesel where the period of operation was greater than or equal to 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> by checking for and removing accumulated water from the day and skid-mounted fuel tanks (Unit 4 - day tank only);

At least once per 31 days by checking for and removing accumulated water from the fuel oil storage tanks; By obtaining a composite sample of new fuel oil in accordance with ASTM-D4057 prior to addition to storage tanks and:

1)

By verifying in accordance with the tests specified in ASTM-D975-81 prior to addition to the storage tanks that the sample has:

a)

An API Gravity of within 0.3 degrees at 60'F, or a specific gravity of within 0.0016 at 60/60'F, when compared to the supplier's certificate, or an absolute "May include gradual loading as recommended by the manufacturer so that the mechanical stress and wear on the diesel engine is minimized.

1

"*Momentary transients outside these load bands do not invalidate this test.

TURKEY POINT " UNITS 3 & 4 3/4 8-5 AMENDMENT NOS.

AND JUN f 6 1990

FiNAL DRAFT ELECTRICAL POWER SYSTEMS SURVEILLANCE RE UIREHENTS Continued

~

~

g.

specsfic gravity at 60/60'F of greater than or equal to 0.83 but less than or equal to 0.89, or an API gravity of greater than or equal to 27 degrees but less than or equal to 39 degrees, when tested in accordance with ASTH-D1298-80; b)

A kinematic viscosity at 40'C of greater than or equal to 1.9 centistokes, but less than or equal to 4. 1 centistokes (alternatively, Saybolt viscosity, SUS at 100 F of greater than or equal to 32.6, but less than or equal to 40.1), if gravity was not determined by comparison with the supplier's certification; c)

A flash point equal to or greater than 125'F; and d)

A clear and bright appearance with proper color when tested in accordance with ASTH-D4176-82.

2)

By verifying within 30 days of obtaining the sample that the other properties specified in Table 1 of ASTM-D975-81 are met when tested in accordance with ASTM-D975-81 except that the analysis for sulfur may be performed in accordance with ASTM-D1552-79 or ASTM-02622-82.

At least once every 31 days by obtaining a sample of fuel oil from the storage tank in accordance with ASTH-D2276-78, and verifying that total particulate contamination is less than 10 mg/liter when checked in accordance with ASTH-D2276-78, Method A; At least once per 18 months, during shutdown (applicable to only the two diesel generator associated with the unit):

ec sng the diesel to an inspection in accordance with procedures prepared in conjunction with its manufacturer's recommendations for this class of standby service; 2)"

Verifying the generator capability to reject a load of greater than or equal to 380 kW while maintaining voltage at 4160 1420 volts and frequency at 60 21. 2 Hz; 3)"

Verifying the generator capability to reject a load of greater than or equal to 2500 kW (Unit 3), 2874 kW (Unit 4) without tripping.

The generator voltage shall return to less than or equal to 4784 volts within 2 seconds following the load rejection; 4)

Simulating a loss-of-offsite power by itself, and:

a)

Verifying deenergization of the emergency busses and load shedding from the emergency

busses, and b)

Verifying the diesel starts on the auto-start signal, energizes the emergency busses with any permanently "For the purpose of this test, warmup procedures, such as idling, gradual 1

acceleration, and gradual loading as recommended by the manufacturer may be Used.

TURKEY POINT - UNITS 3 5 4 3/4 8-6 AMENDMENT NOS.

AND JN 15 LS90

RNAI. 98AFT ELECTRICAL POWER SYSTEMS SURVEILLANCE RE UIREMENTS Continued connected loads within 15 seconds, energizes the auto" connected shutdown loads through the load sequencer and operates for greater than or equal to 5 minutes while its generator is loaded with the auto-connected shutdown loads.

After automatic load sequencing, the steady-state voltage and frequency of the emergency busses shall be maintained at 4160 a 420 volts and 60 f 1.2 Hz during this test.

5)

Verifying that on an ESF Actuation test signal, without loss-of-offsite power, the diesel generator starts on the auto-start signal and operates on standby for greater than or equal to 5 minutes.

The generator voltage and frequency shall be 4160

+ 420 volts and 60 a 1.2 Hz within 15 seconds after the aut'o-start signal; the steady-state generator voltage and frequency shall be maintained within these limits during this test; 6)

Simulating a loss-of-offsite power in conjunction with an ESF Actuation test signal, and:

a)

Verifying deenergization of the emergency busses and load shedding from the emergency busses; b)

Verifying the diesel starts on the auto-start signal, energizes the emergency busses with any permanently connected loads within 15 seconds, energizes the auto-connected emergency (accident) loads through the load sequencer and operates for greater than or equal

. to 5 minutes while its generator is loaded with the emergency loads.

After automatic load sequencing, the steady-state voltage and frequency of the emergency busses shall be maintained at 4160 a 420 volts and 60 a 1.2 Hz during this test; and c)

Verifying that diesel generator trips that are made operable during the test mode of diesel operation are inoperable.

7)"

Verifying the diesel generator operates for at least 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

Ouring the first 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> of this test, the diesel generator shall be loaded to 2550-2750 kW (Unit 3), 2950-3150 kW (Unit 4)*"

and during the remaining 22 hours2.546296e-4 days <br />0.00611 hours <br />3.637566e-5 weeks <br />8.371e-6 months <br /> of this test, the diesel generator shall be loaded to 2300-2500 kW (Unit 3), 2650-2850 kW (Unit 4)"".

The generator voltage and frequency shall be 4160 f 420 volts and 60 2 1.2 Hz within 15 seconds after the start signal; the steady-state generator voltage and frequency "For the purpose of this test, warmup procedures, such as idling, gradual acceleration, and gradual loading as recommended by the manufacturer may be used.

""Momentary transients outside these load bands do not invalidate this test.

TURKEY POINT - UNITS 3 4 4 3/4 8"7 AMENOMENT NOS.

AND JUN 15 1990

FiNAi IlBAFr ELECTRICAL POWER SYSTEMS SURVEILLANCE RE UIREMENTS Continued h.

shall be maintained within these limits during this test.

Within 5 minutes after completin~ this 24-hour test, perform Specification 4.8. 1. 1. 2. g.4)b);"

8)

Verifying that the auto-connected loads to each diesel generator do not exceed 2500 kW (Unit 3), 2874 kW (Unit 4);

9)

Verifying the diesel generator's capability to:

a)

Synchronize with the offsite power source while the generator is loaded with its emergency loads upon a

simulated restoration of offsite power, b)

Transfer its loads to the offsite power source, and c)

Be restored to its standby status.

10)

Verifying that the diesel generator operating in a test mode, connected to its bus, a simulated Safety Injection signal overrides the test mode by:

(1) returning the diesel generator to standby operation, and (2) automatically energizing the emergency loa'ds with offsite power; 11)

Verifying that the fuel transfer pump transfers fuel from the fuel storage tank (Unit 3), fuel storage tanks (Unit 4) to the day tanks of each diesel associated with the unit via the installed cross-connection lines; 12)

Verifying that the automatic load sequence timer is OPERABLE with the interval between each load block within t 10X of its design interval; 13)

Verifying that the diesel generator lockout relay prevents the diesel generator from starting; At least once per 10 years or after any modifications which could affect diesel generator interdependence by starting all required diesel generators simultaneously and verifying that all required diesel generators provide 60 i 1.2 Hz frequency and 4160 2 420 volts in less than or equal to 15 seconds; and At least once per 10 years by:

1)

Draining each fuel oil storage tank, removing the accumulated sediment and cleaning the tank.

2)

For Unit 4 only, performing a pressure test of those portions of the diesel fuel oil system designed to Section III, subsection ND of the ASME Code in accordance with Section XI of the ASME Boiler and Pressure Vessel Code and applicable Addenda.

""IfSpecification 4.8.1.1.2.g.4)b) is not satisfactorily completed, it is not necessary to repeat the 24-hour test.

Instead, the diesel generator may be operated at 2500 kW Unit 3, 2874 kW (Unit 4) for 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or until operating temperature has stabilized and then within 5 minutes repeat Specification 4.8.1.1. 2. g.4)b).

TURKEY POINT - UNITS 3 & 4 3/4 8-8 AMENDMENT NOS.

AND JUN 15 1990

ELECTRICAL POWER SYSTEMS SURVEILLANCE RE UIREMENTS Continued 4.8. 1.1.3 Re orts " All diesel generator failures, valid or nonvalid, shall be reported to t e Commission in a Special Report pursuant to Specification

6. 9. 2 within 30 days.

Reports of diesel generator failures shall include the informa-tion recommended in Regulatory Position C.3.b of Regulatory Guide 1. 108, Revi-sion 1, August 1977.

If the number of failures in the last 100 valid tests is greater than or equal to 7, the report shall be supplemented to include the additional information recommended in Regulatory Position C.3. b of Regulatory Guide 1. 108, Revision 1, August 1977.

TURKEY POINT - UNITS 3 8( 4 3/4 8-9 AMENDMENT NOS.

ANO JUN i 5 1990

RIAL BlQFT NUMBER OF FAILURES IN d

LAST 20 VALID TESTS"

< 1 2*%

TABLE 4.8-1 DIESEL GENERATOR TEST SCHEDULE NUMBER OF FAILURES IN LAST 100 VALID TESTS

> 5 TEST FRE UENCY Once per 31 days Once per 7 days 0

dt fig t

f fit d

t f

lfdt t tilt in accordance with Regulatory Position C.2.e of Regulatory Guide 1.108, but determined on a per diesel generator basis.

For the purpose of determining the required test frequency, the previous test failure count may be reduced 'to zero if a complete diesel overhaul to like-new condition is completed, provided that the overhaul, including appropriate post"maintenance operation and testing, is specifically approved by the manu" facturer and if acceptable reliability has been 'demonstrated.

The reliabil-ity criterson shall be the successful completion of 14 consecutive tests in a single series.

Ten of these tests shall be in accordance with the routine Surveillance Requirements 4.8.1. 1.2.a.4'nd 4.8.1. 1.2.a.5; and four tests in accordance with the 184-day testing requirement of Surveillance Requirements

4. 8. 1. 1. 2. a. 4 and 4.8. 1. 1. 2. a.5.

If this criterion is not satisfied during the first series of tests, any alternate criterion to be used to transvalue the failure count to zero requires NRC approval.

""The associated test frequency shall be maintained until seven consecutive failure free demands have been performed and the number of failures in the last 20 valid demands has been reduced to one.

TURKEY POINT - UNITS 3 8c 4 3/4 8-10 AMENDMENT NOS.

AND JUN i 5 1990

FINi. IIRAET ELECTRICAl POWER SYSTEMS A.C.

SOURCES

~

~

SHUTDOWN LIMITING CONDITION FOR OPERATION 3.8.1.2 As a minimum, the following A.C. electrical power sources shall be OPERABLE:

a.

One startup transformer and associated circuits, or an alternate circuit, between the offsite transmission network and the 4160 volt

bus, A or B, and b.

One diesel generator with:

1)

For Unit 3 (3A or 3B) s A skid-mounted fuel tank and a day fuel tank, with an OPERABLE solenoid valve to permit gravity flow from the day tank to the skid mounted tank, with the two tanks together containing a

minimum of 2000 gallons of fuel oil For Unit 4 (4A or 4B)

A day fuel tank containing a minimum volume of 230 gallons of fuel 2)

A fuel storage system containing a minimum volume of fuel of 38,000 gallons (Unit 3), 34,700 gallons (Unit 4) 3)

An associated fuel transfer pump 4)

For Unit 3 only, lubricating oil storage containing a minimum volume of 120 gallons of lubricating oil 5)

For Unit 3 only capability to transfer lubricating oil from storage to the diesel generator unit and 6)

Energized HCC bus (as identified by Specification 3.8. l.1.b.).

APPLICABILITY:

MODES 5" and 6".

ACTION:

With less than the above minimum required A.C. electrical power sources OPERABLE, immediately suspend all operations involving CORE ALTERATIONS, positive reactivity changes, movement of irradiated fuel, or crane operation with loads over the fuel storage pool, and within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />, depressurize and vent the Reactor Coolant System through a greater than or equal to 2.2 square inch vent.

In addition, when in HODE 5 with the reactor coolant loops not filled, or in MODE 6 with the water level less than 23 feet above the reactor vessel

flange, immediately initiate corrective action to restore the required sources to OPERABLE status as soon as possible and increase RCS inventory as soon as possible.

t "CAUTION - If the opposite unit is in MODES 1, 2, 3 or 4 see Specification 3.8.1.1 TURKEY POINT - UNITS 3 8L 4 3/4 8"11 AMENDMENT NOS.

AND JUN i 5 1S90

ELECTRICAL POMER SYSTEMS FINAi IlRAFT SURVEILLANCE RE UIREMENTS 4.8. 1.2 The above required A.C. e1ectrical power sources shall be demonstrated OPERABLE by the performance of each of the requirements of Specifications 4.8. 1. l. 1. a, 4.8. 1. 1. 2 (except for Specification 4. 8. l. 1. 2a. 5)), and 4.8. l. 1. 3.

TURKEY POINT - UNITS 3 4 4 3/4 8-12 AMENDMENT NOS.

AND JUN 1 5 1990

ANAL BRAFT 3/4.8.2 D.C.

SOURCES

~

~

~

~

OPERATING LIMITING CONDITION FOR OPERATION 3.8.2.1 b.

APPLICAB ACTION:

The following D.C. electrical sources shall be OPERABLE:"~

125-volt D.C. Battery Bank 3A or D-52 and associated full capacity charger(s) 1)

3A1 powered by mot ontrol center (HCC) 3C with EDG 3A OPERABLE, or 2) 3A2 p ed by MCC 40 with EDG 4A and 48 OPERABLE, or 3) powered by MCC 3C with EDG 3A OPERABLE and 3A2 powered by MCC 40 with EDG 4A and 48 OPERABLE, 125-volt D.C. Battery Bank 38 or D-52 and associated full capacity char er s 1) 381 powered by MCC 38 with EDG 38 OPERABLE, or 2) 382 powered by MCC 40 with EDG 4A and 48 OPERABLE, or 3

owered by MCC 38 with EDG 38 OPERABLE and 382 powered by MCC

'DG 4A and 48 OPERABLE, 125-volt D.C. Battery A or 0-52 and associated full capacity harger(s) 1)

powered by MCC 4C with EDG 4A OPERABLE, or 2) 4A2 po ed by HCC 30 with-EDG 3A and 38 OPERABLE, or 3) 4A1 powered MCC 4C with EDG 4A OPERABLE and 4A2 powered by MCC 3D with EDG and 38 OPERABLE, 125-volt D. C. Battery Bank or 0-52 and associated full capacity charger(s) 1)

481 powered by MCC 48 with EDG 48 OPERABLE, or 2) 482 powered by HCC 3D with EDG 3A and 38 OPERABLE, or 3) 481 powered by MCC 48 with EDG 48 OPERABLE and 482 powered by MCC 30 with EDG 3A and 38 OPERABLE.

ILITY:

MODES 1, 2, 3, and 4.

SM ap a, aQb.

0 d ioQ5 Mith one of the required battery banks inoperable, or with none of the full-capacity chargers associated with a battery bank OPERABLE, restore all battery banks to OPERABLE status and at least one charger associated with each battery bank to OPERABLE status within two hours"" or be in at least HOT STANDBY within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

This ACTION applies to both units simultaneously.

"All battery chargers required to satisfy the LCO shall be powered from separate HCCs.

  • "Can be extended to 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> if the opposite unit is in MODE 5 or 6 and each of the remaining required battery chargers is capable of being powered from its associated diesel generator(s).

TURKEY POINT - UNITS 3 8( 4 '/4 8-13 AHENDMENT NOS.

AND Ense.Y 4 2 JUN i 5 19SO

~ '

PInoperability of the required EDG's specified in the LCO requirements below does not constitute inoperability of the associated battery chargers or battery banks.

Attachment to page 3/4 8-13

FIINL SHAFT D.C.

SOURCES

~

~

LIMITING CONDITION FOR OPERATION ACTION:

(Continued) or rior a oem e.A BLE. bu+

With one f t e required battery chargers not capable of being powered from its associated OPERABLE diesel generator(s),

restore the capability within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

This ACTION applies to both units simultaneously.

SURVEILLANCE RE UIREMENTS Continued 4.8.2.1 Each 125-volt battery bank and its associated full capacity charger(s) shall be demonstrated OPERABLE:

a.

At least once per 7 days by verifying that:

1)

The parameters in Table 4.8-2 meet the Category A limits, and b.

C.

2)

The total battery terminal voltage is greater than or equal to 129 volts on float charge and the battery charger(s) output voltage is > 129 volts, and if two battery chargers are connected to the battery bank, the battery charger currents do not differ from each other by more than 10X of the battery charger rating.

At least once per 92 days and within 7 days after a battery discharge with battery terminal,voltage below 105 volts (108.6 volts for spare battery D-52), or battery overcharge with battery terminal voltage above 143 volts, by verifying that:

1)

The parameters in Table 4.8-2 meet the Category B limits, 2)

There is no visible corrosion at either terminals or connectors, or the connection resistance is less than 150 x 10-

ohm, and 3)

The average electrolyte temperature of every sixth cell is above 60 F.

At least once per 18 months by verifying that:

1)

The cells, cell plates, and battery racks show no visual indication of physical damage or abnormal deterioration, 2)

The cell-to-cell and terminal connections are clean, tight, and coated with anticorrosion material, 3)

The resistance of each cell-to-cell and terminal connection is less than or equal to 150 x 10-

ohm, and 4)

Each 400 amp battery charger (associated with Battery Banks 3A and 4B) will supply at least 400 amperes at > 129 volts for at least 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />, and each 300 amp battery charger (associated with Battery Banks 3B and 4A) will supply at least 300 amperes at

> 129 volts for at least 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />.

TURKEY POINT - UNITS 3 & 4 3/4 8"14 AMENDMENT NOS.

AND JUN 1 5 1990

FIINI. 98AFT D. C.

SOURCES SURVEILLANCE RE UIREMENTS Continued d.

At least once per 18 months, during shutdown"",

by verifying that the battery capacity is adequate to supply and maintain in OPERABLE

,status all of the actual or simulated emergency loads for the design duty cycle when the battery is subjected to a battery service test.

e.

At least once per 18 months, during shutdown"*, by giving performance discharge tests of battery capacity to any battery that shows signs of degradation or has reached 85K of the service life expected for the application.

Degradation is indicated when the battery capacity drops more than 10X of rated capacity from its average on previous performance tests, or is below 90K of the manufacturer's rating.>>

f.

At least once per 60 months, during shutdown"",

by verifying that the battery capacity is at least 80K of the manufacturer's rating when subjected to a performance discharge test.

Once per 60-month interval this performance discharge test may be performed in lieu of the battery service test required by Speci.fication 4. 8. 2. 1. d.

3/4 8-15

""Except that the spare battery D-52, and any other battery out of service 1

when D-52 is in service may be tested with simulated loads during operation.

sl <~ beery bo.~W TURKEY POINT - UNITS 3 5 4 AMENDMENT NOS.

AND JUN i 5 1990

I

TABLE 4.8-2 BATTERY SURVEILLANCE RE UIREMENTS FlNAl. QRAFT CATEGORY A( )

CATEGORY 8( )

Electrolyte Level DESIGNATED PI LOT CELL

>Minimum 1 evel indication mark, and

< 4" above maximum level indication mark CONNECTED CELL

>Minimum level indication mark, and

< b" above maximum level indication mark VALUE FOR EACH CONNECTED CELL Above top of

plates, and not overflowing oat o tage vo ts Specific Gravity vo ts

> 1.195 vo ts ot more t an 0.020 below the average of all connected cells verage o

a connected cells

1. 205 verage o

a connected cells

(')

TABLE NOTATIONS (1)

For any Category A parameter(s) outside the limit(s) shown, the battery may be considered

'OPERABLE provided that within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> all the Category B

measurements are taken and found to be within their allowable values, and provided all Category A and B parameter(s) are restored to within limits within the next 6 days.

(2)

For any Category B parameter(s) outside the limit(s) shown, the battery may be considered OPERABLE provided that the Category B parameters are within their allowable values and provided the Category B parameter(s) are restored to within limits within 7 days.

(3)

Any Category B parameter not within its allowable value indicates an inoperable battery.

(4)

Corrected for electrolyte temperature and level.

(5)

Or battery charging current is less than 2 amps when on charge.

(6)

Corrected for average electrolyte temperature.,

TURKEY POINT - UNITS 3 4 4 3/4 8-16 AMENDMENT NOS.

AND JUN

>S 1990

D.C.

SOURCES SHUTDOWN LIMITING CONDITION FOR OPERATION FIND BRAR'.8.2.2 As a minimum, three 125 volt battery banks, each with at least one associated full capacity charger capable of being powered by an OPERABLE diesel generator, shall be OPERABLE.

APPLICABILITY:

MODES 5" and 6".

ACTION:

With one or more of the required 125 volt battery banks or required associated full-capacity chargers inoperable or not capable of being powered from an OPERABLE diesel generator, immediately suspend all operations involving CORE ALTERATIONS, positive reactivity changes, or movement of irradiated fuel; initiate corrective action to restore the required battery banks and associated full-capacity chargers to OPERABLE status as soon as possible, and within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />, depressurize and vent the Reactor Coolant System through at least a

2.2 square inch vent.

. SURVEILLANCE RE UI EMENTS 4.8.2.2 The above required 125 volt battery banks and associated full-capacity

~

~

~

~

~

~

chargers shall be demonstrated OPERABLE in accordance with Specification 4.8.2. l.

"CAUTION - If the opposite unit is in MODES 1, 2, 3 or 4, see the corresponding Limiting Condition for Operation 3.8.2.1.

TURKEY POINT - UNITS 3 8( 4 3/4 8-17 AMENDMENT NOS.

AND JUN i 5 1990

F IA~ SHAFT 3/4.8. 3 ONSITE POWER DISTRIBUTION OPERATING LIMITING CONDITION FOR OPERATION 3.8.3.1 The following electrical busses shall be energized in the specified manner with the tie breakers open between redundant busses within the unit""

and between the busses of Units 3 and 4.

a.

One train of A. C.

Busses consisting of:

1) 4160-Volt Bus A, 2) 480-Volt Load Center Busses A,

C and H"*", and 3) 480-Volt Motor Control Center Busses A (Unit 4 only),C and D*"",

b.

One train of A.C. Busses consisting of:

1) 4160-Volt Bus B

2) 480-Volt Load Center Busses B,

D and H""", and 3) 480-Volt Motor Control Center Busses B and D*""

c.

One opposite unit train of AC busses consisting of either:

1) 4160-Volt Bus A, 480"Volt Load Center Busses A,

C and H""",

and 480-Volt Motor Control Center Busses A (Unit 4 only),

C and D""", or 2) 4160"Volt Bus B, 480-Volt Load Center Busses B,

D and H""",

and 480-Volt Motor Control Center Busses B and D""".

d.

120 Volt AC Vital Panel 3P06 and 3P21 energized from its associated inverter connected to D.C.

Bus 3B.""""

e.

120 Volt AC Vital Panel 4P06 and 4P21 energized from its associated inverter connected to D.C.

Bus 3B.""""

f.

120 Volt AC Vital Panel 3P07 and 3P22 energized from its associated inverter connected to D.C.

Bus 3A.""""

g.

120 Volt AC Vital Panel 4P07 and 4P22 energized from its associated inverter connected to D.C.

Bus 3A.""""

h.

120 Volt AC Vital Panel 3P08 and 3P23 energized from its associated inverter connected to D. C.

Bus 4B. """"

120 Volt AC Vital Panel 4P08 and 4P23 energized from its associated inverter connected to D.C; Bus 4B.**""

"For Motor Control Center busses, vital sections only.

""With the opposite unit in MODE 5 or 6, its 480-Volt Load Center can be cross-tied under. conditions specified in Specification 3,8.3.2. a.

"""Electrical bus can be energized from either train of its unity onX sg't~g (>~~to~

to oPPoS'8'a t~'O raus b< 0PKQ.RSlX Vec We. Qn'A(S'jy

'te YAOlaS 1)'K) 3a ance '4

""*"Abaclup inverter may be used to replace the normal inverter provided the nonaal inverter qnnthe opposite unit is not replaced at the same time.

1

0m th,e. s~~~

hC bus

$ o TURKEY POINT -

I 3

4 3/4 8-18 AMENDMENT NOS.

AND JUN i 5 19SO

FllNL 88AFT ONSITE POWER DISTRIBUTION j.

120 Volt AC Vital Panel 3P09 and 3P24 energized from its associated inverter connected.to D.C.

Bus 4A.""""

k.

120 Volt AC Vital Panel 4P09 and 4P24 energized from its associated inverter connected to O.C.

Bus 4A.*""*

l.

125 Volt D.C.

Bus 3001 energized from an associated battery charger and from Battery Bank 3A or 0-52, m.

n.

125 Volt D.C.

Bus 3023 energized from an associated battery charger and from Battery Bank 3B or 0-52, 125 Volt D.C.

Bus 4D01 energized from an associated battery charger and from Battery Bank 4B or 0-52, and Spark b++k>

~

ba~4, o.

125 Volt D.C.

Bus 4023 energized from an associat charger and from Battery Bank 4A or 0-52 APPLICABILITY:

MODES 1, 2, 3, and 4.

ACTION:

ery b.

With one of the required trains (3.8.3.1a.,

b.,

and c) of A.C.

emergency busses not fully energized (except for the required LC's and MCC s associated with the opposite unit), reenergize the train within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

With any of the required LC's and/or HCC's associated with the opposite unit inoperable, restore the inoperable LC or HCC to OPERABLE status in accordance with Table 3.8-1 or Table 3.8-2 as applicable or place the unit in at least HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

C.

With one A.C. vital panel either not energized from its associated inverter, or with the inverter not connected to its associated O.C.

bus:

(1) Reenergize the A.C. vital panel within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at least HOT STANDBY within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />; and (2) reenergize the A. C. vital panel from an inverter connected to its associated D. C.

bus

  • """Aback-up inverter may be used to replace the normal inverter, provided t

ahe normal inverter (iithe opposite unit is not replaced at the same time.

On the. so~a OG b~S TURKEY POINT - UNITS 3 4 4 3/4 8-19 AMENDMENT NOS.

AND JUN i 5 1990

0

ONSITE POWER DISTRIBUTION LIMITING CONDITION fOR OPERATION Continued FINN. IlRAFT ACTION: (Continued) within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least HOT STANDBY within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />'nd in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

This ACTION applies to both units simultaneously.

d.

With one D.C.

bus not energized from its associated battery bank or associated

charger, reenergize the D.C.

bus from its associated battery bank within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />" or be in at least HOT STANDBY within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

This ACTION applies to both units simultaneously.

1 SURVEILLANCE RE UIREMENTS 4.8.3. 1 The specified busses shall be determined energized and aligned in the required manner at least once per 7 days by verifying correct breaker align-ment and indicated voltage on the busses.

"Can be 'extended to 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> if the opposite unit is in MODE 5 or 6 and each of the remaining required battery chargers is capable of being powered from t

its associated diesel generator(s).

TURKEY POINT - UNITS 3 8E 4 3/4 8"20 AMENDMENT NOS.

AND JUN i 5 1990

TABLE 3.8-1 APPLICABLE TO UNIT 3 BASED ON UNIT 4 LOAD CENTERS AND MOTOR CONTROL CENTERS INOPERABLE ALLOWABLE OUTAGE TIMES ANALgQH Unit 4 Load Centers and Motor Control Centers Inoperable (Any MODE)

Al1 owab l e Outage Times Unit 3 - HODES 1, 2,

3 or 4 ic 4A HCC 4A With AC Trains 3A, 3B,-

4A, 4 4B OPERABLE N/A N/A With AC Trains 3A, 3B, 4 4A OPERABLE 72 N/A With AC Trains 3A, 3B, 8( 4B OPERABLE N/A N/A LC 4C and/or HCC 4C LC 4H and/or HCC 4D LC 4B and/or HCC 4B LC 4D N/A N/A N/A N/A 72 i s not.. a,p pl Ica,I l~ (N/A').

"If the battery charger powered from the ou -o -se v ce LC and/or is not required by LCO 3.8.2. 1, the out-of-service time

""Ifneither of the battery chargers powered from the out-of-service LC and/or HCC is required by LCO 3.8.2. 1, the out-of-service time is 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />.

TURKEY POINT - UNITS 3 84 4 3/4 8-21 AMENDMENT NOS.

AND JUN i 5 19SO

r' a

jj (<~ii PQ fl

TABLE 3.8"2 APPLICABLE TO UNIT 4 BASED ON UNIT 3 LOAD CENTERS AND MOTOR CONTROL CENTERS INOPERABLE ALLOWABLE OUTAGE TIMES Unit 3 Load Centers and Motor Control Centers Inoperable (Any MODE)

Allowable Outage Times Unit 4 -

MODES 1, 2, 3 or 4,

With AC Trains 4A, 4B, 3A, 4 3B OPERABLE With AC Trains 4A, 4B, 83 3A OPERABLE With AC Trains 4A, 4B, 4 3B OPERABLE LC 3A LC 3C and/or MCC 3C LC 3H and/or MCC 30 LC 3B and/or MCC 3B LC 30 N/A N/A 72 2A N/A N/A N/A N/A 72 lS hOt aPP l 3'Ca.b)e,(NlA).

  • Ifthe battery charger powered from the out-of-s rvice LC and/or MCC is not i i d iy Lii 3.8.2.1, ii i-i.

i ii 4

  • "Ifneither of the battery chargers powered from the out-of-service LC and/or MCC is required by LCO 3.8.2. 1, the out-of-service time. is 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />.

TURKEY POINT - UNITS 3 5 4 3/4 8-22 AMENDMENT NOS.

AND JUN 15 1SSQ

).(

1

FIND olgrt'NSITE POWER DISTRIBUTION SHUTDOWN LIMITING CONDITION FOR OPERATION 3.8.3.2 As a minimum, the following electrical busses shall be energized in the specified manner:

a.

One train of A.C. emergency busses associated with the unit (3.8.3. la.

or b. ) consisting of one 4160-volt and three 480-volt A. C.

emergency busses load centers" and three (four for Unit 4 Train A) vital sections of motor control center busses, b.

Two 120-volt A.C. vital busses for the unit energized from their associated inverters"" connected to their respective D.C. busses, and c.

Three 125-volt D. C.

busses energized from their associated battery banks.

APPLICABILITY MODES 5""" and 6""*.

ACT?ON:

. With any of the above required electrical busses not energized in the required

manner, immediately suspend all operations involving CORE ALTERATIONS, positive e

reactivity changes, or movement of irradiated fuel, initiate corrective action to energize the required electiical busses in the specified manner as soon as

possible, and within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />, depressurize and vent the RCS through at least a 2.2 square inch vent.

SURVEILLANCE RE UIREMENTS 4.8.3.2 The specified busses shall be determined energized in the required manner at least once per 7 days by verifying correct breaker alignment and indicated voltage on the busses.

0 "With the opposite unit in MODE 1, 2, 3, or 4, the 480-volt load centers can only be cross-tied upon issuance of an engineering evaluation to prevent exceeding required electrical components maximum design ratings and to ensure availability of the minimum required equipment.

  • "A backup inverter may be used to replace the normal inverter provided the normal inverter in the opposite unit is not replaced at the same time.
  • ""CAUTION-If the opposite unit is in MODES 1, 2, 3, or 4, see the corresponding Limiting Condition for Operation 3.8.3. l.

TURKEY POINT - UNITS 3 & 4 3/4 8-23 AMENDMENT NOS.

AND JUN 15 1990

Fjeii SHAFT REACTIVITY CONTROL SYSTEMS BASES BORATION SYSTEMS (Continued)

The boration flow path specification allows the RWST and the boric acid storage tank to be the boron sources.

Due to the lower boron concentration in the RWST, borating the RCS from this source is less effective than borating from the boric acid tank and additional time may be required to achieve the desired SHUTDOWN MARGIN required by ACTION statement restrictions.

The ACTION statement restrictions for the boration flow paths allow continued operation in mode 1 for a limited time period with either boration source flow path or the normal flow path to the RCS (via the regenerative heat exchanger) inoperable.

In this case, the plant capability to borate and charge into the RCS is limited and the potential operational impact of this limitation on mode 1 operation must be addressed.

With both the flow path from the boric acid tanks and the regenerative heat exchanger flow path inoperable, immediate initiation of action to go to COLD SHUTDOWN is required but no time is specified for the mode reduction due to the reduced plant capability with these flow paths inoperable.

Two charging pumps are required to be OPERABLE to ensure single functional capability in the event an assumed failure renders one of the pumps or power supplies inoperable.

Each bus supplying a pump can be fed from either a

e Emergency Diesel Generator or the offsite grid through a startup transformer.

The boration capability of either flow path is sufficient to provide the required SHUTDOWN MARGIN in accordance with Figure 3. 1-1 from expected qperating conditions after xenon decay and cooldown to 2004F.

The maximum expected boration capability requirement occurs at BOL from full power equilibrium xenon conditions and requires 3080 gallons of 20,000 PPM borated water from the boric acid storage tanks or 320,000 gallons of 1950 PPM borated water from the refueling water storage tank (RWST).

With the RCS temperature below 200'F, one boron injection source flow path is acceptable without single failure consideration on the basis of the stable reactivity condition of the reactor and the additional restrictions prohibiting CORE ALTERATIONS and positive reactivity changes in the event the single boron injection system source flow path becomes inoperable.

The boron capability required below 200'F is sufficient to provide a

SHUTDOWN MARGIN of 1X hk/k after xenon decay and cooldown from 200'F to 140 F.

This condition requires either 500 gallons of 20,000 ppm borated water from the boric acid storage tanks or 20,000 gallons of 1950 ppm borated water from the RWST.

TURKEY POINT " UNITS 3 5 4 B 3/4 1-3 AMENDMENT NOS.

AND JUN 1 5 1S90

FINAL SHAFT 3/4.8 ELECTRICAL POWER SYSTEMS BASES 3/4.8. 1 3/4.8.2 and 3/4.8. 3 A. C.

SOURCES D. C.

SOURCES and ONSITE POWER The OPERABILITY of the A. C.

and D. C power sources and associated distribu-tion systems during operatiori ensures that sufficient power will be available to supply the safety-related equipment required for:

(1) the safe shutdown of the facility, and (2) the mitigation and control of accident conditions within the facility.

The loss of an associated diesel generator for system(s),

subsystem(s),

train(s),

component(s) or device(s) does not result in the system(s),

subsystem(s),

train(s),

component(s) or device(s) being considered inoperable for the purpose of satisfying the requirements of its applicable Limiting Condition for Operation for the affected unit provided:

(1) its corresponding normal power source is OPERABLE; and (2) its redundant system(s),

subsystem(s),

train(s),

component(s),

and device(s) that depend on. the remaining OPERABLE diesel generators as a source emergency power to meet all applicable LCO's are OPERABLE.

This allows operation to be governed by the time limits of the ACTI statement associated with the inoperable diesel generator, not the individ H~~~yeq,

. ACTION statements fov each

system, subsystem, train, component or device.

gue 1

to the existence of shaved

systems, there are certain conditions that require

~

~

~

~

~

special provisions.

These provisions are stipulated in the appropriate LCO's as needed.

The ACTION requirements specified for the levels of degradation of the power sources provide restrictions upon continued facility operation commensurate with the level of degradation.

The OPERABILITY of the power sources is consistent with the initial condition assumptions of the safety analysis and is based upon maintaining adequate onsite A.C. and D. C. power

~

sources and associated distribution systems OPERABLE during accident conditions coincident with an assumed loss-of-offsite power and single failure of on'e onsite A.C. source.

Two physically independent A.C. circuits exist between the offsite transmission network and the onsite Class 1E Distribution System by utilizing the following: (1) a total of eight transmission lines which lead to five separate transmission substations tie the Turkey Point Switchyard to the offsite power grid; (2) two dual-winding startup transformers each provide 100X of the A and'B train 4160 volt power from the switchyard to its associated unit.

In addition, each startup INsevt 3 TURKEY POINT - UNITS 3 8( 4 B 3/4 8-1 AMENDMENT NOS.

AND JUN I 5 NQ

More specifically, LCO's 3.5.2 and 3.8.2. 1 require that associated EDG's be OPERABLE in addition to requiring that Safety Injection pumps, battery chargers, and battery

banks, respectively also be OPERABLE.

This EDG requirement was placed in these particular LCO's due to the shared nature of these systems to ensure adequate EDG availability for the required components.

A situation could arise where a unit in MODES 1, 2, 3, or 4 could be in full compliance with LCO 3.8. 1. 1, yet be using shared equipment that could be impacted by taking an EDG out-of-service on the opposite unit.

In this situation, diesel generator ACTION 3.8. 1. I.d, which verifies redundant train OPERABILITY, may not be applicable to one of the units.

Thus, specific requirements for'EDG OPERABILITY have been added to the appropriate LCO's of the shared systems (3.5.2 and 3.8.2. 1).

It is important to note that in these particular LCO's the inoperability of the required EDG does not constitute inoperability of the other components required to be OPERABLE in the LCO.

Specific ACTION statements are included in 3.5.2 and 3.8.2. 1 for those situations where the required components are OPERABLE (by the definition of OPERABILITY) but not capable of being powered by an OPERABLE EDG.

"Attachment to page B 3/4 8-1

FllNL llRAFT ELECTRICAL POWER SYSTEMS BASES Continued transformer has the capability to supply backup power of approximately 2500 kW to the opposite unit's A-train 4160 volt bus.

Two emergency diesel generators (EDG) provide onsite emergency A; C. power for each unit.

EDG's 3A and 3B provide Unit 3 A-train, and B-train emergency power, respectively.

EDG's 4A and 4B provide Unit 4 A-train and B-train emergency power, respectively.

Due to the shared nature of numerous electrical components between Turkey Point Units 384, the inoperability of a component on an associated unit will often affect the operation of the opposite unit.

These shared electrical components consist primarily of both startup transformers, three out of four 4160 volt busses, and associated 480 volt motor control centers, all four 125 volt D.'C. busses, all eight 120 volt vital A. C. panels and eight out of twelve vital A.C. inverters,.four out of eight battery chargers, and all four battery banks.

Depending on the component(s) which is (are) determined inoperable, the resulting ACTION can range from the eventual shutdown of the opposite unit long after the associated unit has been shutdown (30 days) to an immediate shutdown of both units.

Therefore, ACTION times allow for an orderly sequential shutdown of both units when the inoperability of a component(s) affects both units with equal severity.

When a single unit is affected, the

. time to be in HOT STANDBY is 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

When. an ACTION statement requires a

dual unit shutdown, the time to be in HOT STANDBY is 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

This is to

~

~

~

allow the orderly shutdown of one unit at. a time and not jeopardize the stability of the electrical grid by imposing a dual unit shutdown.

As each startup transformer only provides the limited equivalent power of approximately one EDG to the opposite Units A-train 4160 volt bus, the allowable out-of-service time of 30 days has been applied before the opposite unit is required to be shutdown.

Within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, a unit with an inoperable startup transformer must reduce THERMAL POWER to less than or equal to 30K RATED THERMAL POWER.

The 30K RATED THERMAL POWER limit was chosen because at this power level the decay heat and fission product production has been reduced and the operators are still able to maintain automatic control of the feedwater trains and other unit equipment.

At lower power levels the operators must use manual control with the feedwater bypass lines.

By not requiring a complete unit shutdown, the plant avoids a condition requiring natural circulation and avoids intentionally relying on engineered safety features for non-accident conditions.

TURKEY POINT " UNITS 3 & 4 B 3/4 8-2 AMENDMENT NOS.

AND JUN 1 5 890

FillNi DRAFT ELECTRICAL POWER SYSTEMS BASES Continued With one startup transformer and one of the three required EDG's inoperable, the unit with the inoperable transformer must reduce THERMAL POWER to less than or equal to 30X RATED THERNL POWER within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, based on the loss of its associated startup transformer, whereas operation of the unit with the OPERABLE transformer is controlled by the limits for inoperability of the EDG.

The notification of a loss of startup transformer(s) to the NRC is not a 10 CFR 50.72/50.73 requirement and as such will be made for information purposes only to the NRC Operations Center via commercial lines.

With an EDG out of service, an ACTION statement and a Surveillance Requirement are provided to demonstrate the required startup transformers and their associated circuits are OPERABLE.

Mhen one diesel generator is inoperable, there is also an additional ACTION requirement to verify that required system(s),

subsystem(s),

train(s),

component(s),

and device(s) that depend on the remaining required OPERABLE diesel generators as a source of emergency powe'r to meet all applicable LCO's, are OPERABLE.

This requirement is intended to provide assurance that a loss-of-offsite power event will not result in a complete loss of safety function of critical systems during the period one of the diesel generators is inoperable.

This requirement allows continued operation to be governed by the time limits of the ACTION statement associated with the inoperable diesel generator.

The loss of a diesel generator does not result i the associated system(s),

subsystem(s),

train(s), component(s),

or device s) be'onsidered=inoperable provided: (1) its corresponding normal power source OPERABLE:

and (2) its redundant system(s),

subsystem(s),

train(s),

component(s),

and device(s) that depend on the remaining required OPERABLE diesel generators as a source of emergency power to meet all applicable LCO's, are OPERABLE.

A footnote is added to ensure the remaining required EDG's are tested for OPERABILITY if one of the required EDG's becomes inoperable due to reasons other than preplanned preventative maintenance.

This statement will ensure that tests are performed to verify common mode failures do not exist.

When in Nodes 1, 2, 3 or 4, a unit depends on one EDG and its associated train of busses from the opposite unit in order to satisfy the single active failure criterion for safety injection (SI) pumps and other shared equipment required dur'ing a loss-of-coolant accident with a loss-of-offsite power.

Therefore, one EDG from the opposite unit is required to be OPERABLE along with the two EDG's associated with the applicable unit.

TURKEY POINT - UNITS 3 8L 4 I B 3/4 8-3 AHENDMENT NOS.

AND JLIN 15 1990

FINAi BfQFr ELECTRICAL POWER SYSTEMS BASES Continued With both startup transformers inoperable, the unit(s) are required to be shutdown consecutively, after 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

A consecutive shutdown is used because a unit without its associated transformer must perform a natural circulation cooldown.

By placing one unit in COLD SHUTDOWN before starting shutdown of the second unit, a dual unit natural circulation cooldown is avoided.

The term verify means to administratively check by examining logs or other information to determine if required components are out-of-service for maintenance or other reasons.

It does not mean to perform the surveillance requirements needed to demonstrate the OPERABILITY of the component.

The EDG Surveillance testing requires that each EDG be started from normal conditions only once per 184 days with no additional warmup procedures.

Normal conditions in this instance are defined as the pre-start temperature and lube.oil conditions each EDG normally experiences with the continuous use of prelube systems and immersion heaters.

The fuel supply specified for the Unit 3,EDG's is based on the original

. criteria and design bases used to license the plant.

The specified fuel supply will ensure sufficient fuel for either EDG associated with Unit 3 for

~

~

~

~

~

~

~

~

~

~

~

~

~

~

~

at least a week.

The fuel supply specified for the Unit 4 EDG's's based on the criteria provided in ANSI N195-1976 as endorsed by Regulatory Guide 1.137.

The specified fuel supply will ensure sufficient fuel for each EDG associated with Unit 4 for at least a week.

TURKEY POINT - UNITS 3 4 4 3/4 8-4 AMENDMENT NOS.

AND JUN i 5 19SO

ELECTRICAL POWER SYSTEMS BASES 'ontinued The Surveillance Requirements for demonstrating the OPERABILITY of the diesel generators are in accordance with the recommendations of Regulatory Guides 1.9, "Selection of Diesel Generator Set Capacity for Standby Power Supplies,"

March 10, 1971; 1.108, "Periodic Testing of Diesel Generator Units Used as Onsite Electric Power Systems at Nuclear Power Plants,"

Revision 1, August 1977; and l. 137, "Fuel-oil Systems for Standby Diesel Generators,"

Revision 1, October 1979.

The OPERABILITY of the minimum specified A.C. and D.C, power sources and associated distribution systems during shutdown and refueling ensures that (1) the facility can be maintained in the shutdown or refueling condition for extended time periods, and (2) sufficient instrumentation and control capability is available for monitoring and maintaining the unit status.

During a unit shutdown, the one required circuit between the offsite transmission network and the onsite Class 1E Distribution System can consist of at least the associated unit startup transformer feeding one 4160 volt Bus 'A or B, or the opposite unit's startup transformer feeding the associated unit's 4160 volt Bus A, or the associated unit's 4160 volt Bus A or B backfed through its auxiliary transformers with the main generator isolated.

As inoperability of numerous electrical components often affect the e

operation of the opposite unit, the applicability for the shutdown LIMITING CONDITION FOR OPERATION (LCO) for A.C. Sources, D.C. Sources and Onsite Power Distribution all contain statements to ensure the LCO's of the opposite unit are considered.

The allowable out-of-service time for the D.C.

busses is 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> with one unit shutdown in order to allow for required battery maintenance without requiring both units to be shutdown.

Provisions to substitute the spare battery for any one of the four station batteries have been included to allow for battery maintenance without requiring both units to be shutdown.

The requirement to have only one OPERABLE battery charger associated with a required battery bank permits maintenance to be conducted on the redundant battery charger.

The minimum number of battery chargers required to be OPERABLE is based on the following criteria:

eh 1)

A minimum of one battery charger per bus with each power from a separate 480 volt MCC is required to satisfy the single failure criteria when assuming the failure of a MCC.

This restriction prohibits the use of two chargers powered from the same bus for meeting the minimum requirements.

TURKEY POINT - UNITS 3 8 4 B 3/4 8-5 AMENDMENT NOS.

AND JUN i 5 1SSO

FINAL SHAFT ELECTRICAL POWER SYSTEMS BASES Continued 2)

To satisfy the single failure criteria, when assuming a

loss-of-offsite power with the loss of an

EDG, an additional restriction is stipulated which requires each battery charger to have its associated diesel generator(s),

OPERABLE.

This requires both EDG's associated with a swing bus battery charger to be OPERABLE.

Provisions for requiring the OPERABILITY of the EDG associated with the battery charger is explicitly specified in the LCO.

This is because conditions exist where the affected unit would not enter the applicable ACTION statement in the LCO without this provision.

For example, with Unit 3 in.

MODE 1 and Unit 4 in MODE 5, the operability of both EDG 4A and 4B is not required.

One could postulate conditions where battery chargers 4Al, 3A2, 3B2, or 4B1 could be used to satisfy the LCO without having an associated OPERABLE EDG, unless specific provisions were made to preclude these conditions.

An out-of-service l.imit of 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> is applied when the required EDG is not OPERABLE.

With less than the required battery chargers OPERABLE, an allowable out-of-service time of 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> is applied, which can be extended to 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> if the opposite unit is in MODES 5 or 6 and each of the remaining required battery chargers is capable of being powered from its associated

~

~

~

~

~

~

diesel generator(s).

Verifying average electrolyte temperature above the minimum for which the battery was sized, total battery terminal voltage on float charge, connection resistance

values, and the performance of battery service and discharge tests ensure the effectiveness of the charging system, the ability to handle high discharge
rates, and verifies the battery capability to supply its required load.

Table 4.8-2 specifies the normal limits for each designated pilot cell and each connected cell for electrolyte level, float voltage, and specific gravity.

The limits for the designated pilot cell's float voltage and specific gravity, greater than 2.13 volts and not more than 0. 015 below the manufacturer's full charge specific gravity or a battery charger current that had stabilized at a low value, is characteristic of a charged cell with adequate capacity.

The normal limits for each connected cell for float voltage and specific gravity, greater than 2. 13 volts and not more than 0. 020 below the manufacturer's full charge specific, gravity with an average specific gravity of all connected cells not more than 0. 010 below the manufacturer's full charge specific gravity, ensures the OPERABILITY and capability of the battery.

TURKEY POINT - UNITS 3 5 4 B 3/4 8"6 AMENDMENT NOS.

AND JUN 1 5 1990

FINAI. DRAFT ELECTRICAL POWER SYSTEMS BASES Continued Operation with a battery cell's parameter outside the normal limit but within the allowable value specified in Table 4.8-2 is permitted for up to 7 days.

During this period:

(1) the allowable values for electrolyte level ensures no physical damage to the plates with an adequate electron transfer capability; (2) the allowable value for the average specific gravity of all the cells, not more than 0.020, below the manufacturer's recommended full charge specific gravity, ensures that the decrease in rating will be less than the safety margin provided in sizing; (3) the allowable value for an individual cell's specific gravity ensures that an individual cell's specific gravity will not be more than 0.040 below the manufacturer's full charge specific gravity and that the overall capability of the battery will be maintained within an acceptable limit; and (4) the allowable value for an individual cell's float voltage, greater than or equal to 2.07 volts, ensures the battery's capability to perform its design function.

The ACTION requirements specified for the inoperability of certain Motor Control Centers (MCC's),

Load Centers (LC's) and the 4160-Volt Busses provide restrictions upon continued facility operation commensurate with the level of degradation on each unit and the amount of time one could reasonably diagnose

. and correct a minor problem.

The level of degradation is based upon the types of equipment powered and the out-of-service limit imposed on that equipment by

~

~

~

~

~

~

~

~

~

~

~

~

~

~

~

~

~

the associated ACTION statement.

If this degradation affects the associated unit only, then no restriction is placed on the opposite unit and an out-of-service limit of 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> (except for MCC's 3A, 3K, 4J and 4K) is applied to the associated unit.

Since MCC's 3A, 3K, 4J and 4K are used to power EDG auxiliaries, an out-of-service limit of 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> is applied as required by 3.8.1. 1. If the degradation impacts both units (i.e., required shared systems or cross-unit loads),

then an out-of-service limit of 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> is applied to the associated unit and an out-of-service limit based on the most restrictive ACTION requirement for the applicable shared or cross-unit load is applied to the opposite unit.

For example, if being used to satisfy 3.8.2.1, the Battery Chargers 3A2, 3B2, 4A2, and 4B2 are cross-unit loads and have out-of-service limits of 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />.

This is the most restrictive limit of the applicable equipment powered from MCC 3D and 40.

Therefore, an out-of-service limit of 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> is applied if the battery charger is required to be OPERABLE.

TURKEY POINT - UNITS 3 & 4 B 3/4 8-7 AMENDMENT NOS.

AND JUN 15 1990

rear ssan ELECTRICAL POWER SYSTEMS BASES Continued I

The ACTION requirements specified when an A.C. vital panel is not energized from an inverter connected to its associated D.C.

bus provides for two phases of restoration.

Expedient restoration of an A.C. panel is required due to the degradation of the Reactor Protection System and vital instrumentation.

The first phase requires reenergization of the A. C. vital panel within two hours.

During this'hase the panel may be powered by a Class lE constant voltage transformer (CVT) fed from a vital MCC.

However, the condition is permissible for only 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> as the second phase of the ACTION requires reenergization of the A.C. vital panel from an inverter connected to its associated D.C.

bus within 24'hours.

Failure to satisfy these

ACTIONS, results in a dual unit shutdown.

With one unit shut down one 4160-volt Bus on the associated unit can be deenergized for refueling outage maintenance.

The associated 480-Volt Load Centers can th n be cross-tied upon issuance of an engineering evaluation.

pe.r io6'ic TURKEY POINT - UNITS 3 8r, 4 B 3/4 8"8 AMENDMENT NOS.

AND JUN 1 5 1990

l

,)IJ"