UNITED 'STATES OF AMERICA NUCLEAR REGULATORY COMMISSION BEFORE THE ATOMIC SAFETY AND LICENSING BOARD
'In the Matter of FLORIDA POWER
& LIGHT COMPANY (Turkey Point Nuclear Generating Unit Nos.
3 and 4
Docket Nos.. 50-250-SP 50-251-SP (Proposed Amendments to Facility Operating License to Permit Steam Generator Repairs)
AFFIDAVIT OF FREDERICK G.
FLUGGER AND H.
H. JABALI ON CONTENTION 4A My name is Frederick G. Flugger.
My business address. is P. 0.
Box 529100,
- Miami, Florida, 33152.
I am Manager of Plant Engineering Licensing, Power Plant Engineering Department, Florida Power
& Light Company (FPL).
A statement of my professional background and qualifications is attached to this affidavit and made a part thereof.
My name is Habib H. Jabali.
My business address is P. 0.
Box 529100, Miami, Florida, 33152.
I am Manager of Civil Engineering, Power Plant Engineering Department, Florida Power
& Light Company.
A statement of my professional background and qualifications is attached to this affidavit and made a part thereof.
This affi'davit addresses Contention 4A which states:
There are likely to occur radioactive releases from one or more stored assemblies to unrestricted areas which, violate 10 CFR Part 20 or are not as low as is reasonably achiev-able within the meaning of 10 CFR Part 50, as a result of:
(a) substantial immersion of the steam generators in sea water during a hurricane; 81 0.4830$ Eg,'.
(b) movement of steam generators while so immersed; (c) impact of such moving steam generators upon the walls of the structure in which they are stored or upon another object or objects; (d) corrosion resul ting from moisture, sea water, or sal t spray; or (e) leakage through the floor beneath the stored steam generators.
We are familiar with FPL's plans for storage of the lower assemblies.
The "NRC Staff Second Motion for Summary Disposition" moved, among other things, for the summary disposition of Contention 4A.
There was included in the motion a "Statement of Material Facts as to Which There Are No Genuine Issues to be Heard" (pp. 6-9; variously hereafter "Statement of Material Facts" or "Staff's material facts") which contains statements applicable to each subpart of Con-tention 4A.
With the inconsequential corrections referred to bel'ow, we agree
,with the Statement of Material Facts.
Contention 4A a
, (b
, and c
Statement of Material Facts Nos.
1 through 9 address subparts (a), (b) and (c) of Contention 4A.
The aspect of the contention addressed by these subparts presupposes that the steam generator lower assemblies (SGLAs) will become immersed by the flood associated with a hurricane.
The Staff's material facts correctly demonstrate that the SGLAs will not float and that the steam generator storage compound (SGSC) will be so situated that the flood stage associated with a probable maximum hurricane (PMH) will not immerse the SGLAs.
The discussion infra (i) provides additional technical support of the Staff's material facts, and (ii) demonstrates that SGLAs subjected to hurricane conditions pose no undue radiological hazard to
public health and safety.
Each stored SGLA will weigh about 185 tons and its specific gravity will exceed 1.7 (it will be about 2).
The SGLAs will not float.
If it were postulated that the SGLAs were fully immersed in sea water, based on a
data for comparable environments, the corrosion effect of immersion for one full year would be 0.008 inches.
Since a hurricane induced immersion would be measured in hours, not years, an immersion associated with a hurricane will give rise to much less than 0.008 inches.
Thus corrosion resulting from immersion in sea water does not pose a threat to SGLA integrity.
The area. underlying the proposed site of the SGSC has been
- demucked, and crushed limestone structural fill material was placed directly on the limestone bedrock in layers.
Each layer was compacted before the next layer was set in place.
The result is a compacted limestone plateau with a surface elevation of approximately
+17.5 feet mean low water (MLll).
The SGSC's structural footings will be set about 2 feet below the +17.5 feet HLl< surface elevation of the limestone plateau.
Compacted crushed limestone is a proven structural fillmaterial.
The favorable structural characteristics result, in part, from the chemical bonding which occurs when oolitic limestone, which contains calcium carbonates, is crushed,
- graded, wetted and compacted.
The recementation (chemical bonding) results in a firm monolithic mass which resists hydraulic forces since energy must be expended by the hydraulic forces to break loose particles of material for eventual water-borne migration.
By contrast, compacted sands do'ot have any binding qualities and hence any initial hydraulic energy is immediately available for particle
migration (erosion).
Erosion of compacted 1'imestone is appreciably less than erosion of sand, since erosion of sand is based upon a mass consisting of in-dividual particles of a nominal size that are free to be transported.
Accord-ing'}y, because of the recementation
- process, erosion of the limerock fill during a
PNH will not be sufficient to undermine the SGSC.
The Staff's material facts No.
5 indicates that, there is about 65 feet of com-pacted limestone between the SGSC and the 3/1 slope leading to the +7 foot t1LW elevation.
The 65 foot number was apparently based on a preliminary SGSC loca-tion, which has been altered somewhat by the final SGSC location which is slightly west and south of the location evaluated by the Staff.
The result of SGSC relocation is that about 180 feet of compacted limestone fill will lie to the east of the SGSC (the area most vulnerable to wave attack).
.Based on the cement-like nature of compacted limerock, it can be concluded that PHH-induced erosion effects would not undermine the SGSC foundation.
The large quantities of this material that surround the SGSC ensure building foundation integrity.
The SGLAs will be housed in a substantial reinforced concrete structure, the Steam Generator Storage Compound (SGSC).
This structure will consist of 2'-0" thick reinforced concrete exterior walls with a 2'-0" thick reinforced concrete interior wall that separates the Unit 3 and Unit 4 SGLA storage areas.
These walls will be founded on continuous strip footings located about 2 feet below finished grade.
The SGSC roof will be watertight, consisting of precast concrete
- panels, with a minimum 4 inch reinforced concrete topping, resulting in a one-foot thick roof at a minimum.
The floor wil.l be rei'nforced concrete approximately 6" thick.
Steel saddles will support each SGLA during storage.
The design of the SGSC complies with applicable design requirements of the Code of Metropolitan Dade County, Florida and the South Florida Building Code.
The Code of Metropolitan.Dade County, Florida requires that the elevation of buildings be above the 100 year hurricane flood level of 12 foot MSL.
The South Florida Building Code specifies that buildings shall be designed for wind speeds of not less than 120 mph.
The exterior wall thickness was established based on the radiological shielding requirements and not on the hurricane induced wind loadings which would have required less thickness.
- Thus, the structure has a higher resistance to wind loadings than would result from a design where the wind loading governed.
- Hence, although not specifically designed for the PMH wind loadings, the SGSC has considerable capability to accommodate wind loadings that exceed those associated with the 120 mph design value.
The PMH wind loadings will not cause stresses in structural members to exceed their respective yield stress
- values, and thus, a
catastrophic collapse of the building is precluded.
In addition, prior to removal from the containment, SGLA exterior surfaces will be decontaminated as necessary to ensure that removable contamination will not be significant as defined by 49 CFR 5 173.397 regarding surface contamination on radioactive shipments.
Thus, the potential for radioactive effluent releases from external surfaces is effectively eliminated.
Also, the steam generators will 'be completely sealed to preclude the release of radioactive materials from the internal surfaces of the SGLAs.
The SGLAs will have a minimum wall thickness of'.63 inches, and the various openings in the steam generators will be closed by either steel plates or steel bar stock as follows:
(a)
The large channel head and transition cone openings will have steel
- plates, three inches thick, placed over them and will be welded closed by a 1-1/2 inch fillet.weld.
(b)
The small nozzle connections (i.e., instrument taps,
- drains, and blowdown nozzles, all 2 inches and smaller) will have bar stock inserted into the openings and.will be welded closed by a 1-1/2 inch fillet weld.
(c)
The handhold openings will have steel inserts welded with a l-l/2 inch fillet weld to the inside of the opening.
The handhold cover plates will also be put back into place over the handholes.
Furthermore, the welds on the SGLAs will be coated with a protective coating to provide added protection against corrosion and additional assurance that oxygen will not enter the steam generators via the welds.
In conclusion, the SGLAs will be completely sealed to preclude the release of radioactive materials contained on internal SGLA surfaces; external surfaces will be decontaminated; and the PMH will not jeopardize the integrity of the stored SGLAs.
Thus, there is no credible mechanism for a release of radioactivity from within the lower assemblies during storage as a result of the PMH, and there is no NRC regulation or any real-world radiological concern that would necessitate establishing a
PMH design criterion for the SGSC.
The discussion infra demonstrates that even if it is arbitrarily assumed that the radioactivity contained in the SGLAs were released to the hurricane storm surge, the potential consequences would be acceptable.
It must be noted that the assumed release is an analytical assumption and is not expected to occur during the period of onsite SGLA storage.
I 8efore discussing the postulated release, it is necessary to define the nature of the radioactive source contained in the stored SGLAs.
The earliest time that a
SGLA could be placed in the SGSC is 80 days after shutdown.
Since the repair activities for Units 3 and 4 and placement of their respective SGLAs in storage are scheduled to commence about one year apart, the maximum curie content in the SGSC would occur about 445 days after commencement of repair activities on the first unit.
At this time, the activity within three lower assemblies will have experienced 80 days of decay since shutdown and the three other lower assemblies will have experienced 445 days of decay since shutdown.
In assessing the potential radiological hazard associated with the stored
- SGLAs, the properties of the radioactivity must be defined and evaluated.
Physical characteristics relevant to the evaluation are:
~ The radioactive properties of the radionuclides present.
~ The physical nature of the radioactive material.
~ The solubility of the radionuclides present in water.
~ The volatility of the radionuclides present.
The activity contained on the interior surfaces of the steam generators prior to removal is distributed as follows:
~ Tubes
~ Tube Sheet
~ Tube Ends
~ Divider Plates
~ Channel Head 88.0/o 1.45 5.3g 2.6/
2.7X The radioactivity in a SGLA consists almost entirely of activated corrosion products in the form of metal oxides, most of which are insoluble'hese metallic oxides form a thin, tightly adherent layer'n the primary side surfaces of the steam generator.
Sea water has negligible ability to dissolve these corrosion products.
During normal operation, the primary coolant flows through the steam generator's tubes at 24 feet/sec and 2235 psig and 546-602'F - - - the erosive effects of this flow do not remove this radioactive layer from the tubes.
In fact, if one wants to remove the film, i.e.,
decontaminate the SGLA interior
- surfaces, extreme measures must be used.
These include blasting with oxide grit or soaking in harsh chemicals.
Hence, it is difficult to envision any realistic mechanism during storage which could release more than a negligible amount of this oxide layer.
Table 1 provides a compilation of the isotopes present in the oxide layer.
The activity at 80 and 445 days is indicated thereon for a single SGLA.
The
point to note is that the total activity has fallen from about 220 curies to about 105 curies in a period of one year.
This is due to the natural decay of the radio-nuclides contained in the oxide layer.
The process is ongoing, thus, the potential radiological hazard diminishes with time.
The table also shows the time for each radionuclide to reach 1/10, 1/100 and 1/1000 of its initial concentration.
The overall decay of the SGLA radioactive source with time is depicted by Figure l.
Examination of Table 1 and Figure 1 indicates that:
( 1)
The bulk of the nuclides essentially disappear in a year or two, and that only Hn-54, Ce-144, Cs-137 and Co-60 remain for appreciable periods of time.
(2)
There is a rapid reduction in total activity in the SGLAs during the first year or so.
Thereafter, the decay is characterized by the behavior of the longer lived isotopes, predominantly Co-60.
The only appreciable soluble isotopes remaining after 30 days are cerium, barium, ruthenium, and cesium.
However, their contribution to the total number of curies is less than 1/2X at 445 days, and only Cs-137 is long-lived.
There are no volatile radionuclides present.
When considering hurricane-related
- effects, the soluble isotopes are the isotopes of concern since they could be potentially dissolved and carried to the environment via the receding hurricane storm surge.
The insoluble isotopes are not of concern because. of the adherent nature of the activated corrosion products.
For the sake of this evaluation, it will be assumed that 100'f the soluble isotopes in all six SGLAs would be released to the receding storm surge.
We believe this assumption to be conservative.
Before proceeding further, it should be noted that storms with surges greater than the 100-year hurricane flood level will result in more dilution of any postulated radiological release than that associated with the 100-year hurricane flood level.
Therefore, from a radiological standpoint, the postulated release to the 100-year hurricane flood level is limiting - -
use of PMH flood conditions would yield more favorable results.
The 100-year flood results in a sufficient flood stage to transport the postulated release to Biscayne
- Bay, and since it is the limiting radiological hurricane flood level, it was selected as a basis for evaluation.
The result.of this evaluation is that the release of 100Ã of the soluble isotopes contained in all six SGLAs at day 445 will rapidly be diluted by the turbulent waters created by the storm to inconsequential levels.. Analysis shows that 2.5 X
10 ft of water would be needed to dilute the release to within the levels of 10 CFR Part 20, Appendix B, Table II. Sufficient mixing of the release with the 3
X 10 ft of water in Biscayne Bay would occur within 17 hours1.967593e-4 days <br />0.00472 hours <br />2.810847e-5 weeks <br />6.4685e-6 months <br /> to dilute the release to average concentrations within these levels.
This analytical evaluation can be extended further.
If 100K of all (soluble and insoluble) isotopes contained in all six SGLAs at day 445 is assumed to be
- released, the conclusion is substantially the same.
Within 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />, the available dilution volume of water in Biscayne Bay would be sufficient to dilute the entire radioactive inventory of the SGLAs to average concentrations wi thin the levels of 10 CFR Part 20, Appendix B, Table II.
Since hurricane conditions will prevail during the dilution period, and since Biscayne Bay is not potable, and since it can be reasonably assumed that public use of Biscayne Bay during hurricane con-ditions is unlikely, any postulated release of SGLA radioactivity during a
hurricane will not endanger the public health and safety.
moreover, it must be reemphasized that the above-postulated release is entirely hypothetical.
Since the steam generators will be completely sealed and housed in a substantial structure, and since there is no realistic way to release an appreciable fraction of their radioactive inventory, a hurricane poses no radiological hazard to public health and safety of consequence.
There is no factual basis to demonstrate that radioactive releases of any consequence can resul't from the landfall of a severe hurricane at, or in the vicinity of, the Turkey Point site.
To the contrary, the facts demonstrate that the proposed design is proper and that it is in 'full compliance with NRC and local'equirements.
Contention 4A d
and e
Statement of Viaterial Facts Nos.
10 through 22 address subparts (d) and (e) of Contention 4A.
The aspect of the contention addressed by these subparts is premised on a corrosion-related mechanism releasing radioactivity to the en-vironment.
.The Staff's material facts correctly demonstrate that there is no credible liquid pathway to the environment from the stored SGLAs.
The discus-sion infra is provided to (i) further support and clarify the Staff's position, and (ii) demonstrate that the liquid or gaseous pathways pose no undue radio-logical hazard to public health and safety.
As dicussed
~su ra. the SGLAs will be completely sealed and the external surfaces decontaminated prior to placing the SGLAs in storage.
During the period of onsite
- storage, the SGLAs will not be unattended; a
SGLA surveillance program will be in effect.
The SGLA surveillance program will be comprised of quarterly visual in-spections of the external surfaces of the lower assemblies, area radiation surveys, and random swipes of the welds sealing the covered openings in the lower assemblies.
Standard swipe techniques as described in 49 CFR 0 173.397 will be used to assess removable contamination.
49 CFR 0
173.389 (e) defines removable radioactive contamination as that radioactive contamination which can be readily removed in measurable quantities by wiping the contaminated surface with an absorbent material.
The measurable quantity is not considered significant if it does not exceed the limits specified in 49 CFR 5 173.397.
If the contamination levels on the swipe of the SGLA exceed the appropriate limit, the external surfaces will be decontaminated until the. meas'ured activity on the swipe is within the limit, and the source of any leakage will be investigated.*
J The SGLA surveillance program will periodically reaffirm the in situ integrity of the stored SGLAs during the period of onsite storage.
The only mechanism that could potentially breach the in situ integrity of the SGLAs during normal storage conditions would be corrosion related.
But for the reasons cited infra, through-wall corrosion is not likely.
Thus, there is no mechanism that could be expected to lead to a release of radioactive materials from the interior of the stored SGLAs.
- Statement of Material Facts No.
10 states that "the outside of the assemblies will be periodical:ly decontaminated..."
As stated
- above, they will be decontaminated only when swipes indicate it to be necessary.
' Corrosion of the exterior of the SGLAs was evaluated assuming (1) normal atmosphere, (2) continuous condensation atmosphere, and
(,'3) sea water spray conditions.
Corrosion which may be expected on the interior of the SGLAs was evaluated.assuming (1) dry atmosphere, and (2) the presence of residual reactor coolant water contained in plugged tubes of the SGLA.
The results of this evaluation indicate that (1) under normal atmospheric con-
- ditions, a total exterior surface corrosion of 0.03 inches is estimated for a 30-year storage period; (2) under conditions of continuous atmospheric conden-
- sation, a total exterior surface corrosion of 0.06 inches is estimated for a 30-year storage period; (3) sea water spray conditions are not expected inside the storage compound because the SGSC wi 11 be located at approximately elevation
+17.5'LW, because.
the SGSC will be an enclosed structure, and because of the distance of the SGSC from the shoreline; (4) there is insufficient oxygen available within the sealed,SGLA to support oxidation (corrosion) of the steel to the extent that through-wall penetration could.result from interior corrosion; (5) under dry conditions within the sealed steam generators, the corrosion is negligible; and (6) under conditions of residual reactor coolant water within the SGLA, the total uniform corrosion of the immersed. portions of the inside.
surfaces of the steam generators is 0.025 inches, and of the unimmersed portions of the inside surfaces will be less than 0.005 inches.
The phenomenon of pitting, corrosion was also evaluated.
Pitting corrosion is a
very localized corrosive attack that can manifest itself under stagnant conditions.
The results indicate that (1) localized pit corrosion can.be reasonably estimated to.be 5 times the uniform. corrosion rate; (2) the maximum depth of internal corrosion pits is estimated to be 0.125 inches for immersed surfaces and 0.025 inches for unimmersed surfaces, and (3) the rate of external corrosion pitting is estimated to be 0.005 inches per year for humid conditions and 0.01 inches per year for conditions of a continuous atmospheric condensation.
The corrosion evaluation reaffirms the Staff's material fact No.
18 relating to through-wall corrosion, viz, "the probabili.ty of a through-wall corrosion crack is so small as to be insignificant."
In order to assess analytically the potential consequences of 'a radioactive release from the stored
- SGLAs, a radioactive release was postulated.
The evalua-tion that follows demonstrates that the stored SGLAs pose no radiological hazard to public health and safety.
It should be emphasized that the release discussed infra is an analytical assumption and is not expected to occur during the period of onsite SGLA storage.
The potential for airborne releases associated with SGLA storage does not exist since:
( 1)
For the reasons described
~su ra the,level of contamination on the exterior surfaces of the SGLA will not be significant.
(2)
The SGLAs will be completely sealed, thereby precluding an air-borne release.
- However, even if it is assumed that an SGLA, as a result of corrosion, develops an airborne release
- pathway, the activity that could be released would not be in a volatile or aerosol form, i.e., in a form that could be dispersed as a gaseous effluent.
The oxide layer in the SGLAs does not contain any radio-nuclides that will vaporize.
Particulates that conceivably could be postulated to leave the oxide layer would:be too heavy to disperse to the environment as an airborne release.
The occurrence of a radioactive release to the environment via the liquid release pathway is very unlikely since; (1)
For the reasons described
~su ra, a mechanism.that could cause a breach in the integrity of the sealed SGLA is not present.
(2)
Only a small fraction of the SGLA inventory is soluble in water and thus, potentially available for transport, via the liquid pathway.
(3)
Liquids released. to the SGSC would likely be retained by the reinforced concrete floor of the SGSC.
If an SGLA leak is postulated, and the SGSC reinforced concrete floor is assumed to be cracked, and it is assumed that the leakage passes through approximately 18 feet of compacted limerock fill and limestone
- bedrock, then the leakage would enter the aquifer that underlies
.the site, which at that location is saline and non-potable.
While any of the four Turkey Point units are in operation, the movement of ground water beneath the site of the SGSC is controlled by the Turkey Point Cooling Canal System.
Ground water movement is controlled by the differential operating head maintained between the intake approach channel and the discharge basin of the cooling canal system.
Operation of the cooling system maintains the water level in the intake channel at a level slightly below the water table, so that it behaves as a discharge sink for the adjacent ground water.
At the same time, water in the discharge channel is maintained slightly above the water table, so that it behaves as a source of recharge to the adjacent ground water.
The result is that ground water beneath the SGSC site moves to the intake channel.
In the highly unlikely event that none of the four Turkey Point u~its are opera-
- tional, ground water movement beneath the site of the SGSC would be controlled by the natural ground water gradient, which is generally away from land.
Any leakage under this condition would tend to move to the intake channel, as described above.
It should be noted that the cooling system-dominated ground water regime would result in movement of the postulated leakage to the cooling canal system more rapidly than the transit time of several years cited in the Staff's material fact No.
15.
This is due to the hydraulic gradient i~posed on the natural ground-water gradient by operation of the cooling system.
As shown infra, the transient time is inconsequential since the postulated leakage will be diluted in the cooling canal system to inconsequential levels.
Should it be conservatively assumed that 100% of the solubles were simultaneously released from all six of the SGLAs at day 445 after shutdown of the first unit to be repaired, a volume of 2.5 X 10 ft of water would be required to dilute 8
this hypothetical release to within the NRC limits contained in Appendix B, Table II of, 10 CFR Part 20 (commonly known as "drinking water" limits).
The water normally available in the cooling canals is 7
X 10 ft Thus, there is more 8
3 than ample water available to dilute a postulated release to inconsequential levels; levels that are within 10 CFR Part 20, Appendix B, Table II.
To place the values of 10 CFR Part 20 into perspective, compare the drinking water guideline value of 0.02 pCi/ml for the only long-lived soluble isotope contained in the SGLAs, Cs-137, to the naturallyoccurring radioactivity in a few common substances.
The naturally occurring radioactive content of tea is 0.4 pCi/m1, of cereal is 0.6 pCi/ml, and of human blood is 0.9 pCi/m1.
Since any assumed leakage will enter.the cooling canals, and since the cooling canals are saline and unfit for human consumption, and since the analytically postulated leak results in concentrations in the cooling canals that are within the commonly called "drinking water" standard of 10 CFR Part 20, and since the resulting con-centrations are comparable to the natural radioactivity found in common substances, it is clear that a postulated radioactive leak from the SGSC poses no undue radio-logical hazard to public health and safety.
If one addresses the real-world effects of SGLA storage, the material facts indicate:
( 1)
There is no potential for airborne radioactive release from the SGSC.
(2)
There is no reasonable mechanism for a liquid radioactive release from the SGSC.
Storage of the SGLAs in the proposed SGSC poses no radiological hazard of con-sequence to public health and safety.
~
~ FURTHER AFFIANT SAYETH NOT Date:
A ril/i, 1981 Frederi ck G.-'Flugger
~
i
~i".~,
~ ~
9 C~
STATE OF FLORIDA
)
)
SS.
COUNTY OF DADE
)
SWORN to and subscribed before me this, I
1991.
9 j
9 9
5'F )CY"< n 'i FF day Notary Public NOTARY PllSLIC STATE Of FloklOA AT LARGE IAY COPAhiISSION EXNkES DEC. 26 l98I FURTHER AFFIANT SAYETH NOT Date:
A rile~
1981
~
'TATE OF FLORIDA
)
)
ss.
COUNTY OF DADE
)
H.
H. Jabal i
(
9 F
~,
9 9
'9 SWORN to and subscribed before me this Si'A
.c:-c -.i Zii day of
/ >z,i', 1981.
Notary PubldSi~xv wsllc STATE cf Rcelcp, AT huaK IO
TABLE 1
SGL'A CONTENTS ISOTOPE ACTIVITY (Ci)
HALF-LIFE TIME TO REACH Cr-51 80 day decay 445 day decay
.966 27.7 days 92d 1
184d 276d Mn-54 Fe>>59 Co-58 Co<<60 Zr-95 Nb 95 Nb-95m Mo-99 Tc-99m Rv-103 Xe-131m I-131 I"132 Te<<132 Cs-137 Ba>>137m aa-140 La-140 Ce-141 Ce-144 Pr-144 Np-239 8.99
.709 62.98 92.99 5.01 9.063
. 048
- 1. 951
.002
.358
.339
. 031
.036
.722 16.2 16.2 4.01
.002 1.771 81.54
.097
.210
.001
.0032
.350
.332
.0 6.667 6.667 312.5 days 44.6 days 70.8 days 5.27 years 64.0 days 35.0 days 87.0 hours0 days <br />0 hours <br />0 weeks <br />0 months <br /> 66.0 hours0 days <br />0 hours <br />0 weeks <br />0 months <br />
'.02 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> 39.4 days 11.74 days 8.06 days 2.28 hours3.240741e-4 days <br />0.00778 hours <br />4.62963e-5 weeks <br />1.0654e-5 months <br /> 78 hours 30.2 years 2.55 minutes 12.8 days 40.3 hours3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> 32.5 days 284.8 days 17.3 minutes 2.35 days 1038d 148d 235d 17.5y 212d 116d 116d 219h 219h 13ld 38.9d 26.0d 7h 259h 100.3y 100.3y 42d 42d 108d 945d 945d 7.8d 2076d 3114d 296d 444d 470d 705d 35y 52.5y 425d 638d 232d 349d 232d 349d 438h 658h 438h 658h 262d 392d 77.9d 116.9d 53d 80d 15h 22h 518h 777h 200.7y 30ly 200.7y 301y 85d 127d 85d 127d 216d 324d 1889d 2834d 1889d 2834d
- 15. 6d 23.4d
-3
<Activity less than 10
100 50.
58 M AT 80 DAYS
'30 2796 AT 445 DAYS 10 LOWER 'ASSEMBLY GAMMARADIOACTIVE DECAY VS TIME FIGURE -1
.1 0
10 15 20 TIME AFTER SHUTDOWN (YEARS) 35
STATEMENT OF PROFESSIONAL QUALIFICATIONS FREDERlC G.
FLUGGER EXPERIENCE 1973 Florida Power 6 Light Company:
present Mana er, Plant En ineerin Licensin
, Power Plant Engineering Department for Florida Power 6 Light Company.
Responsible for nuclear licensing, fossil licensing, quality assurance and administrative procedures.
Direct engineering activities of FPL, the architect. engineer and other consultants required to secure permits and
- licenses, to respond to NRC and other government
- agencies, and to select sites for the Company's generating facilities.
Provide expert testimony at public hearings and to regulatory bodies; engineering evaluations required by regulatory bodies; safety evaluations for modifications to operating nuclear units; independent design review; QA training of engineering personnel; and develop and maintain licensing related computer codes.
Pro 'ect En ineer, St. Lucie Units l,and 2, for Florida Power 6 Light Company.
Directed internal and external engineering efforts'or two 810 Mw nuclear units (PWR).
Numerous presentations to NRC and ACRS,,and testified at the St. Lucie Unit 62 public. hearing.
Provided technical direction to Architect Engineer, Nuclear Steam System Supplier and technical consultants.
1972-1973 NUS/Southern Nuclear Engineering:
Developed and managed the NUS Licensing 'Information
,Service.
Responsible for the development of a 500 Mw nuclear units'PWR) hot functional test program.
1970-1972 Long Island Lighting Company:
Assistant to the Mana er of Nuclear Pro'ects for Long Island Lighting Company.
Responsible for the licensing, safety, nuclear related design and fuel management aspects of the Shoreham Nuclear Project
'(819 Mw BWR).
A member of the Company's Engineering Assurance Review Committee.
Extensive involvement in the Shoreham public hearing.
'1964-1970 Consolidated Edison Company of New York, Inc.:
Mana er of Nuclear Bureau of Consolidated Edison Company of New York.
Directed the Company's Nuclear and Reactor Fuels Divisions.
Responsible for AEC licensing, shielding design, accident analysis, reactor plant safety, nuclear computer code development and fuel cycle engineering.
Member Nuclear Facilities Safety Committee.
En ineer, Nuclear Division for Consolidated Edison Company of New York.
Directed development of safety analysis reports and technical specifications; engineering associated with engineered safety features
- design, containment leak rate testing, urban nuclear plant siting studies and shielding design; and offsite radiological dose evaluations.
Instructor for the Company's Power Reactor Technolo course.
E~n ineer for Consolidated Edison Company of Neo York.
An engineer in the Control and Instrument Division and at the Company's Ravenswood generating station.
1963-1964 U.
S. Merchant Marine:
Licensed En ineerin Officer aboard U.S. Merchant vessels.
In charge of maintenance and operation of marine steam-turbine power plants and indirect mechanical refrigeration systems.
1962-1963 University of Maryland:
Teachin Assistantshi in the Mechanical Engineering Department, University of Maryland.
Taught undergraduate courses in Thermodynamics, Strength of Materials and Engineering Graphics.
EDUCATION State Universit of New York Maritime Colle e; Bachelor of Marine Engineering, with Honors, 1960.
Universit of California at Berkele
- Master of Science in Engineering
- Science, Atomic Energy Commission Science and Engineering Feollow, 1961.
Specialized graduate work in Advanced Mathematics, Heat
- Transfer, Reactor Theory, Reactor Kinetics, and Nuclear Fuel Management (42 credits),
1962-1968.
MIT Nuclear Reactor Safety, 1966.
NUS Advanced Nuclear Fuel Management, 1970.
Florida Power a Light Management Development Coursesf 1975 Present.
MEMBERSHIP/
LICENSES American Nuclear Society.
American Society of Mechanical Engineers (ASME).
ASME Committee on Nuclear Quality Assurance, 1977 Present; Vice Chairman, Design Control Work Group, 1980 Present.
Third Assistant Marine Engineer, Steam and Diesel.
Atomic Industrial Forum, Probablistic Risk Assessment Subcommittee, 1981 Present.
PUBLICATIONS 1.
F.
G.. Flugger, et. al., "Turkey Point Units 3
a 4
Steam Generator Repair-Licensing Evaluation",
American Nuclear Society Winter Meeting, November 1978.
2.
F.
G. Flugger, J.
N. Burford, "A Fire Hazard, Evaluation for Operating Nuclear Plants",
American Nuclear Society Winter Meeting, December 1977.
3.
Masters Thesis, "Associated Particle Method for Measurement, of the. Absolute Neutron Flux Produced by the T (d,n)
~ Reaction", University.of California at
- Berkeley, 1961.
~
~
STAT)~)ENT OF PROFESSIONAL QUALIFICATIONS HABIB H. 3ABALI EXPERIENCE Florida Power
& Light Company."fiami, Florida:
1976 to present
~fang er, Plant Civil En ineerin Power Plant Engineering Department.
Responsible for overall plant Civil Engineering, both internal and external to FPL, for nuclear and fossil generating, stations.
Also responsible 'for monitoring plant construction to trouble shoot and resolve technical problems as they are identified to ensure that building codes and civil standards are met.
- Plan, organize and manage the Civil section to ensure most effective use of available manpower.
Interview prospective employees,
- select, develop and assign personnel and oversee their training to ensure technical competence to meet civil engineering objectives.
Supervisor Plant Civil Enaineerin Power Plant Engineering Department.
Establish scope and design criteria of power plants in the civil, structural and architectural areas and direct the engineering activities of architect-engineers and other consultants to ensure implementation thereof.
Responsible for supervising the Civil Engineering Section personnel in preparing design modifications and additions at operating power plants and in providing tecnnical assistance in the civil engineering areas to other FPL departments.
Senior Civil En ineer Power Plant Engineering Department.
Respon-sible for the review and approval of design, procurement, bid reviews and resolution of construction problems for all civil/
structural related activities for 'St. Lucie Unit 1 and' Nuclear Power Plants.
1980 to present Lecturer in civil engineering, University of Hiami, Department of Civil Engineering.
1971 1976 Sargent
& Lundy Engineers Chicago Illinois Senior Structural En ineer Responsible for developing and coordinating structural standards pertaining to the design of power plants.
Review and evaluate sta'te of the art technical papers, studies and reports and determine their impact on on-going power plant design.
Supervised the design of the Turbine Building Complex for the Bailly Nuclear Power Plant.
Directed and supervised the design of major modifications and additions to several existing power plants.
This included the design of structures supporting Electrostatic Precipitators, air and gas ducts, chimneys and ID and FD fan foundations.
1971 1973, Desi n
En ineer.
liorked on the design of various buildings and structures within power plant complex, such as:
Auxiliary Building, Reactor Building, Fuel Handling Building, etc.
This included steel as well as rein-forced concrete designs for both Category I and non-Category I structures.
1970 1971 Research Assistant Northwestern University.
This research dealt with the behavior of structures under dynamic loads and was sponsored by a grant from the U.S.
Army.
The results led to the development of an improved mathematical model for soil-structure interaction and the selection of dynamic stiffness of foundations.
1968 1969 Research Assistant University of Miami.
Duties consisted mainly of analyzing and developing solutions to stress con-centrations around cracks in composite members.
This research'as sponsored by a grant from the National Science Foundation.
EDUCATION University of Miami Coral Gables, Florida.
Graduated in 1968 with a Bachelor of Science in Civil Engineering, Cum Laude and Departmental Honors.
Graduated in 1970 with a Master of Science in Civil Engineering.
Northwestern Universit Evanston, Illinois.
Graduated in 1971 with a:iaster of Science in Theoretical
& Applied Mechanics.
University of Miami Coral Gables, Florida.
Currently preparing for Doctoral Dissertation in Structural Mechanics.
MEMBERSHIPS Professional Engineer in the states of Florida and Illinois.
Member of American Concrete Institute.
Member of American Society of Mechanical Engineers.
Member of American Institute of Steel Construction.
Academic Honorary Phi Eta Sigma Pi Mu Epilson Pi Delta Phi PUBLICATIOiVS 1.
"Torsional Oscillations of a Layer Bonded to an Elastic Half-Space",
INTERVATIONAL JOURNAL OF SOLIDS
& STRUCTURES.
Vol. ~10 'anuary
- 1974, pp. 1-13.
2.
"Torsional Stiffness of Layer Bonded to an Elastic Half-Space",
INTERNATIONAL JOURNAL OF SOLIDS
& STRUCTURES.
Vol. 11.
1975 pp.
1219-1221.
3.
"Stresses in Concrete Chimneys Weakened by Openings",
JOURNAL OF THE AMERICAN CONCRETE INSTITUTE, Proceedings Vol. ~73 No.
~8 August 1976 PP.
465-468.
UNITED STATES OF AMERXCA'UCLEAR REGULATORY COMMXSSON BEFORE THE ATOMIC SAFETY AND LICENSING BOARD Docket Nos.
50-250-SP 50-251-SP IN THE MATTER OF
)
FLORIDA POWER
& LIGHT COMPANY
)
(Turkey Point Nuclear Generating
)
Units Nos.
3 and 4
)
(Proposed Amendments to Facility Operating License to Permit Steam Generator Repairs)
CERTIFICATE OF SERVICE I HEREBY CERTIFY that copi'es of Licensee's Answer
.Supporting NRC Staff Motion for Summary Disposition of Contention 4a and Affidavit of Frederick G., Flugger and H.
H. Jabali on Contention 4a were served on the following by deposit in the United States mail, first class, properly stamped and addressed, on the date shown below:
- Marshall E. Miller, Esq., Administrative Judge
- Chairman, Atomic Safety and Licensing Board Panel U.S.. Nuclear Regulatory Commission Washington, D.C.
20555
- Dr. Emmeth A. Luebke, Administrative Judge Atomic Safety and Licensing Board Panel U.S. Nuclear Regulatory Commission
'ashington, D.C.
20555
- Dr. Oscar H. Paris, Administrative Judge Atomic Safety and Licensing Board Panel U.S. Nuclear Regulatory Commission Washington, D.C.
20555 Mr. Mark P.
Oncavage 12200 S.W. 110th Avenue Miami, Florida 33176
~~ego ussso
~~(~, ()s(<(yy$gAS
Harold F. Reis, Esq.
Steven P. Frantz, Esq.
Lowenstein,
- Newman, Reis a Axelrad 1025 Connecticut
- Avenue, N.W.
Washington, D.C.
20036
- Steven C. Goldberg, Esq.
Office o'f the Executive Legal Director U.S. Nuclear Regulatory Commission Washington, D.C.
20555 Atomic Safety and Licensing Board Panel U.S. Nuclear Regulatory Commission Washington, D.C.
20555 Docketing and Service Section Office of the Secretaiy U.S. Nuclear Regulatory Commission Washington, D.C.
20555
- Burt Saunders, Esq.
Assistant Dade County Attorney 1626 Dade County Courthouse Miami, Florida 33130
- Henry H. Harnage, Esq.
Peninsula Federal Building 10th Floor 200 S.E. First Street Miami, Florida 33131
- Neil Chonin, Esq.
1400 AmeriFirst Building One Southeast Third Avenue Miami, Florida 33131 STEEL HECTOR 6 DAVIS Co-counsel for Licensee 1400 Southeast First National Bank Building Miami, Florida 33131 Telephone (305) 577-2863 By Norman A. Coll April 17, 1981
- Additional Service By Hand or Courier