UNIT SHUTDOWNS AND POWER REDUCTIONS REPORT MONTH: JULY 1995 REVISION 1 UNIT NAME:

DATE COMPLETED BY:

TELEPHONE:

PAGE:

October 9, 1995 D.C.

COOK UNIT-1 August 8, 1995'.F.

Bussone 616-465-5901 Page 1 of 1 I

DURATION NO.

DATE TYPE HOURS METHOD OF SHUTTING LiCENSEE DOWN EVENT SYSTEM COMPONENT CAUSE AND CORRECTIVE ACTION REASON REACTOR REPORT NO.

CODE CODE TO PREVENT RECURRENCE 317 950714 F

X QN tlUI

%0'IO CIM ClIXI UIUI O< 318 950716 F

'~

OO DOO au~

56.1 371.5 H

95-003 N/A SB*

N/A V*

N/A At 0426 Unit 1 received a reactor trip signal as a result of a turbine trip due to low condenser vacuum.

The cause of the loss of condenser vacuum was a cracked socket weld connecting the 'drain trap to the condenser A steam dump control valve.

At 1153 while attempting to parallel the main generator to the grid excessive field voltage was applied.

This resulted in damage to the transformer core and the accumulation of hydrogen in the transformer.

Revised Data 10/9/95 F:

S:

Forced Scheduled 2

Reason:

A:

Equipment Failure (Explain)

B:

Maintenance or Test C:

Refueling D:

Regulatory Restriction E:

Operator Training and License Examination F:

Administrative G:

Operational Error (Explain)

H:

Other (Explain) 3 Method:

1:

Manual 2:

Manual Scram 3:

Automatic Scram 4:

Other (Explain) 4Exhibit G Instructions for preparation of data entry sheets for Licensee Event Report (LER) File (NUREG 0161) 5Exhibit I:

Same Source

0

'C