Monthly Operating Rept for Mar 1991 for DC Cook Unit 2
ML17328B005
Person / Time
Site: Cook 
Issue date: 03/31/1991
From: Gillett W
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To:
Shared Package
ML17328B004 List:
References
NUDOCS 9104160361
Download: ML17328B005 (6)


Text

N.R.C.

OPERATING DATA REPORT DOCKET NO.

50-316 DATE 01-Apr-91 COMPLETED BY WT GILLETT TELEPHONE 616-465-5901 OPERATING STATUS

1. Unit Name D.

C.

Cook Unit 2

2. Reporting Period MAR.91
3. Licensed Thermal Power (MWt) 3411 4.

Name Plate Rating (Gross MWe) 1133

5. Design Electrical Rating (Net MWe) 1100 6.

Maximum Dependable Capacity (GROSS MWe) 1100 7.

Maximum Dependable Capacity (Net MWe) 1060 notes

8. If Changes Occur in Capacity Ratings (Items no.

3 through 7) Since Last Report Give Reasons 9.

Power Level To Which Restricted. If Any (Net MWe) 10.

Reasons For Restrictions. If Any:

11. Hours in Reporting Period 12.

No. of Hrs. Reactor Was Critical

'13. Reactor Reserve Shutdown Hours 14.

Hours Generator on Line

15. Unit Reserve Shutdown Hours 16.

Gross Therm.

Energy Gen.

(MWH) 17.

Gross Elect.

Energy Gen.

(MWH)

18. Net Elect.

Energy Gen.

(MWH)

19. Unit Service Factor
20. Unit Availability Factor
21. Unit Capacity Factor (MDC Net)
22. Unit Capacity Factor (DER Net)
23. Unit Forced Outage Rate 24.

Shutdowns Scheduled over Next Six This Mo.

Yr.

744.0 691.7 0.0 686.4 0.0 2241782 738100 712823 92.3 92.3 90.4 87.1 7.7 Months (Type, to Date 2160.0 2107.7 0.0 2102.4 0.0 6885186 2271720 2193907 97.3 97.3 95.8 92.3 2.7 Date,and Cumm.

116112 '

77242.6 0.0 75688.3 0.0 233052239 76058560 73252874 66.5 66.5 60.7 59.1 13.3 Duration):

25. If Shut Down At End of Report Period, Estimated Date of Startup:
26. Units in Test Status (Prior to Commercial Operation):

Forcast INITIALCRITICALITY INITIALELECTRICITY COMMERCIAL OPERATION Achieved 9104160361 910403 PDR ADOCK 05000316 R

PDR

AVERAGE DAILY POWER LEVEL (MWe-Net)

DOCKET NO.

50-316 UNIT TWO DATE 01-Apr-91 COMPLETED BY WT GILLETT TELEPHONE 616-465-5901 DAY MONTH AVERAGE DAILY POWER LEVEL MAR.91 DAY AVERAGE DAILY POWER LEVEL 1

2 3

4 5

6 7

8 9

10 11 12 13 14 15 16 1091 1079 1081 1085 1087 1090 1086 1090 1092 1090 1092 1090 314 0

62 417 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 666 1069 1091 1089 1083 1093 1086 1092 1083 1082 1088 1098 1097 1048 1089

UNIT SHUIDOWNS AND POWER REDUCZIONS REPORT MOl~:

March 1991 DOCKET NO:

UNIT NAME DATE:

OOMPLEZED BY:

TELEPHONE 50-316 D.C.

OOOK UNIT 2 April 3, 1991 E.C. Schimmel (616) 465-5901 METHOD OF SHVZXXNG LICENSEE DURATION DOWN EVEPZ SYSZEM ODMPONENZ CAUSE AND CORR1&ZIVE ACZION TO NO.

DATE TYPE HOURS R1RSON REACIOR REPORT NO.

CODE CODE5 PREVENT RIKURRENCE 214 910313 F

57.7 H

91-003-00 ZZ ZZZZZZ A turbine/reactor trip occurred at 0651 hours0.00753 days <br />0.181 hours <br />0.00108 weeks <br />2.477055e-4 months <br /> on 910313 during a severe sy electrical disturbance caused by down 345 KV and 765 KV transmission lines during an ice storm. Ihe turbine trip was initiated by the moisture separator high level trip. The return to power was delayed due to an unexplained overspeed trip on the turbine driven auxiliary feedpump.

Ihe unit was returned to service at 1631 hours0.0189 days <br />0.453 hours <br />0.0027 weeks <br />6.205955e-4 months <br /> on 910315. A study of the system disturbance induced trip is being initiated.

1 F:

S:

2 Forced Reason:

Scheduled A:

Bpu.pment Failure (Explain)

B:

Maintenance or Test C:

Refueling D:

Regulatory Restriction E:

Operator Training and Li~Rumination F:

Administrative G:

Operational Error (Explain)

H:

Other (Explain) 3 Method:

1:

Manual 2:

Manual Scram 3:

Automatic Scram 4:

Other (Explain) 5 Exhibit G Instructions Exhibit I:

Same Source for preparation of data entry sheets for Licensee Event Report (LER) File (NUREG 0161)

DOCKET NO:

UNIT NAME:

COMPLETED BY:

TELEPHONE:

DATE PAGE 50-316 D.C.

Cook Unit, 2 E. C.

Schimmel (616) 465-5901 April 3, 1991 1 of 2

MONTHLY OPERATING ACTIVITIES March 1991 HIGHLIGHTS The unit entered the reporting period at 100% Rated Thermal Power.

A turbine/reactor trip occurred at 0651 hours0.00753 days <br />0.181 hours <br />0.00108 weeks <br />2.477055e-4 months <br /> on 910313 during a severe system electrical disturbance caused by downed 345 KV and 765 KV transmission lines during an ice storm.

The turbine trip was initiated by the moisture separator high level trip. The return to power was delayed due to an unexplained overspeed trip on the turbine driven auxiliary feedpump.

The unit was returned to service at 1631 hours0.0189 days <br />0.453 hours <br />0.0027 weeks <br />6.205955e-4 months <br /> on 910315.

A study of the system disturbance induced trip is being initiated.

The unit exited the reporting period at 100% Rated Thermal Power.

Gross electrical generation for the month of March was 738100 MWH.

DETAILS 03/13/91 0651 A unit trip occurred from high moisture separator level.

The transient was initiated by a system electrical disturbance caused by downed transmission lines.

03/15/91 1022 Commenced reactor startup.

1113 The reactor is critical.

1258 The reactor is in Mode 1.

1631 The main generator is paralleled to the system power grid.

Commenced unit power increase to 45%

RTP.

03/16/91 0348 The unit is at 454 RTP. Unit power is being held at 454 RTP per the system power dispatcher.

0735 Released by system dispatcher to increase power.

Commenced unit power increase to 904 RTP.

1931 The unit is at 904 RTP. Unit power is being held at 904-RTP for main turbine valve testing.

4

~

~

Monthly Operating Activities page 2 of 2 03/17/91 0103 Main turbine valve testing is complete.

Commenced unit power increase to 97% RTP.

0420 The unit is at 97< RTP. Unit power is being held at, 97'TP to investigate a 24 mismatch in power range nuclear instrumentation indications.

0501 The 2~ mismatch in power range nuclear instrumentation indications is resolved.

Commencing unit. power increase to 100% RTP.

0533 The unit is at 1004 RTP.

DOCKET NO.

UNIT NAME:

COMPLETED BY:

TELEPHONE:

DATE:

PAGE'0-316 D.C.

Cook Unit 2 E.C.

Schimmel (616) 465-5901 April 3, 1991 1 of 1 MAJOR SAFETY-RELATED MAINTENANCE - March 1991 There were no major safety-related maintenance items during the month of March.