Special Rept:On 890426-0516,Tech Specs Violated.Caused by Seven Listed Fire Barriers/Penetration Seals Being Inoperable for More than 7 Days.Fire Door 347 Returned to Svc on 890518 After Determining Door Improperly Setup
ML17325B202
Person / Time
Site: Cook  
Issue date: 06/01/1989
From: Will Smith
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To: Davis A
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
NUDOCS 8906120014
Download: ML17325B202 (4)


Text

AC CELEBRATED REGULATORY INFORMATION DISTRIBUTION SYSTEM (RIDS)

ACCESSION NBR:8906120014 DOC.DATE: 89/06/01 NOTARIZED: NO DOCKET N

FACIL:50-315 Donald C.

Cook Nuclear Power Plant, Unit 1, Indiana 05000315 50-316 Donald C.

Cook Nuclear Power Plant, Unit 2, Indiana 05000316 AUTH.NAME AUTHOR AFFXLIATION SM1TH,W.G.

Indiana Michigan Power.Co.

(formerly Xndiana.&. Michigan Ele RECIP.NAME

'ECIPIENT.AFFILXATION' DAVIS,A.B.

Document Control Branch (Document Control Desk)

SUBJECT:

Special rept: on 890426-0516,listed fire barriers/penetration seals inoperable longer than 7 days.

DISTRIBUTION CODE:

IE22D COPIES RECEIVED: LTR g ENCL 0 SIZE:

3 TITLE:.,50.,73/50.9 Licensee 'Event Report.(j ER), Incident Rpt, l'tc,,

V

~

~

2 NOTES:

RECIPIENT ID CODE/NAME PD3-1 LA STANG,J INTERNAL'CRS MICHELSON ACRS WYLIE AEOD/DSP/TPAB DEDRO NRR/DEST/ADE 8H NRR/DEST/CEB 8H NRR/DEST/ICSB 7

NRR/DEST/MTB 9H NRR/DEST/RSB 8E

'NRR/DLPQ/HFB 10 NRR/DOEA/EAB 11 NUDOCS-ABSTRACT

" RES/DSIR/EIB RGN3 'ILE 01 EXTERNAL: EG&G WILLIAMS,S L ST LOBBY WARD NRC PDR NSXC MURPHY,G.A COPIES LTTR ENCL 1

1 1

1 1

1 1

1 1

1 1

1 1

1 1'

RECIPIENT ID CODE/NAME PD3-1 PD ACRS MOELLER AEOD/DOA AEOD/ROAB/DSP IRM/DCTS/DAB NRR/DEST/ADS 7E NRR/DEST/ESB 8D NRR/DEST/MEB 9H NRR/DEST/PSB 8D NRR/DEST/SGB 8D NRR/DLPQ/PEB 10 NRR/J)REP/RPB 10

~XQQ 02 ESTDSR/PRAB

(

FORD BLDG HOY,A LPDR NSIC MAYS,G, I

COPXES

'LTTR ENCL 2

1 2

1 V

1 1

1 1

1 2

1 1

h MXKm ALL 'KIDS" RECIPGWKo POSE HEXiP US Io RHXKB %ASTElf QMIRCZ 'IHE DOQlMEÃZ CCRCL,DESK, L'ZSTB MR DOCGMEHXS KU DCNPT KKD!

D D

TOTAL NUMBER OF COPIES REQUIRED:

LTTR 43 ENCL

Indiana Michigan~

Power Company Cook Nuclear Pfanr P.O, Box 458 Bridgman. Ml 49I06 6I6 465 590l INDIANA NICHIGiAN POlVER June 1,

1989 Donald C.

Cook Nuclear Plant Unit Nos.

1 and 2

Docket Nos.

50-315, 50-316 License Nos.

DPR-58, DPR-74 United States 'Nuclear Regulatory Commission Document Control Desk Washington, D.C.

20555 ATTN:

A.B. Davis

Dear Mr. Davis:

This special report is being submitted in accordance with Technical Specification 3.7.10 Action a, to:

1) inform you that the following seven fire barriers/penetration seals have been inoperable longer than the seven days allowed by Technical Specification 3.7.10 Action a, and;
2) provide an update regarding inoperable Fire Door 347 (reported in previous letter dated May 16, 1989).

Fire barrier penetration seal W-3041 separating the unit one control room and the unit one auxiliary building 633'evel was declared inoperable on April 27, 1989 and returned to service on May 15, 1989.

A fire watch.,

as required by Technical Specification 3.7.10 Action a, was maintained while the seal was inoperable.

The TSI fire retardant material was removed from Cable Tray 2-AZC-62 located in the Unit Two Auxiliary Building Fire Zone 6S on April 26, 1989.

~ At.that time a fire

watch, as required by Technical Specification 3.7.10 Action.a, was established and remained in effect until the TSI fire retardant material was returned to operable status on May 16, 1989.

Fire Door 357A in the Unit 1

4KV complex was declared inoperable on April 30,,

1989 when it failed to latch.

Following repair the door was returned to operable status on May 16, 1989.

A fire watch, as required by Technical Specification 3.7.10 Action a, was maintained while the door was inoperable.

Fire Door 387 in Unit One Reactor Cable Tunnel Quad Two was declared inoperable on May 4, 1989 when it failed to close during an operability check.

Fire Door 387 is a

double door set.

After an evaluation of the condition=of the door closing and latching mechanism, it was determined that a new door should be installed.

They 8906120014 890601 PDR ADOCK 05000315 PDO

~gy g/

l~

are presently on order.

It is anticipated that the doors will be obtained and returned to operable status by July 15, 1989.

A fire watch, as required by Technical Specification 3.7.10 Action a is being maintained while the doors are inoperable.

Fire Door 392, the auxiliary building access control entry door, was declared inoperable on May 5, 1989 due to the'failure of the door knob mechanism.

Following

repairs, the door was returned to operable status on May 17, 1989.

A fire watch, as required by'echnical Specification 3.7.10 Action a, was maintained while the door was inoperable.

Fire Door 371, the contractor access building entrance

door, was declared inoperable on May 14, 1989 when it failed to close and latch properly during an operability check.

Due to the unique design of the three-point latch on the door, we have had difficulty in obtaining certified parts to repair the door. It is anticipated that the repair parts will be obtained and the door returned to operable status by July 25, 1989.

A fire watch, as required by Technical Specification 3.7.10 Action a> is being maintained while the door is inoperable.

On April 28, 1989, the west wall of the Unit One CD Diesel Generator Room was removed (so that repairs could be effected on the Unit One CD Diesel Generator) rendering the wall an inoperable fire barrier.

The wall was restored to operability on May 17,,

1989.

A fire

watch, as required by Technical Specification 3.7.10 Action a, was maintained while the fire wall and C02 system were inoperable.

In a letter dated May 16,

1989, we informed you that fire door 347 in the unit one 4KV complex was considered inoperable based on an adverse trend involving fire doors failing to close from the open condition during C02 system testing.

Following. an analysis of the door latch and closure mechanism, we have determined that the door was improperly set up for testing, and would have closed during an actual system actuation.

The door was returned to service on May 18, 1989.

Respectfully, W.G. Smith, Jr.

Plant Manager See attached distribution