Tech Spec Page 3/4 9-9 Re Containment Purge & Exhaust Isolation Sys
ML17319B620
Person / Time
Site: Cook 
Issue date: 10/29/1982
From:
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To:
Shared Package
ML17319B619 List:
References
NUDOCS 8211020062
Download: ML17319B620 (2)


Text

REFUELING OPERATIONS CONTAINMENT PURGE AND EXHAUST ISOLATION SYSTEM LIMITING CONDITION FOR OPERATION 3.9.9 The Containment Purge and Exhaust isolation system shall be OPERABLE.

APPLICABILITY:

During Core Alterations or movement of irradiated fuel within the containment.

ACTION:

Mith the Containment Purge and Exhaust isolation system inoperable, close each of the Purge and Exhaust penetrations providing direct access from the containment atmosphere to the outside atmosphere.

The provision of Specification 3.0.3 are not applicable.

SURVEILLANCE RE UIREMENTS r

4.9.9 The Containment Purge and Exhaust isolation system shall be demonstrated OPERABLE within 100 hours0.00116 days <br />0.0278 hours <br />1.653439e-4 weeks <br />3.805e-5 months <br /> prior to the start of and at least once per 7 days during CORE ALTERATIONS by verifying that containment Purge and Exhaust isolation occurs on manual initiation and on a high radiation test signal from each of the containment radiation monitoring instrumentation monitors.

3/4 9-9 During the refueling outage commencing about November 1982, the Containment Purge and Exhaust Isolation System shall be defined to include (l) a radiation signal to either the inner or outer valve or a provision for immediate manual closure of the valve in the event the valve closure may be required, and (2) any one penetration out of service to replace a valve with the remaining valve locked or sealed closed or closed by a blind flange.

This definition is tem-porary and it and this footnote shall no longer apply following the refueling outage commencing about November 1982. For the temporary relief period, the prov>sions of Specification 3,0,4 are not applicable.

82ii0200b2 82i029 PDR ADOCK 050003ib V