ML17319B499

From kanterella
Jump to navigation Jump to search
Proposed Revisions to Tech Specs 3/4.6.3,Table 3.6-1, 3.6.1.7 & 4.6.1.7.1 to Allow Containment Purging During Normal Operation
ML17319B499
Person / Time
Site: Cook  
Issue date: 08/30/1982
From:
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To:
Shared Package
ML17319B498 List:
References
NUDOCS 8209020314
Download: ML17319B499 (20)


Text

CONTAINMENT SYSTEMS 3/4.6.3 CONTAINMENT ISOLATION VALVES LIMITING CONDITION FOR OPERATION 3.6.3.1 The containment isolation valves specified in Table 3.6-1 shall be OPERABLE with isolation times as shown in Tabl.e 3.6-1.

The ACTION statement of T/S 3/4.6.3 is not applicable to the containment purge sup-ply and exhaust isolation valves, VCR-101 through 106 and VCR-201 through

'206, listed in Table 3.6-1.

The Limiting Condition for Operation and its associated ACTION statement for these valves is given in Technical Speci-fication 3/4.6.1.7.

APPLICABILITY:

NODES 1, 2, 3 and 4.

ACTION:

With one or more of the isolation valve(s) specified in Table 3.6-1 inoperable, either:

a e b.

c ~

d.

Restore the inoperable valve(s) to OPERABLE status within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />, or Isolate each affected penetration within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> by use of at least one deactivated automatic valve secured in the isolation position, or A

Isolate each affected penetration within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> by use of at least one closed manual valve or blind flange, or Be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE RE UIREflENTS 4.6.3.1.1 The isolation 'valves specified in Table 3.6-1 shall be demonstrated OPERABLE:

a ~

At least once per 92 days by cycling each OPERABLE power operated or automatic valve testable during plant operation through at least one complete cycle of full travel.

b.:

Immediately prior to returning the valve to service after maintenance, repair or replacement work is performed on the D.

C.

COOK-UNIT 1 8209020314 820830 PDR ADQCK 05000315 PDR

.,3/4 6-14

'TABLE 3.6-1 (Continued)

VALVE NVMBER I'UNCTION TESTABLE DURING PLANT OPERATION ISOLATION TQQ?

IN SECONDS B.

Pl&SE "B" ISOLATION Continued A

OO 44

'5.

46.

47.

48.

49.

50.

51.

52.

53.

54.

55.

56.

57.

58.

59.

60.

61.

62.

63.

64.

65.

66.

67.

MCR-961 MCR-963

".'CR-965 WCR-967 MCR-900 WCR-902 MCR-904 WCR-906 MCR-908 MCR-910 WCR-912 MCR-914 WCR-920 WCR-922 WCR-924 MCR-926 WCR-928 WCR-930 MCR-932 WCR-934 MCR-960 WCR-962 WCR-964 MCR-966 NESW to Instr.

Rm. Hast Vent NESW from Instr.

Rm. West Vent NESM to Instr.

Rm. East Vent NESM from Instr.

Rm. West Vent NESW to RCP Lower Containment Vent 81 NESM from Lower Containment Vent //1 NESM to RCP Lower Containment Vent //2 NESW from Lower Containment Vent.82 NESM to RCP Lower Containment Vent //3 NESM from Lower Containment Vent //3 NESW to RCP Lower Containment Vent'/4 NESW from Lower Containment Vent //4 NHSM to RCP Upper Containment Vent //1 NESW from Upper Containment Vent //1 NESW to RCP Upper Containment Vent //2 NESW from Upper Containment Vent //2 NESM to RCP Upper Containment Vent 83 NESM from Upper Containment Vent //3 NESM to RCP Upper Containmen" Vent 84 NESM from Upper Containment Vent 84 NESM to Instrument Room East Vent NESW from Instrument Room East Vent NESW to Instrument Room West Vent NESW from Instrument Room Mest Vent Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10'0 10 10 10 10 10 10 10 10 C.

l.

2.

3.

4 ~

5 ~

6.

7 ~

8.

9.

10.

11.

CONTAINMENT VCR-101 VCR-102 VCR-103 VCR-104 VCR-105 VCR-106 VCR-107*

VCR-201 VCR-202 VCR-203 VCR-204 PURGE AND EXllAUST **

Instr.

Room Purge Air Inlet Instr.

Room Purge Air Outlet Lower Comp. Purge Air Inlet Lower Comp. Purge Air Outlet Upper Comp. Purge Air Inlet Upper Comp. Purge Air Outlet Cont. Press.

Relief Fan.Isolation Instr.

Room Purge Air Inlet Instr.

Room Purge Air Outlet Lower Comp. Purge Air Inlet Lower Comp. Purge Air Outlet Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes 5

5 5

5 5

5 5

5 5

5 5

TABLE 3.6-1 (Continued)

VALVE NUMBER FUNCTION TESTABLE DURING PLANT OPERATION ISOLATION TIME IN SECONDS A

OO Q

12.

VCR-205 13.

VCR-206 14.

VCR-207*

Upper Comp. Purge Air Inlet Upper Comp. Purge Air Outlet Cont. Press Relief Fan Isolation C;

CONTAINMENT PURGE EXHAUST Continued Yes Yes Yes 5

5 5

D. MANUAL ISOLATION VALVES 1.

ICM-111 2.

ICH-129 3.

IQl-250

.4.

ICH-251 5.

ICH-260 6.

ICH-265 7.

ICH-305 8.

ICH-306 9.

IQl-311 10.

ICH-321 11.

NPX 151 VI 12'A 145 13.

SF-151 14.

SF-153 15.

SF-159 16.

SF-160 17.

SI-171 18.

SI-172 RHR to RC Cold Legs RHR Inlet to Pumps Boron Injection Inlet Boron Injection Inlet Safety Injection Inlet Safety Injection Inlet RHR Suction from Sump RHR Suction from Sump RHR to RC Hot Legs RHR to RC Hot Legs Dead Weight Tester Containment Service Air Refueling Water Supply Refueling Water Supply Refueling Cavity Drain to Purification System

'efueling Cavity Drain to Purification System Safety Injection Test Line Accumulator Test Line Yes No Yes Yes Yes Yes Yes Yes Yes Yes Yes No Yes Yes Yes Yes Yes Yes NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA

a VALVE NUMBER FUNCTION TABLE 3.6-1 (Continued TESTABLE DURING PLANT OPERATION ISOLATION TIME IN SECONDS D. MANUAL ISOLATION VALVES Continued)

(1)

Q

~

Q PC I

5 19.

CCR-440 20.

CCR-441 21.

HCM-221 22.

MCH-231 23.,

CCM-430 24.

CCM-431 25.

CCM-432 26.

CCM-433 27.

SH-8*

28.

SM-10*

, 29.

SH-4*

30.

SH-6*

CCW from Hain Steam Penetration CCW from Hain Steam Penetration Main Steam to Auxiliary Feed Pump Main Steam to Auxiliary Feed Pump CCW to East Pressure Equalization Fan CCW from East Pressure Equalization Fan CCW to West Pressure Equalization Fan CCW from West Pressure Equalization Fan Upper Containment Sample Upper Containment Sample Instrument Room Sample Instrument Room Sample Yes Yes No No Yes Yes Yes Yes Yes Yes Yes Yes NA

. NA NA NA NA NA NA NA NA NA NA NA NA Manual Valve-Isolation time not applicable.

(1)

Includes motor operated valves Mhich do not isolate automatically.

Hay he opened on an intermittent basis under administrative control.

Containment purge supply and exhaust isolation valves (VCR-101 through 106 and VCR-201 through 206) may be opened under Technical Specification 3/4.6.1.7.

CONTAIAKNT SYSTEMS CONTAI&fENT VENTILATION SYSTEM LIMITING CONDITION FOR OPERATION 3.6.1.7 The containment purge supply and exhaust isolation valves shall be closed except when operation of the containment purge system is required for safety related reasons.

No more than one purge supply path and one purge exhaust path shall be open at a time.

APPLICABILITY:

MODES 1, 2, 3, and 4.

ACTION:

a.

With one containment purge supply and/or one exhaust isolation valve inoperable, isolate the affected penetration by use of at least one automatic valve secured in the closed position, and, within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />, either:

1)

Restore the inoperable valve to OPERABLE status, or, 2)

Deactivate the automatic valve secured in the closed position.

b.

Operation may then continue until performance of the next required valve test provided that the automatic valve secured in the closed position is verified to be deactivated in the closed position at least once per 31 days.

c.

Otherwise, be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

d.

The provisions of Specification 3.0.4 are not applicable.

SURVEILLANCE REQUIREMENTS 4.6.1.7.1 The surveillance requirements of Technical Specification 3/4.6.3.1 apply.

D. C.

COOK - UNIT 1 3/4 6-9a

CONTAIRfENT SYSTEMS BASES 3/4.6.1.7 CONTAINMENT PURGE AND EXHAUST ISOLATION VALVES This specification ensures that the containment purge supply and exhaust isolation valves are closed for the ma)ority of the time during normal operation.

It allows for containment purging for safety related reasons.

Safety-related reasons are meant to be the need to improve containment working conditions to perform surveillance and/or maintenance on a safety-related system or piece of equipment..

Examples of improved working conditions include reducing temperature, humidity and airborne activity to permit efficient performance or to significantly reduce occupational radiation exposures. It is intended that purging and venting times will be as short as possible.

Allowing purge operations in Modes 1, 2, 3, and 4 is more beneficial than a

cooldown to Mode 5 from the standpoint of (a) imposing unnecessary thermal stress cycles on the reactor coolant system and its components and (b) reducing the potential for causing unnecessary challenges to the reactor trip and safeguards systems.

The containment purge system is designed in accordance with the requirements of NRC Branch Technical Position CSB 6-4, Rev.

1.

This includes, but is not limited to, an

'analysis of the impact of purging on ECCS performance, an evaluation of the radiological consequences of a design basis accident while purging, and limiting purge operation to using no more than one supply path and one exhaust path at a time.

The purge isolation valves have been demonstrated capable of. closing against the dynamic forces associated with a loss-of-coolant accident and are assured of receiving a

Containment Ventilation Isolation signal.

Reset switches have been protected against inadvertent'se in a manner which facilitates the administrative controls governing their use, The use of the pressure relief (vent) line is allowed for containment pressure control.

The purge and vent isolation valves do not use resilient seating/sealing material and are not subject to the type of environmental degradation common to resilient materials.

D.

C.

COOK UNIT 1

B 3/4 6>>2a

.~

~

~

CONTAINMENT SYSTEMS 3/4.6. 3 CONTAINMENT ISOLATION VALVES LIMITING CONDITION FOR OPERATION 3.6.3.1 The containment isolation valve" specified in Table 3.6-1 shall be OPERABLE with isolation times as shown in Table 3.6-1.

The ACTION statement of Technical Specification 3/4.6.3 is not applicable to the containment purge and exhaust isolation valves, VCR-101 through 106 and VCR-201 through 206, listed in Table 3.6-1.

The Limiting Condition for Operation and its associated ACTION statement for these valves is given in Technical Specification 3/4.6. 1.7.

APPLICABILITY:

Modes 1, 2, 3 and 4.

ACTION:

With one or more of the isolation valves(s) specified in Table 3.6-1 inoperable, maintain at least one isolation valve OPERABLE in each affected penetration that is open and either:

'a v b.

Co d.

Restore the inoperable valve(s) to OPERABLE status within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />, or Isolate each affected penetration within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> by use of at least one deactivated automatic valve secured in the isolation position, or Isolate each affected penetration within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> by use of at least one closed manual valve or blind flange; or Be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE RE UIREMENTS'.6.3.1.1 The isolation valves specified in Table 3.6-1 shall be demonstrated OPERABLE prior to returning the valve to service after maintenance, repair or replacement work is performed on the valve or its associated

actuator, control or power circuit by performance of a cycling test and verification of isolation time.

D. C.

COOK -.UNIT 2

~ "3/4 6-13

,a J

TABLE 3.6-1 (Continued)

VALVE NUMBER CONTAINMENT ISOLATION VALVES PUNCTION ISOLATION TIME IN SECOND I'I ~

B.

PHASE "B" ISOLATION Continued OOO LO c

Ch IIV Ln 56'CR-920 57.

WCR-922 58.

WCR-924 59 'WCR-926 60.

WCR-928 61.

WCR-930 62.

WCR-932 63.

WCR-934 64.

WCR-960 65.

WCR-962 66.

WCR-964 67.

WCR-966 NESW to RCP Upper Containment Vent 81 NESW from Upper Containment Vent 81 NESW to RCP Upper Containment Vent 82 NESW from Upper Containment Vent 82 NESW to RCP Upper Containment Vent 83 NESW from Upper Containment Vent 83 NESW to RCP Upper Containment Vent 84, NESW from Upper Containment Vent 84 NESW to Instrument Room East Vent NESW from Instrument Room East Vent NESW to Instrument Room West Vent NESW from Instrument Room West Vent

<10

<10

<10

<10 C.

CONTAINMENT PURGE AND EXHAUST **

, I.

VCR-101 2.

VCR-102 3.

VCR-103 4.

VCR;104.

5.

VCR-105 Instr.

Room Purge Air Inlet Instr-Room Purge Air Outlet Lower Comp. Purge Air Inlet Lower Comp. Purge Air Outlet Upper Comp. Purge Air Inlet c5 c5

'I II I

I

CD TABLE 3.6-1 (Continued)

CONTAINMENT ISOLATION VALVES CD CD VALVE NUMBER FUNCTION ISOLATION TIME IN SECONDS C.

CONTAINMENT PURGE AND EXHAUST Continued) **

6.

VCR-106 7.

VCR-107*

8.

VCR-201 9.

VCR-202 10.

VCR-203 11.

VCR-204 12.

VCR-205 13.

VCR-206 14.

VCR-207*

D.

MANUAL ISOLATION VALVES 1.

ICM-1114 2.

1CM-129 Upper Comp.

Purge Air Outlet Cont. Press.

Relief Fan Isolation Instr.

Room Purge Air Inlet Instr.

Room Purge Air Outlet Lower Comp.

Purge Air Inlet Lower Comp.

Purge Air Outlet Upper Comp.

Purge Air Outlet Upper Comp.

Purge Air Outlet Cont.

Press Relief Fan Isolation RilR to RC Cold Legs RHR In 1 e t to Pumps 5

5 5

5 5

5 5

5 5

TABLE 3.6-1 (Continued)

CONTAINMFNT ISOLATION VALVES TABLE NOTATION Hay be opened on an intermittent basis under administrative control.

Not subject to Type "B" or "C" Leak Tests.

NA Check valves, blind flanges on normally closed valves which do not receive containment isolation signals; isolation time not applicable.

(1)

Includes motor operated valves which do not isolate automatically.

Containment purge supply and exhaust isolation valves (VCR-1Ql through 106 and

'CR-201 through 206) may be opened under Technical Specification 3/4,6,l.l.

CONTAINMENT SYSTEMS CONTAINMENT VENTILATION SYSTEM LIMITING CONDITION FOR OPERATION 3.6.1.7 The containment purge supply and exhaust isolation valves shall be closed except when operation of the containment purge system is required for safety related reasons.

No more than one purge supply path and one purge exhaust path shall be open at a time.

APPLICABILITY:

MODES 1, 2, 3, and 4.

ACTION:

a.

With one containment purge supply and/or one exhaust isolation valve inoperable, isolate the affected penetration by use of at least one automatic valve secured in the closed position, and, within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />, either:

1)

Restore the inoperable valve to OPERABLE status,

'or, 2)

Deactivate the automatic valve secured in the closed position.

b.

Operation may then continue until performance of the next required valve test provided that the automatic valve secured in the closed position is verified to be deactivated in the closed position at least once per 31 days.

C ~

d ~

Otherwise, be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

M The provisions of Specification 3.0.4 are not applicable.

SURVEILLANCE REQUIREMENTS 4.6.1.7.1 The surveillance requirements of Technical Specification 3/4.6.3.1 apply.

D; C.

COOK '- UNIT 2 3/4 6-9a

\\

'k

CONTAINMENT SYSTEMS BASES 3/4.6.1.7 CONTAIAKNT PURGE AND EXHAUST ISOLATION VALVES This specification ensures that the containment purge supply and exhaust isolation valves are closed for the ma)ority of the time during normal operation.

It allows for containment purging for safety related reasons.

Safety-related reasons are meant to be the need to improve containment working conditions to perform surveillance and/or maintenance on a safety-related system or piece of equipment.

Examples of improved working conditions include reducing temperature, humidity and airborne activity to permit efficient performance or to significantly reduce occupational radiation exposures. It is intended that purging and venting times will be as short as possible.

Allowing purge operations in Modes 1, 2, 3, and 4 is more beneficial than a cooldown to Mode 5 from the standpoint of (a) imposing unnecessary thermal stress cycles on the reactor coolant system and its components and (b) reducing the potential for causing unnecessary challenges to the reactor trip and safeguards systems.

The containment purge system is designed in accordance with the requirements of NRC Branch Technical Position CSB 6-4, Rev.

1.

This includes, but is not limited to, an analysis of the impact of purging on ECCS performance, an evaluation of the radiological consequences of a design basis accident while purging, and limiting purge operation to using no more than one supply path and one exhaust path at a time.

The purge isolation valves have been demonstrated capable of closing against the dynamic forces associated with a loss-of-coolant, accident and are assured of receiving a

Containment Ventilation Isolation signal.

Reset switches have been protected against inadvertent use in a manner which facilitates the administrative controls governing their use.

The use of the pressure relief (vent) line is allowed for containment pressure control.

The purge and vent isolation valves do not use resilient seating/sealing material and are not subject to the type of environmental degradation common to resilient materials.

D.

C, COOK UNIT 2 B 3/4 6-2a

k V