ML17311A424
| ML17311A424 | |
| Person / Time | |
|---|---|
| Site: | Palo Verde |
| Issue date: | 11/22/1994 |
| From: | Stewart W ARIZONA PUBLIC SERVICE CO. (FORMERLY ARIZONA NUCLEAR |
| To: | NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM) |
| Shared Package | |
| ML17311A426 | List: |
| References | |
| 102-03190-WLS-S, 102-3190-WLS-S, IEIN-94-060, IEIN-94-60, NUDOCS 9412010234 | |
| Download: ML17311A424 (7) | |
Text
PRIGRITY I (ACCELERATED RIDS PROCESSING REGULATORY INFORMATXON DISTRIBUTION SYSTEM (RIDS)
ACCESSXON NBR:9412010234 DOC.DATE: 94/11/22 NOTARIZED: YES DOCKET FACIL:STN-50-528 Palo Verde Nuclear Station, Unit 1, Arizona Publi 05000528 AUTH.NAME AUTHOR AFFILIATION STEWART,W.L.
Arizona Public Service Co.
(formerly Arizona Nuclear Power P
RECIP.NAME RECXPIENT AFFXLIATION Document Control Branch (Document Control Desk)
SUBJECT:
Application for amend to License NPF-4l,proposing TS Section 3/4.7.1 by adding note to table 3.7.2.
DISTRIBUTION CODE:
AOOID COPIES RECEIVED:LTR Q ENCL Q SIZE:
TITLE: OR Submittal:
General Distribution 0
NOTES:STANDARDIZED PLANT 05000528 RECIPIENT ID CODE/NAME PD4-2 LA HOLIAN, B INTERNAL'CRS NRR/DE/EELB NRR/DRPW NRR/DSSA/SRXB OGC/HDS2 EXTERNAL'OAC COPIES LTTR ENCL 1
1 1
1 RECIPIENT ID CODE/NAME PD4-2 PD TRAN,L NRR/ DRCH/HICB NRR/DSSA/SPLB NUDOCS-ABSTRACT NRC PDR COPIES LTTR ENCL 1
1 1
1 1
1 1
1 1
1 1
1 1
1 0
N NOTE TO ALL"RIDS" RECIPIENTS:
PLEASE HELP US TO REDUCE iVKSTE!CONTACTTIIEDOCl'XfENTCONTROL DESK, ROO!1f Pl-37 (EXT. 504-o083 ) TO ELIi1INATEYOI.'R iAifLTFROif DISTRIBUTIONLIS'I'S I'OR DOC!.'NfEi'I'S YOL'ON"I'L'ED!
TOTAL NUMBER OF COPIES REQUIRED:
LTTR 20 ENCL 19
II t
Arizona Public Service Company P.O. BOX 53999
~
PHOENIX, ARIZONA85072-3999 WILLIAML. STEWART EXECUTIVEVICEPRESIOENT NUCLEAR U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Mail Station P1-37 Washington, DC 20555 102-03190-WLS/SAB/RKR November 22, 1994
Dear Sirs:
Subject:
Palo Verde Nuclear Generating Station (PVNGS)
Unit 1 Docket No. STN 50-528 Proposed Amendment to Technical Specification Section 3/4.7.1, Under Exigent Circumstances File: 94-056-026 Arizona Public Service Company (APS) is requesting an amendment to PVNGS Unit 1 Technical Specification Section 3/4.7.1 under exigent conditions.
The proposed Technical Specification amendment will add a note to Table 3.7-2.
The note will allow continued operation during Unit 1, Cycle 5 at 100% Maximum Steady State Power Level with one main steam safety valve (MSSV) inoperable per steam generator.
This note applies only during the current fuel cycle (Cycle 5) for Unit 1. Analysis shows that the reduction in relief capacity has no affect on the original accident analysis conclusions (no affect on peak secondary or reactor coolant system pressure) due to the time in core life.
Unit 1 is currently limited to 98.2% Maximum Steady State Power Level in accordance with ACTION a. of Limiting Condition for Operation 3.7.1.1.
APS has also reviewed NRC Information Notice 94-60, "Potential Overpressurization of Main Steam System" with regard to this amendment request.
Since Unit 1 will be returned to 100% power, the concern addressed by the Information Notice does not affect this amendment request.
APS Engineering also looked at the secondary system performance for the current Unit 1 condition (one MSSV inoperable per steam generator at 98.2% power) and determined that any pressure increase would not be significant and design limits would be maintained.
3000'74 9412010234 94ii22 PDR ADOL'K 05000528 P
t
U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Proposed Amendment to Technical Specification Page 2 Provided in the enclosure to this letter are the following sections which support the proposed Technical Specification amendment:
A.
B.
C.
D.
E.
F.
G.
Description of the Technical Specification Amendment Request Purpose of the Technical Specification Explanation of the Need for the Technical Specification Amendment and the Exigent. Circumstances Safety Analysis for the Technical Specification Amendment Request No Significant Hazards Consideration Determination Environmental Consideration Marked-up Technical Specification Page In accordance with Technical Specification 6.5, the Plant Review Board and the Offsite Safety Review Committee have reviewed and concurred with this request.
By copy of this letter, the Arizona Radiation Regulatory Agency is being notified of this Technical Specification amendment request, pursuant to 10 CFR 50.91(b)(1).
Should you have any questions, please contact Scott A.
Bauer of my staff at (602) 393-5978.
Sincerely, WLS/SAB/RKR/rv Enclosure CC:
L. J. Callan K. E. Perkins B. E. Holian K. E. Johnston A. V. Godwin ARRA
STATE OF ARIZONA
)-) ss.
COUNTY OF MARICOPA )
I, W. L. Stewart, represent that I am Executive Vice President - Nuclear, that the foregoing document has been signed by me on behalf of Arizona Public Service Company with full authority to do so, that I have read such document and know its contents, and that to the best of my knowledge and belief, the statements made therein are true and correct..
W. L. Stewart Sworn To Before Me This ~+
Day Of (1 A9Yl,1994.
Notary Public My Commission Expires
I I
e 4