EOP I ECA-0.2 LOSS OF ALL AC POWER RECOVERY WITH SI REQUIRED REV:

8 PAGE 1 of 8 ROCHESTER GAS AND ELECTRIC CORPORATION GINNA STATION CONTROLLED COPY NUMBER TECHNICAL REVIEW PORC REVIEW DATE

~ ~~ /9 PLANT SUPERINTENDENT 4-7-0 EFFECTIVE DATE CATEGORY 1.0 REVIEWED BY:

9404i90153 940414 PDR ADOCK 05000244 P

PDR

EOP:

ECA-0.2 TITLE:

LOSS OF ALL AC POWER RECOVERY WITH SI REQUIRED REV:

8 PAGE 2 of 8 A.

PURPOSE This procedure provides actions to use engineered safeguards systems to recover plant conditions following restoration of AC emergency power.

B.

ENTRY CONDITIONS/SYMPTOMS l.

ENTRY CONDITIONS This procedure is entered from:

a.

ECA-O.O, LOSS OF ALL AC POWER, when AC emergency power is restored and SI is required.

b ~

ECA 0 ~l g LOSS OF ALL AC POWER RECOVERY WITHOUT SI REQUIRED, if SI is required.

EOP:

ECA-0.2 LOSS OF ALL AC POWER RECOVERY WITH SI REQUIRED REV:

8

.PAGE 3 of 8 STEP ACTION/EXPECTED RESPONSE

RESPONSE

NOT OBTAINED NOTE:

o CSFSTs should be monitored for information only.

FR procedures should not be implemented prior to completion of Step 7.

o Adverse CNMT values should be used whenever CNMT pressure is greater than 4 psig or CNMT radiation is greater than 10+

R/hr.

1 Check RCP CCW Isolation Status:

a.

CCW pumps BOTH PUMPS OFF b.

RCP CCW return valves CLOSED

~ MOV-759A

~ MOV-759B a.

Go to Step 2.

b. Manually close valves as necessary:

o RCP CCW thermal barrier outlet valves

~ AOV-754A

~ AOV-754B

-OR-o RCP CCW supply valves

~ MOV-749A

~ MOV-749B 2

Check RWST Level GREATER THAN 284 Go to ES-1.3, TRANSFER TO COLD LEG RECIRCULATION, Step 1.

EOP:

ECA-0.2 TITLE:

LOSS OF ALL AC POWER RECOVERY WITH SI REQUIRED REV 8

PAGE 4 of 8 STEP ACTION/EXPECTED RESPONSE

RESPONSE

NOT OBTAINED NOTE:

SI actuation to establish safeguards valve alignment is not recommended.

3 Manually Align SI And RHR Pumps To Establish SI Injection:

a.

SI pump suction valves from RWST OPEN

~ MOV-825A

~ MOV-825B a.

Ensure at least one SI pump suction valve from RWST open.

~ MOV-825A

~ MOV-825B

b. SI pump suction valves from BASTs -

CLOSED

~ MOV-826A

~ MOV-826B

~ MOV-826C

~ MOV-826D b.

Ensure at least one valve in each SI pump suction line from BASTs closed.

~ MOV-826A or MOV-826B

~ MOV-826C or MOV-826D

c. Verify SI pump C discharge valves OPEN
c. Manually open valves as necessary.

~ MOV-871A

~ MOV-871B d.

RHR pump discharge to Rx vessel deluge OPEN

~ MOV-852A

~ MOV-852B

d. Ensure at least one deluge valve open.

~ MOV-852A

~ MOV-852B

EOP:

ECA-0.2 TITLE:

LOSS OF ALL AC POWER RECOVERY WITH SI REQUIRED REV 8

PAGE 5 of 8 STEP ACTION/EXPECTED RESPONSE

RESPONSE

NOT OBTAINED CAUTION THE LOADS PLACED ON THE ENERGIZED AC EMERGENCY BUS SHOULD NOT EXCEED THE CAPACITY OF THE POWER SOURCE.

4 Manually Load Following Safeguards Equipment On AC Emergency Bus:

a. Start all SI pumps a.

Perform the following:

1) Start available SI pumps.
2) IF SI pump A or B NOT available, THEN verify SI pump C aligned as follows:

o IF SI pump A NOT available, THEN ensure MOV-871B closed.

o IF SI pump B NOT available, THEN ensure MOV-871A closed.

b.

Check RCS pressure:

o Pressure

- GREATER THAN 250 psig

[465 psig adverse CNMT]

o Pressure STABLE OR INCREASING

b. Manually start both RHR pumps and go to Step 4d.
c. Place RHR pump switches in AUTO
d. Start all available CNMT RECIRC fans

0 C

EOP:

ECA-0.2 TITLE:

LOSS OF ALL AC POWER RECOVERY WITH SI REQUIRED REV 8

PAGE 6 of 8 STEP ACTION/EXPECTED RESPONSE

RESPONSE

NOT OBTAINED CAUTION o

IF CST LEVEL DECREASES TO LESS THAN 5 FEET, THEN ALTERNATE WATER SOURCES FOR AFW PUMPS WILL BE NECESSARY (REFER TO ER-AFW.1, ALTERNATE WATER SUPPLY TO AFW PUMPS).

o IF S/G NR LEVEL DECREASES TO LESS THAN 5%

[25% ADVERSE CNMT] AND FEED FLOW IS LESS THAN 200

GPM, THEN THE MDAFW PUMPS SHOULD BE MANUALLYLOADED ON AC EMERGENCY BUS TO SUPPLY WATER TO THE S/G(S).

NOTE':

o If MDAFW pump operation is not required, pump switches should be maintained in PULL-STOP to prevent automatic start.

o TDAFW pump flow control valves fail open on loss of IA.

  • 5 Monitor Intact S/G Levels:
a. Narrow range level - GREATER THAN 5%

[25% adverse CNMT]

a. Maintain total feed flow greater than 200 gpm until narrow range level greater than 5%

[25%

adverse CNMT] in at least one S/G.

IF feed flow less than 200 gpm, THEN perform the following:

1) Verify MDAFW pump discharge valve to intact S/G(s) open.

~ S/G A, MOV-4007

~ S/G B, MOV-4008

b. Control feed flow to maintain narrow range level between 17%

[25% adverse CNMT] and 50%

2) Manually start MDAFW pumps as necessary (228 KW).

0 C

~t

EOP:

ECA-0.2 TlTLE:

LOSS OF ALL AC POWER RECOVERY WITH SI REQUIRED REV 8

PAGE 7 of 8 STEP ACTION/EXPECTED RESPONSE

RESPONSE

NOT OBTAINED 6 Place CNMT Spray Pumps In AUTO 7

Check RCP Seal Injection Needle Valves CLOSED

~ V-300A

~ V-300B Locally close valves before starting charging pump.

CAUTION o

RCP THERMAL BARRIER COOLING SHOULD BE ESTABLISHED SLOWLY TO MINIMIZE POTENTIAL INTRODUCTION OF STEAM INTO THE CCW SYSTEM AND THERMAL SHOCK TO RCP.

o RCP THERMAL BARRIER COOLING SHOULD NOT BE ESTABLISHED TO AN RCP WITH EXCESSIVE SEAL LEAKAGE.

o RCP SEAL INJECTION SHOULD BE ESTABLISHED SLOWLY TO MINIMIZE RCP THERMAL STRESSES AND POTENTIAL SEAL FAILURES.

o AS PART OF SUBSEQUENT RECOVERY ACTIONS, RCP(S)

SHOULD NOT BE STARTED PRIOR TO A STATUS EVALUATION UNLESS REQUIRED BY AN INADEQUATE CORE COOLING SITUATION.

NOTE:

FR procedures may nov be implemented as necessary.

8 Check CCW To RCPs:

o Annunciator A-7, RCP 1A CCW RETURN HIGH TEMP OR LOW FLOW EXTINGUISHED o

Annunciator A-15, RCP 1B CCW RETURN HIGH TEMP OR LOW FLOW EXTINGUISHED Establish normal CCW cooling to RCPs (Refer to Attachment SEAL COOLING).

EOP:

ECA-0.2 LOSS OF ALL AC POWER RECOVERY WITH SI REQUIRED REV:

8 PAGE 8 of 8 STEP ACTION/EXPECTED RESPONSE

RESPONSE

NOT OBTAINED 9

Go to E-l, LOSS OF REACTOR OR SECONDARY COOLANT, Step l

-END-

(