ML17215A770

From kanterella
Jump to navigation Jump to search
Safety Evaluation Granting Licensee 830412 & 25 Requests for Exemptions from 10CFR50,App R
ML17215A770
Person / Time
Site: Saint Lucie 
Issue date: 02/21/1985
From:
Office of Nuclear Reactor Regulation
To:
Shared Package
ML17215A769 List:
References
NUDOCS 8503080146
Download: ML17215A770 (20)


Text

8 REDO (4

qo 0

Cy l%

0 UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D. C. 20555 SAFETY EVALUATIONBY'THE OFFICE OF NUCLEAR REACTOR REGULATION 1.0 Introduction By letters dated April 12, 1983 and April 25, 1983, the licensee requested exemptions from Sections III.G and III.O of Appendix R.

These requests superseded all previous exemption requests.

These letters also provided information concerning SER open item 3.7 Ventilation Duct Penetrations.

By letters dated August 24, 1983, September 16, 1983, and December 14, 1983, the licensee provided additional information.

Section III.G.2 of Appendix R requires that one train of cables and equipment necessary to achieve and maintain safe shutdown be maintained free of fire damage by one of the following means:

(1)

Separation of cables and equipment.and associated nonsafety circuits of redundant trains by a fire barrier having a 3-hour rating.

Structural steel forming a part of or supporting such fire barriers shall be protected to provide fire resistance equivalent to that required of the barrier.

(2)

Separation of cables and equipment and associated nonsafety circuits of redundant trains by a horizontal distance of more than 20 feet with no intervening combustibles or fire hazards.

In addition, fire detectors and an automatic fire suppression system shall be installed in the fire area.

(3)

Enclosure of cable and equipment and associated nonsafety circuits of one redundant train in a fire barrier having a I-hour rating.

In addition, fire detectors and an automatic fire suppression system shall be installed in the fire area.

If these conditions are not met,Section III.G.3 requires that there be an alternative shutdown capability independent of the fire area of concern.

It also requires that a fixed suppression system be installed in the fire area of concern if it contains a large concentration of cables or other combustibles.

These alternative requirements are not deemed to be equivalent; however, they provide equivalent protection for those configurations in which they are accepted.

Because it is not possible to predict the specific conditions under which fires may occur and propagate, the design-basis protective features rather than the design-basis fire are specified in the rule.

Plant-specific features may require protection different from the measures specified in Section III.G.

In such a case, the licensee must demonstrate, by means of a detailed fire hazards

analysis, that existing protection or existing 8503080i46 85022i PDR ADOCK 05000335 F

PDR

~

I

protection in conjunction with proposed modifications will provide a level of safety equivalent to the technical requirements of Section III.G of Appendix R

In summary,Section III.G is related to fire protection features for ensuring that systems and associated circuits used to achieve and maintain safe shutdown are free of damage.

Either fire protection configurations must meet the specific requirements of Section III.G or an alternative fire protection configuration must be justified by a fire hazard analysis.

Generally, the staff will accept an alternative fire protection configuration if:

(1)

The alternative ensures that one train of equipment necessary to achieve hot shutdown from either the control room or emergency control stations is free of fire damage.

(2)

The alternative ensures that fire damage to at least one train of equipment necessary to achieve cold shutdown is limited so that it can be repaired within a reasonable time (minor repairs using components stored on the site).

(3)

Fire-retardant coatings are not used as fire barriers.

(4)

Modifications required to meet Section III.G would not enhance fire protection safety levels above those provided by either existing or proposed alternatives.

(5)

Modifications required to meet Section III.G would be detrimental to overall facility safety.

2.0 Control Room (Fire Area F) 2.1~

tt The licensee requested an exemption from Section III.G.3.b to the extent that it requires the installation of a fixed suppression system in the control room ~

2.2 Discussion The control room is a continuously occupied space that houses controls and instruments necessary to remotely operate

valves, pumps, motors, etc.,

required for plant operation.

Most of these controls and instruments are mounted on centrally located panels.

Redundant safe shutdown related cables are routed in the area to various control panels.

Ionization type fire detectors are located in the control room.

No automatic fire suppression capability is provided.

However, portable fire extinguishers and standpipe hose stations are available for use in the control room.

The licensee will install alternative shutdown capability independent of the control room.

2.3 Evaluation ifications require that the control room be continuously t fth 1

t i d

he fire bri ade.

Therefore, these personnel constitute a con-The fuel load in the area is low.

Manual suppression d ff t've'hus a fixed suppression if a fire occurr ed woul d be prompt an e

ec i e, system would not enhance the fire protection in this area.

2.4 Conclusion Based on the above evaluation, the staff concludes that the existing and pro-osed fire rotection for the Control Room (Fire Area F) provides a level of fire protection equiva en o

e e

1 t t th t chnical requirements of Section III.6.3.b.

Therefore, the exemption should be granted.

3.0 Reactor Containment Buildin (Fire Area K) 3.1 xem t on e ueste Th 1

e scensee reque sted an exemption from Section III.G.2.d to the extent that it requires the separation of redundant safe shutdown trains y

combustible radiant energy shield or by a horizontal separation of greater than 20 feet.

'This request concerns three locations:

(I) pressurizer

cubicle, (2) annular region inside Containment, and (3) valve locations.

3.2 Discussion The Reactor Containment Building is separated from other plant areas by 3-hour fire'ated barriers.

The containment is one fire area with a large volume and a high ceiling.

There are four floor levels ins'ide containment at the 18 ft., 23 ft., 45 ft., and 62 ft. elevations.

Normal access to the containment is controlled and limited.

Redundant safe shutdown trains inside containment include Power Operated R 1' V

1 (PORV ) and associated Block Valves, valves for shutdown cooling, Letdown Valves, char ging, auxiliary spray and instrumentation and ass c

o iated cabling.

The pressurizer cubicle is:inaccessible during plant operation.

All cables inside the pressurizer cubicle are r outed in conduit.

The PORVs and their Block Valves are located within the pressurizer cubicle.

The annular area inside containment contains shutdown cable trays that are located 15 feet to 55 feet above the basemat.

All nonqualified IEEE-383 cables are covered with a fire retardant mastic material.

Redundant cable trays are separated from each other by horizontal distance of more than 7

feet.

They are installed on separate elevations separated by approximately 25 feet.

Combustible material in the area consists of lubricating oil contained in various components and cables.

Portable fire extinguishers are available inside containment.

Ionization smoke detectors are provided in selected locations.

The licensee proposes to install radiant energy shields between redundant trains in the cable penetration area.

In addition, the licensee has verbally committed to relocate one pressurizer level transmitter to achieve separation by a radiant energy shield.

The licensee documented this commitment in a

letter of December 14, 1983.

3.3 Evaluation The technical requirements of Section III.G.2.d are not met in three locations inside containment because radiant energy shields are not provided to separate redundant trains.

Because of the configuration and location of the pressurizer cubicle within the containment and the restricted access of this zone during plant operation, an exposure fire involving the accumulation of significant quantities of transient combustible material is unlikely.

Because of the limited amount of cable insulation in the pressurizer cubicle and because the majority of insulation is enclosed in conduit, a fire of sufficient magnitude to damage redundant cables, or components inside the pressurizer cubicle is unlikely.

The staff has reasonable assurance that one of the redundant trains will remain free of fire damage.

Because of the restricted access to the containment, an exposure fire from the accumulation of transient combustibles in the annular area inside con-tainment would be limited in size and duration.

The high ceiling.and the open metal grating walkways in the annular area inside containment will allow hot gases from anticipated exposure fires to be safely dissipated.

Because of the configuration of redundant cables in the annular area inside containment and the limited size and duration of anticipated fires, the staff has reasonable assurance that one train of redundant cables will be free of fire damage.

3.4 Conclusion Based on the above evaluation, the existing protection and proposed modifica-tions for the pressurizer cubicle, the annular area within the containment, and valve locations (Fire Area K) provide a level of protection equivalent to the technical requirements of Section III.G.2.d of Appendix R.

Therefore, these exemptions should be granted.

4.0 Shutdown Heat Exchan er Room (Fire Area L) 4.1 xem tson e ueste The licensee requested an exemption from Section III.G.2.a of Appendix R to the extent that it requires separation of redundant trains by 3-hour fire rated barriers.

4.2 Discussion The Shutdown Heat Exchanger Room is located on elevation

-.0.5 feet of the Reactor Auxiliary Building.

The room is separated from other areas by 3-hour fire rated barriers.

The room is approximately 30 feet x 57 feet with a 20 foot ceiling.

The room contains redundant cold shutdown heat exchangers.

These heat ex-changers are separated by 16 feet and a partial height concrete wall.

The wall is 8 feet high and runs the entire length of the room.

All redundant valves and cables associated with each heat exchanger are installed below the top of the wall.

The room is a high radiation area with limited personnel access.

The in-situ fuel load is negligible.

Fire protection in the area consists of early warning fire detection installed in the HUE lOA and 10B ventilation system exhaust ducts with manual hose stations and portable fire extinguishers available for use in the shutdown heat exchanger room.

4.3 Evaluation The technical requirements of Section III.G.2.a are not met because the 3-hour fire rated wall does not completely separate the redundant cold shutdown components.

Because the in-situ fuel load in the area is negligible and located below the partial height wall and because of the limited accessibility, the staff would not expect any significant quantities of transient combustibles to accumulate in the area.

Any postulated exposure fire would be limited in size and would be located on one side of the partial height wall.

The convective heat and smoke of such fires would rise into the ceiling area and away from the redundant component.

The concrete wall between the components will prevent radiant heat released by a fire near one component from damaging the redundant cold shutdown components that are located on the other side of.

the wall.

~

Because of the smoke detection system in the area, a fire, if one should occur, would be discovered early.

This would assure the timely response of the plant fire brigade.

Although some time delay is expected before eventual fire extinguishment, the staff has reasonable assurance that the components from at least one shutdown division will not sustain fire damage.

4.4 Conclusion Based on the above evaluation, the staff concludes that the licensee's existing fire protection will achieve an acceptable level of, fire protection equivalent to that provided by the technical requirements of Section III.G.2.a.

However, Appendix R,Section III.G.2.a does not apply in this

area, because it contains no hot shutdown components.

Therefore, no exemption is required.

5.0 ECCS Pum Room Fire Area M

5.1 xem t on e ueste The licensee requested an exemption from Section III.G.2.a of Appendix R to the extent that it requires separation of redundant trains by 3-hour fire rated barriers.

5.2 Discussion The ECCS Pump Room is located on elevation -0.5 feet of the Reactor Auxiliary Building.

The room is separated from other plant areas by 3-hour fire rated barriers.

The ECCS Pump Room is divided by a partial height 3-hour fire rated barrier, ranging in height from 20 feet from column line RAI to RAG, to 9.5 feet from column line RAG to RAE.

The wall divides the room into two zones.

Each zone contains one Low Pressure Safety Injection Pump (LPSI), one Containment Spray Pump and one High Pressure Safety Injection Pump.

Only one LPSI pump is required for cold shutdown.

The valves and cabling for each system are also located in the same zone as their associated pumps.

The area contains a negligible fuel loading and, as a radiation area, it has limited personnel access.

The area is provided with ionization smoke detectors.

Hose stations and portable fire extinguishers located outside the area are provided for manual fire fighting.

The separation of redundant safe shutdown cables in some locations is less than 20 feet.

The licensee has verbally comnitted to enclose all redundant safe shutdown cables not separated by 20 feet that run above the partial height barrier in an approved one-hour fire rated barrier.

The licensee documented this commitment in a letter of December 14, 1983.

5.3 Evaluation The technical requirements of Section III.G.2.a are not met because the three-hour fire rated wall does not completely separate the redundant cold shutdown components.

The in-situ 'fuel load in the area is negligible.

Because of the limited accessibility, the staff would not expect any significant quantities of transient combustibles to accumulate in the area.

Any postulated fire would

be located on one side of the partial barrier and not propagate td any significant degree.

The convective heat from the fire would be dissipated in the high ceiling area.

The existing partial height 3-hour fire rated harrier between the redundant LPSI pumps would prevent any radiant heat released by a fire near one LPSI pump from damaging the redundant pump located on the other side of the barrier.

Because of the smoke detection system in the area, a fire, if one should occur, would be discovered early.

This would assure timely response of the plant fire brigade.

Although some time delay is expected before eventual fire extinguishment, the staff has reasonable assurance that components from at least one shutdown division would not sustain damage.

5.4 Conclusion Based on the above evaluation, the existing protection combined with the proposed modifications and coomitments provides a level of fire protection in the ECCS Pump Room equivalent to the technical requirements of Section III.G.2.a.

However, Appendix R Section III.G.2.a does not apply in this area, because it contains no hot shutdown components.

Therefore, no exemption is needed.

6.0 Char in Pum Area Fire Area N

6.1 xem t on e ueste The licensee requested an exemption from Section III.G.2.a of Appendix R to the extent that it requires separation of redundant trains by 3-hour fire rated barriers.

6.2 Discussion The Charging Pump Area is located in the Reactor Auxiliary Building at elevation -0.50 feet.

The area is separated from other plant areas by 3-hour fire rated barriers.

The ceiling height in the area fs 20 feet.

The area contains three redundant charging pumps.

The pumps are installed 10

'feet on centers with approximately 20 feet between the end pumps.

The pumps are separated from each other and a

common hallway by cubicles consisting of partial height (7 feet) 3-hour fire rated walls.

The power cables for the Division B and C pumps are routed in conduit embedded in concrete up to the pump motors.

The licensee has committed to enclose the power cables associated with the Division A pump located in the Division C pump cubicle in a one-hour fire rated barrier.

In addition, the licensee has committed to relocate the Division B manual control station and associated wiring located in the common hallway to inside the Division B pump cubicle.

The licensee documented these commitments in a letter of December 14, 1983.

The in-situ combustible in the area is limited to the lubricating oil, approximately 3 gallons per pump.

The oil provides unpressurized lubrication.

The oil has a flash point of greater than 450'F.

The area does not contain hot surfaces that could ignite the oil.

Fire protection in the area consists of early warning fire detection.

Manual hose stations and portable fire extinguishers are available for use in this area.

6.3 Evaluation The technical requirements of Section III.G.2.a are not met because the three-hour fire rated wall does not completely separate the redundant shutdown components.

The in-situ fire load in the area is negligible and because of the limited accessibility to the area, the staff would not expect any significant quantities of transient combustibles to accumulate in these areas.

Any postulated fire would therefore not propagate to any significant degree.

For anticipated fires, heat and smoke would rise into the ceiling area, which would act as a heat sink; therefore, the damaging effects of convective heat from a fire would be dissipated in the ceiling area.

The existing partial height 3-hour fire rated barrier between the charging pumps would effectively prevent any heat caused by a fire near one pump from damaging the redundant pumps that are located on the other side of the wall.

Because of the smoke detection system in the area, a fire, if one should occur, would be discovered early.

This would assure the timely response of the plant fire brigade.

Although some time delay is expected before eventual fire extinguishment, the staff has reasonable assurance that the existing fire wall will prevent components from at least one shutdown division from sustaining fire damage.

6.4 Conclusion Based on the above evaluation, the existing protection combined with the proposed modifications and commitments provides a level of fire protection in the Charging Pump Area (Fire Area N) equivalent to the technical requirements of Section III.G.2.a; therefore, the exemptions should be granted.

7.0 Intake Coolinq Water Area Fire Area R-R 7.1 xem tron e ueste The licensee requests an exemption from Section III.G.2.b to the extent that it requires the installation of an automatic fire suppression system in the area.

7.2 Discussion This is an outdoor area that contains the Intake Structure, Chlorine Building and a storage building.

The concrete intake structure deck elevation is 16.5 feet.

The safe shutdown related components in this area are the three intake cooling water (ICW) pumps.

The three intake cooling water pumps are on approximately 13 foot centers.

These pumps rest on concrete pedestals

approximately 31 inches high.

All three pumps are enclosed in a common steel tornado missile barrier approximately 20 feet high, 9 feet wide and 37 feet long.

This tornado missile barrier is surrounded by grating that drains to the Intake Canal below.

Openings at the top and bottom of the missile barrier allow for free convection cooling of ICW pump motors.

There are four circulating water pumps on 14 feet centers.

Two screen wash pumps on approximately 6 feet centers are located 4.5 feet south of the southernmost intake cooling water pump.

A separation of approximately 6 feet exists between a circulating water pump and the closest ICW pump.

A 6-inch curb surrounding each circulating water pump directs any leakage from the respective pump away from the ICW pump enclosure and into the deck grating.

Safe shutdown related cables, associated with the ICW pumps, are routed in three separate manhole systems, each containing the cables for one ICW pump.

The manholes are located a minimum of 14 feet from the circulating water pumps.

The cables from the manholes to the ICW pump motor terminal boxes are routed in galvanized steel conduit and are encased in concrete from the man-holes up to the intake structure deck.

The combustibles in the area consist of 235 qts. of lubricating oil in each of the four circulating water pump motors, 53 qts. in each of the three cooling water pump motors, and four qts. in each of the two screen wash pump motors.

The oil provides unpressurized lubrication.

The oil has a flash point of greater than 450'F.

This area does not contain hot surfaces to ignite the oil.

The area is provided with portable fire extinguishers and manual hose stations.

The licensee has installed early warning fire detection in the area that will initiate an alarm locally and in the Control Room.

This is documented in a letter of September 16, 1983.

7.3 Evaluation This area does not comply w'ith Section III.G.2.b of Appendix R because an automatic suppression system is not installed in the area.

The fire detection system will provide reasonable assurance that a fire will be discovered at an early stage before significant damage results.

~j Because of the low fire load, the open area, the separation of the redundant components and the early warning fire detection system, it is the staff's opinion that any postulated fire in the area would be extinguished within a short time.

Although a time delay is anticipated between the receipt of the initial fire alarm and the arrival of the fire brigade, the staff has reasonable assurance that one train of equipment will remain free of fire damage.

7.4 Conclusion Based on the above evaluation, the existing fire protection combined with the licensee's commitments provides a level of fire protection in the Intake Cooling Hater Area (Fire Area RR) equivalent to the technical requirements of Section III.G.2.b; therefore, the exemption should be granted.

8.0 Steam Trestle Area (Fire Area S-S 8.1 xem tron e ueste The licensee requested an exemption from Section III.G.2.b to the extent that it requires the installation of an automatic fire suppression system in the area.

8.2 Discussion

/

The Steam Trestle Area is an outdoor area located on the west side of the containment at elevation 19.0 feet.

The area includes the auxiliary feedwater pumps (AFW) 1A, 1B, and 1C and their associated cabling and valves.

The AFW pumps are bounded on three sides by I inch thick steel plates and by the Containment Building on the remaining side.

The two 'electrically driven AFW pumps (lA and

18) are separated from the turbine driven AFW pump 1C by concrete floodwalls and two I-inch thick steel missile shields.

The in-situ combustibles in the area are limited to the lubricating oil contained in the pumps'otor housing.

The oil has a flash point of greater than 450'F.

Manual hose stations and portable fire extinguishers are available for use in this area.

The licensee has committed to install early warning fire detectors in the area.

The licensee documented this comnitment in a letter dated December 14, 1983.

8.3 Evaluation This area does not comply with Section III.G.2.b of Appendix R because an automatic suppression system is not installed in the area.

The area is outdoors and open without a ceiling.

The staff finds the arrangement will prevent the accumulation of hot stratified oases from anticipated fires.

Redundant cables and equipment are separated by 28 feet free of intervening combustibles.

The fire detection system consisting of detectors by each pump which the licensee has committed to install in the area, will provide reasonable assurance that a fire will be discovered at an-early stage before significant damage results.

Because of the low in-situ fuel load, available manual fire fighting equipment, and fire brigade training, it is our opinion that any postulated fire in the area would not be beyond the capabilities of the fire brigade to extinguish within a short time span.

Although a time delay is anticipated between the receipt of the initial fire alarm and the arrival of the fire brigade, the separation of redundant trains by missile shield walls and 28 feet, and the location of the trains outdoors will provide sufficient passive fire protection until the fire is extinguished.

8.4 Conclusion Based on the above evaluation, existing fire protection combined with the licensee's commitments provides a level of fire protection in the Steam Trestle Area (Fire Area S-S) equivalent to the technical requirements of Section III.G.2.b of Appendix R; therefore, the exemption should be granted.

9.0 Com onent Coolin Pum s

Fire Area U-U 9.1 xem tron e ueste The licensee requested an exemption from Section III.G,2.b to the extent that it requires the installation of automatic fire suppression and fire detection systems throughout the area.

9.2 Discussion The Component Cooling Water Area is an outdoor area located at elevation 28.5 feet just north of the refueling water tank.

It includes the three component cooling water (CCW) pumps, the CCW heat exchangers and associated

cables, valves, and piping.

The CCW pumps are mounted on 11 feet high concrete pedestals that extend up to a metal grating at elevation 23.5 feet.

The area below the grated platform contains piping in a dike at elevation 12.0 feet.

Each pump is enclosed by a steel missile barrier.

There is approximately 12 feet between adjacent CCW pumps.

CCW system control valves and motor operated valves are located just under the metal grating surrounding the CCW pumps.

Power and control cables for each pump are imbedded in concrete, with only a short exposed section at each pump.

The combustible loading in this area consists of approximately 15 gallons of lubricating oil and four pounds of grease contained within the pump motor housings.

The oil provides unpressurized lubrication.

The oil has a flash point of greater than 450'F.

This area does not contain hot surfaces to ignite the oil.

Manual hose stations and portable fire extinguishers are available for use in this area.

The licensee committed to install early warning fire detection at each CCW pump.

The licensee documented this commitment in a letter of December 14, 1983.

9.3 Evaluation The area does not comply with Section III.G.2.b because automatic suppression systems are not installed and the fire detection system is not throughout the area.

The area is open without ceiling or walls.

This arrangement will prevent the accumulation of hot stratified gases from anticipated fires.

The fire detection system will provide reasonable assurance that a fire will be discovered at an early stage before significant damage results.

Because of the low fire load, the open area, and the separation of redundant components, it is the staff's opinion that any postulated fire in the area would not be beyond the capabilities of the fire brigade to extinguish within a short time span.

Although a time delay is anticipated between the receipt of the initial fire alarm and the arrival of the fire b}igade, the staff has reasonable assurance that one train of components will remain free of fire damage.

9.4 Conclusion Based on the above evaluation, the existing fire protection combined with the licensee's commitments provides a level of fire protection in the Component Cooling Pump Area (Fire Area U-U) equivalent to the technical requirements of Section III.G.2.b; therefore, the exemptions should be granted.

10.0 Diesel Oil Stora e Tank Area Fire Area T-T 10.1 xem t on e ueste The licensee requested an exemption from Section III.G.2.b to the extent it requires the installation of early warning fire detection and an automatic fire suppression. system.

10.2 Discussion Fire Area (T-T) is the Diesel Oil Storage Tank area located at elevation 19.0'.

It includes 2 diesel oil storage tanks, diesel oil transfer

pumps, and associated valves and piping.

Each tank is surrounded by a 5.5 foot high concrete wall and holds about 20,000 gallons of diesel fuel.

They are built in accordance with API standards and meet the requirements of the National Fire Code.

The fuel oil transfer pumps are located in tornado protected concrete enclosures; one north and one south of the diesel oil storage tanks.

These enclosures are approximately 60 feet apart.

The in-situ combustibles in this area consist of approximately 20,000 gallons of diesel oil contained in each tank.

Portable fire extinguishers and manual hose stations are provided in the area.

Gu~p~Ln8 E~e~~~xny ~ogaeag aug go uo~goas gsamq~aou ay~ u[ 'Ig g Gt; q3 ge pageoo~

aie

~auung adt.d aug pue easy uoigewgauad

~eo~agoa~3 y uoLsLnig aug eaa uo Zea~aua a[qeg y uo~s~nig pue

[auuny a

~d aug uaazga8 uoigea~auag Zing e

uo~ssnossg g

gg

'(q easy aa)g) moog aaGueqox3 ieaH ggg3 aug pue (p easy aa~g)

Lauuny added aug uaaegaq

~Lee ag.

Gu~ge~Zauad gonp I (y easy aa)g) easy uo)geagauad

)eougoa)3 y uo)sic)g aug pue (p easy aa~g)

~auuny ad~g ag, uaaegaq

~[em aqZ Gu~~e~Zauad Zanp y

sea~e Gu[wo((og aqZ u) su[eaZ Zuepunpaa age~edas qIiw swa~a~eq page~

aa~g ~noq-g ageagauad ye~. sgonp u~ s~admep page~

asap snot-g Gugpsho~d moog suoggdwaxa pagsanbaa seq aasuaag[

any

'g x<puaddy wo~g sgsanbaa uo[gdmaxa guasa~daa og paaap[suoo awe s~esodoad asap'a[no aug qg~e E[dwov ~ou saop ma~a uado ag, aA[osaa og s~esodoad s,aasuaoi[

aug geqq. guagxa aug og 'g[nsa~

e sy

'Og gled gag pT og g xipuaddy go suoLs~hoad aLqeag[dde aug og ~oaCqns sg gg 'g86g 'gg Eaenwqag

'sgue[d ~ea[onu Guggeaado cog a~n~

uoggoagoad awing aug go agep anggoagga aug og coped pangosa~

you see wag~ uado g3g sgqg asneoa8 maZ~ uado g3g Ue seN s((eM pages aa~g qGno~qg suoige~gauad gonp 'aniZoagpa aweoaq a~no uo[goaZoad aa[g a~.

awLg aug gy agsan a

uoig wax sea)vae8 pageg aa)g anoH-g ug uo)gewgauad gong p'gy

'paguezG aq p~noqs uo[gdmaxa aug 'aaogaaaqg

'.q'g g

~~~ uo~goag go sguawaa~nbaa

[eo~uqoag aqua oq. Zua[eh[nba uo[q.oakwood a~tg go [aha[

e sap)hood ease abc~ops

[~o [asat.p aug u[ uocgoago~d Gujgscxa aug pepin spumy ggegs a~. 'uoigen[ena ahoqe aug uo pase8 uo~sn~ouog y'Og

'ea~e s~q~

uL uo~goaZo~d aa[g go Lama[ ay~ aouequa E[ZueoLg~uG~s you pLnoe magsEs uoLq,oagap pue uo~ssa~ddns o[gewogne ue go uo~Ze((eZsu~

any aGewep aa~g go aaag pau)e~u[em aq (([w urea~

auo ~eq> aoue~nsse a~qeuoseaa s~ aaaqg pepin uo~u~do s,ggegs aug s~

g~ 'squeg uaaeZaq Gusq~p pue ague>s~p uog>e~edas aug jo asneoa8

'sguawa~~nbaa Gu[aeds a~qeog~dde q$ )hl aOUel~dwoo u~ pa~~egsu~

awe pepin az~s s~q'I go squeg

~op wagsEs ou~qs~nG

-u~Zxa aa[g e puawmooaa

~ou saop Og 'p~g ydgN squeZ aGeao~s puno~G-ahoqe

'quartet.'pe go Gu~oeds aug ~op aport spinb~q a~q~gsnqmog pue a~qewwe[g

'Og 'pgg ydgN qgiM aoue~[dwoo u~

st. squeg go uo[geaedas any

'slue~

aug po sguaguoo act.qua aug Gu~uceguoo go a~qedeo aq~p e pue paar yp Eq page~edas awe squeg a6ewogs L~o [asa~p aug pap[hood you awe swagsEs uocZoaZap pue uo~ssa~ddns o~gemoZne asneoaq q g.B

~g~ uo~~oag

~.~e ELdwoa Zou saop ease siqy UO Lien [eh3 f'Q'f 1

Early warning fire detection is provided in the Division A cable penetration area.

Fire extinguishers and hose stations are provided for use in the area.

The combustible fuel loading for the Division A Electrical Penetration Area is high; however, all cabling in the area has been coated with a flame retardant coating or is qualified to IEEE-383.

The fuel load in the Pipe Tunnel is negligible.

The duct penetration is located in the east wall approximately 18 feet above the floor.

The penetration is approximately 2 sq. ft. in size.

The Pipe Tunnel is a high radiation area and access is limited.

The Pipe Tunnel contains valves required for cold shutdown.

b.

Duct Penetration Between the Pi e Tunnel (Fire Area J and ECCS Heat xc an er oom re rea The ECCS Heat Exchanger Room (Fire Area L) is located on elevation -0.50 ft. of the Reactor Auxiliary Building.

Early warning fire detection is provided in the ECCS heat exchanger room.

Fire extinguishers and hose stations are provided in the imnediate area.

The fuel load in both areas is negligible.

The licensee has committed to install 3-hour fire rated dampers in all duct penetrations with the exception of a penetration between the Pipe Tunnel and the ECCS Heat Exchanger Room.

The licensee documented this commitment in a letter of December 14, 1983.

The duct penetration in question is located in the north wall approximately 13 feet above the floor.

The Pipe Tunnel that the duct enters is a high radiation area and access is limited.

The only safe shutdown equipment in the pipe tunnel are valves required for cold shutdown.

The licensee indicated that the valves can be manually operated to their correct cold shutdown position in the event of a fire.

11.3 Evaluation The technical'requirements of Section III.G.2.a are not met in these areas because of the unprotected penetrations in the 3-hour fire rated walls.

Because the fuel load in the Pipe Tunnel is negligible and access to*the tunnel is limited due to high radiation levels, a fire in this area would be small and would not present a threat to the redundant components.

A fire in the Division A cable penetration area would involve only Division A systems.

Because the cables are coated with a fire retardant coating or qualified to IEEE-383, any postulated fire would tend to propagate slowly and with initially low heat generation.

The damage-producing effects of such a fire, i.e., the radiant and convective heat and other products of combustion, would be confined to the area of fire origin by the fire rated walls.

A small quantity of smoke and hot gases would be expected to propagate beyond the walls into the Pipe Tunnel because of the unprotected penett ations.

However, the unprotected penetrations are located away from the redundant shutdown systems.

Therefore, hot gases passing through the penetrations would not affect components or cabling of redundant divisions.

Because of the configuration, the area-wide fire detection capability and the accessibility of the areas within the Reactor Auxiliary Building, the staff has reasonable assurance that one safe shutdown system train will remain free of fire damage.

11.4 Conclusion Based on the above evaluation, the staff concludes that the existing fire protection in the Division A Cable Penetration Area (Fire Area A), Pipe Tunnel (Fire Area J),

and the ECCS Heat Exchanger Room (Fire Area L) provides

~

an acceptable level of safety equivalent to that provided by Section III.G.2.a and, therefore, the exemptions should be granted.

12.0 Penetrations In 3-Hour Fire Rated Barriers 12.1 xem tron e ueste The licensee requested an exemption from providing 3-hour fire rated doors in doorways in a 3-hour fire rated barrier that separates redundant trains.

12.2 Discussion The barrier separates the Personnel Area (Fire Area C) from the Hold Up Tank Area (Fire Area E).

The barrier is located on elevation 19.50 ft. of the Reactor Auxiliary Building.

The unprotected openings in the fire barrier are two 3 ft. by 7 ft. passageways between the two areas.

The passageways are protected by a concrete "T" shaped labyrinth installed in Fire Area C.

The fuel load in the vicinity of the opening in both areas is negligible.

Fire protection in the areas is provided by early warning fire detection.

Manual hose stations and portable fire extinguishers are available for use in these areas.

12.3 Evaluation The technical requirements of Section III-.G.2.a are not met in these areas because of the unprotected openings in the 3-hour fire rated barrier.

If a fire occurred in one of these

areas, a small quantity of smoke and hot gases would be expected to propagate through the unprotected openings.

Because the in-situ combustibles in the vicinity of the unprotected openings are minimal and because the safe shutdown systems are located away from the openings, the redundant divisions in the other areas would not be threatened.

Because these areas are provided with early warning fire detection and because they are located in an area of the Auxiliary Building that is easily accessible to the fire brigade, the staff has 'reasonable assurance that one safe shutdown system train will be free of fire damage.

12.4 Conclusion Based on the above evaluation, the staff concludes that the existing fire protection in the Personnel Area (Fire Area C) and the Hold Up Tank Area (Fire Area E) provides an acceptable level of safety equivalent to that provided by Section III.G.2.a and, therefore, the exemption should be granted.

13.0 Penetrations In 3-Hour Fire Rated Floor Ceilin Assemblies 13.1 xem tron e ueste The licensee has requested exemptions from sealing two hatch openings in 3-hour fire rated barriers separating redundant trains in the Reactor Auxiliary Building.

13.2 Discussion The hatch openings are between elevations

-0.50 ft. and 19.50 ft. in the Reactor Auxiliary Building.

One hatch opening is located between column lines RAJ and RA5.

The other hatch is located between column lines RA4 and RAC.

Steel plates, I/O inch thick, are used to cover the hatch opening at elevation 19.5 ft.

The openings are protected with early warning detection.

There are negligible combustibles in the inmediate area of the hatch openings.

The licensee committed to install an automatic water curtain consisting of sidewall sprinkler leads to provide protection for each hatch opening.

The licensee documented this commitment in a letter of December 14, 1983.

13.3 Evaluation The technical requirements of Section III.G.2.a are not met in these areas because 3-hour penetration seals have not been provided for openings in 3-hour fire rated floor/ceiling assemblies used to separate redundant trains.

The in-situ fuel load in the immediate area of each hatch opening is negli-gible; however, unanticipated circumstances could result in the presence of transient combustibles creating significantly higher levels of combustibles in these areas.

The automatic water curtain will provide active fire pro-tection to aid in the protection of the hatch openings.

Because (I) the hatch openings are covered with noncombustible

covers,

{2) automatic fire detection and fire suppression have been provided, and (3) the concentration of in-situ combustibles is neqligible beneath each hatch opening, the staff finds that the installation of 3-hour penetration seals in lieu of the hatch covers would not significantly increase the level of fire safety.

p )g 17 13.4 Conclusion Based on the above evaluation, the existing protection in the Reactor Auxiliary Building elevations

-0.5 ft. and 19.5 ft. and commitments provide a

level of fire protection equivalent to the technical requirements of Section III.G.2.a; therefore, the exemptions should be granted.

14.0 Exterior Mall Penetration The licensee requested an exemption from installing 3-hour fire rated penetration

seals, doors and dampers in exterior wall penetrations in the Reactor Auxiliary Building and Diesel-Generator Building.

The staff has reviewed the licensee's requests and finds that the exterior walls in these buildings do not separate redundant safe shutdown equipment and no fire hazards exist within 50 feet of the building.

The staff finds this acceptable.

Therefore, no exemptions from Section III.G.2.a of Appendix R

are needed.

15.0 Oil Collection S stem for Reactor Coolant Pum s

15.1 xem tron e ueste An exemption is requested from Section III.O to the extent it requires an oil collection tank sized to hold the lube oil inventory of all three Reactor Coolant Pump (RCP) motors.

15.2 Discussion The unit has four reactor coolant pumps with an oil collection system that drains to a vented closed collection tank.

The quantity of lubricating oil in each pump is 190 gallons.

The capacity of, the oil collection tank is 225 gallons.

The components have been designed so that they are capable of withstanding a safe shutdown earthquake (SSE).

0 The collection tank is arranged such that, if a failure of more than one RCP motor lube system occurred, the oil collection tank would overflow onto the lower containment floor.

The lubricating oil used in the RCP motors has a

flash point of approximately 450'F; There are no ignition sources at the floor level of the lower containment.

15.3 Evaluation The RCP motor lube oil system does not comply with Section III.O because the oil collection tank is not sized to contain the entire lube oil system inventory.

The oil collection tank is provided with sufficient capacity to hold the total lube oil inventory of one reactor coolant pump with margin and is designed so that any overflow will be drained to a safe location and will not present an exposure fire hazard to or otherwise endanger safety related equipment.

The staff agrees with the licensee that this combination of features is acceptable.

15.4 Conclusion Based on the above evaluation, the existing RCP motor lube oil collection system provides a level of safety equivalent to the technical requirements of Section III.O and, therefore, the exemption should be granted.

16.0 U

rade Existin Fire Pum s

16.1 xem tron e ueste An exemption is requested from Section III.Afor the fire pump controller.

16.2 Discussion As a part of the licensee's response to open items of the Amendment 33 safety evaluation and the staff's letter dated November 24, 1980, the licensee requested an exemption for their fire pump controllers.

In a February ll, 1981 letter, the licensee provided a comparison of their fire pump controllers to the requirements of NFPA Std.

20.

16.3 Evaluation The staff has evaluated the February 11, 1981 submittal with regard to the fire pumps and controllers and finds them equivalent to an approved system that meets NFPA Std.

20.

16.4 Conclusion Based on the above evaluation, the fire pumps and controllers provide a level of safety equivalent to the technical requirements of Section III.A. However, Appendix R,Section III.A does not require meeting NFPA Std.

20 in this case.

Therefore, no exemption is needed.

17.0 Fire Doors 17.1~

d An exemption is requested for six watertight doors that are not approved fire doors.

17.2 Discussion The licensee has based this exemption request on the test report dated February 1982, "Fire Evaluation of Doors and a Water Curtain," Southwest Research Insti-tute project number 01-6763-201, This report shows that watertight doors of the type proposed successfully passed a 3-hour fire test conducted in accordance with test method ASTH E-119, an acceptable method of demonstrating fire resist-ance.

-19'-

17.3 Evaluation The staff has evaluated the February 1982 test report and the supplemental in-formation provided and agrees that the proposed alternative provides a level of fire protection equivalent to the level of protection required by the technical requirements of III.G.2.a.

17.4 Conclusion Based on the above, the staff concludes that the watertight doors are acceptable in meeting the requirements of III.G.2.a; therefore the exemption should be granted.

18.0 Sumnar v Based on the staff's evaluation, the following exemptions should be granted:

1.

Control Room (Fire Area F) 2.

Reactor Containment Building (Fire Area K) 3.

Charging Pump Area (Fire Area N) 4.

Intake Cooling Water Area (Fire Area R-R) 5.

Steam Trestle Area (Fire Area S-S) 6.

Component Cooling Pumps (Fire Area U-U) 7.

Diesel Oil.storage Tanks (Fire Area T-T) 8.

Penetrations In Three Fire Rated Barriers (Three Exemptions) 9 Steel Hatches (Two Exemptions) 10.

Oil Collection System ll.

Fire Doors.

l.

2.

3.

4, Based on the staff's evaluation, the following exemptions are not needed:

Shutdown Heat Exchanger Room (Fit e Area L)

ECCS Pump Room (Fire Area M)

Fire Pumps and Controllers Outside Wall Penetrations Date:

February 21, 1985 Principal Contributors:

J. Stang D. Sells