ML17212A287

From kanterella
Jump to navigation Jump to search
Ack Receipt of IE Insp Rept 50-335/81-09.No Proprietary Info.Corrective Actions:Addl Fire Hose Installed
ML17212A287
Person / Time
Site: Saint Lucie 
Issue date: 06/05/1981
From: Robert E. Uhrig
FLORIDA POWER & LIGHT CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML17212A286 List:
References
NUDOCS 8107080482
Download: ML17212A287 (3)


Text

i

~

P,O. SOX 5291CO "q1IAMI,FL 33~>52

<<<VI~>~

~~

g

'fji i'une 5

1981 L-81-238 Mr. James P. O'Reilly, Director, Region II Office of Inspection and Enforcement U.

S. Nuclear Regulatory Commission 101 Marietta Street, Suite 3100 Atlanta, Georgia 30303

Dear Mr. O'Reilly:

Re:

St. Lucie Unit 1

Docket No. 50-335 Ins ection Re ort 81&9 Florida Power

& Light Company has reviewed the subject inspection report and a

response is attached.

There is no proprietary information in the report.

Robert'.

Uhrig Vice President Advanced Systems

& Technology REU/PLP/ras Attachment cc:

Mr. Harold F. Reis, Esquire j Bi07080482 810707 i PDR ADOCK 05000335, PDR I'

"GPL=..

55RV/NG p-"Qpti

~

4 I

RE:

ST.

LUCIE UNIT 1 DOCKET NO. 50-335 INSPECTION REPORT 81&9 FINDING:

Florida Power

& Light (FPGL) Company's report "Fire Protection A

Reevaluation of Existing Plant Design Features and Administrative Controls" of March 1977, Section 6.2.2 and Table 6-2, indicates the amount of fire hose and other accessories to be stored in the fire hydrant equipment houses located throughout the plant for protection of safety related systems and components.

Contrary to the above, equipment houses FH1 and FH3 were equipped April 8, 1981 with 100 feet of 1 1/2 inch fire hose, whereas Table 6-2 states that 200 feet of 1 1/2 inch fire hose was to be provided.

RESPONSE

1.

Houses FH1 and FH3 now have 200 feet of 1 1/2 inch hose each.

2.

People responsible for inventory of fire equipment have received instructions to preclude repetition of this problem.

3.

Corrective action was completed on May 20, 1981.