OCT 2 7 1992 MEMORANDUM FOR:
John A. Zwolinski, Assistant Director for Region III Reactors Division of Reactor Projects - III/IV/V Office of.Nuclear Reactor Regulation (NRR)
FROM:
Hubert J. Miller, Director Division of Reactor Safety, Region III
SUBJECT:
REQUEST FOR TECHNICAL ASSISTANCE INTERPRETATION AND RESOLUTION OF REGULATORY GUIDE (RG) 1.97 AT DRESDEN;*
DOCKET NUMBERS 50-237 AND 50-249 (AITS # 92-0636)
ENCLOSURE 2 Determine if the licensee complieg with RG 1.97, Revision 2 for the neutron flux monitoring instrumentation and the use of Moore Industries signal conditioners.
Two unresolved items remain open.
Unresolved Item C237/90016-03CDRSl:249/90015-03CDRSll:
Determine adequacy of the neutron flux monitoring instrumentation in meeting the Category 1 requirements.
The licensee's position is documented in the BWR Owner's Group letter.dated February 21, 1990, and was also stated during subsequent discussions with the NRC, which indicated that further review by NRR was required.
Unresolved Item C237/90016-04CDRSl:249/90015-04CDRSll:
Evaluate and determine acceptance of the licensee's use of Moore Industries signal conditioners.as isolators~ Maximum credible fault*testing of these devices was completed per Nutherm Test Report CWE-#3690R dated December 1989, copies of which were previously forwarded to NRR/SICB (Models SCT/4-20mA/4-20mA/117VAC(STD) and MVT/80-160mV/4-20mA/117VAC(STD)).
Direct an~ questions concerning this subject to either George Hausman at (708) 790-5523 or Frank Jablonski at (708) 790-5555.
We consider this to be a Priority 2 item with a completion date of January 16, 1993.
See Attached Distribution Riii Riii Riii Hubert J. Miller, Director Division of Reactor Safety Riii
~*
~
~man Jab.tlnski ~*
l/W' Ring Martin lOh~ /92 10/Zf;/92 10/~ /92 10/{f:./92
. 10;-1-1 /92 92 9211030116 921027 PDR ADOCK 05000237 p
J. A. Zwolinski cc:
B. L. Siegel; NRR A. G. Hansen, NRR B. S. Marcus, NRR S. F. Newberry, NRR DCD/DCB (RIDS) 2 QC.1 2., 199Z