ML17164A779

From kanterella
Jump to navigation Jump to search
Insp Repts 50-387/98-09 & 50-388/98-09 on 980729-0807. Violations Noted.Major Areas Inspected:Review Unresolved Issues from Fpfi Insp to Characterize Findings for Appropriate Enforcement Actions
ML17164A779
Person / Time
Site: Susquehanna  Talen Energy icon.png
Issue date: 09/04/1998
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To:
Shared Package
ML17164A778 List:
References
50-387-97-201, 50-387-98-09, 50-387-98-9, 50-388-97-201, 50-388-98-09, 50-388-98-9, NUDOCS 9809140229
Download: ML17164A779 (28)


See also: IR 05000387/1998009

Text

U.S. NUCLEAR REGULATORYCOMMISSION

REGION I

Docket Nos:

50-387, 50-388

License Nos:

NPF-14, NPF-22

Report Nos.:

50-387/98-09, 50-388/98-09

Licensee:

Pennsylvania Power and Light Company

Facility:

Susquehanna

Steam Electric Station

Location:

Salem Township, Luzerne County, Pennsylvania

Dates:

July 29 - August 7, 1998

Inspectors:

Roy L. Fuhrmeister, Sr. Reactor Engineer

Approved by:

William H. Ruiand, Chief

Electricai Engineering Branch

Division of Reactor Safety

Region

I

9809i40229

980904

PDR

ADOCK 05000387

8

PDR

Table Of Contents

PAGE

Executive Summary ......... ~.....................

~... ~......

~

~ ..

~

~

~ ii

Report Details ....... ~....................... ~.....................

1

V. Plant Support ....... ~.............. ~...........................

1

I

F8

Miscellaneous Fire Protection Issues ............. ~..................

1

F8.1

(Closed) URI 50-387&388/97-201-01:

Failure to follow plant

'dministrative controls in the essential safeguards

service water

(ESSW) pumphouse .......................

~ ~..............

1

F8.2

(Closed) Program Weakness:

Fire brigade effectiveness to control and

extinguish a flammable/combustible liquids fire ...................

1

F8.3

(Closed) Program Weakness:

Failure to meet NDAP-OA-0445 procedural

.

requirements for annual physicals for fire brigade members ...........

2

F8.4

(Closed) URI 50-387&388/97-201-02: Post-fire safe shutdown

methodology does not assure availability of keep-fill system...........

2

F8.5

(Closed) URI 50-387&388/97-201-03: Failure of the automatic

depressurization

system/core spray (ADS/CS) post-fire safe shutdown

methodology to meet the performance goal ....... ~..............

3

F8.6

(Closed) URI 50-387&388/97-201-04: Failure to identify preferred

post-fire safe shutdown instrumentation and required post-fire safe

shutdown actions in procedures ..............................

4

F8.7

(Closed) URI 50-387&388/97-201-05:

Fire mitigation system design and

installation does not appear to meet minimum industry codes and

standards ..............................................

4

F8.8

(Closed) URI 50-387&388/97-201-06: Operational suppression capability

of the CO~ systems has never been demonstrated..................

7

F8.9

(Closed) URI 50-387&388/97-201-07: Failure to provide the required

post-fire safe shutdown lighting ..............................

8

V. Management Meetings ....................... ~.............. ~... 9

X1

Exit Meeting Summary ..........................................

9

PARTIALLISTING OF PERSONNEL CONTACTED....... ~.......,............

10

LIST OF ITEMS OPENED, CLOSED, AND DISCUSSED ........................

11

LIST OF ACRONYMSUSED...........................................

13

Executive Summary

This inspection was conducted as a followup to the Fire Protection Functional Inspection

(FPFI) performed during October and November 1997, and documented

in NRC Inspection

Report 50-387 and 50-388/97-201.

The purpose of this inspection was to review the

unresolved issues from the FPFI inspection to characterize the findings for appropriate

enforcement actions.

The inspection included review of the Pennsylvania Power and Light

(PP&L) letter dated July 20, 1998, which responded to the issues raised in the FPFI

Report, independent verification of information provided in the July 20,-1 998, letter, and

tours of selected areas of the plant.

Plan

Su

o

The failure to properly implement controls of combustible material and transient

equipment in the ESSW Pumphouse

is an apparent violation.

(EEI 60-387&388/98-

09-01) (Section F8.1)

The failure to perform annual physical examinations for fire brigade members, as

required by NDAP-QA-0445 is an apparent violation.

(EEI 60-387&388/984942)

(Section F8.3)

The failure to provide the necessary tools and materials to make the connection

from the fire water system to the CTS for keepfill, as described in the post-fire safe

shutdown analysis, is an apparent violation.

(EEI 50-387&388/98-0943)

The failure of the ADS/CS shutdown methodology to meet the safe shutdown

performance goals specified in 10 CFR 50, Appendix R, Section III.Lis an apparent

violation.

(EEI 60-387&388/98%9%4)(Section

F8.5)

This failure to properly implement the requirements of NFPA 72E in the design and

installation of the fire detection system is an apparent violation.

(EEI 50-387&388/98-09-05)(Section

F8.7)

The failure to properly implement the requirements of NFPA 13 in the design and

installation of the sprinkler systems is an apparent violation.

(EEI 60-387&388/98-

09-06) (Section F8.7)

The failure to properly implement the requirements of NFPA 14 in the design and

installation of the standpipe and hose reel system was considered

a non-cited

violation as a result of being identified by PP&L. (NCV 50-387&388/98-09-07)

(Section F8.7)

The failure to provide emergency lighting an all areas requiring manual actions to

achieve safe shutdown is an apparent violation.

(EEI 50-387&388/98-09-08)

(Section F8.9)

Re ort Details

This inspection was conducted as a followup to the Fire Protection Functional Inspection

(FPFI) performed during October and November 1997, and documented in NRC Inspection

Report 50-387 and 50-388/97-201.

The purpose of this inspection was to review the

unresolved issues from the FPFI inspection to characterize the findings for appropriate.

enforcement actions.

The inspection included review of the Pennsylvania Power and Light

(PP&L) letter dated July 20, 1998, which responded to the issues raised in the FPFI

Report, independent verification of information provided in the July 20 1998, letter, and

tours of selected

areas of the plant.

IV. Rant Su

ort

F8

~

Miscellaneous Fire Protection Issues

F8.1

Closed

URI 50-387&388 97-201-0: Failure to follow plant administrative

controls in the essential safeguards

service water (ESSW) pumphouse.

Combustible

material in excess of five pounds was stored in the transient material area at the

east end of the pump house.

In addition, a portable stairway was chained to a

spare conduit without approval from engineering.

These deficiencies were corrected prior to the end of the FPFI by removal of the

combustible material and chaining the portable stairway to nearby structural steel.

PP&L personnel performed additional walkdowns of the facility and found no similar

problems.

Subsequent

actions by PP&L included prohibiting the use of small plastic

vacuum cleaners

in the plant.

The inspector conducted tours of the facilityto confirm the'effectiveness

of the

corrective actions.

No additional deficiencies were identified.

The Fire Protection Review Report (FPRR), Table 5.0-1, Section B.2.c states that

administrative controls at Susquehanna

Steam Electric Station (SSES) govern the

handling of, and limit, transient fire loads.

Procedure NDAP-QA-0440 implements

these administrative controls.

In addition, procedure NDAP-QA-0552 governs the

handling of transient equipment in the plant.

The failure to properly implement the requirements of NDAP-QA-0440, Rev. 2,

Control of Transient Combustible/Hazardous

Material," and NDAP-QA-0552, Rev.1,

"Transient Equipment Controls," in the ESSW Pumphouse

appears to be a violation

of the license condition.

(EEI 50-387&388/98-0941)

F8.2

Closed

Pro ram Weakness:

Fire brigade effectiveness to control and extinguish a

flammable/combustible liquids fire impacted by the policy to restrict the use of fire

fighting foam on site. Amendment 27 to the Final Safety Analysis Report (FSAR)

excludes the installation of fire protection foam anywhere in the plant.

In its response letter dated July 20, 1998, PP&L stated that all of the flammable

liquids hazards would be three-dimensional or pressure fires, not pool type fires with

a horizontal surface.

It further stated that, since the turbine generator lubricating oil

system, hydrogen seal oil system and transformers have pre-action or deluge

sprinkler systems, the use of manual fire fighting foam is not appropriate.

This is

due to the discharge of the sprinkler system breaking up the foam blanket and

rendering it ineffective.

The inspector reviewed the April 1981 Safety Evaluation Report (SER) for the SSES.

Amendment 7 to the FSAR added leak proof metal covers to the new fuel storage

vault, and Amendment 27 prohibited installation of fire fighting foam systems

h

i

.

i ..1~

ih

the applicants that the addition of the metal covers and the absence of fire fighting

foam systems would be an acceptable alternative to performing k

calculations

assuming optimum moderation."

The policy to restrict fire fighting foam is in

conformance to the facility's licensing basis.

This matter is resolved and closed.

F8.3

losed

Pro

a

k

s

Failure to meet NDAP-QA-0445 procedural

requirements for annual physicals for fire brigade members.

Operations Department

had changed over to biennial physicals for fire brigade members in 1995. The entire

operations fire brigade complement received their first biennial physical in 1996.

The July 20, 1998, response to the FPFI report states that the operations

department procedures NDAP-QA-0625 and 0653 have been revised to require

annual physicals for fire brigade members.

It further states that, with the

exception of five operations personnel scheduled for October 1998, all fire brigade

members have had their annual physicals.

The annual cycle for physicais willbe

restored by the end of 1998.

The revisions brings the operations procedures into compliance with NDAP-QA-

0445, Rev. 2, "Fire Brigade." The completion of the physical exams in October,

1998 willbring all members of the fire brigade into compliance with the

requirements.

The failure to perform annual physical examinations for fire brigade members, as

required by NDAP-OA-0445 appears to be a violation of the license condition.

(EEI 50-3878>388/98-09-02)

Closed

URI 50-3875388 97-201-02: Post-fire safe shutdown methodology does

not assure availability of keep-fill system to prevent water hammer in the high

pressure coolant injection (HPCI), reactor core isolation cooling (RCIC), core spray

(CSS), and residual heat removal (RHR) system discharge piping. The condensate

transfer system (CTS) and the cross-tie to the demineralized water system

alternative keepfill scheme are not powered from a 1E bus, which would make them

unavailable during a fire which causes

a loss of offsite power (LOOP). PPLL had

previously developed an alternate keepfill scheme using a temporary hose to supply

water from the fire water system to the CTS.

During a walkthrough conducted by

the FPFI team, the tools and equipment necessary to make the connection were not

available.

r

The July 20, 1998, PP&L response states that the tools and equipment necessary

to make the connection from the fire water system to CTS were staged

November 26, 1997. The response further states that the time lines documented in

calculation EC-013-0843 show the systems being initiated within the first

40 minutes after a fire in most cases, which indicates that the loss of keepfill would

not adversely affect the ability of the systems to perform their safe shutdown

functions.

This conclusion is born out by testing conducted subsequent to the FPFI

which showed that the discharge piping pressure was maintained in the CSS for

over 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

The inspector reviewed the timelines documented in calculation EC-013-0843,

Rev. 5, "SSES 10CFR50 Appendix R Compliance Manual," and verified the starting

times of the systems in the analyses.

In addition, the inspector inventoried the

equipment and tools staged for making the fire water to CTS cross-tie and

determined that appropriate connectors, hose, check valves and tools were

provided.

The failure to provide the necessary tools and materials to make the connection

from the fire water system to the CTS for keepfill, as described in the post-fire safe

shutdown analysis, appears to be a violation of the license condition, since

Section 1.2 of the FPRR commits to Section III.G of Appendix R to 10 CFR Part 50,

and Section 5.1.1 of the attachment to Generic Letter 86-10 states that the

performance goals of Section III.Lof Appendix R also apply to the remote and

alternative shutdown capabilities specified in Section III.G.3 of Appendix R.

(EEI 50-387&388/9849-03)

Clo ed

URI 50-3 7&

9 -2

3: Failure of the automatic depressurization

'.:

system/core spray (ADS/CS) post-fire safe shutdown methodology to meet the

performance goal of maintaining the reactor water level above the top of active fuel

(TAF). Calculation EC-013-0843 showed that spurious safety relief valve (SRV)

opening could cause reactor water level to drop below TAF. Further, calculation

EC-013-0509, Rev. 1, "Minimum Reactor Water Level Under Spurious SRV

Operation During a Control Room Fire," showed that spurious opening of one or two

SRVs could cause reactor water level to go below TAF.

Deviation Request ¹33 in the SSES FPRR states "... the reactor coolant makeup

function will be capable of maintaining the reactor coolant level above the top of the

core." The deviation request was to allow use of the ADS/CS shutdown

methodology in lieu of high pressure injection systems.

The FPRR was approved, as

documented

in an NRC SER dated August 9, 1989.

The July 20, 1998, PP&L response to the FPFI report indicates that a revision to a

thermal-hydraulic calculation, EC-THYD-1035, was performed to evaluate the

coolant level inside the core shroud for the ADS/CS safe shutdown methodology.

This analysis did not specifically model the case of spurious actuations of SRVs

since that scenario would start the reactor depressurization

at a lower pressure,

reducing the time necessary to inject using the low pressure system.

PP&L

concluded that the two-phase steam and water mixture inside the core shroud, with

a maximum void coefficient of approximately 0.8 (void fraction at core exit is

approximately 0.7 at normal full power conditions) would remain above TAF.

The inspector reviewed EC-THYD-1035, Rev. 1, "ln-Shroud Level Response for a

Boildown Transient with ADS at TAF," to evaluate the results of the ADS/CS

analysis.

Assuming that ADS actuates. automatically at the appropriate setpoint,

the calculation shows that reactor coolant level drops to 52 inches below TAF, with

partial core uncovery for a period of about 5 minutes.

If ADS actuation is delayed

until the manual action in the emergency operating procedures

(EOPs), minimum

level reaches 84 inches below TAF. The inspector also reviewed calculation

'C-013-0509, Rev. 1, "Minimum Reactor Vessel Water level Under Spurious SRV

Operation During a Control Room Fire," to evaluate the vessel level response

in the

case of spurious actuation of SRVs caused by hot shorts.

EC-013-0509 determined

that for the case of one or two SRVs opening due to fire damage, partial core

uncovery can occur for periods of up to one and one half hours if no operator action

is taken.

The failure of the ADS/CS shutdown methodology to meet the safe shutdown

performance goals specified in 10 CFR 50, Appendix R, Section lll.Lappears to be a

violation of the license condition, since Section 1.2 of the FPRR commits to

Section III.G of Appendix R, and Section 5.1.1 of Enclosure

1 to Generic Letter 86-10 states that the performance goals of Section III.Lof Appendix R apply

to remote and alternative shutdown methods under Section III.G.3 of Appendix R.

(EEI 50-387&388/98%9-04)

F8.6

I sed

Rl 5

-

&

8 9 - 0 -04: Failure to identify preferred post-fire safe

shutdown instrumentation and required post-fire safe shutdown actions in

procedures used for post-fire safe shutdown from inside the control room.

~

In the event of a fire in the plant; the operators use emergency operating procedures

(EOPs), off-normal (ON) procedures,

operating procedures

(OPs), and pre-fire plans

for guidance on actions to be taken and equipment which is available.

The ON for

fire conditions is ON-013-001, "Post-Fire Shutdown Procedure."

The inspector reviewed Revision 8 to ON-013-001 to determine what information it

provided operators for post-fire conditions.

The attachments

provide specific

guidance for actions to compensate for fires in different areas of the facility, as well

as a listing of locations of sound-powered telephone stations for establishing

communication.

The pre-fire plans for the various fire areas list the equipment and

instrumentation which may be affected by a fire in that area.

Based on the fire affected instrumentation being identified in the pre-fire plans, and

the required actions being identified in the attachments to the off-normal procedure,

there is no violation of requirements.

This issue is closed.

F8.7

Closed

URI 50-387&388 97-201-05: Fire mitigation system design and

installation does not appear to meet minimum industry codes and standards.

Smoke detector locations do not take into consideration all aspects of ceiling shape

and surface, ceiling height, and the effects of the ventilation system, as required by

National Fire protection Association (NFPA) Standard 72E. Sprinkler installations do

not conform to the requirements of NFPA 13.

Hose reel and standpipe locations do

,, ~

not conform to the requirements of NFPA 14. These deficiencies were identified by

FPFI team members who performed a walkdown of several elevations in the Unit 1

and Unit 2 Reactor Buildings, with the exception of the hose reel and standpipe

locations.

The code of record for the fire and smoke detection system is the 1975 edition of

NFPA 72D, "Standard for the Installation, Maintenance and Use of Proprietary

Signaling Systems for Watchmen, Fire Alarm and Supervisory Service." The

associated

standard for fire and smoke detector placement is the 1974 edition of

NFPA 72E, "Standard on Automatic Fire Detectors.

During tours of the facility,

the FPFI inspection identified the following deficiencies with smoke and heat

detector placement:

~

On the 670'-0" level of the Unit 1 Reactor Building, the FPFI team identified

two detectors (1-I-222 and 1-I-219) which were suspended

more than

one foot below the ceiling. This is contrary to NFPA 72E Section 4-3, which

requires that spot type smoke detectors be mounted on the ceiling.

~

On the 719'-0" level of the Unit 2 Reactor Building, the team found smoke

detectors in rooms 406 and 407 which were mounted within one foot of the

supply air diffuser, with the air flow directed across the detector.

This is

contrary to NFPA 72E, Section 4-4, which prohibits placing smoke detectors

where air from supply diffusers could dilute smoke before it reaches the

detector.

This failure to properly implement the requirements of NFPA 72E in the design and

installation of the fire detection system appears to be a violation of the license

condition.

(EEI 50-3878c388/98%9%5)

FPRR Sections 4.2, "Automatic Wet pipe Sprinkler Systems," 4.3, "Dry Pipe

Sprinkler Systems," and Table 5.0-1, Section E.3.c state that the sprinkler systems

were designed in accordance with NFPA Standard 13. The code of record for the

sprinkler systems

is the 1974 edition of NFPA 13, "Standard for the Installation of

Sprinkler Systems."

Additional guidance on sprinkler system design and installation

is contained in NRC Generic Letter (GL) 86-10, "Implementation of Fire Protection

Requirements."

During facilitytours, the inspection team identified the following

deficiencies regarding sprinkler installation:

~

The upright sprinkler head located outside door 1-109 (Unit 1 remote

shutdown panel room) has the sprinkler head and deflector located at a

45 degree angle, and appears to have fire barrier material on its fusible link

and deflector.

This is contrary to NFPA 13 Section 4-2.4.7 which requires

sprinkler deflectors to be parallel to roofs and ceilings, and NFPA 13

Section 3-16 which prohibits application of coatings to sprinklers after they

leave the place of manufacture.

~

~

~

~

An upright sprinkler head located above the Unit 1 HPCI pump is connected

to a /*"X4"pipe nipple, and is located in

a beam pocket such that the spray

pattern is obstructed on all sides.

This is contrary to NFPA 13 Section 4-2A

which requires sprinklers in bays to be at sufficient distances from beams to

avoid obstruction of sprinkler discharge pattern, and NFPA 13 Section 7-1,

which prohibits the use of ferrous piping less than one inch nominal size.

~

There are obstructions below the sprinkler heads outside the door to the

Unit 2 traversing incore probe room (door 406 on the 719'-0" level of the

Unit 2 Reactor Building) including light fixtures, beams and electrical boxes.

This is contrary to NFPA 13 Chapter 4 which requires minimizing the

interference to discharge patterns from beams, braces, girders, trusses,

lighting fixtures, and air conditioning ducts.

~

The control rod drive pump area on the 719'-0" level of the Unit 2 Reactor

Building has overhead obstructions, including lighting fixtures, beams, and

electrical components that inhibit the sprinkler from developing and delivering

an effective spray pattern to the floor within the protected area.

This is

contrary to NFPA 13, Chapter 4.

~

On the 749'-0" level of the Unit 2 reactor building, near column-line T30.5,

the ceiling level sprinklers are obstructed by a four feet wide ventilation duct

and by Thermo-Lag barrier E2KK21, which is also greater than four feet

wide. This is contrary to NFPA 13 Chapter 4.

The failure to properly implement the requirements of NFPA 13 in the design and

installation of the sprinkler systems appears to be a violation of the license

conditions.

(EEI 50-387&388/98-09-06)

FPRR Section 4.6 and Table 5.0-1 Section E.3.d state that NFPA 14 was used as

guidance for the design and installation of the system of standpipes

and hose reels

in the station.

The code of record is the 1974 edition of NFPA 14, "Standard for

the Installation of Standpipe and Hose Systems."

SSES uses

a Class II system.

consisting of 1-1/2" hoses intended for use by the building occupants until the

arrival of the fire department.

Section 3-2.2 requires that the location and spacing

of the hose stations be such that all portions of each story of the building are within

30 feet of a nozzle when attached to not more than 100 feet of hose.

The FPFI

team examined several hose stations serving the main control room and the Unit 1

lower cable spreading room.

No deficiencies were identified. During the week of

October 27, 1997 (while the FPFI team was off-site), PPSL performed additional

walkdowns, and identified several hose stations which did not meet the area

coverage requirement.

These deficiencies were documented

in condition report 97-

3650. This non-repetitive licensee-identified violation, with committed corrective

actions, of the fire protection license condition ultimately NFPA 14is being

treated as a Non-Cited Violation, consistent with Section VII.B.1 of the NRC

Enforcement Policy. (NCV 50-3878c388/98-09-07)

In its July 20, 1998, letter, PP&L stated they are performing a comprehensive

assessment

of the fire detection and suppression systems for safety related areas of

the facility. This assessment

willinclude walkdowns of the in-plant installation to

determine the level of compliance of the installed systems.

Deviations from the

requirements willbe justified based on additional analyses,

or entered in to the

corrective action program.

Corrections willimplemented under the plant

modification process.

PP&L expects to complete the walkdowns and evaluations by

the end of 1998.

F8.8

Closed

URI 50- 87&3 8 97-2: Operational suppression capability of the

CO, systems has never been demonstrated

by code-required system full discharge

tests.

The only CO, total flooding system at SSES which was full discharge tested

failed the test.

No additional full discharge tests were performed, and an alternative

testing methodology was used.

FPRR Section 4.8, and Table 5.0-1, Section E.5 state that the carbon dioxide fire

suppression

systems are designed in accordance with NFPA 12. The code of record

for the carbon dioxide systems is the 1973 edition of NFPA 12, "Standard on

Carbon Dioxide Extinguishing Systems."

In addition, Table 5.0-1, Section A.2

states, "Appropriate procurement and drawing procedures existed in Bechtel for the

control of inspections, tests, and instructions for the fire protection equipment and

systems during the procurement and construction phases.

Total flooding gaseous

suppression systems are installed in cable chases,

relay

rooms, control room under floor areas, control room soffit areas, and rooms C-411,

C-412, C-413, and C-414 soffit areas.

These systems were designed and

installed

under Bechtel Specification 8856-M-344. Section 10.3 of the specification states,

"Afull carbon dioxide discharge test and concentration test shall be made for-each

hazard.

The only total flooding CO~ suppression system to be full discharge tested

at SSES, the elevation 698'orth cable chase, failed the test, due to inadequate

agent retention time. The test results are documented on work authorization (WA)

U27611. The WA does not contain any data in the "CO, Concentration %"

column. Strip chart traces attached to the WA indicate that the longest time the

agent was maintained at 50% concentration was 13 minutes at one foot from the

floor elevation.

The test results were not signed for acceptance

by the Factory

Mutual witness, as required.

In a Mutual Atomic Energy Reinsurance

Pool (MAERP)

reinspection report dated April 23, 1982, the test was accepted

on the basis that

the retention time was expected to have been met had the access door not been

left open.

The report concluded, "In the future during testing, carbon dioxide

concentration levels will be monitored for a minimum of twenty minutes to permit a

more complete evaluation of how well the extinguishing agent is holding." The

"future" tests were never conducted.

NRC Inspection report 50-387&388/89-09

documented that initial acceptance

tests of the other systems were not performed.

To resolve the 1989 open item, PP&L proposed alternate testing to verify the

capability of the carbon dioxide total flooding suppression

systems to maintain the

required concentration for the required time to ensure complete extinguishment.

This test methodology is based on the alternate testing described in the 1989

edition of NFPA 12A, "Standard on Halogenated

Fire Extinguishing Agent Systems-

Halon 1301." This alternate test methodology was reviewed and approved by the

Office of Nuclear Reactor Regulation (NRR) in an SER dated May 12, 1992. That

SER refers to the failed full discharge test documented on WA-U27611, and the fact

that no other preoperational testing was performed to demonstrate the

systems'apabilities.

Thus, it can-be shown that NRR was aware of the test failure, and the

reasons to which it was attributed, at the time they reviewed and approved the .

alternate test methodology.

4

Based on the SER specifically recognizing that the only full discharge test attempted

at SSES failed, and approving the alternate testing, this matter is resolved and

closed.

F8.9

Cl se

URI 50-3 7&388 7-2: Failure to provide the required post-fire.safe

shutdown lighting in areas, and have a program that assures the operability of

required lighting in the "E" diesel building. During a walkthrough of the procedure

for shutdown outside the control room, the FPFI team identified several areas of the

plant where manual actuations were required to be performed that did not have the

required 8-hour battery supplied emergency lights.

In addition, the team found that

the emergency lights in the "E" diesel generator building, where manual actions

would need to be performed in the event the "E" diesel generator were aligned in

place of one of the divisional diesel generators,

had not been evaluated to determine

which were needed for safe shutdown.

FPRR Section 3.3.2 and Table 5.0-1, Section D.5.a, state that SSES willconform to

the emergency lighting requirements in Section III.J of Appendix R to 10 CFR,

Part 50.Section III.J requires that emergency lighting units (ELUs) with at least an

8-hour battery power supply be provided an all areas needed for operation of safe

shutdown equipment, and in access

and egress areas thereto.

The FPFI team conducted

a walkthrough of the Unit 1 alternate shutdown

procedure, ON-100-109.

During that walkthrough, the following emergency lighting

deficiencies were identified:

The procedure required reactor water cleanup (RWCU) system equipment

located in a corridor on the west side of the 779'-0" level of the reactor

building to be checked for evidence of leakage or flow diversion.

There are

no safe shutdown emergency lights in this area.

The procedure requires that breaker 018 in power panel 1Y219 be opened to

stop RWCU leakage, or flow diversion to radioactive waste or the main

condenser via RWCU. Power panel 1Y219, located on the 719'-0" level of

the Unit 1 reactor building is not illuminated by an ELU.

To ensure that shutdown cooling return flow is injected into the reactor

vessel, rather than the recirculation loop, flow control valve HV-243-FO23A

must be closed.

Since this valve can not be controlled from the remote

shutdown panel, for shutdown outside the control room, actions must be

carried out at motor control center (MCC) 2B237043.

No emergency lighting

was installed at the MCC.

The FPFI team also evaluated emergency lighting in other areas of the plant.

In the

event that the "E" diesel generator is aligned in place of one of the divisional diesel

generators,

manual actions will need to be carried out in the "E" diesel generator

building for shutdown outside the control room.

No safe shutdown lights had been

provided in the "E diesel generator building.

In their July 20, 1998, response,

PP&L stated that the RWCU actions were not

needed to reach hot shutdown conditions.

This statement is supported by a

revision to calculation EC-013-0859, "Appendix R Analysis for a Control Room

Fire." Revision 7 to the calculation, dated June 24, 1998, documents that there are

more than eight hours after the fire, in which to isolate the RWCU system.

This

calculation revision also shows that RWCU isolation is not needed to achieve hot

shutdown conditions.

As a result, PP&L is removing the RWCU isolation actions

from the alternate shutdown procedures.

PP&L has identified those ELUs in the "E diesel generator building necessary for

post-fire safe shutdown.

Those ELUs have been added to the maintenance

and

surveillance testing programs.

The failure to provide'emergency lighting in all areas requiring manual actions to

achieve safe shutdown appears to be a violation of the requirements of Section III.J

of Appendix R to 10 CFR 50, as committed to in Section 1.2 of the FPRR, and

therefore an apparent violation of the license condition.

(EEI 60-387&388l98%9-

08)

V. IVlana ement IVlee in s

X1

Exit Meeting Summary

An exit meeting was conducted by telephone on August 7, 1998. At that time, PP&L

acknowledged the inspection findings and provided additional information regarding the

time frame for corrective actions.

The inspector was also informed that several of the

issues are being pursued generically by the Boiling Water Reactor Owners Group.

None of the information reviewed during the course of the inspection was identified as

proprietary.

PARTIALLISTING OF PERSONNEL CONTACTED

Penns

Ivania Power and

I

G. Miller, General Manager, Nuclear Engineering

R. Pagodin, Manager, Nuclear System Engineering

M. Simpson, Manager, Nuclear Technology

T. Gorman, Project Manager, Nuclear Engineering

J.

Kenney, Supervisor, Nuclear Licensing

R. Prego, Supervisor, Site Surveillance Services

R. Wehry, Supervising Engineer, licensing

S.

Davis, Site Fire Protection Engineer

W. Williams, Senior Engineer, Licensing

Nuclear Re ulato

Commission

J.

Richmond, Resident Inspector

A. Blarney, Resident Inspector

~

~

~Oened

LIST OF ITEMS OPENED, CLOSED, AND DISCUSSED

0

EEI 50-387&388/98-09-01

EEI 50-387&388/98-09-02

Failure to properly implement the requirements of

NDAP-QA4440 and NDAP-OA-0552 in the ESSW

Pumphouse

Failure to perform annual physical examinations for

members of the fire brigade

EEI 50-387&388/98-09-03

Failure to provide tools and equipment necessary to

make the connection from the fire water system to the

condensate

transfer system for keepfill

EEI 50-387&388/98-094

Failure to meet the safe shutdown performance goal of

maintaining reactor vessel level above the top of the

active fuel

EEI 50-387&388/09-09-05

Failure to properly implement the requirements of NFPA

72E in the design and installation of the fire detectors

EEI 50-387&388/98-09-06

NCV 50-387&388/98-09-07

Failure to properly implement the requirements of NFPA

13 in the design and installation of the fire suppression

sprinkler systems.

Failure to properly implement the requirements of NFPA

14 in the design and installation of standpipe system.

EEI 50-387&388/98-09-08

Failure to provide 8-hour battery powered emergency

lighting units in all areas requiring manual actions to

achieve safe shutdown

Closed

URI 50-387&388/97-201-01

Failure to follow plant administrative control procedures

in the essential safeguards

pumphouse

URI 50-387&388/97-202-02

Post-fire safe shutdown methodology does not assure

availability of keepfill system to prevent water hammer

in the HPCI, RCIC, CSS and RHR system discharge

piping

URI 50-387&388/97-201-03

Failure of the ADS/CS post-fire safe shutdown

methodology to meet Appendix R reactor performance

goals by maintaining the reactor water level above the

top of the active fuel

URI 50-3875388/97-201-04

Failure to identify preferred post-fire safe shutdown

instrumentation and required post-fire safe shutdown

actions in procedures used for post-fire safe shutdown ~

'RI

50-3878(388/97-201-05

Fire mitigation system design and installation does not

appear to meet minimum industry codes and standards

URI 50-387&388/97-201-06

The operational suppression capability of the CO,

systems has never been demonstrated

by code required

system full discharge tests

URl 50-3878E388/97-201-07

Failure to provide the required post-fire safe shutdown

lighting in areas and have a program that assures the

operability of required lighting in the "E" diesel building

LIST OF ACRONYMS USED

ADS

CFR

CSS

CTS

ELU

EOP

ESSW

FPFI

FPRR

FSAR

GL

HPCI

cleft

LOOP

NFPA

NRC

MAERP

MCC

ON

OP

PP&L

RCIC

RHR

RWCU

SER

SRV

SSES

TAF

WA

Automatic Depressurization System

Code of Federal Regulations

Core Spray System

Condensate

Transfer System

Emergency Lighting Unit

Emergency operating Procedure

Essential Safeguards

Service Water

Fire Protection Functional Inspection

Fire Protection Review Report

Final Safety Analysis Report

NRC Generic Letter

High Pressure Coolant Injection

Effective Neutron Multiplication Factor

Loss of Offsite Power

National Fire Protection Association

Nuclear Regulatory Commission

Mutual Atomic Energy Reinsurance

Pool

Motor Control Center

Off Normal Operating Procedure

Operating Procedure

Pennsylvania Power and Light

Reactor Core Isolation Cooling

Residual Heat Removal

Reactor Water Cleanup

Safety Evaluation Report

Safety Relief Valve

Susquehanna

Steam Electric Station

Top of the Active Fuel

Work Authorization

~t

A