SUBJECT:
CALVERT CLIFFS NUCLEAR POWER PLANT, UNITS 1 AND 2 -
CORRECTION TO TECHNICAL SPECIFICATION PAGES 1.1-2, 1.1-3, AND 1.1-4 TO CORRECT ERRORS INTRODUCED DURING THE ISSUANCE OF AMENDMENT NOS. 286 AND 263 (CAC NOS. MD7315 AND MD7316)
Dear Mr. Hanson:
On April 23, 2008 (Agencywide Documents Access and Management System Accession No. ML080840339), the U.S. Nuclear Regulatory Commission issued Amendment Nos. 286 and 263 to Renewed Facility Operating License Nos. DPR-53 and DPR-69 for the Calvert Cliffs Nuclear Power Plant (Calvert Cliffs}, Units 1 and 2, respectively. During the issuance of the amendments, errors were inadvertently introduced on Technical Specification pages 1.1-2, 1.1-3, and 1.1-4. Specifically, the definitions of "DOSE EQUIVALENT 1-131" and "La" were inadvertently changed. These inadvertent changes were neither addressed in the notice for the amendments nor reviewed as part of the license amendment request.
Enclosed are the corrected pages. Please, replace Technical Specification pages 1.1-2, 1.1-3, and 1.1-4 of the Calvert Cliffs, Units 1 and 2, Renewed Facility Operating Licenses with the enclosed corrected pages.
If you have any questions, please contact me at (301) 415-2871 or Michael.Marshall@nrc.gov.
Docket Nos. 50-317 and 50-318
Enclosure:
Corrected Calvert Cliffs, Unit 1 and 2, Technical Specification Pages cc w/encls: Distribution via Listserv Sincerely, ~~
Michael L. Marshall, Jr., Senior Project Manager Plant Licensing Branch I Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation
ENCLOSURE CORRECTED PAGES 11.1-2, 1.1-3, AND 1.1-4 OF RENEWED FACILITY OPERATING LICENSE NOS. DPR-53 AND DPR-69 FOR AMENDMENT NOS. 286 AND 263 EXELON GENERATION COMPANY, LLC CALVERT CLIFFS NUCLEAR POWER PLANT, UNITS 1 AND 2 DOCKET NOS. 50-317 AND 50-318
1.1 Definitions CHANNEL FUNCTIONAL TEST CORE OPERATING LIMITS REPORT (COLR)
DOSE EQUIVALENT I-131 CALVERT CLIFFS - UNIT 1 CALVERT CLIFFS - UNIT 2 Definitions 1.1 indication and status to other indications or status derived from independent instrument channels measuring the same parameter.
A CHANNEL FUNCTIONAL TEST shall be:
Analog Channels - the injection of a simulated signal into the channel as close to the primary sensor as practicable to verify OPERABILITY of a11 devices in the channel required for channel OPERABILITY.
Bistable Channels - the injection of a simulated signal into the channel sensor to verify OPERABILITY of all devices in the channel ired r channel ILITY.
The CHANNEL FUNCTIONAL TEST may be performed by means of any series of sequential. overlapping or total channel steps.
The COLR is the unit specific document that provides cycle specific parameter limits for the current reload cycle. These cycle specific parameter limits shall be determined for each reload cycle in accordance with Specification 5.6.5. Plant operation within these limits is addressed in individual Specifications.
DOSE EQUIVALENT I-131 shall be that concentration of I-131 (microcuries/gram) that alone would produce the same thyroid dose as the quantity and isotopic mixture of 1-131, 1-132, I-133, 1-134, and 1-135 actually present.
The TEDE (Total Effective Dose Equivalent) inhalation dose conversion factors used for this calculation shall be those listed in Table 2.1 in the column headed "effective" of Federal Guidance Report 11, ORNL, 1988, "Limiting Values of Radionuclide Intake and 1.1-2 Amendment No. 286 Amendment No. 263
1.1 Definitions f-AVERAGE DISINTEGRATION ENERGY ENGINEERED SAFETY FEATURE (ESF} RESPONSE TIME LEAKAGE CALVERT CLIFFS - UNIT 1 CALVERT CLIFFS - UNIT 2 Definitions 1.1 Air Concentration and Dose Conversion Factors for Inhalation, Submersion, and Ingestion."
E shall be the average (weighted in proportion to the concentration of each radionuclide in the reactor coolant at the time of sampling} of the sum of the average beta and gamma energies per disintegration (in MeV) for isotopes, other than iodines, with half lives> 15 minutes, making up at least 95% of the total non-iodine activity in the coolant.
The ESF RESPONSE TIME shall be that time interval from when the monitored parameter exceeds its ESF actuation setpoint at the channel sensor until the ESF equipment is capable of performing its safety function (i.e., the valves travel to their required positions, pump discharge pressures reach their required values, etc.). Times shall include diesel generator starting and sequence loading delays, where applicable.
The response time may be measured by means of any series of sequential, overlapping, or total steps so that the entire response time is measured.
In lieu of measurement, response time may be verified for selected components provided that the components and methodology for verification have been previously reviewed and approved by the NRC.
The maximum allowable containment leakage rate, L., shall be 0.16% of containment air weight per day at the calculated peak containment pressure (P.).
LEAKAGE shall be:
- a.
Identified LEAKAGE
- 1.
LEAKAGE, such as that from pump seals or valve packing (except reactor coolant 1.1-3 Amendment No. 286 Amendment No. 263
1.1 Definitions MODE CALVERT CLIFFS - UNIT 1 CALVERT CLIFFS - UNIT 2 Definitions 1.1 pump (RCP) seal leakoff), that is captured and conducted to collection systems or a sump or collecting tank;
- 2.
LEAKAGE into the containment atmosphere from sources that are both specifically located and known either not to interfere with the operation of leakage detection systems or not to be pressure boundary LEAKAGE; or
- 3.
Reactor Coolant System (RCS) LEAKAGE through a steam generator to the Secondary System (primary to secondary LEAKAGE).
- b.
Unidentified LEAKAGE All LEAKAGE (except RCP seal leakoff) that is not identified LEAKAGE;
- c.
Pressure Boundary LEAKAGE LEAKAGE (except primary to secondary LEAKAGE) through a nonisolable fault in an RCS component body, pipe wall, or vessel wall.
A MODE shall correspond to any one inclusive combination of core reactivity condition, power level, average reactor coolant temperature, and reactor vessel head closure bolts specified in Table 1.1-1 with fuel in the reactor vessel.
1.1-4 Amendment No. 286 Amendment No. 263
SUBJECT:
CALVERT CLIFFS NUCLEAR POWER PLANT, UNITS 1 AND 2 -
CORRECTION TO TECHNICAL SPECIFICATION PAGES 1.1-2, 1.1-3, AND 1.1-4 TO CORRECT ERRORS INTRODUCED DURING THE ISSUANCE OF AMENDMENT NOS. 286 AND 263 (CAC NOS. MD7315 AND MD7316) DATED MAY 12, 2017 DISTRIBUTION:
Public LPL 1 R/F RidsNrrDorlLpl1 Resource RidsNrrPMCalvertCliffs Resource RidsNrrLALRonewicz Resource RidsRgn1 MailCenter ADAMS Accession Number: ML17129A506 OFFICE DORL/LPL 1 /PM DORL/LPL 1 /LA DORL/LPL 1 /BC NAME MMarshall LRonewicz Joanna DATE 05/11/2017 05/09/2017 05/10/2017 OFFICIAL RECORD COPY DORL/LPL 1 /PM MMarshall 05/12/2017