Forwards Request for Addl Info Re Util 860512 & 870218 & 1112 Submittals in Response to IE Bulletin 85-003, Motor Operated Valve Common Mode Failures During Plant Transients Due to Improper Switch.... for Response within 1 Month
ML17055D773
Person / Time
Site: Nine Mile Point 
Issue date: 04/11/1988
From: Wenzinger E
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To: Mangan C
NIAGARA MOHAWK POWER CORP.
References
IEB-85-003, IEB-85-3, NUDOCS 8804200095
Download: ML17055D773 (10)


Text

. ~'cczzzm Tzo n~isU~o~

nEMo~s&vrox nsTzM

\\)

REGULATORY INFORMATION DISTRIBUTION SYSTEM (RIDS)

ACCESSION NBR:8804200095 DOC.DATE: 88/04/11 NOTARIZED-NO DOCKET g FACXL:50-410 Nine Mile Point Nuclear Station, Unit, 2, Niagara Moha 05000410 AUTH.NAME AUTHOR AFFILIATION WENZINGER,E.C.

Region 1, Ofc of the Director RECIP.NAME RECIPIENT AFFILIATXON MANGAN,C.V.

Niagara Mohawk Power Corp.

SUBJECT:

Forwards reguest for addi info to evaluate valve operabzlxty considerations'in accordance w/IE Info Bulletin 85-003.

SIZZ:

DISTRIBUTION CODE:

IE11D COPIES RECEIVED:LTR ENCL SIZE:

TXTLE: Bulletin Response (50 DKT)

NOTES:

RECIPXENT ID CODE/NAME PD1-1 LA HAUGHEY,M INTERNAL: AEOD/DOA AEOD/DSP/TPAB NRR/DEST/ADS 7E NRR/DOEA/EAB ll NRR/DREP/EPB 10 IZQ 02 RGN1 FILE Ol EXTERNAL: LPDR NSIC COPIES LTTR ENCL 1

0 1

1 1

1 1

l 1

1 1

l 1

1 1

1 I

3, 1

1 1

1 RECIPIENT ID CODE/NAME PD1-1 PD BENEDICT,R AEOD/DSP NRR/DEST/ADE 8H NRR/DEST/MEB 9H NRR/DORA/GCB ll NRR/PMAS/ILRB12 RES/DE/EIB NRC PDR COPIES LTTR ENCL 1

1 1

1 1

1 l

1 1

1 l

l 1

1 S

~

A TOTAL NUMBER OF COPIES REQUIRED:

LTTR 20 ENCL 19

1lAPR ass

=Docket No. 50-410 Niagara Mohawk Power Corporation ATTN:

Mr. C.

V. Mangan Senior Vice President 301 Plainfield Road

Syracuse, New York 13212 Gentlemen:

Subject:

Additional Information on IEB 85-03 This transmits a request for additional information needed by the NRC to evaluate valve operability considerations in accordance with IEB 85-05, "Motor-Operated Valve Common Mode Failures During Plant Transients Due to Improper Switch Settings."

l To facilitate NRC review, we are requesting that you supplement your May 12,

1986, February 18, 1987 and November 12, 1987 responses to IEB 85-03 with the information identified in the enclosure to this letter.

Please make the submittal within one month of the date of this letter, if practicable.

If development and submittal of the information will take longer, please make an interim submittal in one month, including the considerations in and timing for providing the remaining information.

Your submittal should be made to the NRC Document Control Desk, with copies to this office and the NRR Division of Operational Events Assessment.

Thank you for your cooperation.

Sincerely,

<earp Edward C. Wenzinger, Chief Projects Branch No.

2 Division of Reactor Projects

Enclosure:

Request for Additional Information (RAI)

Contact:

R. J. Kiessel, NRR (301) 492-1154 8304200095 830411 PDR ADOCK 05000410 9

DCD OFFICIAL RECORD COPY LTR IEB 85 0003.0.0 04/08/88

0 l

Niagara Mowhawk Power Coporation iiAPR 1988 cc w/encl:

J.

A. Perry, Vice President, Quality Assurance W. Hansen,

Manager, Corporate Quality Assurance J. Aldrich, Unit I Superintendent, Operations R.

G. Smith, Unit 2 Superintendent, Operations C.

Beckham, Manager, Nuclear Quality Assurance Operations T. J. Perkins, General Superintendent R.

B. Abbott, Unit 2 Station Superintendent Connor 5 Wetterhahn John W. Keib, Esquire Department of Public Service, State of New York Public Document Room (PDR)

Local Public Document Room (LPDR)

Nuclear Safety Information Center (NSIC)

NRC Resident Inspector State of New York bcc w/encl:

Region I Docket Room (with concurrences)

Management Assistant, DRMA (w/o encl)

DRP Section Chief Region I SLO Robert J.

Bores, DRSS R. Kiessel,
NRR, EAB M. Haughey,
NRR, PDI-. I RI: DR John 4/$ /88 We

'nger 4/

/88

,OFFICIAL RECORD COPY LTR IEB 85 0004.0.0 04/08/88

0

~

MAR 14 1988 age 1 of 2

REQUEST FOR ADDITIONAL INFORMATION (RAI) RE:

Review of Responses to Action Item e of IE Bulletin 85-03 Licensee:

Niagara Mowhawk Power Corporation 301 Plainfield Road

Syracuse, New York 13212 Unit(s): Nine Mile Point 2

Date of Response:

05-12-86 02-18-87

+11-13-87

+This response to Action, Item f has not been reviewed completely.

Respondent C. V. Mangan, Senior Vice President The information provided in your response to.Action Item e of IE Bulletin 85-03 was found to be deficient in some areas.

Provide the additional information necessary to resolve the following comments and questions:

l. If MOVATS is planned for application to some MOVs which are not included in its data
base, commit to and describe an alternate method for determining the extra thrust necessary to overcome the pressure differentials for these valves.
2. Revise Table 1 of the response dated 02-18-87 to include RCIC Turbine Trip and Throttle MOV 150, or justify its exclusion.

This valve is identified as MOV X on Page 74 of BWROG Report NEDC-31322 dated September

1986, and is shown normally open in Zone J-8 of Drawing 12177-PID-35B-4.

This MOV is listed in the response for one other GE Class 5 facility.

Assume inadvertent equipment operations, as required by Action Item a of the bulletin.

How would operation of the RCIC Turbine be ensured if this valve were to be (a) actuated inadvertently to the closed position upon intended initiation of the system or (b) left closed inadventently?

3.

The proposed program for action items b,

c and d of the bulletin is incomplete.

Provide the following details as a

minimum:

(a) commitment to a training program for setting switches, maintaining valve operators, using, signature testing equipment and interpreting signatures,

~

hlAR 14 1988 Page of 2

RAI for Nine Mile Point 2

(b) description of a method possibly needed to extrapolate valve stem thrust determined by testing at less than maximum differential pressure, and (c) consideration of pipe break conditions as required by the bulletin.

Note:

A partial review of the response dated ll-'13-87 indicates these comments apply to it as well as to the earlier response.

lj