UNITEDSTATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D. C. 20555 AUG 0 6 tSR6 SAFETY EVALUATION BY THE OFFICE OF NUCLEAR REACTOR REGULATION RELATING TO APPENDIX R, FULL COVERAGE DETECTION AND SUPPRESSION SYSTEMS NIAGARA MOHAWK POWER CORPORATION NINE MILE POINT NUCLEAR STATION UNIT NO.

1 DOCKET NO. 50-220

1.0 INTRODUCTION

Generic Letter 83-.33 dated October 19, 1983, stated that to satisfy the requirements of Subsections III.G.2.b, III.G.2.c and III.G.2.e of Appendix R to 10 CFR Part 50, fire detectors and automatic suppression systems need to be installed throughout the fire area.

By letter dated December 22, 1983, the licensee requested an exemption from these require-

ments, as interpreted in Generic Letter 83-33, for the Reactor Building.

At the Appendix R Lessons Learned Workshop held in Region I on April 18, 1984, the NRC informed the industry of a draft revised interpretation of these subsections that would accept partial coverage detection and automatic suppression systems that were supported by.a fire hazards analysis as meeting the requirements of the subsections.

By letter dated May 11, 1984, the licensee withdrew the exemption request dated December 22, 1983.

The supporting analysis for the partial coverage detection and suppression systems remained for staff review.

During the period January 21-25, 1985, the NRC inspected the facility and reviewed the licensee's analysis for the reactor building.

The inspection team requested additional information and the subject (50-220/85-01-02) was referred to NRR for resolution.

By letter dated February ll, 1985, the licensee provided the additional information requested by the inspection team.

The aforementioned interpretation was aporoved by the Commission on March 6, 1986 (SECY 85-306/3068).

Therefore, we have evaluated the lack of full coverage detection and suppression systems for compliance with that interpretation.

2.0 2.1 EVALUATION General 8608190171 860806 PDR ADOCK 05000220 F

PDR Section III.G.2.b and III.G.2.c of Appendix R state that "In addition, fire detectors and automatic fire suppression system shall be installed in the fire area...."

Other provisions of Appendix R also use the phrase "fire detectors and an automatic fire suppression system in the fire area...."

(see e.g.,Section III.G.2.e).

In order to comply with these provisions, suppression and detection sufficient to protect against the hazards of the area must be installed.

In this regard, detection and suppression providing less than full area coverage may be adequate to comply with the regulation.

Where full area

fr n

suppression and detection is not installed, licensees must perform an evaluation to assess the adequacy of partial suppression and detection to protect against the hazards in the area.

The evaluation must be performed by a fire protection engineer and, if required, a systems engineer.

Although not required, licensees may submit their evaluations to the staff for'eview and concurrence.

In any event, the evaluations must be retained for subsequent NRC audits.

Where a licensee is providing no suppression or detection, an exemption must be requested.

2.2

~fl The Reactor Building is considered to be one fire area.

It is separated vertically into Fire Sub-Area I and Fire Sub-Area 2.

Fire Sub-Area I consists of fire zones R1A, RIC, RID, R2A, R3A, R4A, R5A and R6A; i.e.,

the east half of the building on all elevations.

Fire Sub-Area 2

consists of fire zones

R1B, R2B,
R2C, R3B, R4B, R58, and R6B; i.e., the west'alf of the Reactor Building.

One train of safe shutdown capability is located in Fire Sub-Area I; a second train is 'located in Fire Sub-Area 2.

Fire Break Zones (FBZ) are provided on each elevation to separate Fire Sub-Area I and 2.

These FBZ's are at least 20 feet wide with little or no in-site combustibles.

These FBZ's have full coverage detection systems and, automatic pre-action sprinkler systems designed in accordance with NFPA-13.

The combustible loading on each elevation is low.

The corresponding maximum fire times range from 0.5 minute to 17 minutes.

Automatic detectors are installed throughout both Fire Sub-Area I and 2.

Automatic pre-action

systems, or Halon 1301 systems, are provided for specific hazards; i.e., (1) heavy concentrations of cables, (2) designated storage
area, (3) change
rooms, and (4) emergency condenser valve room.

Cables in the FBZ's are coated with fire retardant material.

Floor penetrations at elevations 218, 298, 318 and 340 are sealed where the FBZ on adjacent elevations do not coincide.

2.3 Discussion In regard to full coverage detection and suppression

systems, automatic suppression systems are provided for specific hazards in the fire area.

Further, the locations of the redundant shutdown trains on opposite sides of the Reactor Building provide substantial physical separation between the trains.

Moreover, the automatic pre-action sprinkler throughout the FBZ provides additional protection for the redundant trains on each elevation.

The intervening combustibles in the FBZ are negligible.

~

4 In addition, by letter dated February 11, 1985, the licensee committed that if new cable is installed in an FBZ, it will be run in conduit, be coated with a fire retardant coating, or will have approved cable tray fire stops at each boundary of the FBZ in tray fire stops that traverse the FBZ. It is our understanding that all new cabl'e would be qualified to IEEE 383.

3.0 CONCLUSION

Based on the above evaluation, the configuration of protection complies with the aforementioned interpretation and is, therefore, acceptable.

AUG 0 5 598 Principal Contributor:

. R. Ferguson