Forwards IE Bulletin 80-06, Engineered Safety Feature (ESF) Reset Controls. No Written Response Required
ML17053B508
Person / Time
Site: Nine Mile Point 
Issue date: 03/13/1980
From: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To: Rhode G
NIAGARA MOHAWK POWER CORP.
References
NUDOCS 8003260147
Download: ML17053B508 (10)


Text

~8 REoy

~4 0

~o~

++*++

Docket No.- 50-410 UNITEDSTATES NUCLEAR REGULATORY COMMISSION REGION I 631 PARK AVENUE KING OF PRUSSIA, PENNSYLVANIA19406 March 13, 1980 74K Niagara. Mohawk Power Corporation ATTN:

Mr.

G.

K.

Rhode Vice President System Project Management 300 Erie Boulevard, West

Syracuse, New York 13202 Gentlemen:

The enclosed IE Bulletin No. 80-06, "Engineered Safety Feature (ESF)

Reset Controls," is forwarded to you for information.

No written response is required.

If you desire additional information regarding this matter, please contact this office.

Sincerely, Boyce H. Grier Director

Enclosures:

l.

IE Bulletin No. 80-06 2.

List of Recently Issued IE Bulletins CONTACT:

D.

L. Caphton (215-337-5266) cc w/encls:

Eugene B. Thomas, Jr.,

Esquire S003a60 (y7

ENCLOSURE 1 UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.

20555 SSINS:

6820 Accession No.:

8002280639 ENGINEERED SAFETY FEATURE (ESF)

RESET CONTROLS Description of Circumstances:

IE Bulletin No. 80-06 Date:

March 13, 1980 Page 1 of 3,.

On November 7, 1979, Virginia Electric and Power Company (VEPCO) reported that following initiation of Safety Injection (SI) at North Anna Power Station Unit 1, the use of the SI Reset pushbuttons alone resulted in certain ventila-tion dampers changing position from their safety or emergency mode to their normal mode.

Further investigation by VEPCO and the architect-engineer resulted

. in discovery of circuitry which similarly affected components actuated by a Containment Depressurization Actuation (CDA, activated on Hi-Hi Containment Pressure).

The circuits in question are listed below:

Component/System Outside/Inside Recirculation Spray Pump Motors Pressurized Control Room Ventilation Isolation Dampers Safeguards Area Filter Dampers Containment Recirculation Cooler Fans Service Water Supply and Discharge Valves to Containment Service Water Radiation Monitoring Sample Pumps Problem Pump motors will not start after actuation if CDA Reset is depressed prior to starting timer running out (approx.

3 minutes)

Dampers will open on SI Reset Dampers reposition to bypass filters when CDA Reset is depressed Fans will restart when CDA Reset is depressed If service water is being used as the cooling medium prior to CDA actuation, valves will reopen upon depressing CDA reset Pumps will not start after actuation if CDA reset is depressed prior to motor starting timers running out

Enclosure 1

IE Bulletin 80-06 Date:

March 13, 1980 Page 2 of 3 Main Condenser Air Ejector Exhaust Isolation Valves to the Containment After receiving a high radiation monitor alarm on the air ejector

exhaust, SI actuation would shut these valves and depressing SI Reset would reopen them Review of circuitry for ventilation dampers,
motors, and valves reported by VEPCO resulted in discovery of similar designs in ESF-actuated components at Surry Unit 1 and Beaver Valley; where it has been found that certain equipment would return to its normal mode following the reset of an ESF signal;
thus, protective actions of the affected systems could be compromised once the associated actuation signal is reset.

These two plants had Stone and Mebster Engineering Corporation for the architect-engineer as did the North Anna Units.

The Stone and Webster Engineering Corporation and VEPCO are preparing design changes to preclude safety-related equipment from moving out of its emergency mode upon reset of an Engineered Safety Features Actuation Signal (ESFAS).

This corrective action has been found acceptable by the NRC, in that, upon reset of ESFAS, all affected equipment remains in its emergency mode.

The NRC has performed reviews of selected areas of ESFAS reset action on PWR facilities and, in some cases," this review was limited to examination of logic diagrams and procedures.

It has been determined that logic diagrams may not adequately reflect as-built conditions; therefore, the requested review of drawings must be done at the'chematic/elementary diagram level.

There have been several communications to licensees from the NRC on ESF reset actions.

For example, some of these communications have been in the form of Generic Letters issued in November, 1978 and October, 1979 on containment-venting and purging during normal operation.

Inspection and Enforcement Bulletins Nos. 79-05, 05A, 05B, 06A, 06B and 08 that addressed the events at TMI-2 and NUREG-0578, TNI-2 Lessons Learned 'Task Force Status Re ort and Short-Term Recommendations.

However, each of these communications has addressed only a limited area of the ESF's.

Me are requesting that the reviews undertaken for this Bulletin address all of the ESF's.

Actions To Be Taken By Li'censees:

For all PMR and BWR facilities with operating licenses:

1.

Review the 'drawings for all systems serving safety-related functions at the 'schematic level to determine whether or not upon the reset of an ESF actuation signal, all associated safety-related equipment remains in its emergency mode.

Enclosure 1

IE Bulletin No. 80-06 Date:

March 13, 1980 Page 3 of 3 2.

Verify the actual installed instrumentation and controls at the facility are consistent with the schematics reviewed in Item 1 above by conducting a test to demonstrate that all equipment remains in its emergency mode upon removal of the actuating signal and/or manual resetting of the various isolating or actuation signals.

Provide a schedule for the performance of the testing in your response to this Bulletin.

3.

If any safety-related equipment does not remain in its emergency mode upon reset of an ESF signal at your facility, describe proposed system modification, design

change, or other corrective action planned to resolve the problem.

4.

Report in writing within 90 days, the results of your review and include a list of all devices which respond as discussed in item 3 above, actions taken or planned to assure adequate equipment control, and a schedule for implementation of corrective action.

This information is requested under the provisions of 10 CFR 50.54(f).

Accordingly, you are requested to provide within the time period specified above, written statements of the above information, signed under oath or affirmation.

Reports shall be submitted to the Director of the appropriate NRC Regional Office and a copy shall be forwarded to the NRC Office of Inspection and Enforcement, Division of Reactor Operations Inspection, Mashington, D.C.

20555.

For all power reactor facilities with a construction permit, this Bulletin is for information only and no written response is required.

Approved by GAO, B180225 (R0072); clearance expires 7-31-80.

Approval was given under a blanket clearance specifically for identified generic problems.

Bulletin No.

Subject ENCLOSURE 2 RECENTLY ISSUED IE BULLETINS Date Issued IE Bulletin No. 80-06 Date:

March 13, 1980 Page 1 of 1 Issued To 79-27 79-28 Loss of Non-Class-1-E 11/30/79 Instrumentation and Con-trol Power System Bus During Operation Possible Malfunction 12/7/79 of NAMCO Model EA180 Limit Switches at Elevated Temperatures All Power Reactor Facilities with an Operating License (OL) and those nearing Licensing (for Action)

All Power Reactor Facilities with a Construction Permit (CP) (for Informa-tion).

All Power Reactor Facilities with an OL or CP 79-01B Environmental guali-fication of Class IE Equipment 1/14/80 All Power Reactors with an OL except SEP Plants 80-01 80-02 80-03 80-04 Operability of ADS Valve 1/14/80 Pneumatic Supply Inadequate guality Assurance for Nuclear Supplied Equipment 1/21/80 Loss of Charcoal From 2/6/80 Standard Type II, 2 Inch, Tray Adsorber Cells Analysis of a PWR Main 2/8/80 Steam Line Break with Continued Feedwater Ad-dition All BWRs with an OL All BWRs with an OL or CP All Power Reactor Faci 1 ities with an OL or CP All Power Reactor Facilities with an (OL) or (CP)79-01B 80-05 Environmental equal i-fication of Class IE Equipment Vacuum Conditions Resulting in Damage to Chemical Volume Control System (CVCS) Holdup Tanks 2/29/80 3/10/80 All Power Reactors with an OL except SEP Plants All PWR Power Reactor Facilities with an OL or CP