ML17046A425

From kanterella
Jump to navigation Jump to search
9 to Updated Final Safety Analysis Report, Section 7.7, Control Systems Not Required for Safety
ML17046A425
Person / Time
Site: Salem  
Issue date: 01/30/2017
From:
Public Service Enterprise Group
To:
Office of Nuclear Reactor Regulation
Shared Package
ML17046A230 List: ... further results
References
LR-N17-0034
Download: ML17046A425 (38)


Text

7.7 CONTROL SYSTEMS NOT REQUIRED FOR SAFETY The Nuclear Steam System's controls for the Salem Generating Station and the D. C. Cook Plant are functionally the same.

7.7.1 Design Basis 7.7.1.1 Reactor Control System The Reactor Control System is designed to reduce nuclear plant transients for the design load perturbations, so that reactor trips will not occur for these load changes.

Overall, reactivity control is achieved by the combination of chemical shim and Rod Cluster Control Assemblies (RCCA).

Long-term regulation of core reactivity is accomplished by adjusting the concentration of boric acid in the reactor coolant.

Short-term reactivity control for power changes is accomplished by moving RCCAs.

The function of the Reactor Control System is to provide automatic control of the RCCAs during power operation of the reactor.

The system uses input signals including neutron

flux, coolant temperature, and turbine load, The Chemical and Volume Control System (CVCS)(Section 9) supplements the Reactor Control System by the addition and removal of varying amounts of boric acid solution.

There is no provision for a direct continuous visual display of primary coolant boron concentration.

When the reactor is critical, the best indication of reactivity status in the core is the position of the control group in relation to power and average coolant temperature.

There is a direct relationship between control rod position and power, and it is this relationship which establishes the lower insertion limit calculated by the rod insertion limit monitor.

There are two alarm setpoints to alert 7.7-1 SGS-UFSAR Revision 6 February 15, 1987

the operator to take corrective action in the event a control group approaches or reaches its lower limit.

Any unexpected change in the position of the control group under automatic control, or a change in coolant temperature under manual control provides a direct and immediate indication of a change in the reactivity status of the reactor.

In addition, periodic samples are taken for determination of the coolant boron concentration.

The variation in concentration during core life provides a further check on the reactivity status of the reactor including core depletion.

The Reactor Control System is designed to enable the reactor to follow load changes automatically when the output is above approximately 15 percent of nominal power.

Control rod positioning may be performed automatically when plant output is above this value, and manually at any time.

The operator is able to select any single bank of rods for manual operation.

This is accomplished with a multiposition switch so that he may not select more than one bank.

He may also select automatic or manual reactor control, in which case the control banks can be moved only in their normal sequence with some overlap as one bank reaches its full withdrawal position and the next bank begins to withdraw.

The system enables the nuclear unit to accept a step load increase of 10 percent and a ramp increase of 5 percent per minute within the load range of 15 percent to 100 percent without reactor trip subject to possible xenon limitations.

Similar step and ramp load reductions are possible within the range of 100 percent to 15 percent of nominal power.

The Steam Dump System permits the plant to accept an additional 40-percent load reduction without reactor or turbine trip.

7.7-2 SGS-UFSAR Revision 6 February 15, 1987

The Reactor Control System is capable of restoring coolant average temperature to within the programmed temperature

deadband, unexpected change in load.

following a

scheduled or The pressurizer water level is programmed to be a function of the auctioneered coolant average temperature.

This is to minimize the requirements on the CVCS and Waste Disposal System (WDS) resulting from coolant density changes during loading and unloading from full power to zero power.

Following a reactor and turbine trip, sensible heat stored in the reactor coolant is removed without actuating the steam generator safety valves by means of controlled steam dump to the condenser and by injection of auxiliary feedwater into the steam generators.

Reactor Coolant System (RCS) temperature is reduced to the no load condition.

This no load coolant temperature is maintained by steam dump to the condensers which removes residual heat.

7.7.1.2 Operating Control Stations The Salem Generating Stations have a common Control Room with separate control stations for each unit, as shown on Plant Drawing 204803.

The Control Rooms are located in the Auxiliary Building.

The information presented in this section pertains to both Control Rooms, although only one is described.

Each unit is equipped with separate Control Stations which contain those controls and instrumentation necessary for operation of that unit under normal and abnormal conditions.

The Control Room is continuously occupied by the operating personnel under all operating conditions.

Equipment in this area had been designed to minimize the possibility of a condition which could lead to inaccessibility or evacuation.

Control Room shielding and ventilation are designed such that the occupants of the room shall not receive doses in excess of 5 rem 7.7-3 SGS-UFSAR Revision 27 November 25, 2013

to the whole body, or its equivalent to any part of the body, during the course of a Loss-of-COolant Accident (LOCA).

This includes doses received during ingress and egress.

The control Room Air Conditioning System is described in section 9.

The control Room is designed to be continuously occupied by qualified operating personnel under all operating and Design Basis Accident (DBA) conditions.

Both Control Rooms share a number of separate Communication Systems.

One system consists of direct dialing telephones. Another independent Communication System is a party line and voice paging system which provides the primary means of communication between plant operations personnel throughout the station.

Battery-operated portable two-way transceivers are provided for special purposes.

There is a separate system interconnecting the Containment Building, COntrol Room and refueling area.

These systems are energized from inverter powered buses.

The capability to bring the reactor to a hot shutdown condition is provided at locations outside the Control Room. The majority of equipment for this condition is located in the auxiliary feedwater pump area.

7.7.2 System Design Two independent Control Systems of different principles provide redundancy of reactivity control. One of the two Reactivity Control Systems employs RCCAs to regulate the position of the neutron absorbers within the reactor core.

The other Reactivity Control system employs the eves to regulate the concentration of boric acid solution neutron absorber in the RCS.

These systems are described in sections 3 and 9, respectively.

The Reactor Control System is designed to provide stable system control over the full range of automatic operation throughout core life without requiring operator adjustment of setpoints other than normal calibration.

7.7-4 SGS-UFSAR Revision 6 February 15, 1987

A simplified block diagram of the Reactor Control System is shown on Figure 7.7-1.

The Reactor Control System controls the reactor coolant average temperature by regulation of control rod bank position.

The system is capable of restoring reactor coolant average temperature to the progranuned value following a change in load.

The progranuned coolant average temperature increases linearly from zero power to the full power condition.

The Reactor Control System will also initially compensate for reactivity changes caused by fuel depletion and/or xenon transients.

Long-term compensation for these two effects is periodically made by adjustment of the boron concentration to return the control rod bank to its normal operating range.

The reactor coolant loop average temperatures are determined from hot leg and cold leg measurements in each reactor coolant loop.

The error between the programmed average temperature and the highest of the measured average temperatures from each of the reactor coolant loops constitutes the primary control signal as shown on Figure 7.7-1.

An additional control input signal is derived from the reactor power vs. turbine load mismatch signal.

This additional control input signal improves system performance by enhancing response and reducing transients peaks.

From these input signals, the rod direction command signals are derived.

The rod speed conunand signal varies over the corresponding range of 3.75 to 45 inches per minute depending on the magnitude and the rate of change of the input signals.

The rod direction command signal is determined by the positive or negative value of the temperature difference signal.

The rod speed and rod direction command signals are fed to the Rod Control System.

7.7.2.1 Rod Cluster Control Assembly Arrangements There are 53 RCCAs divided into four shutdown banks of 24 RCCAs and four control banks of 29 RCCAs.

The control banks are the only rods that can be manipulated under automatic control.

The control rods are divided into groups to obtain smaller incremental 7.7-5 SGS-UFSAR Revision 6 February 15, 1987

reactivity changes per step.

All RCCAs in a group are electrically paralleled to move simultaneously.

There is individual position indication for each RCCA.

7.7.2.2 Rod Control For a complete description of rod control and position indication systems, see I References 1, 2 and 3.

7.7.2.2.1 Control Bank Rod Insertion Monitor The purpose of the control bank rod insertion monitor is to give warning to the operator of a decrease in shutdown margin.

Since the amount of shutdown reactivity required for the design shutdown margin following a reactor trip increases with increasing power, the allowable rod insertion limits must be decreased with increasing power.

One parameter which is proportional to power is used an input to the insertion monitor.

This is the ~T between the hot leg and the cold leg, which is a direct function of reactor power.

The rod insertion monitor uses this parameter for each control rod bank as follows:

where:

SGS-UFSAR A(~T) auct (dT) auct A, C maximum permissible insertion limit for affected control bank highest ~T for all four loops constants chosen to maintain z11

~ actual limit based on physics calculations 7.7-6 Revision 18 April 26, 2000

The actual control rod bank position (Z) is compared to ZLL as follows:

If Z -

ZLL < D, a low alarm is actuated If Z -

ZLL < E, a low-low alarm is act.uated Since the highest value of 4T is chosen by the auctioneering unit, a

conservatively high representation of power is used in the insertion limit calculation.

Actuation of the low alarm alerts the operator of an approach to a reduced shutdown reactivity situation. Administrative procedures require the operator to add boron following normal procedures with the eves. Actuation of the low-low alarm requires the operator to initiate emerqency boration procedures. The value for "E" is chosen to account for all instrumentation errors so that the low-low alarm would normally be actuated before the insertion limit is reached.

The value for "D" is chosen to allow the operator to follow normal boration procedures.

Figure 7.7-2 shows a schematic representation of the control rod insertion monitor.

In addition to the rod insertion monitor for the control banks, an Alarm System is provided to warn the operator if any shutdown RCC leaves the fully withdrawn position.

7.7.2.2.2 Rod Deviation Alarm The demand and actual rod position signals are displayed on the control console.

They are also monitored by the plant computer which provides a visual printout and an audible alarm whenever an individual rod position signal deviates from the bank demand signal by a preset limit. Figure 7. 7-3 is a block diagram of the rod deviation comparator and alarm system.

The design criterion for this system is that the alarm be actuated before rod deviation, which would allow the core design hot channel factors to be exceeded, with appropriate allowance for instrument error.

7.7-7 SGS-UFSAR Revision 16 January 31, 1998

7.7.2.3 7.7.2.3.1 Rod Stops Rod are provided to prevent abnormal power conditions which could result from excessive control rod withdrawal initiated by either a Control malf0nction or operator violation of administrative procedures.

7.7.2.3.2 Automatic Turbine Load Runback Auto~atic turbine load runback is initiated by an approach to an overpower or overtemperature condition.

This will prevent high power operation which might lead to an overpower or an overtemperature AT trip.

Turbine load reference reduction is initiated by either an overtemperature or overpower AT signal in two of four loops.

7.7.2.4 Pressurizer Pressure Control The RCS pressure is maintained at constant value by using either the heaters (in the water region) or the spray (in the steam region of the pressurizer).

The electrical immersion heaters are located near the bottom of the pres~urizer.

A portion of the heater groups are proportional heaters which are used: to control small pressure variations.

These variations are due to heat losses, including heat losses due to a small continuous spray.

The remaining (backup) heaters are turned on when the pressurizer pressure controller signal is below a given value.

The spray nozzles are located on the top of the pressurizer.

Spray is init~atect when the pressure controller signal is above a given setpoint.

The spra~ rate increases pioportionally with increasing pressure until it reaches a maxijnum value.

Steam condensed by the spray reduces the pressurizer pressure.

A small continuous spray is normally maintained to reduce thermal stresses and thermal shock and to help maintain uniform water chemistry and temperature in the pressurizer.

Two power relief valves limit system pressure for large load reduction 7.7-8 SGS-UFSAR Revision 21 December 6, 2004

Spring-loaded safety valves limit load occur without direct reactor 7.7

.5 Pressurizer Level Control pressure should a complete loss of turbine bypass.

The ! water inventory in the RCS maintained by the CVCS.

The positive displacement pump performs the charging function.

The pressurizer level is controlled by the charging flow controller which controls the displacement pump speed to produce the flow demanded by the zer level controller.

When a high head safety injection pump is performing the charging fun~tion, the pressurizer level is controlled by the charging-flow controller that: modulates flow control valve

CV55, located in the discharge piping downstream from the charging pumps.

A flow transmitter (FT128) in the discharge header provides actual flow indication to the control board bezel and to flow control valve CV55.

The output of desired flow from the zer level controller is compared to the actual flow from FT128 and flow valve CV55 is positioned so that they match.

The pressurizer water level is programmed as a function of coolant average temperature.

The pressurizer water level decreases as the load is reduced from full load. This is the result of coolant contraction following programmed coolant temperature reduction from full power to low power.

The programmed level is designed to match as nearly as possible the level changes resulting from the coolant temperature changes.

To permit manual control of pressurizer level during startup and shutdown operations, the charging flow can be manually regulated from the main control room.

7.7.2.6 Steam Generator Water Level Control The steam generator water level is controlled by a digital microprocessor con~rolled steam generator feedwater control system termed the advanced digital feedwater control system (ADFCS).

The ADFCS provides automatic control of the programmed level in the steam generators without the need for operator intervention over the range of power operation.

This range of operation extends from the point at which the transition is made from feeding via the auxiliary feedwater system to feeding via the main feedwater system on the bypa~s control valve (approximately 2-3% power) up to full power.

One control system operates on both the main and bypass feedwater control valves without the ~eed for manual action to switch operating modes or switch between valves.

The basic control system functional design is similar to the original analog feedwater control system; however 1 a number of features have been added to improve the performance of the system, Functional block diagrams of the system are shown in Figures 7. 7-7,

7. 7-8, and 7. 7-9.

A feedwater temperature-dependent gain has been added to the narrow-range level regulator as shown in Figures 7. 7-7 and 7. 7-8.

The response of steam generator water level to changes in feedwater 7.7-9 SGS-UFSAR Revision 21 December 6 1 2004

flow is a function of feedwater temperature.

At low feedwater temperatures and low power levels the level response exhibits more of the classical shrink/swell effect.

This non-minimum-phase response is a destabilizing influence on the feedback control system.

Therefore the control system lowers the gain at low feedwater temperature to preserve stability and increases the gain at high feedwater temperature to improve the response of the system.

The flow regulator has a high-power mode and a low-power mode which is shown in Figure 7. 7-8.

This is necessary because the feedwater flow and steam flow signals are not usable at low power levels.

The switching between these two modes is done automatically within the system and is performed in a bumpless manner without the need for operator action.

To compensate for the lack of steam flow signals at low power, a feedforward signal, which is based on wide range steam generator water level deviation from its zero power value, is utilized.

This difference generates a reference feedwater flow demand that is proportional to changes in steam flow.

Wide range level is used for this purpose since wide range level responds quickly and in proportion to changes in total steam flow.

In high power mode, feedwater flow is regulated in response to the deviation between steam flow and feedwater flow, and the compensated steam generator water level deviation from setpoint.

A steam flow/feed flow rate lag compensation is included in the algorithm to respond quickly to rapid changes in the steam flow/feed flow mismatch.

During steady-state conditions (when the steam flow mismatch is constant),

this rate lag compensation does not contribute to the response.

Additionally, the proportional and integral gains for the level control PID are scheduled based on the steam flow.

As was the case with the low-power mode load index, the feed flow and steam flow signals will automatically be switched in and out of the system. This mode switching is performed independently of which valve (main or bypass) is being used for control.

An additional unique feature of the control system design is the valve lift calculator or the "linearization circuit."

The block diagram of this part of the system is shown in Figure 7. 7-9.

The output of the flow regulator is a demanded feedwater flow.

The relationship between changes in valve position and changes in feedwater flow is highly nonlinear.

It depends on the valve flow characteristic, pressure drop across the system, and system hydraulic characteristics.

The linearization circuit calculates the amount that the control valve(s) must be moved to accomplish the change in flow demanded by the control system.

The valve lift calculator operates on both the main and bypass control valves and is independent of the control mode.

The bypass and main control valves are stroked open sequentially with some overlap. Either of the valves may be operated in manual while leaving the other valve in auto as shown in Figure 7.7-9.

The valves are closely coupled through the algorithms in the valve demand portion of the system in order to minimize disturbances on the process (flow and level) 7.7-9a SGS-UFSAR Revision 29 January 30, 2017

As the plant is taken from low power to high power, the bypass and main control valves are opened sequentially.

Before the bypass valve reaches its nominal full-open condition, the control system begins to open the main valve from its full-closed position.

As the plant increases in power, the feedwater flow demand increases and the main and bypass valves operate in a "split-range" fashion with both valves continuing to open as controlled by the system's valve sequencing logic.

As flow demand is increased the main and bypass valves continue to open until a predetermined steam flow setpoint is reached, at which point the bypass valve closes at a constant rate versus time.

opens to compensate for the closing bypass valve.

The main valve As flow demand decreases, flow setpoint is reached, the main valve closes until a predetermined steam at which point the bypass valve opens at a constant rate versus time.

The main valve closes to compensate for the opening bypass valve.

The main and bypass valves then operate in a "split-range" fashion until the main valve closes completely.

The normal sequence described above can be altered by placing either or both of the valves in manual control.

The feedwater control system includes signal validation for input signals to reduce the probability of a failed sensor causing an upset condition in the plant.

The input channel signal validation configuration is shown in Figure

7. 7-7.

When three channels of a variable are available, the median signal select method is used.

In this method, the middle value of the three input values is used as the input to the control algorithms.

This will prevent high or low failures of a single input from affecting the control system.

When two input channels of a variable are available, an arbitration method is used.

In this method, the two inputs are compared, and if they agree to within a certain criterion, they are averaged and the result is sent to the control algorithms.

If the two channels disagree significantly, they are compared to an estimate of the variable, which is calculated using other process measurements.

The primary input that is closest to the estimate is used in the control system.

The signal validation feature of the feedwater control system allowed elimination of the low feedwater flow reactor trip that was the original design of the plant.

WCAP-13502 provides elimination of the trip (Reference 1) 7.7-9b SGS-UFSAR incorporated into justification for Revision 29 January 30, 2017

A summary of the signals input to the advanced digital feedwater control system is as follows:

Process Variable Narrow-range steam generator water level Wide-Range steam generator water level Steam flow Feedwater flow Feedwater temperature Steam generator pressure Turbine steamline inlet pressure Feedwater header pressure Valve position Number of Channels 12, 3/loop 4, 1/loop 12, 3/loop 12, 3/loop 4, 1/loop 4, 1/loop 3

3 8, 1/valve Continued delivery of feedwater to the steam generators is required as a sink for the heat stored and generated in the reactor coolant following a reactor trip and turbine trip.

An override signal closes the feedwater valves when the average coolant temperature is below a given temperature.

Following a

turbine trip, the feedwater regulating valves are closed at approximately a uniform rate, decreasing flow to a low percent of full flow at about one minute after the trip.

This provides an optimum heat sink.

Subsequently, the operator remotely controls the valves to maintain steam generator water level.

Manual override of the Feedwater Control System is available at all times.

7.7.2.7 Steam Dump Control The Steam Dump System is designed to relieve steam from the steam generators to the condenser to reduce the sensible heat in the primary system in the event of load reduction not exceeding 50 percent.

The bypass system can accommodate 40 percent of full load flow, which, in conjunction with the 10-percent load follow capability of the Reactor Control System, enables the Nuclear Steam Supply System to accept a 50-percent load rejection from full load without reactor trip.

All steam dump steam flows to the main condenser via the bypass lines.

When a

load rejection

occurs, temperature setpoint of the RCS predetermined amount, a

signal controller.

SGS-UFSAR if the difference and the actual average will actuate the load 7.7-10 between the required temperature exceeds a rejection steam dump Revision 29 January 30, 2017

This circuit prevents a large increase in reactor coolant temperature a large, sudden load decrease.

The error is a difference between the lead/lag compensate ioneered T and the reference T and is based on avg avg turbine steamline inlet pressure.

The IT signal is the same as that used in the RCS. The lead/lag compensation avg for the T signal is to compensate for lags in the plant thermal response and avg in valve positioning.

lowing a sudden load decrease, is immediately decreased and T tends to increase, thus generating an immediate demand avg sig~al for steam dump.

Since rods are available in this stea,m dump terminates as the error comes within the maneuvering capability of the *control rods.

The steam dump flow reduces proportionally as the control rods act to reduce the average coolant temperature.

The artificial load is therefore removed as the coolant average temperature is restored to its programmed equilibrium value.

The purpose of the Steam Dump System is to reduce RCS transients following a substantial turbine load reduction by bypass main steam directly to the condenser, thereby maintaining an artificial load on the steam generators. The Control Rod System can then reduce the rE)actor temperature to a new equilibrium value without causing overtemperature and/or overpressure conditions.

The dump valves are modulated by the reactor coolant average temperature signal.

The required number of steam dump valves can be tripped quickly to full open or modulate, depending upon the magnitude of the temperature error signal resulting from loss of load.

Foll:owing a reactor and turbine trip, decay heat and sensible heat stored in the reactor coolant are removed without actuating the steam generator safety valves by means of controlled steam dump to

7. 7-11 SGS-.UFSAR Revision 21 December 6, 2004

the condenser and by injection of feedwater to the steam generators.

Following a turbine trip, as moni tared by the turbine ection steam dump controller is defeated and the turbine the load steam dump controller becomes active.

Since control rods are not available in this situation, the demand signal is the error signal between the lead/lag When the error compensated auctioneered T and the no load reference T avg avg exceeds a the dump valves are open in a sequence.

As the error reduces in that the RCS T is being reduced toward the reference no load value, the dump avg valves are modulated by the plant trip controller to regulate the rate of removal of decay heat and thus gradually establish the equilibrium hot shutdown condition.

The error determines whether a group of valves is to be tripped open or modulated open.

In either case, they are modulated when the error is be_ow the trip-open setpoints.

7.7.2.8 The in-core instrumentation is designed to yield information on the neutron flux distribution and fuel assembly outlet at selected core locations.

Using the information thus obtained, it is to confirm the reactor core The movable in-core detection system shall be considered operable for use when the following criteria are met:

a.

At least 75%* of the detector thimbles,

b.

A minimum of 2 detector thimbles per core quadrant, and

c.

Sufficient movable detectors, drive, and readout equipment to map these thimbles.

APPLICABILITY:

When the movable in-core detection system is used for:

a.

Recalibration of the excore neutron flux detection

b.

Monitoring the quadrant power tilt ratio, or

c.

Measurement of FN11H, FQ(Z) and Fxy With the movable incore detection system inoperable, do not use the system for the above applicable monitoring or calibration functions.

The provisions of Specification 3.0.3 are not applicable.

7.7-12 SGS-UFSAR Revision 24 May 11, 2009

The movable incore detection system shall be demonstrated (once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />) by normalizing each detector output to be used during its use when required for:

a.

Recalibration of the excore neutron flux detection system, or

b.

Monitoring the quadrant power tilt ratio, or

c.

Measurement of FNliH, F0 (Z) and Fxy

  • For U2 Cycle 11, when the number of available movable detector thimbles is than 50% but less than 75% of the total, the movable incore system can be considered operable provided the
FNliH, F0 ( Z) and Fxy uncertainties are appropriately adjusted.

Also there should be a minimum of four thimbles available per quadrant, where quadrant includes both horizontal-vertical and diagonally-bounded quadrants (eight individual quadrants in total).

The operability of the movable incore detectors with the specified minimum complement of equipment ensures that the measurements obtained from use of this system accurately represent the spatial neutron flux distribution of the reactor core.

The operability of this system is demonstrated by irradiating each detector used and its respective output.

The operability requirements of the movable incore detector system for the purposes of calibration of the PDMS is specified in Specification 3.3.3.14.

For the purpose of measuring F0 {Z) or FNliHt a full incore flux map or the PDMS is used.

Quarter-core flux maps, as defined in WCAP-8648, June 1976, may be used in recalibration of the excore neutron flux detection system, and full incore flux maps or symmetric incore thimbles may be used for the quadrant power tilt ratio when one Power Range Channel is 7.7.2.9 Operating Control Stations The Control Room provides the necessary controls and indication to start, operate and shut down the unit with sufficient redundant information displays and alarm indications to ensure safe and reliable operation under all normal and abnormal conditions.

\\..,

The most important unit controls are located on the control console, which is of freestanding, horseshoe shaped design 1 constructed of steel.

The front horizontal portion contains the most frequently used operating controls while the rear vertical portion contains less frequently used controls and indicators.

7.7-13 SGS-UFSAR Revision 24 May 11/ 2009

Controls and indicators are functionally grouped on a

system basis to facilitate safe, reliable operation of the unit during transients as well as normal operation. Those systems requiring more frequent operator attention are located in the central area, while less frequently used controls are located on either side.

Most of the console instruments consist of plug-in, back-lighted pushbutton stations and vertical scale indicators.

Operator action consists of a

momentary push of a button.

The lights in the buttons are used for status, information and alarm indication.

Alarms are provided in the Control. Room to alert the operator of abnormal plant conditions.

The alarm displays are located either on a console pushbutton control station, where corrective action would be taken, or on the overhead annunciator.

An alarm signal causes a back-lighted pushbutton to flash and the console audible alarm to sound until acknowledged by the operator, Upon clearing of an alarm condition/ the console audible ringback is sounded.

Other alarms are displayed on an annunciator panel located overhead above the console. This panel consists of illuminated windows and separate audible alarm and ringback tones.

Two first-out annunciator panels indicate, by means of red and white lights, the first reactor or turbine trip to occur.

A comprehensive status panel, employing the same type of illuminated windows as the console, indicates the condition of trip channels and alarms.

By means of a "mimic bus" arrangement, the interaction of trip conditions and permissives can be quickly analyzed.

Diesel generator automatic load sequencing, critical valve status and other important information are also clearly displayed, A computer is employed to assist the operator and to monitor the unit. Selected parameter trends can be recorded while alarm conditions are indicated to the operator.

The computer output consists of a video display mounted on the console, logging printer mounted on Control room panels located convenient to the plant operators.

The video display and printers are independent devices.

Vertical panels form the walls of the Control Room and contain controls for

systems, which require only occasional operator attention as well as miscellaneous recorders and indicators.

Reliability and ease of service has been designed into the Control Room.

The majority of the console instruments are plug-in modules.

In the unlikely case that a pushbutton station or indicator on the console malfunctions, it can be readily removed and replaced from the front of the console.

No access to the inside of the console is needed. Re-lamping can also be quickly accomplished from the front of the pushbutton.

7. 7-14 SGS-UFSAR Revision 23 October 17, 2007

All pushbutton stations, the fire protection display panel, the overhead annunciator and the status panel contain at least two lamps at each point for increased reliability.

Low voltage {28 V de} control is *utilized for the console pushbutton stations.

A Relay Logic System performs the required switching and memory functions and provides the interface between the 28 V de and the control voltage {125 V de or 115 V ac) for the equipment.

The Relay Room and Control Equipment Room contain equipment used for signal conditioning, circuit switching and logic operations.

The wiring between the console and equipment cabinets in these rooms makes use of plug-in cables, which reduces the exposure of terminations.

Normal servicing of devices in the console requires no access to the inside of the console.

For ease of servicing and maintenance, much of the equipment in the Relay Room and Control Equipment Room is designed for plug-in module type construction.

Relays are heavy-duty plug-in units.

All components are carefully chosen and conservatively rated.

The Control Room, Relay Room, Control Equipment Room and Computer Room are air conditioned to maintain a clean, temperature-controlled environment.

Reliable sources of control power, as described in Section 8, are provided to ensure continual operation of controls and instrumentation. Emergency lighting is provided in the Control Room, Control Equipment Room and Relay Room as well as other parts of the station.

7.7.2.10 Plant Alarm and Annunciator Systems The Alarm and Annunciator Systems for this plant consist of three major areas of alarm indication.

They are:

1.

The Overhead Annunciator System

2.

The Auxiliary Alarm System (sequential data operations record)

3.

The Control Console Alarm System These systems serve to indicate and/or record all abnormal or alarm conditions to be brought to the operator's immediate attention inside the Control Room.

Each system is discussed below independently; however, mention is made when there is redundancy of alarm indication.

7.7-15 SGS-UFSAR Revision 23 October 17, 2007

I The Overhead Annunciator System This system is comprised of seven cabinets containing all the power supplies, relays, terminals, hardware and logic to actuate ten groups of forty-eight 2-inch x 3-inch backlighted windows for a system total capacity of 480 alarms.

The ten displays are located in a dropped ceiling fascia above the control console for easy viewing by the control operator.

An annunciator CRT display is located on the control console to identify alarm points.

The various plant alarms are grouped into systems or related areas and situated above the console section containing the associated system control pushbuttons and indicators.

The ten displays of the Overhead Annunciator System do not represent ten specific alarm groupings but ten 48-point alarm window displays.

Each 48-point display contains various plant alarms; however, alarms which are common to a system or of a related nature are grouped together within a display. There may be several such groupings on a display; see Table 7.7-2.

Most of the assigned inputs to the Aux:LHary Alarm System contaj.n status information for safety-related equipment.

This information can be considered a backup to the other annunciator systems provided.

Since Indication and Alarm Systems are not part of the Plant Protection System, and failures within these systems cannot affect the operation of the Protection System, there is no reason to impose limiting conditions for operation on the Alarm Systems.

Alarm Systems cannot be considered as part of a safety-related

system, since they perform no function in the actuation of safety-related equipment.

Limiting conditions for operation are imposed on the Plant Protection Systems and equipment to assure the safe operation of the unit.

One display serves as first-out indication and is divided into two separate and independent systems.

These are Reactor Trip First-Out", and "Turbine Trip First-Out."

The "Reactor Trip First-Out" group has been divided into "Reactor Trip" and "Safety Injection" groups for identification purposes.

There are separate and independent push buttons located on the control console which the operator uses to silence, acknowledge, and reset the overhead alarms.

A key operated switch is located on the main console to reset the "First-Out" indications.

7.7-16 SGS-OFSAR Revision 23 October 17, 2007

The Overhead Annunciator System is a high speed distributed data acquisition and display system.

Non-redundant input scanners collect alarm contact state data for redundant Sequential Events Recorders (SER).

The SER's provide alarm data to redundant distributed logic channels, the output of which is diode auctioneered to drive the window boxes.

All field inputs are optically coupled to scanner electronics that can read 64 inputs per scanner.

When an input change of state is detected, the point address, real time, and alarm state are stored in a buffer in the scanner.

'l'he scanner is polled by the SER and transfers alarm status to the SER.

The SER stores this event data in chronological order in a circular historical buffer.

Normal configuration causes each alarm point to be displayed on the system console CRT, the appropriate window box, printed on the hard copy printer, and placed in the historical buffer in the local PC.

If the primary controller fails due to a processor lockup (processor halts) or Port 4 failure, the primary watchdog timer circuit will switch to the backup controller.

A local PC runs the Remote Configuration Workstation (RCW) software.

The RCW allows the SER to be queried for various reports and to check for errors in the system.

Password entry and RCW/SER switch selection provides access for reprogramming alarms.

Periodic internal self tests are run by the SER.

One test places all inputs at the scanner level in an alarm state and verifies that all inputs are passed to the SER.

The SER then removes all the inputs from the alarm state and verifies that all inputs returned to their prior state.

Any point not responding correctly will be printed as a faulty point.

This test can also be initiated manually via the Functional Test swiLch located on the operator panel in annunciator cabir.et 115 (F).

Operation of this test function does not affect the normal operation of the system.

An independent Annunciator Verification System continuously tests Overhead Annunciator System alarm processing by inputting simulated alarm stimuli through two of the scanners.

These signals are then processed through the Sequential Events Recorder, and sent through the redundant chains of distributed logic controllers.

Depending on the response of the two distributed logic controller trains to the stimulus, the Annunciator Verification System determines whether the annunciator system is functioning.

If failures are detected, the Annunciator Verification System inputs an annunciator system trouble alarm to the Overhead Annunciator System and to an independent indicator lamp/console group alarm.

The Annunciator Verification System also provides a separate trouble alarm for loss of power or self-diagnostics faults.

7.7-17 SGS-UFSAR Revision 25 October 26, 2010

I The system is powered by two separate 115 VAC, 60Hz supplies.

Loss of either of the 115 VAC power supplies will initiate a loss of power alarm on the

OHA, the plant process
computer, and on a

console ind~cator lamp/console group alarm independent of the OHA system on the control console.

Redundant power supplies are provided for the field contact power, the scanners, the SER, and the distributed logic channels (including the associated window box lamps).

The output of each power supply is also monitored to alarm on loss of potential in the same manner as the 115 VAC supplies.

The remotely located annunciator logic cabinets are connected by plug-in cables to the overhead display units.

A test switch is also provided on the control console to test the window box lamps for operability. Operation of the test function does not affect the normal operation of the system.

System input ground detection is provided.

A ground detected on an input will alarm on the OHA and on the plant process computer.

The system also has a logic failure output which provides an input to the OHA and to an indicator lamp/console group alarm independent of the OHA system on the control console when certain hardware failures or communications errors occur.

The Auxiliary Alarm System (Auxiliary Annunciator System)

Each Salem Unit has an independent Auxiliary Annunciator System (AAS).

The AAS is a sequential data operations recorder system used primarily for alarming and recording the loss of control circuits' potential and the off-normal position of valves. Each system consists of four (4) remote panels (133, 134, 33 and 34) containing all the input terminals, input logic, sequential memory, software, relays, power supplies, local/backup printer, system controls, and associated hardware to output sequential alarm conditions to a main printer in the Control Room.

The Unit 1 AAS monitors Unit 1 parameters and provides alarm data at the Unit 1 Control Room.

The Unit 2 AAS monitors Unit 2 parameters and provides corresponding alarm data to the Unit 2 Control Room.

Each Unit's system has over 700 active inputs.

Each input is adequately isolated from the field at the point of the system.

The system applies a field contact wetting voltage to the field circuits/alarm points* and monitors the field contacts for a change in state to initiate/clear an alarm.

On a contact change of state, the "contact stateu and legend is printed on the main printer with an Overhead alarm "Annunciator System Printer printing."

7.7-17a SGS-UFSAR Revision 18 April 26, 2000

Each system is powered two 120 VAC power sources.

The AAS system can be configured to monitor normally open (NO) and/or normally closed (NCl contac::

conditions.

The system configuration is protected by password to ensure control of database programs.

The AAS monitors its system performance and provide notification of internal failures {system faults or system alerts),

indicating a in system operations.

The AAS provides outputs to the Unit 1/Unit 2 Overhead Annunciator

{OHA) monitoring system performance.

Operator controls (pushbuttons, etc.)

for operation are provided in control room panel 1RP9 (2RP9) and AAS panel 133-1 {134-2).

7.7-l?b SGS-UFSAR Revision 18 April 26, 2000

THIS PAGE INTENTIONALLY BLANK 7.7-18 SGS-UFSAR Revision 18 April 26, 2000

(This text has been deleted)

Control Console Alarm System To facilitate operation of the plant, certain alarms are located on pushbutton control stations on the control console.

These alarms are located to facilitate immediate corrective action and are by either the Process Control or the plant motor controls.

An alarm signal causes a back-lighted pushbutton to flash and the console audible alarm to sound until acknowledged by the operator.

Acknowledgement of an alarm condition causes the audible to be silenced and the alarm pushbutton to remain lit.

When the alarm condition is cleared, the console audible ring-back signal sounds and the back-lighted pushbutton flashes again.

Acknowledgement silences the audible signal and turns off the back-lighted pushbutton.

To facilitate the location of any pushbutton in alarm, the control console is divided into six sections, referred to as Console Alarm Groups.

Each group or console section has a bull' s eye indication light at the top to direct the operator's attention to that specific section of the control console containing the pushbutton 7.7-19 SGS-UFSAR Revision 18 April 26, 2000

in alarm.

One cabinet contains the electronics, power supplies and grou!1d detection circuitry for the Console Group Alarm system.

The Console Group Alarm system has six outputs to actuate each individual alarm group indicating and four outputs to sound the alarm and ringback horns.

Alarm horns sound a two step warble until silenced or acknowledge.

Ringback horns sound a steady tone for two seconds if not silenced by the Operator.

The Process Control Systems provide alarms via four separate and independent alarm interface cabinets, one per process control group, each containing all the necessary input terminals, alarm logic, power supplies, and hardware to actuate the associated console alarms.

The alarm cabine.ts are connected to the pushbutton stations via plug-in cables.

Each alarm cabinet is powered by two 115 V ac, 60 Hz feeds, which feed redundant de power supplies.

The outputs of both power supplies are diode auctioneered to a common bus.

Each ac feed and de potential is monitored and will actuate an alarm on the auxiliary annunciator system upon loss of voltage.

The alarm logic is entirely solid-state designed for increased reliability.

Each alarm point can be actuated from either a normally closed initiating contact or by the application or removal of 115 V ac or 125 V de.

A contact change of state or change in voltage level indicates an alarm condition until it returns to its normal state.

Alarm contacts are moni tared by internally ied 125 v de.

The plant Motor Control Systems provide for numerous alarms from various plant systems.

These alarms are initiated by field contacts which are monitored by the internal relay logic of the system to actuate the associated pushbutton alarm.

These alarms are either of the ring-back type as previously described or of the non-ring-back type.

This system is supplied from 115 V ac, 125 V de and 28 V de sources.

There are no internal power supplies.

use of independent breakers.

SGS-UFSAR Each 28 V de control circuit is protected by the 7.7-20 Revision 18 April 26, 2000

7.7.2.11 Residual Heat Removal Performance Monitoring System The residual heat removal performance monitoring system provides an early warning of loss of decay heat removal capabilities.

The system includes:

1.

Two independent narrow range continuous Reactor Coolant System level indications and wide range RCS level indication whenever the RCS is in a reduced inventory (mode 5 or 6).

The narrow level range monitored is from Elevation 97' to Elevation 91. 1'.

The wide range level is monitored from elevation 97 feet to 109.5 feet.

The wide range midloop level is used while reactor vessel level is above the narrow range midloop level indication.

2.

Other monitoring capability:

a.

RHR pump discharge flow

b.

RHR pump discharge pressure

c.

RHR pump suction pressure

d.

RHR pump motor current The system is shown on the RCS and RHR system drawings (Plant Drawings 205301 and 205332).

The system is designed to accurately monitor water level while the RHR system is operating with the RCS drained to the mid level of the RPV nozzles.

This level allows draining of the steam generators but establishes a very narrow operating level over which the RHR pumps will have adequate NPSH.

The Reactor Vessel Level Indicating System (Plant Drawing 205332) provides a wide range level indication but is not accurate enough for the purposes described in NRC Generic Letter 88-17.

The testing design criteria are the same as used for instruments that are connected to full reactor temperature and pressure.

The channel design and physical location of the transmitters prevent any physical damage from a

refueling seal failure even though the system is not specifically designed to function while flooded or over this range.

The low side of the level transmitter is connected to the pressurizer and can be manually aligned to measure the static water level in the vessel with or without pressure in the vessel.

The system is not required for safe shutdown, and is used only during cold

shutdown, therefore, it is not safety related.

However, it is designed, installed, and maintained as if it were safety related.

7.7.2.12 Seismic Monitoring Instrumentation The operability of the seismic monitoring instrumentation ensures that sufficient capability is available to promptly determine the magnitude of a seismic event and evaluate the response of those features important to safety.

This capability 7.7-21 SGS-UFSAR Revision 27 November 25, 2013

is required to permit comparison of the measured response to that used in the design basis for the facility.

Accordingly, the seismic monitoring instrumentation shown in Table 7. 7-3 should be maintained operable by the performance of the channel check, channel calibration and channel functional tests at the frequencies shown in Table 7.7-4. Additionally, each of the above seismic monitoring instruments actuated during a seismic event shall be restored to operable status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> and a channel calibration performed within 5 days following the seismic event.

Data should be retrieved from actuated instruments and analyzed to determine the magnitude of the vibratory ground motion.

7.7.2.13 Meteorological Monitoring Instrumentation The operability of the meteorological instrumentation ensures that sufficient meteorological data is available for estimating potential radiation doses to the public as a result of routine or accidental release of radioactive materials to the atmosphere. This capability is required to evaluate the need for initiating protective measures to protect the health and safety of the public. Accordingly, the meteorological monitoring instrumentation shown in Table 7.7-5 should be maintained operable by the performance of the channel check and channel calibration tests at the frequencies shown in Table 7.7-6.

7.7.3 System Design Evaluation 7.7.3.1 Unit Stability The Rod Control System is designed to limit the amplitude and the frequency of continuous oscillation of coolant average temperature about the Control System setpoint within acceptable values. Continuous oscillation can be induced by the introduction of a feedback control loop with an effective loop gain which is either too large or too small with respect to the process transient response, i.e., instability induced by the control system itself.

Because stability is more difficult to maintain at low power under automatic control, no provision is made to provide automatic control below 15 percent of full power.

The control System is designed to operate as a stable system over the full range of automatic control throughout core life.

7.7.3.2 Step Load Changes Without steam Dump A typical power control requirement is to restore equilibrium conditions, without a trip, following a plus or minus 10 percent step change in load demand, over the 15 to 100 percent power range for automatic control. The design must necessarily be based on conservative conditions and a greater transient capability is expected for actual operating conditions.

A load demand greater than full power is prohibited by the turbine control load limit devices.

7.7-21a I SGS-UFSAR Revision 16 January 31, 1998

The function of the Control System is to minimize the reactor coolant average temperature deviation during the transient within a given value and to restore average temperature to the programmed setpoint within a given time.

Excessive pressurizer pressure variations are prevented by using spray and heaters in the pressurizer.

7.7-2lb SGS-UFS~R Revision 14 December 29, 1995

The margin between overtemperature AT setpoint and the measured AT is of primary concern for the step load changes.

This margin is influenced by nuclear flux, pressurizer pressure, reactor coolant temperature, and temperature rise across the core.

7.7.3.3 Loading and Unloading Ramp loading and unloading of 5 percent per minute can be accepted over the 15 to 100 percent power range under automatic control without tripping the plant.

The function of the Control System is to maintain the coolant average temperature and pressure as functions of turbine generator load.

The minimum control rod speed provides a sufficient reactivity insertion rate to compensate for the reactivity changes resulting from the moderator and fuel temperature changes.

The coolant average temperature increases during loading and causes a continuous insurge to the pressurizer as a result of coolant expansion. The sprays limit the resulting pressure increase.

Conversely, as the coolant average temperature is decreasing during unloading, there is a continuous outsurge from the pressurizer resulting from coolant contract ion.

The heaters limit the resulting system pressure decrease. The pressurizer level is programmed such that the water level is above the setpoint at which the heaters cut out during the loading and unloading transients.

The primary concern during loading is to limit the overshoot in average coolant temperature and to provide sufficient margin in the overtemperature 4T setpoint.

The automatic load controls are designed to safely adjust the unit generation to match load requirements within the limits of the unit capability and licensed rating.

7.7-22 SGS-UFSAR Revision 6 February 15, 1987

7.7.3.4 Loss of Load with Steam Pump The Reactor Control System is designed to accept load reduction not exceeding 50 percent for which no reactor trip or turbine trip should be actuated.

The Automatic Steam Dump System is able to accommodate this abnormal load rejection and to reduce the effects of the transient imposed upon the RCS.

The reactor power is reduced at a rate consistent with the capability of the Rod Control System.

Reduction of the reactor power is automatic down to 15 percent of full power.

The steam dump flow reduction is as fast as RCCAs are capable of inserting negative reactivity.

The pressurizer power operated relief valves might be actuated for the most adverse conditions, e.g.,

the most negative Doppler coefficient, and the minimum incremental rod worth.

The relief capacity of the power operated relief valves is sized large enough to limit the system pressure to prevent actuation of high pressure reactor trip for the above conditions.

7.7.3.5 Turbine Generator Trip with Reactor Trip Whenever the turbine generator unit trips at an operating level above 50-percent power, the reactor also trips.

The unit is operated with a programmed average temperature as a function of load, with the full load average temperature significantly greater than the saturation temperature corresponding to the steam generator pressure at the safety valve setpoint.

The thermal capacity of the RCS is greater than that of the secondary system, and because the full load average temperature is greater than the no load steam temperature, a beat sink is required to remove heat stored in the reactor coolant to prevent actuation of steam generator safety valves for a trip from full power.

7.7-23 SGS-UFSAR Revision 11 July 22, 1991

This heat sink is provided by the combination of controlled release of steam to the condenser and by makeup of cold feedwater to the steam generators.

The Steam Dump System is controlled from the reactor coolant average temperature signal whose setpoint values are reset upon trip to the no load value.

Actuation of the steam dump must be rapid to prevent actuation of the steam generator safety valves.

With the dump valves open the average coolant temperature starts to reduce quickly to the no load setpoint.

A direct feedback of temperature acts to proportionally close the valves to minimize the total amount of steam which is bypassed.

Following the turbine trip, the steam voids in the steam generator will collapse and the fully opened feedwater valves will provide sufficient feedwater flow to restore water level in the downcomer.

The feedwater flow is cut off when the average coolant temperature decreases below a given temperature value or when the steam generator water level reaches a given high level.

Additional feedwater makeup is then controlled manually to restore and maintain steam generator water level while assuring that the reactor coolant temperature is at the desired value.

Heat removal is maintained by the steam header pressure controller (manually selected) which controls the amount of steam flow to the condensers.

This controller operates a portion of the same steam dump valves to. the condensers which are used during the initial transient following turbine and reactor trip.

The pressurizer pressure and level fall rapidly during the transient because of coolant contraction.

The pressurizer water level is prograDIDled so that the level following the turbine and reactor trip is above the low level safety injection setpoint.

If heaters become uncovered following the trip, the eves will provide full charging flow to restore water level in the pressurizer.

Heaters are then turned on to restore pressurizer pressure to normal.

7.7-24 Revision 6 February 15, 1987

7.7 6

The *In-Core Instrumentation System consists of 58 (see Note 1) flux thimbles, which* run the length of selected fuel assemblies to permit measurement of the flux distribution within the reactor core, and 58 (see Note

1) thermocouples located at the top of the flux thimbles to measure coolant outlet temperature.

The high seals for the thermocouples and flux thimbles

~re shown on Figure 7.7-4.

The data obtained from the in-core temperature and flux distribution instrumentation system, in conjunction with previously determined analytical infqrmation, can be used to determine the fission power distribution in the cor~ at any time throughout core life.

This method is more accurate than using calculational techniques alone.

Once the fission power distribution has been established, the maximum power output is primarily determined by thermal power distribution and the thermal and hydraulic limitation which determine the maximum core capability.

The lin-core instrumentation provides information which may be used to calculate the coolant enthalpy distribution:

the fuel burn up and to estimate the flow distribution.

Both radial and azimuthal symmetry of power distributions may be evaluated by comparing the detector and thermocouple information from one quadrant with similar data obtained from the other three quadrants.

7. 7.!3. 6.1 Thermocouples Chromel-alumel thermocouples are routed through the annular area between the inside and outside tubes of the flux thimble and terminate at the top of the flux thimble which is at the top of core.

Each of the 58 (see Note 1) flux thimbles has a back-up thermocouple to provide greater system availability.

The thermocouples are integral with the flux thimbles.

If both thermocouples faLl;, they cah be replaced by replacing the flux thimbles.

Note 1 There 58 locations designated as Flux Thimble and Thermocouple locations (see Figures 4.4-16 and 4.4-17).

The minimum number of Flux Thimbles and Thermocouples in use, as well as the minimum number per quadrant, is controlled by the Technical Speci 7.7-25 SGS-UFSAR Revision 21 December 6, 2004

Thermocouple readings are monitored by the core exit thermocouple processor, SPDS, and the computer.

The core exit thermocouple system, including the processor, meets R.G.l.97 requirements.

7.7.3.6.2 Moveable Miniature Neutron Flux Detectors Miniature neutron flux detectors, remotely positioned in the core, provide remote readout for flux mapping.

The basic system for the insertion of these detectors is shown on Figures 7. 7-4 and 7. 7-6. Retractable thimbles, into which the miniature detectors are driven, are pushed into the reactor core through conduits that extend from the bottom of the reactor vessel down through the concrete shield area, then to a thimble seal table.

The thimbles are closed at the leading ends, are dry inside, and serve as the pressure barrier between the reactor water pressure and the atmosphere.

Mechanical seals between the retractable thimbles and the conduits are provided at the seal line.

The thimbles consist of a tube within a tube.

The space between each inner and outer tube is used to route the thermocouple wires.

Normally, only the outside of the outer tube is exposed to reactor pressure.

However, on a failure of the outer tube, the inner tube can withstand full reactor pressure.

During reactor operation, the retractable thimbles are stationary.

They are extracted downward from the core during refueling to avoid interference within the core. A space above the seal line is provided for the retraction operation.

The drive system for the insertion of the miniature detectors consists of six combinations of drive assemblies, five-path rotary transfer devices, and ten-path rotary transfer devices, as shown on Figure 7.7-6.

The drive system pushes hollow helical-wrap drive cables into the core. Miniature detectors are attached to the leading ends of the cables and small diameter sheathed coaxial cables threaded through the hollow centers back to the ends of the 7.7-26 SGS-UFSAR Revision 15 June 12, 1996

drive cables.

Each drive assembly consists of a gear motor which pushes a helical-wrap drive cable and detector through a selective thimble path by means of a special drive box which includes a

7.7-26a SGS-UFSAR Revision 11 July 22, 1991

THIS PAGE INTENTIONALLY BLANK 7.7-26b SGS-UFSAR Revision 11 July 22, 1991

storage device that accommodates the total drive cable length.

information on mechanical design and support is provided in section 3.

Further The COntrol and Readout System provides means to rapidly traverse the miniature neutron detectors to and from the reactor core at 72 feet per minute, and to traverse the reactor core at 12 feet per minute, while plotting the thermal neutron flux versus detector position.

The Control System consists of two sections: one physically mounted with the drive units, and the other contained in the control room.

Limit switches in each tubing run provide signals to the path display to indicate the active detector path during the flux mapping operation.

Each gear box drives an encoder for position indication. One five-path group path selector is provided for each drive unit to route the detector into one of the flux thimble groups or to storage.

A ten-path rotary transfer assembly is used to route a detector into any one of up to ten selectable thimbles. Manually-operated isolation valves on each thimble allow free passage of the detector and drive cable when open.

When closed, these valves prevent steam leakage from the core in case of a thimble rupture.

Provision is made to separately route each detector into a common flux thimble to permit cross calibration of the detectors.

The control Room contains the necessary equipment for control, position indication and flux recording. Panels are provided to indicate the position of the detectors, and for plotting the flux level versus the detector position.

Additional panels are provided for such features as drive motor controls, core path selector switches, plotting and gain controls. A "flux-mapping" operation consists of selecting {by panel switches) flux thimbles in given fuel assemblies at various core locations. The detectors are driven to the top of the core and stopped automatically.

An x-y plot (position vs. flux level) is initiated with the slow withdrawal of the detectors through the core from top to a point below the bottom. In a similar manner, other core locations are selected and plotted.

7.7-27 SGS-UFSAR Revision 6 February 15, 1987

Bach detector provides axial flux distribution data along the canter of a fuel assembly.

various radial positions of detectors are than compared to obtain a flux map for a region of the cora.

The thimbles are distributed nearly uniformly over the cora, with about the same number of thimbles in each quadrant.

CUrrent nc approved methods (section 4.3.4, Reference 2) for Westinghouse plants using the moveable in-core fission chamber detector system statistically support a 4\\ nuclear enthalpy rise hot channel peaking factor (P4B) uncertainty.

Similarly, a 5' measurement uncertainty and a 3\\ manufacturing tolerance has bean approved for the local nuclear heat flux hot channel factor (F0). Therefore, the measured.P4B will be increased by 4\\ for possible instrument error, while the measured 1'0 will be increased by 8.15\\ (1.05 x 1.03) to allow for possible instrument error and manufacturing tolerances.

The departure from nucleate boiling ratio (DNBR}

calculated with the measured bot channel factor will be compared to the DNBR calculated from the design nuclear hot channel factors.

If the measured power peaking is larger than expected, reduced power capability will be indicated.

This unit will have the capability for using fixed in-core detectors, if required.

7.7.3.7 Operating Qontrol Systems 7.7.3.7.1 Control Room Availability The Control Room is designed to be available at all times. Safe occupancy of the Control Room during an abnormal condition is provided in the design of the Auxiliary Building.

Adequate shielding, ventilation and air conditioning are used to maintain the environment within established limits (see Section 9.4).

To limit the possibility and potential magnitude of a fire in the Control Room, Relay Room or Control Equipment Room, many precautions are taken. Noncombustible materials are used in construction.

Control Room furnishings are of metal construction.

The control console and side panels are made of steel.

Combustible supplies, such as records, logs, procedures, manuals, etc., are limited to the number required for station operation. All areas of the Control, Relay and Control Equipment Rooms are 7.7-28 SGS-OPSAR Revision 16 January 31, 1998

readily accessible.

Portable fire extinguishers and breathing apparatus are provided.

Detectors sensitive to smoke and combustion are installed in the Control Room, control console, ventilation plenum and throughout the Relay and Control Equipment Rooms.

Fire detection alarms are provided in the Control Room with indication of the detector zone actuated.

Further description of the fire protection provisions is given in Section 9.5.

The probability of the Control Room becoming inaccessible as a result of any cause is considered extremely small.

If the operator must leave the Control

Room, however, operating procedures require that he trip the reactor and turbine generator prior to leaving, thus ensuring control at the Hot Shutdown Control Stations.

If necessary, the required trips can be accomplished at locations outside the Control Room.

'.7.3.7.2 Control Room Evaluation The Control Room is designed to provide the operator with the controls,

~ndications and alarms necessary to control the unit during normal or abnormal condit~ons.

It is also designed for continuous occupancy, but provisions are made to attain and maintain hot shutdown from outside the control room.

7.7.3.8 All equipment is designed with highly reliable components.

Maximum use is made of solid state components in the electronic instruments; spring loaded control valves are employed to fail safe on loss of air or power.

All instrumentation and control, containment structure and in where possible, is installed outside of the locations accessible maintenance.

Automatic control instruments in 7.7-29 SGS-UFSAR for inspection Revision 18 April 26, 2000 and I

I selected systems are provided with backup manual control.

Alarms are provided to warn of abnormal conditions.

7.7.4 References for Section 7.7

1.

Blanchard, A.

and Katz, D.N., "Solid State Rod Control System -

Full Length,"

WCAP-9012-L (Proprietary),

January 1970 and WCAP-7778 (Non-Proprietary).

2.

T.

Baker, B.
Cassidy, J.
Freeland, S.

Fowler "Rod Evaluation Program" June 7, 1994; WCAP-13864 Rev. 1.

Control System I 3.

Blanchard, A., "Rod Position Monitoring," WCAP-7571, March 1971.

7.7-30 SGS-OFSAR Revision 18 April 26, 2000