LER-2016-005, Potential Loss of Safety Function of Onsite AC Sources and Operations Prohibited by Technical Specifications Due to Uncorrected Circuit Breaker Control Logic Design Causing Intermittent Failure to Close
River Bend Station - Unit 1
Event date: 02-24-2016
Report date: 04-25-2016
4582016005R00 - NRC Website

comments regarding burden estimate to the FOIA, Privacy and Information Collections Branch (T-5 F53), U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001, or by intemet e-mail to used to impose an information collection does not display a currently valid OMB control number, the.

NRC may not conduct or sponsor, and a person is not required to respond to, the information collection.

U.S. NUCLEAR REGULATORY COMMISSION 05000- River Bend Station - Unit 1 458

REPORTED CONDITION

On February 24, 2016, with the plant in cold shutdown, the operations shift manager was made aware of a notification regarding a certain model of Masterpact 480-volt safety-related circuit breakers (**BKR**) that described a failure mode that could potentially prevent the automatic closure of the breakers. The initial information regarded the emergency ventilation fans in the Division 1 and 2 emergency diesel generator rooms. These fans are not in Technical Specifications, but they provide a support function to the emergency diesel generators (**DG**). This condition required that both diesel generators to be declared inoperable. This constituted a condition that could potentially prevent fulfillment of the safety function of onsite AC power sources [ED].

Later on the same date, further evaluation of the notification identified four other circuit breakers affected by the same condition. These breakers supply power to Division land 2 containment unit coolers and the Division 1 and 2 auxiliary building 141 ft. elevation general area unit coolers. The auxiliary building unit coolers are not in Technical Specifications, but they provide a support function to the electrical distribution system. The required action in Technical Specification is to declare both trains of the residual heat removal system (shutdown cooling mode) [BO] inoperable. This inoperability constituted a condition that could have potentially prevented the fulfillment of the decay heat removal safety function.

Division 2 residual heat removal was operating in shutdown cooling, satisfactorily maintaining reactor coolant temperature. The affected breakers can be manually operated to start/stop their associated equipment, if necessary for operation

INVESTIGATION AND IMMEDIATE ACTIONS

Masterpact breakers were installed at RBS as replacements for obsolete General Electric AKR breakers. Subsequently, at RBS and elsewhere, there were isolated failures of the breakers to close upon demand. Failure analyses had been conducted by both the vendor and the utilities, but no such analyses determined that a potentially generic problem existed.

In 2014, the breaker vendor issued a non-conformance report that concluded that the closure failures were from intermittent mechanical binding of the anti-pump mechanism. The binding was the result of a "standing close signal," which is the condition where the relay that actuates the closing mechanism remains energized, either indefinitely or for a defined period of time following a closure actuation. The control logic for any given breaker is an inherent design feature of the circuitry of the switchgear, not internal to the breaker itself. It was eventually determined by the vendor that this condition could cause any Masterpact breaker to intermittently fail to close. The vendor indicated that the failure mode could not be predicted, but was repeatable, and occurred on both new and old breakers.

When RBS evaluated the vendor's nonconformance report, a population of affected circuit breakers was identified, and the served systems were evaluated for adverse effects on their ability to perform their safety functions. The operational history of the, breakers was examined, and it was determined that the observed increase in failure rate was not statistically significant. The affected systems were determined to be operable.

The nonconformance report stated that the failure mode could be averted by pressing the PUSH TO OPEN button on the front of the breaker after remote opening. This information was used to develop an Operations Standing Order, and this action was performed after every breaker opening for any of the affected breakers during power operations or hot shutdown until the modification to remove the standing close signal was installed. No failures of these breakers occurred when standing order was utilized.

Isolated failures occurred in breakers serving the control building air conditioning system in the refueling outage in 2015, and vendor recommendations for modifying the breaker control circuitry were implemented. Those modifications were limited, however, to breakers with continuously energized closure relays.

In the February 2016 notification, the vendor provided information regarding the identification of a potential defect, with a recommendation that Masterpact breakers designed for electrical closing operation be evaluated. The vulnerable breakers identified in connection with the notification were not surfaced during previous extent-of-condition reviews due to being limited to the population with the, continuously energized closing relay. The new information provided in February 2016 revealed that even breakers with a time-delayed removal of power from the closing relay could be vulnerable while the relay was energized.

CAUSAL ANALYSIS

The first direct cause of the event is that station personnel failed to recognize the breaker vulnerability to this failure mode. As a result, an additional population of breakers that had a time-delayed de-energization of the closing relay was identified in February 2016. These additional breakers included components that supported the emergency diesel generators and portions of the safety-related AC distribution system in the auxiliary building.

The second direct cause of the untimely corrective actions is that the breakers were incorrectly determined to be operable when the original condition with Masterpact breakers was discovered in 2014. Specifically, the procedure for development of operability determinations' contained inadequate guidance on the use of reliability-based evaluations.

One contributing cause of the event was the insufficient detail in the procedure regarding distribution of OE information for screening. This caused the component engineer for circuit breakers to be bypassed in the OE review cycle, likely preventing early detection of the condition. Additionally, the OE notices did not contain detailed information regarding the failure mode.

CORRECTIVE ACTIONS TO PREVENT RECURRENCE

The following actions have been completed to prevent recurrence of the reported condition.

  • All safety-related Masterpact circuit breakers with the control circuit configuration that applied a standing close signal have been modified to eliminate this condition.
  • The fleet procedure for operability evaluations has been revised to address conditions involving reduced reliability of safety-related components.

PREVIOUS OCCURRENCE EVALUATION

The reported condition resulted from a very specific design feature of a certain model of circuit breakers. No previous event reports regarding this condition have been submitted by RBS in the last three years.

SAFETY SIGNIFICANCE

The plant was in cold shutdown when the vendor notification was received. Technical Specification limiting condition for operations for the affected system were entered, and the required actions were completed. Dedicated operators were assigned to implement the standing order to mitigate the failure mode. All safety-related Masterpact circuit breakers with the control circuit configuration that applied a standing close signal were modified to eliminate this condition prior to plant startup.

A probabilistic risk analysis of this condition has concluded that this condition was of very low risk significance.