Tennessee Valley Authority, Post Office Box 2000, Decatur, Alabama 35609-2000 August24,2015 ATTN: Document Control Desk U.S. Nuclear Regulatory Commission Washington, D.C. 20555-0001 Browns Ferry Nuclear Plant, Unit 1 Renewed Facility Operating License No. DPR-33 NRC Docket No. 50-259 10 CFR 50.4

Subject:

Browns Ferry Nuclear Plant, Unit 1 Core Operating Limits Report for Cycle 11 Operation, Revision 2

References:

1. Letter from TVA to NRC, "Browns Ferry Nuclear Plant, Unit 1 Core Operating Limits Report for Cycle 11 Operation," dated October 6, 2014
2. Letter from TVA to NRC, "Browns Ferry Nuclear Plant, Unit 1 Core Operating Limits Report for Cycle 11 Operation Revision 1," dated February 19, 2015 In accordance with the requirements of Technical Specification 5.6.5.d, the Tennessee Valley Authority is submitting the Browns Ferry Nuclear Plant (BFN), Unit 1, Cycle 11,

Core Operating Limits Report (COLR), Revision 2. Revision 0 of the BFN, Unit 1, Cycle 11, COLR (Reference 1) included all modes of operation (Modes 1 through 5).

Revision 1 of the BFN, Unit 1, Cycl6 11, COLR (Reference 2) provided the correct equation statement for Linear Heat Generation Rate and the pointers to the contained COLR tables. Revision 2 of the BFN, Unit 1, Cycle 11, COLR provides updates to reflect the new reload safety analysis.

There are no new commitments contained in this letter. If you have any questions please contact Jamie L. Paul at (256) 729-2636.

U.S. Nuclear Regulatory Commission Page 2 August 24, 2015

Enclosure:

Core Operating Limits Report, (105% OLTP), for Cycle 11 Operation TVA-COLR-BF1C11, Revision 2 cc: (w/Enclosure)

NRC Regional Administrator - Region II NRC Senior Resident Inspector - Browns Ferry Nuclear Plant

Enclosure Tennessee Valley Authority Browns Ferry Nuclear Plant Unit 1 Core Operating Limits Report, (105% OLTP), for Cycle 11 Operation TVA-COLR-BF1C11, Revision 2 (See Attached)

(i!lilNPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga, TN 37402 EDMS L32 150813 800 QA Document Pages Affected: All BFE-3756, Revision 2 Browns Ferry Unit 1 Cycle 11 Core Operating Limits Report, (105°/o OL TP)

TV A-COLR-Bf 1 C11 Revision 2 (Final)

(Revision Log, Page v)

August 2015 Prepared: "2-. ~.&- ;f

~ichenberg, Sr. Spec~list Verified:

Approved:

11

1) Zo/_;,-

Date: Q.i--+.......

~--.a....

t __

Date: -~-~_I 3_/_!c_S-Bft3/tS' Date: _____

G. C. Storey, Mana er, BWR Fuel Engineering Reviewed: ~

Date: _ K_/_1_1_1_1 ~--

D. D. Coffey, Manager, Reactor Engineering Date: a>-/1-d Approved:

Date: __ o_* _,~_

'5~

Plant Manager

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 Table of Contents Total Number of Pages = 57 (including review cover sheet)

List of Tables................................................................................................................................................. iii List of Figures................................................................................................................................................ iv Revision Log................................................................................................................................... v Nomenclature................................................................................................................................................ vi References.................................................................................................................................................. viii 1

Introduction.......................................................................................................................... 1 1.1 Purpose......................................................................................................................... 1 1.1.1 Revision 2.............................................................................................................. 1 1.2 Scope............................................................................................................................ 1 1.3 Fuel Loading.................................................................................................................. 1 1.4 Acceptability.................................................................................................................. 2 2

APLHGR Limits.................................................................................................................... 3 2.1 Rated Power and Flow Limit: APLHGRRATED................................................................ 3 2.2 Off-Rated Power Dependent Limit: APLHGRP............................................................. 3 2.2.1 Startup without Feedwater Heaters....................................................................... 3 2.3 Off-Rated Flow Dependent Limit: APLHGRF................................................................ 3 2.4 Single Loop Operation Limit: APLHGRSLO.................................................................... 3 2.5 Equipment Out-Of-Service Corrections......................................................................... 6 3

LHGR Limits......................................................................................................................... 7 3.1 Rated Power and Flow Limit: LHGRRATED..................................................................... 7 3.2 Off-Rated Power Dependent Limit: LHGRP.................................................................. 7 3.2.1 Startup without Feedwater Heaters....................................................................... 7 3.3 Off-Rated Flow Dependent Limit: LHGRF..................................................................... 8 3.4 Single Loop Operation Limit: LHGRSLO........................................................................ 8 3.5 Equipment Out-Of-Service Corrections......................................................................... 8 4

OLMCPR Limits................................................................................................................. 19 4.1 Flow Dependent MCPR Limit: MCPRF....................................................................... 19 4.2 Power Dependent MCPR Limit: MCPRP.................................................................... 19 4.2.1 Startup without Feedwater Heaters..................................................................... 19 4.2.2 Scram Speed Dependent Limits (TSSS vs. NSS vs. OSS)................................. 20 4.2.3 Exposure Dependent Limits................................................................................ 20 4.2.4 Equipment Out-Of-Service (EOOS) Options....................................................... 21 4.2.5 Single-Loop-Operation (SLO) Limits................................................................... 21 4.2.6 Below Pbypass Limits......................................................................................... 21 5

Oscillation Power Range Monitor (OPRM) Setpoint.......................................................... 43 6

APRM Flow Biased Rod Block Trip Settings...................................................................... 44 7

Rod Block Monitor (RBM) Trip Setpoints and Operability.................................................. 45 8

Shutdown Margin Limit....................................................................................................... 47 Browns Ferry Unit 1 Cycle 11 Page ii Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 List of Tables Nuclear Fuel Types....................................................................................................................... 2 Startup Feedwater Temperature Basis......................................................................................... 7 Nominal Scram Time Basis......................................................................................................... 20 MCPRP Limits for ATRIUM-10: Optimum Scram Time Basis..................................................... 23 MCPRP Limits for GE-14: Optimum Scram Time Basis............................................................. 24 MCPRP Limits for ATRIUM-10: Nominal Scram Time Basis...................................................... 25 MCPRP Limits for GE 14: Nominal Scram Time Basis............................................................... 27 MCPRP Limits for ATRIUM-10: Technical Specification Scram Time Basis.............................. 29 MCPRP Limits for GE 14: Technical Specification Scram Time Basis....................................... 31 Startup Operation MCPRP Limits for Table 3.1 Temperature Range 1 for ATRIUM-10: Nominal Scram Time Basis....................................................................................................................... 33 Startup Operation MCPRP Limits for Table 3.1 Temperature Range 1 for GE 14: Nominal Scram Time Basis....................................................................................................................... 34 Startup Operation MCPRP Limits for Table 3.1 Temperature Range 2 for ATRIUM-10: Nominal Scram Time Basis....................................................................................................................... 35 Startup Operation MCPRP Limits for Table 3.1 Temperature Range 2 for GE 14: Nominal Scram Time Basis....................................................................................................................... 36 Startup Operation MCPRP Limits for Table 3.1 Temperature Range 1 for ATRIUM-10: Technical Specification Scram Time Basis................................................................................................. 37 Startup Operation MCPRP Limits for Table 3.1 Temperature Range 1 for GE 14: Technical Specification Scram Time Basis................................................................................................. 38 Startup Operation MCPRP Limits for Table 3.1 Temperature Range 2 for ATRIUM-10: Technical Specification Scram Time Basis................................................................................................. 39 Startup Operation MCPRP Limits for Table 3.1 Temperature Range 2 for GE 14: Technical Specification Scram Time Basis................................................................................................. 40 MCPRP Limits for ATRIUM-10: Single Loop Operation for All Scram Times............................. 41 MCPRP Limits for GE-14: Single Loop Operation for All Scram Times...................................... 42 OPRM Setpoint Range............................................................................................................... 43 OPRM Successive Confirmation Count Setpoint........................................................................ 43 Analytical RBM Trip Setpoints.................................................................................................... 45 RBM Setpoint Applicability.......................................................................................................... 45 Control Rod Withdrawal Error Results........................................................................................ 46 Browns Ferry Unit 1 Cycle 11 Page iii Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 List of Figures APLHGRRATED for ATRIUM-10 Fuel.............................................................................................. 4 APLHGRRATED for GE 14 Fuel....................................................................................................... 5 LHGRRATED for ATRIUM-10 Fuel................................................................................................... 9 LHGRRATED for GE14 UO2 Fuel................................................................................................... 10 Base Operation LHGRFACP for ATRIUM-10 Fuel...................................................................... 11 Base Operation LHGRFACP for GE 14 Fuel............................................................................... 12 LHGRFACF for ATRIUM-10 Fuel................................................................................................ 13 LHGRFACF for GE 14 Fuel......................................................................................................... 14 Startup Operation LHGRFACP for ATRIUM-10 Fuel: Table 3.1 Temperature Range 1.............. 15 Startup Operation LHGRFACP for ATRIUM-10 Fuel: Table 3.1 Temperature Range 2.............. 16 Startup Operation LHGRFACP for GE 14 Fuel: Table 3.1 Temperature Range 1.................. 17 Startup Operation LHGRFACP for GE 14 Fuel: Table 3.1 Temperature Range 2.................. 18 MCPRF for GE 14 and ATRIUM-10 Fuel..................................................................................... 22 Browns Ferry Unit 1 Cycle 11 Page iv Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 Revision Log Number Page Description 0-R2 No Changes to Section 2; Sections 5 through 8. Other changes driven by CR 1014002.

1-R2 viii Updated References 1 & 5.

2-R2 1

Added Section 1.1.1; identify new basis of revised reload safety analysis report.

3-R2 11 Updated Figure 3.3.

4-R2 15-16 Updated Figures 3.7 and 3.8.

5-R2 19 Edited Table number cross referencing.

6-R2 23-42 Updated Tables 4.2 through 4.17 1-R1 11 Implement QA Recommendation (PER 960548) 2-R1 17 First equation was fixed to include the LHGRSLO (which was defined below the equation). Constitutes a clarification of the generalized representation for LHGR. No impact on limits. (PER 951981) 3-R1 31 Section 4.2.5: Fixed table pointers to indicate correct tables. Values in tables are not altered. (PER 951981) 0-R0 All New document.

Browns Ferry Unit 1 Cycle 11 Page v Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 Nomenclature APLHGR Average Planar LHGR APRM Average Power Range Monitor AREVA NP Vendor (Framatome, Siemens)

BOC Beginning of Cycle BSP Backup Stability Protection BWR Boiling Water Reactor CAVEX Core Average Exposure CD Coast Down CMSS Core Monitoring System Software COLR Core Operating Limits Report CPR Critical Power Ratio CRWE Control Rod Withdrawal Error CSDM Cold SDM DIVOM Delta CPR over Initial CPR vs. Oscillation Magnitude EOC End of Cycle EOCLB End-of-Cycle Licensing Basis EOOS Equipment OOS FFTR Final Feedwater Temperature Reduction FFWTR Final Feedwater Temperature Reduction FHOOS Feedwater Heaters OOS ft Foot: english unit of measure for length GNF Vendor (General Electric, Global Nuclear Fuels)

GWd Giga Watt Day HTSP High TSP ICA Interim Corrective Action ICF Increased Core Flow (beyond rated)

IS In-Service kW kilo watt: SI unit of measure for power.

LCO License Condition of Operation LFWH Loss of Feedwater Heating LHGRFAC LHGR Multiplier (Power or Flow dependent)

LPRM Low Power Range Monitor LRNB Generator Load Reject, No Bypass MAPFAC MAPLHGR multiplier (Power or Flow dependent)

Browns Ferry Unit 1 Cycle 11 Page vi Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 MCPR Minimum CPR MSRV Moisture Separator Reheater Valve MSRVOOS MSRV OOS MTU Metric Ton Uranium MWd/MTU Mega Watt Day per Metric Ton Uranium NEOC Near EOC NRC United States Nuclear Regulatory Commission NSS Nominal Scram Speed NTSP Nominal TSP OLMCPR MCPR Operating Limit OOS Out-Of-Service OPRM Oscillation Power Range Monitor OSS Optimum Scram Speed PBDA Period Based Detection Algorithm Pbypass Power, below which TSV Position and TCV Fast Closure Scrams are Bypassed PLU Power Load Unbalance PLUOOS PLU OOS PRNM Power Range Neutron Monitor RBM Rod Block Monitor RCPOOS Recirculation Pump OOS (SLO)

RPS Reactor Protection System RPT Recirculation Pump Trip RPTOOS RPT OOS SDM Shutdown Margin SLMCPR MCPR Safety Limit SLO Single Loop Operation TBV Turbine Bypass Valve TBVIS TBV IS TBVOOS Turbine Bypass Valves OOS TIP Transversing In-core Probe TIPOOS TIP OOS TLO Two Loop Operation TSP Trip Setpoint TSSS Technical Specification Scram Speed TVA Tennessee Valley Authority Browns Ferry Unit 1 Cycle 11 Page vii Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 References

1.

ANP-3320, Revision 1, Browns Ferry Unit 1 Cycle 11 Reload Safety Analysis, AREVA NP, Inc., August, 2015.

2.

0000-0113-6833-SRLR, Revision 1, Supplemental Reload Licensing Report Browns Ferry 1 Reload 8 Cycle 9, Global Nuclear Fuels, Inc., November 2010.

3.

MEF-TVA-ER1-11-071, GE 14C LHGR Limits for non-EPU Plants, Letter from M.

Fitzpatrick (GNF) to D. McNelley (TVA), Global Nuclear Fuels, Inc., June 28, 2011.

4.

ANP-3031P, Rev. 3, Mechanical Design Report for Browns Ferry Units 1, 2, and 3 ATRIUM-10 Fuel Assemblies, AREVA NP, Inc., May 2014.

5.

ANP-3271P Revision 1, Browns Ferry Unit 1 Cycle 11 Plant Parameters Document, AREVA NP, Inc., June 2015.

6.

BFE-3719, Revision 0, Browns Ferry Unit 1 Cycle 11 In Core Shuffle, Calculation File, Tennessee Valley Authority, September, 2014.

Methodology References

7.

NEDE-24011-P-A-16, General Electric Standard Application for Reactor Fuel, October 2007.

8.

NEDE-24011-P-A-16-US, General Electric Standard Application for Reactor Fuel (Supplement for United States), October 2007.

9.

XN-NF-81-58(P)(A) Revision 2 and Supplements 1 and 2, RODEX2 Fuel Rod Thermal-Mechanical Response Evaluation Model, Exxon Nuclear Company, March 1984.

10.

XN-NF-85-67(P)(A) Revision 1, Generic Mechanical Design for Exxon Nuclear Jet Pump BWR Reload Fuel, Exxon Nuclear Company, September 1986.

11.

EMF-85-74(P) Revision 0 Supplement 1(P)(A) and Supplement 2(P)(A), RODEX2A (BWR) Fuel Rod Thermal-Mechanical Evaluation Model, Siemens Power Corporation, February 1998.

12.

ANF-89-98(P)(A) Revision 1 and Supplement 1, Generic Mechanical Design Criteria for BWR Fuel Designs, Advanced Nuclear Fuels Corporation, May 1995.

13.

XN-NF-80-19(P)(A) Volume 1 and Supplements 1 and 2, Exxon Nuclear Methodology for Boiling Water Reactors - Neutronic Methods for Design and Analysis, Exxon Nuclear Company, March 1983.

14.

XN-NF-80-19(P)(A) Volume 4 Revision 1, Exxon Nuclear Methodology for Boiling Water Reactors: Application of the ENC Methodology to BWR Reloads, Exxon Nuclear Company, June 1986.

15.

EMF-2158(P)(A) Revision 0, Siemens Power Corporation Methodology for Boiling Water Reactors: Evaluation and Validation of CASMO-4/MICROBURN-B2, Siemens Power Corporation, October 1999.

Browns Ferry Unit 1 Cycle 11 Page viii Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015

16.

XN-NF-80-19(P)(A) Volume 3 Revision 2, Exxon Nuclear Methodology for Boiling Water Reactors, THERMEX: Thermal Limits Methodology Summary Description, Exxon Nuclear Company, January 1987.

17.

XN-NF-84-105(P)(A) Volume 1 and Volume 1 Supplements 1 and 2, XCOBRA-T: A Computer Code for BWR Transient Thermal-Hydraulic Core Analysis, Exxon Nuclear Company, February 1987.

18.

ANF-524(P)(A) Revision 2 and Supplements 1 and 2, ANF Critical Power Methodology for Boiling Water Reactors, Advanced Nuclear Fuels Corporation, November 1990.

19.

ANF-913(P)(A) Volume 1 Revision 1 and Volume 1 Supplements 2, 3 and 4, COTRANSA2: A Computer Program for Boiling Water Reactor Transient Analyses, Advanced Nuclear Fuels Corporation, August 1990.

20.

ANF-1358(P)(A) Revision 3, The Loss of Feedwater Heating Transient in Boiling Water Reactors, Advanced Nuclear Fuels Corporation, September 2005.

21.

EMF-2209(P)(A) Revision 3, SPCB Critical Power Correlation, AREVA NP Inc.,

September 2009.

22.

EMF-2245(P)(A) Revision 0 Application of Siemens Power Corporations Critical Power Correlations to Co-Resident Fuel, Siemens Power Corporation, August 2000.

23.

EMF-2361(P)(A) Revision 0, EXEM BWR-2000 ECCS Evaluation Model, Framatome ANP Inc., May 2001, as supplemented by the site specific approval in NRC safety evaluation dated April 27, 2012.

24.

EMF-2292(P)(A) Revision 0, ATRIUM'-10: Appendix K Spray Heat Transfer Coefficients, Siemens Power Corporation, September 2000.

25.

EMF-CC-074(P)(A), Volume 4, Revision 0, BWR Stability Analysis: Assessment of STAIF with Input from MICROBURN-B2, Siemens Power Corporation, August 2000.

26.

BAW-10255(P)(A), Revision 2, Cycle-Specific DIVOM Methodology Using the RAMONA5-FA Code, AREVA NP Inc., Inc., May, 2008.

PRNM Setpoint References

27.

Filtered Setpoints - EDE-28-0990 Rev. 3 Supplement E, PRNM (APRM, RBM, and RFM) Setpoint Calculations [ARTS/MELLL (NUMAC) - Power-Uprate Condition] for Tennessee Valley Authority Browns Ferry Nuclear Plant, October 1997.

28.

Unfiltered Setpoints - EDE-28-0990 Rev. 2 Supplement E, PRNM (APRM, RBM, and RFM) Setpoint Calculations [ARTS/MELLL (NUMAC) - Power-Uprate Condition]

for Tennessee Valley Authority Browns Ferry Nuclear Plant, October 1997.

29.

GE Letter LB#: 262-97-133, Browns Ferry Nuclear Plant Rod Block Monitor Setpoint Clarification - GE Proprietary Information, September 12, 1997.

Browns Ferry Unit 1 Cycle 11 Page ix Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015

30.

NEDC-32433P, Maximum Extended Load Line Limit and ARTS Improvement Program Analyses for Browns Ferry Nuclear Plant Unit 1, 2, and 3, GE Nuclear Energy, April 1995.

31.

NEDO-32465-A, Licensing Topical Report - Reactor Stability Detect and Suppress Solutions Licensing Basis Methodology for Reload Applications, GE Nuclear Energy, August 1996.

Browns Ferry Unit 1 Cycle 11 Page x Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 1 Introduction In anticipation of cycle startup, it is necessary to describe the expected limits of operation.

1.1 Purpose The primary purpose of this document is to satisfy requirements identified by unit technical specification section 5.6.5. This document may be provided, upon final approval, to the NRC.

1.1.1 Revision 2 The purpose of this revision is a consequence of the Reference 1 reload safety analyses revision. The Reference 1 revision is in response to condition report (CR) 1014002.

1.2 Scope This document will discuss the following areas:

Average Planar Linear Heat Generation Rate (APLHGR) Limit (Technical Specifications 3.2.1 and 3.7.5)

Linear Heat Generation Rate (LHGR) Limit (Technical Specification 3.2.3, 3.3.4.1, and 3.7.5)

Minimum Critical Power Ratio Operating Limit (OLMCPR)

(Technical Specifications 3.2.2, 3.3.4.1, 3.7.5 and Table 3.3.2.1-1)

Oscillation Power Range Monitor (OPRM) Setpoint (Technical Specification Table 3.3.1.1)

Average Power Range Monitor (APRM) Flow Biased Rod Block Trip Setting (Technical Requirements Manual Section 5.3.1 and Table 3.3.4-1)

Rod Block Monitor (RBM) Trip Setpoints and Operability (Technical Specification Table 3.3.2.1-1)

Shutdown Margin (SDM) Limit (Technical Specification 3.1.1) 1.3 Fuel Loading The core will contain previously exposed GNF GE14, and AREVA NP, Inc., ATRIUM-10 fuel, along with fresh ATRIUM-10 fuel. Nuclear fuel types used in the core loading are shown in Table 1.1. The core shuffle and final loading were explicitly evaluated for BOC cold shutdown margin performance as documented per Reference 6.

Browns Ferry Unit 1 Cycle 11 Page 1 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 1.4 Acceptability Limits discussed in this document were generated based on NRC approved methodologies per References 7 through 26.

Table 1.1 Nuclear Fuel Types*

Fuel Description Original Cycle Number of Assemblies Nuclear Fuel Type (NFT)

Fuel Names (Range)

GE14-P10DNAB406-15GZ-100T-150-T6-3079 8

1 16 JYE295 GE14-P10DNAB408-16GZ-100T-150-T6-3363 9

111 1

JYP101-JYP280 GE14-P10DNAB412-16GZ-100T-150-T6-3364 9

40 2

JYP281-JYP320 GE14-P10DNAB404-15GZ-100T-150-T6-3365 9

9 8

JYP321-JYP336 GE14-P10DNAB408-17GZ-100T-150-T6-3366 9

16 19 JYP337-JYP352 ATRIUM-10 A10-3562B-14GV80-FAA 10 168 20 FAA001-FAA168 ATRIUM-10 A10-3676B-10GV80-FAA 10 24 21 FAA169-FAA192 ATRIUM-10 A10-4111B-15GV80-FAA 10 87 22 FAA193-FAA280 ATRIUM-10 A10-3840B-14GV80-FAB 11 200 23 FAB301-FAB500 ATRIUM-10 A10-4117B-13GV70-FAB 11 72 24 FAB501-FAB572 ATRIUM-10 A10-4112B-15GV70-FAB 11 36 25 FAB573-FAB608

  • The table identifies the expected fuel type breakdown in anticipation of final core loading. The final composition of the core depends upon uncertainties during the outage such as discovering a failed fuel bundle, or other bundle damage. Minor core loading changes, due to unforeseen events, will conform to the safety and monitoring requirements identified in this document.

Browns Ferry Unit 1 Cycle 11 Page 2 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 2 APLHGR Limits (Technical Specifications 3.2.1 & 3.7.5)

The APLHGR limit is determined by adjusting the rated power APLHGR limit for off-rated power, off-rated flow, and SLO conditions. The most limiting of these is then used as follows:

APLHGR limit = MIN ( APLHGRP, APLHGRF, APLHGRSLO )

where:

APLHGRP off-rated power APLHGR limit

[APLHGRRATED

  • MAPFACP]

APLHGRF off-rated flow APLHGR limit

[APLHGRRATED

  • MAPFACF]

APLHGRSLO SLO APLHGR limit

[APLHGRRATED

  • SLO Multiplier]

2.1 Rated Power and Flow Limit: APLHGRRATED The rated conditions APLHGR for ATRIUM-10 fuel is identified in Reference 1 and shown in Figure 2.1; for GE 14 fuel is identified in Reference 2, and shown in Figure 2.2.

2.2 Off-Rated Power Dependent Limit: APLHGRP Reference 1, for both GE14 and ATRIUM-10 fuel, does not specify a power dependent APLHGR. Therefore, MAPFACP is set to a value of 1.0.

2.2.1 Startup without Feedwater Heaters There is a range of operation during startup when the feedwater heaters are not placed into service until after the unit has reached a significant operating power level. No Additional power dependent limitation is required.

2.3 Off-Rated Flow Dependent Limit: APLHGRF Reference 1, for GE14 and ATRIUM-10 fuel, does not specify a flow dependent APLHGR.

Therefore, MAPFACF is set to a value of 1.0.

2.4 Single Loop Operation Limit: APLHGRSLO The single loop operation multiplier for ATRIUM-10 fuel is 0.85, per Reference 1; for GE 14 fuel the multiplier is 0.93 per Reference 2.

Browns Ferry Unit 1 Cycle 11 Page 3 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 0

3 6

9 12 15 0

20 40 60 80 APLHGR (kW/ft)

Planar Average Exposure (GWd/MTU)

Planar Avg.

APLHGR Exposure Limit (GWd/MTU)

(kW/ft) 0.0 12.5 15.0 12.5 67.0 7.3 Figure 2.1 APLHGRRATED for ATRIUM-10 Fuel Browns Ferry Unit 1 Cycle 11 Page 4 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 0

3 6

9 12 15 0

20 40 60 80 APLHGR (kW/ft)

Planar Average Exposure (GWd/MTU)

Planar Avg.

APLHGR Exposure Limit (GWd/MTU)

(kW/ft) 0.00 12.82 21.09 12.82 63.50 8.00 70.00 5.00 Figure 2.2 APLHGRRATED for GE 14 Fuel Browns Ferry Unit 1 Cycle 11 Page 5 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 2.5 Equipment Out-Of-Service Corrections The limits shown in Figure 2.1 and Figure 2.2 are applicable for operation with all equipment In-Service as well as the following Equipment Out-Of-Service (EOOS) options; including combinations of the options.

In-Service All equipment In-Service*

RPTOOS EOC-Recirculation Pump Trip Out-Of-Service TBVOOS Turbine Bypass Valve(s) Out-Of-Service PLUOOS Power Load Unbalance Out-Of-Service FHOOS (or FFWTR)

Feedwater Heaters Out-Of-Service or Final Feedwater Temperature Reduction RCPOOS One Recirculation Pump Out-Of-Service

  • All equipment service conditions assume 1 SRVOOS.

Requires application of multipliers to rated APLHGR limits as described in Section 2.4.

Browns Ferry Unit 1 Cycle 11 Page 6 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 3 LHGR Limits (Technical Specification 3.2.3, 3.3.4.1, & 3.7.5)

The LHGR limit is determined by adjusting the rated power LHGR limit for off-rated power and off-rated flow conditions. The most limiting of these is then used as follows:

LHGR limit = MIN ( LHGRP, LHGRF, LHGRSLO )

where:

LHGRP off-rated power LHGR limit

[LHGRRATED

  • LHGRFACP]

LHGRF off-rated flow LHGR limit

[LHGRRATED

  • LHGRFACF]

LHGRSLO SLO LHGR limit

[LHGRRATED

  • SLO Multiplier]

3.1 Rated Power and Flow Limit: LHGRRATED The rated conditions LHGR for ATRIUM-10 fuel is identified in Reference 1 and shown in Figure 3.1; for GE 14 fuel, is identified in Reference 3, and shown in Figure 3.2 for UO2 fuel. Separate, concentration dependent limits apply for rods containing Gadolinium; LHGR limits are provided in Reference 3.

3.2 Off-Rated Power Dependent Limit: LHGRP LHGR limits are adjusted for off-rated power conditions using the LHGRFACP multiplier provided in Reference 1, for both ATRIUM-10 and GE 14 fuel. The multiplier is split into two sub cases: turbine bypass valves in and out-of-service. The multipliers are shown in Figure 3.3 and Figure 3.4.

3.2.1 Startup without Feedwater Heaters There is a range of operation during startup when the feedwater heaters are not placed into service until after the unit has reached a significant operating power level. Additional limits are shown in Figure 3.7 thru Figure 3.10, based on temperature conditions identified in Table 3.1.

Table 3.1 Startup Feedwater Temperature Basis Power Range 1 Range 2

(% Rated)

(°F)

(°F) 25 160.0 155.0 30 165.0 160.0 40 175.0 170.0 50 185.0 180.0 Temperature Browns Ferry Unit 1 Cycle 11 Page 7 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 3.3 Off-Rated Flow Dependent Limit: LHGRF LHGR limits are adjusted for off-rated flow conditions using the LHGRFACF multiplier provided in Reference 1, for both ATRIUM-10 and GE 14 fuel. Multipliers are shown in Figure 3.5 and Figure 3.6.

3.4 Single Loop Operation Limit: LHGRSLO The single loop operation multiplier is 0.93, per Reference 2 for GE 14 fuel. There is no single loop operation restriction for ATRIUM-10; therefore the multiplier is 1.0.

3.5 Equipment Out-Of-Service Corrections The limits shown in Figure 3.1 and Figure 3.2 are applicable for operation with all equipment In-Service as well as the following Equipment Out-Of-Service (EOOS) options; including combinations of the options.*

In-Service All equipment In-Service RPTOOS EOC-Recirculation Pump Trip Out-Of-Service TBVOOS Turbine Bypass Valve(s) Out-Of-Service PLUOOS Power Load Unbalance Out-Of-Service FHOOS (or FFWTR)

Feedwater Heaters Out-Of-Service or Final Feedwater Temperature Reduction RCPOOS One Recirculation Pump Out-Of-Service Off-rated power corrections shown in Figure 3.3 and Figure 3.4 are dependent on operation of the Turbine Bypass Valve system. For this reason, separate limits are to be applied for TBVIS or TBVOOS operation. The limits have no dependency on RPTOOS, PLUOOS, FHOOS/FFWTR, or RCPOOS.

Off-rated flow corrections shown in Figure 3.5 and Figure 3.6 are bounding for all EOOS conditions.

Off-rated power corrections shown in Figure 3.7 through Figure 3.10 are also dependent on operation of the Turbine Bypass Valve system. In this case, limits support FHOOS operation during startup. These limits have no dependency on RPTOOS, PLUOOS, or RCPOOS.

  • All equipment service conditions assume 1 SRVOOS.

Requires application of multipliers to rated LHGR limits as described in Section 3.4.

Browns Ferry Unit 1 Cycle 11 Page 8 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 0

3 6

9 12 15 0

20 40 60 80 LHGR (kW/ft)

Pellet Exposure (GWd/MTU)

Pellet LHGR Exposure Limit (GWd/MTU)

(kW/ft) 0.0 13.4 18.9 13.4 74.4 7.1 Figure 3.1 LHGRRATED for ATRIUM-10 Fuel Browns Ferry Unit 1 Cycle 11 Page 9 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 0

3 6

9 12 15 0

20 40 60 80 LHGR (kW/ft)

Pellet Exposure (GWd/MTU)

Pellet LHGR Exposure Limit (GWd/MTU)

(kW/ft) 0.00 13.40 16.00 13.40 63.50 8.00 70.00 5.00 Figure 3.2 LHGRRATED for GE14 UO2 Fuel Browns Ferry Unit 1 Cycle 11 Page 10 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 20 30 40 50 60 70 80 90 100 110 LHGRFACP Core Power (% Rated)

Turbine Bypass Valve Out-of-Service, TBVOOS Turbine Bypass Valve In-Service, TBVIS TBVIS, > 50% Core Flow TBVIS, 50% Core Flow TBVOOS, > 50% Core Flow TBVOOS, 50% Core Flow Core Power LHGRFACP

(% Rated) 100.0 1.00 30.0 0.62 30.0 0.57 25.0 0.53 30.0 0.58 25.0 0.54 Turbine Bypass In-Service Core Flow > 50% Rated Core Flow 50% Rated Core Power LHGRFACP

(% Rated) 100.0 0.90 30.0 0.62 30.0 0.49 25.0 0.45 30.0 0.52 25.0 0.46 Turbine Bypass Out-of-Service Core Flow > 50% Rated Core Flow 50% Rated Figure 3.3 Base Operation LHGRFACP for ATRIUM-10 Fuel (Independent of other EOOS conditions)

Browns Ferry Unit 1 Cycle 11 Page 11 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 20 30 40 50 60 70 80 90 100 110 LHGRFACP Core Power (% Rated)

Turbine Bypass Valve Out-of-Service, TBVOOS Turbine Bypass Valve In-Service, TBVIS TBVIS, > 50% Core Flow TBVIS, 50% Core Flow TBVOOS, > 50% Core Flow TBVOOS, 50% Core Flow Core Power LHGRFACP

(% Rated) 100.0 1.00 75.0 0.79 30.0 0.55 30.0 0.40 25.0 0.36 30.0 0.42 25.0 0.38 Turbine Bypass In-Service Core Flow > 50% Rated Core Flow 50% Rated Core Power LHGRFACP

(% Rated) 100.0 1.00 75.0 0.77 30.0 0.55 30.0 0.37 25.0 0.31 30.0 0.42 25.0 0.37 Turbine Bypass Out-of-Service Core Flow > 50% Rated Core Flow 50% Rated Figure 3.4 Base Operation LHGRFACP for GE 14 Fuel (Independent of other EOOS conditions)

Browns Ferry Unit 1 Cycle 11 Page 12 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 0.80 0.85 0.90 0.95 1.00 1.05 1.10 25 35 45 55 65 75 85 95 105 LHGRFACF Core Flow (% Rated)

Core Flow LHGRFACF

(% Rated) 0.0 0.93 30.0 0.93 44.2 1

107.0 1

Figure 3.5 LHGRFACF for ATRIUM-10 Fuel (Values bound all EOOS conditions)

(107.0% maximum core flow line is used to support 105% rated flow operation, ICF)

Browns Ferry Unit 1 Cycle 11 Page 13 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 0.50 0.60 0.70 0.80 0.90 1.00 1.10 25 35 45 55 65 75 85 95 105 LHGRFACF Core Flow (% Rated)

Core Flow LHGRFACF

(% Rated) 0.0 0.56 30.0 0.56 82.2 1

107.0 1

Figure 3.6 LHGRFACF for GE 14 Fuel (Values bound all EOOS conditions)

(107.0% maximum core flow line is used to support 105% rated flow operation, ICF)

Browns Ferry Unit 1 Cycle 11 Page 14 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 20 30 40 50 60 70 80 90 100 110 LHGRFACP Core Power (% Rated)

Turbine Bypass Valve Out-of-Service, TBVOOS Turbine Bypass Valve In-Service, TBVIS TBVIS, > 50% Core Flow TBVIS, 50% Core Flow TBVOOS, > 50% Core Flow TBVOOS, 50% Core Flow Core Power LHGRFACP

(% Rated) 100.0 1.00 30.0 0.55 30.0 0.52 25.0 0.47 30.0 0.53 25.0 0.48 Turbine Bypass In-Service Core Flow > 50% Rated Core Flow 50% Rated Core Power LHGRFACP

(% Rated) 100.0 0.90 30.0 0.55 30.0 0.47 25.0 0.42 30.0 0.48 25.0 0.42 Turbine Bypass Out-of-Service Core Flow > 50% Rated Core Flow 50% Rated Figure 3.7 Startup Operation LHGRFACP for ATRIUM-10 Fuel:

Table 3.1 Temperature Range 1 (no Feedwater heating during startup)

(Limits valid at and below 50% power)

Browns Ferry Unit 1 Cycle 11 Page 15 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 20 30 40 50 60 70 80 90 100 110 LHGRFACP Core Power (% Rated)

Turbine Bypass Valve Out-of-Service, TBVOOS Turbine Bypass Valve In-Service, TBVIS TBVIS, > 50% Core Flow TBVIS, 50% Core Flow TBVOOS, > 50% Core Flow TBVOOS, 50% Core Flow Core Power LHGRFACP

(% Rated) 100.0 1.00 30.0 0.55 30.0 0.51 25.0 0.47 30.0 0.52 25.0 0.48 Turbine Bypass In-Service Core Flow > 50% Rated Core Flow 50% Rated Core Power LHGRFACP

(% Rated) 100.0 0.90 30.0 0.55 30.0 0.46 25.0 0.42 30.0 0.48 25.0 0.42 Turbine Bypass Out-of-Service Core Flow > 50% Rated Core Flow 50% Rated Figure 3.8 Startup Operation LHGRFACP for ATRIUM-10 Fuel:

Table 3.1 Temperature Range 2 (no Feedwater heating during startup)

(Limits valid at and below 50% power)

Browns Ferry Unit 1 Cycle 11 Page 16 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 20 30 40 50 60 70 80 90 100 110 LHGRFACP Core Power (% Rated)

Turbine Bypass Valve Out-of-Service, TBVOOS Turbine Bypass Valve In-Service, TBVIS TBVIS, > 50% Core Flow TBVIS, 50% Core Flow TBVOOS, > 50% Core Flow TBVOOS, 50% Core Flow Core Power LHGRFACP

(% Rated) 100.0 1.00 75.0 0.78 30.0 0.46 30.0 0.35 25.0 0.31 30.0 0.37 25.0 0.33 Turbine Bypass In-Service Core Flow > 50% Rated Core Flow 50% Rated Core Power LHGRFACP

(% Rated) 100.0 1.00 75.0 0.76 30.0 0.46 30.0 0.34 25.0 0.27 30.0 0.37 25.0 0.27 Turbine Bypass Out-of-Service Core Flow > 50% Rated Core Flow 50% Rated Figure 3.9 Startup Operation LHGRFACP for GE 14 Fuel:

Table 3.1 Temperature Range 1 (no Feedwater heating during startup)

(Limits valid at and below 50% power)

Browns Ferry Unit 1 Cycle 11 Page 17 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 20 30 40 50 60 70 80 90 100 110 LHGRFACP Core Power (% Rated)

Turbine Bypass Valve Out-of-Service, TBVOOS Turbine Bypass Valve In-Service, TBVIS TBVIS, > 50% Core Flow TBVIS, 50% Core Flow TBVOOS, > 50% Core Flow TBVOOS, 50% Core Flow Core Power LHGRFACP

(% Rated) 100.0 1.00 75.0 0.78 30.0 0.46 30.0 0.35 25.0 0.31 30.0 0.37 25.0 0.33 Turbine Bypass In-Service Core Flow > 50% Rated Core Flow 50% Rated Core Power LHGRFACP

(% Rated) 100.0 1.00 75.0 0.76 30.0 0.46 30.0 0.34 25.0 0.27 30.0 0.37 25.0 0.27 Turbine Bypass Out-of-Service Core Flow > 50% Rated Core Flow 50% Rated Figure 3.10 Startup Operation LHGRFACP for GE 14 Fuel:

Table 3.1 Temperature Range 2 (no Feedwater heating during startup)

(Limits valid at and below 50% power)

Browns Ferry Unit 1 Cycle 11 Page 18 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 4 OLMCPR Limits (Technical Specification 3.2.2, 3.3.4.1, & 3.7.5)

OLMCPR is calculated to be the most limiting of the flow or power dependent values OLMCPR limit = MAX ( MCPRF, MCPRP )

where:

MCPRF core flow-dependent MCPR limit MCPRP power-dependent MCPR limit 4.1 Flow Dependent MCPR Limit: MCPRF MCPRF limits are dependent upon core flow (% of Rated), and the max core flow limit, (Rated or Increased Core Flow, ICF). MCPRF limits are shown in Figure 4.1, per Reference 1. Limits are valid for all EOOS combinations. No adjustment is required for SLO conditions.

4.2 Power Dependent MCPR Limit: MCPRP MCPRP limits are dependent upon:

Core Power Level (% of Rated)

Technical Specification Scram Speed (TSSS), Nominal Scram Speed (NSS), or Optimum Scram Speed (OSS)

Cycle Operating Exposure (NEOC, EOC, and CD - as defined in this section)

Equipment Out-Of-Service Options Two or Single recirculation Loop Operation (TLO vs. SLO)

The MCPRP limits are provided in the following tables, where each table contains the limits for all fuel types and EOOS options (for a specified scram speed and exposure range). The CMSS determines MCPRP limits, from these tables, based on linear interpolation between the specified powers.

4.2.1 Startup without Feedwater Heaters There is a range of operation during startup when the feedwater heaters are not placed into service until after the unit has reached a significant operating power level. Additional power dependent limits are shown in Table 4.8, thru Table 4.15, based on temperature conditions identified in Table 3.1.

Browns Ferry Unit 1 Cycle 11 Page 19 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 4.2.2 Scram Speed Dependent Limits (TSSS vs. NSS vs. OSS)

MCPRP limits are provided for three different sets of assumed scram speeds. The Technical Specification Scram Speed (TSSS) MCPRP limits are applicable at all times, as long as the scram time surveillance demonstrates the times in Technical Specification Table 3.1.4-1 are met. Both Nominal Scram Speeds (NSS) and/or Optimum Scram Speeds (OSS) may be used, as long as the scram time surveillance demonstrates Table 4.1 times are applicable.*

Table 4.1 Nominal Scram Time Basis Notch Nominal Optimum Position Scram Timing Scram Timing (index)

(seconds)

(seconds) 46 0.420 0.380 36 0.980 0.875 26 1.600 1.465 6

2.900 2.900 In demonstrating compliance with the NSS and/or OSS scram time basis, surveillance requirements from Technical Specification 3.1.4 apply; accepting the definition of SLOW rods should conform to scram speeds shown in Table 4.1. If conformance is not demonstrated, TSSS based MCPRP limits are applied.

On initial cycle startup, TSSS limits are used until the successful completion of scram timing confirms NSS and/or OSS based limits are applicable.

4.2.3 Exposure Dependent Limits Exposures are tracked on a Core Average Exposure basis (CAVEX, not Cycle Exposure).

Higher exposure MCPRP limits are always more limiting and may be used for any Core Average Exposure up to the ending exposure. Per Reference 1, MCPRP limits are provided for the following exposure ranges:

BOC to NEOC NEOC corresponds to 28,986.6 MWd / MTU BOC to EOCLB EOCLB corresponds to 32,248.5 MWd / MTU BOC to End of Coast End of Coast 33,643.5 MWd / MTU NEOC refers to a Near EOC exposure point.

  • Reference 1 analysis results are based on information identified in Reference 5.

Drop out times consistent with method used to perform actual timing measurements (i.e., including pickup/dropout effects).

Browns Ferry Unit 1 Cycle 11 Page 20 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 The EOCLB exposure point is not the true End-Of-Cycle exposure. Instead it corresponds to a licensing exposure window exceeding expected end-of-full-power-life.

The End of Coast exposure point represents a licensing exposure point exceeding the expected end-of-cycle exposure including cycle extension options.

4.2.4 Equipment Out-Of-Service (EOOS) Options EOOS options* covered by MCPRP limits are given by the following:

In-Service All equipment In-Service RPTOOS EOC-Recirculation Pump Trip Out-Of-Service TBVOOS Turbine Bypass Valve(s) Out-Of-Service RPTOOS+TBVOOS Combined RPTOOS and TBVOOS PLUOOS Power Load Unbalance Out-Of-Service PLUOOS+RPTOOS Combined PLUOOS and RPTOOS PLUOOS+TBVOOS Combined PLUOOS and TBVOOS PLUOOS+TBVOOS+RPTOOS Combined PLUOOS, RPTOOS, and TBVOOS FHOOS (or FFWTR)

Feedwater Heaters Out-Of-Service (or Final Feedwater Temperature Reduction)

RCPOOS One Recirculation Pump Out-Of-Service For exposure ranges up to NEOC and EOCLB, additional combinations of MCPRP limits are also provided including FHOOS. The coast down exposure range assumes application of FFWTR. FHOOS based MCPRP limits for the coast down exposure are redundant because the temperature setdown assumption is identical with FFWTR.

4.2.5 Single-Loop-Operation (SLO) Limits When operating in RCPOOS conditions, MCPRp limits are constructed differently from the normal operating RCP conditions. The limiting event for RCPOOS is a pump seizure scenario, which sets the upper bound for allowed core power and flow. This event is not impacted by scram time assumptions. Specific MCPRP limits are shown in Table 4.16 and Table 4.17.

4.2.6 Below Pbypass Limits Below Pbypass (30% rated power), MCPRP limits depend upon core flow. One set of MCPRP limits applies for core flow above 50% of rated; a second set applies if the core flow is less than or equal to 50% rated.

  • All equipment service conditions assume 1 SRVOOS.

RCPOOS limits are only valid up to 50% rated core power, 50% rated core flow, and an active recirculation drive flow of 17.73 Mlbm/hr.

Browns Ferry Unit 1 Cycle 11 Page 21 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 1.00 1.20 1.40 1.60 1.80 2.00 30 40 50 60 70 80 90 100 110 MCPRF Core Flow (% Rated)

Core Flow MCPRF

(% Rated) 30.0 1.61 78.0 1.28 107.0 1.28 Figure 4.1 MCPRF for GE 14 and ATRIUM-10 Fuel (Values bound all EOOS conditions)

(107.0% maximum core flow line is used to support 105% rated flow operation, ICF)

Browns Ferry Unit 1 Cycle 11 Page 22 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 Table 4.2 MCPRP Limits for ATRIUM-10: Optimum Scram Time Basis*

BOC BOC BOC Pow er to to to End of

(% of rated)

NEOC EOCLB Coast 100 1.45 1.46 1.48 75 1.58 1.59 1.60 65 1.66 1.66 1.70 50 1.80 1.80 50 1.83 1.83 1.86 40 1.99 1.99 2.09 30 2.29 2.29 2.40 30 at > 50%F 2.34 2.34 2.43 25 at > 50%F 2.56 2.56 2.66 30 at 50%F 2.33 2.33 2.40 25 at 50%F 2.50 2.50 2.60 100 1.47 1.48 75 1.60 1.60 65 1.70 1.70 50 50 1.86 1.86 40 2.09 2.09 30 2.40 2.40 30 at > 50%F 2.43 2.43 25 at > 50%F 2.66 2.66 30 at 50%F 2.40 2.40 25 at 50%F 2.60 2.60 Operating Condition Base Case FHOOS

  • All limits, including Base Case, support RPTOOS operation; operation is supported for any combination of 1 MSRVOOS, up to 2 TIPOOS (or the equivalent number of TIP channels), and up to 50% of the LPRMs out-of-service.

FFWTR/FHOOS is supported for the BOC to End of Coast limits.

Browns Ferry Unit 1 Cycle 11 Page 23 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 Table 4.3 MCPRP Limits for GE-14: Optimum Scram Time Basis*

BOC BOC BOC Pow er to to to End of

(% of rated)

NEOC EOCLB Coast 100 1.47 1.51 1.52 75 1.60 1.64 1.65 65 1.70 1.71 1.75 50 1.85 1.85 50 1.86 1.86 1.91 40 2.04 2.04 2.14 30 2.36 2.36 2.48 30 at > 50%F 2.42 2.42 2.52 25 at > 50%F 2.64 2.64 2.76 30 at 50%F 2.41 2.41 2.48 25 at 50%F 2.58 2.58 2.68 100 1.49 1.52 75 1.63 1.65 65 1.73 1.75 50 50 1.91 1.91 40 2.14 2.14 30 2.48 2.48 30 at > 50%F 2.52 2.52 25 at > 50%F 2.76 2.76 30 at 50%F 2.48 2.48 25 at 50%F 2.68 2.68 Operating Condition Base Case FHOOS

  • All limits, including Base Case, support RPTOOS operation; operation is supported for any combination of 1 MSRVOOS, up to 2 TIPOOS (or the equivalent number of TIP channels), and up to 50% of the LPRMs out-of-service.

FFWTR/FHOOS is supported for the BOC to End of Coast limits.

Browns Ferry Unit 1 Cycle 11 Page 24 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 Table 4.4 MCPRP Limits for ATRIUM-10: Nominal Scram Time Basis*

BOC BOC BOC Pow er to to to End of

(% of rated)

NEOC EOCLB Coast 100 1.46 1.47 1.49 75 1.59 1.60 1.62 65 1.67 1.67 1.71 50 1.82 1.82 50 1.84 1.84 1.90 40 2.03 2.03 2.12 30 2.33 2.33 2.45 30 at > 50%F 2.34 2.34 2.45 25 at > 50%F 2.56 2.56 2.66 30 at 50%F 2.33 2.33 2.45 25 at 50%F 2.50 2.50 2.60 100 1.49 1.51 1.52 75 1.62 1.62 1.66 65 1.71 1.71 1.74 50 50 1.84 1.84 1.90 40 2.03 2.03 2.12 30 2.33 2.33 2.45 30 at > 50%F 2.90 2.90 3.00 25 at > 50%F 3.23 3.23 3.32 30 at 50%F 2.74 2.74 2.85 25 at 50%F 3.10 3.10 3.24 100 1.49 1.49 75 1.62 1.62 65 1.71 1.71 50 50 1.90 1.90 40 2.12 2.12 30 2.45 2.45 30 at > 50%F 2.45 2.45 25 at > 50%F 2.66 2.66 30 at 50%F 2.45 2.45 25 at 50%F 2.60 2.60 100 1.46 1.47 1.49 75 1.59 1.60 1.62 65 1.75 1.77 1.77 50 50 1.84 1.84 1.90 40 2.03 2.03 2.12 30 2.33 2.33 2.45 30 at > 50%F 2.34 2.34 2.45 25 at > 50%F 2.56 2.56 2.66 30 at 50%F 2.33 2.33 2.45 25 at 50%F 2.50 2.50 2.60 Operating Condition Base Case TBVOOS FHOOS PLUOOS

  • All limits, including Base Case, support RPTOOS operation; operation is supported for any combination of 1 MSRVOOS, up to 2 TIPOOS (or the equivalent number of TIP channels), and up to 50% of the LPRMs out-of-service.

FFWTR and FHOOS assume the same value of temperature drop. Consequently, FHOOS limits are not provided for BOC to End of COAST due to redundancy. Thermal limits for the BOC to End of COAST exposure applicability window are developed to conservatively bound FHOOS limits for earlier exposure applicability windows.

Browns Ferry Unit 1 Cycle 11 Page 25 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 Table 4.4 MCPRP Limits for ATRIUM-10: Nominal Scram Time Basis (continued)*

BOC BOC BOC Pow er to to to End of

(% of rated)

NEOC EOCLB Coast 100 1.51 1.52 75 1.66 1.66 65 1.74 1.74 50 50 1.90 1.90 40 2.12 2.12 30 2.45 2.45 30 at > 50%F 3.00 3.00 25 at > 50%F 3.32 3.32 30 at 50%F 2.85 2.85 25 at 50%F 3.24 3.24 100 1.49 1.51 1.52 75 1.62 1.62 1.66 65 1.75 1.77 1.77 50 50 1.84 1.84 1.90 40 2.03 2.03 2.12 30 2.33 2.33 2.45 30 at > 50%F 2.90 2.90 3.00 25 at > 50%F 3.23 3.23 3.32 30 at 50%F 2.74 2.74 2.85 25 at 50%F 3.10 3.10 3.24 100 1.49 1.49 75 1.62 1.62 65 1.75 1.77 50 50 1.90 1.90 40 2.12 2.12 30 2.45 2.45 30 at > 50%F 2.45 2.45 25 at > 50%F 2.66 2.66 30 at 50%F 2.45 2.45 25 at 50%F 2.60 2.60 100 1.51 1.52 75 1.66 1.66 65 1.75 1.77 50 50 1.90 1.90 40 2.12 2.12 30 2.45 2.45 30 at > 50%F 3.00 3.00 25 at > 50%F 3.32 3.32 30 at 50%F 2.85 2.85 25 at 50%F 3.24 3.24 TBVOOS FHOOS TBVOOS PLUOOS FHOOS PLUOOS TBVOOS FHOOS PLUOOS Operating Condition

  • All limits, including Base Case, support RPTOOS operation; operation is supported for any combination of 1 MSRVOOS, up to 2 TIPOOS (or the equivalent number of TIP channels), and up to 50% of the LPRMs out-of-service.

FFWTR and FHOOS assume the same value of temperature drop. Consequently, FHOOS limits are not provided for BOC to End of COAST due to redundancy. Thermal limits for the BOC to End of COAST exposure applicability window are developed to conservatively bound FHOOS limits for earlier exposure applicability windows.

Browns Ferry Unit 1 Cycle 11 Page 26 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 Table 4.5 MCPRP Limits for GE 14: Nominal Scram Time Basis*

BOC BOC BOC Pow er to to to End of

(% of rated)

NEOC EOCLB Coast 100 1.49 1.52 1.53 75 1.62 1.65 1.66 65 1.71 1.72 1.76 50 50 1.87 1.87 1.94 40 2.08 2.08 2.18 30 2.40 2.40 2.52 30 at > 50%F 2.42 2.42 2.52 25 at > 50%F 2.64 2.64 2.76 30 at 50%F 2.41 2.41 2.52 25 at 50%F 2.58 2.58 2.68 100 1.52 1.56 1.57 75 1.65 1.69 1.70 65 1.75 1.77 1.80 50 50 1.90 1.90 1.96 40 2.09 2.09 2.18 30 2.40 2.40 2.52 30 at > 50%F 2.96 2.96 3.06 25 at > 50%F 3.28 3.28 3.36 30 at 50%F 2.81 2.81 2.93 25 at 50%F 3.19 3.19 3.33 100 1.51 1.53 75 1.66 1.66 65 1.75 1.76 50 50 1.94 1.94 40 2.18 2.18 30 2.52 2.52 30 at > 50%F 2.52 2.52 25 at > 50%F 2.76 2.76 30 at 50%F 2.52 2.52 25 at 50%F 2.68 2.68 100 1.49 1.52 1.53 75 1.62 1.65 1.66 65 1.78 1.78 1.78 50 50 1.87 1.87 1.94 40 2.08 2.08 2.18 30 2.40 2.40 2.52 30 at > 50%F 2.42 2.42 2.52 25 at > 50%F 2.64 2.64 2.76 30 at 50%F 2.41 2.41 2.52 25 at 50%F 2.58 2.58 2.68 Operating Condition Base Case TBVOOS FHOOS PLUOOS

  • All limits, including Base Case, support RPTOOS operation; operation is supported for any combination of 1 MSRVOOS, up to 2 TIPOOS (or the equivalent number of TIP channels), and up to 50% of the LPRMs out-of-service.

FFWTR and FHOOS assume the same value of temperature drop. Consequently, FHOOS limits are not provided for BOC to End of COAST due to redundancy. Thermal limits for the BOC to End of COAST exposure applicability window are developed to conservatively bound FHOOS limits for earlier exposure applicability windows.

Browns Ferry Unit 1 Cycle 11 Page 27 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 Table 4.5 MCPRP Limits for GE 14: Nominal Scram Time Basis (continued)*

BOC BOC BOC Pow er to to to End of

(% of rated)

NEOC EOCLB Coast 100 1.54 1.57 75 1.69 1.70 65 1.78 1.80 50 50 1.96 1.96 40 2.18 2.18 30 2.52 2.52 30 at > 50%F 3.06 3.06 25 at > 50%F 3.36 3.36 30 at 50%F 2.93 2.93 25 at 50%F 3.33 3.33 100 1.52 1.56 1.57 75 1.65 1.69 1.70 65 1.78 1.78 1.80 50 50 1.90 1.90 1.96 40 2.09 2.09 2.18 30 2.40 2.40 2.52 30 at > 50%F 2.96 2.96 3.06 25 at > 50%F 3.28 3.28 3.36 30 at 50%F 2.81 2.81 2.93 25 at 50%F 3.19 3.19 3.33 100 1.51 1.53 75 1.66 1.66 65 1.78 1.78 50 50 1.94 1.94 40 2.18 2.18 30 2.52 2.52 30 at > 50%F 2.52 2.52 25 at > 50%F 2.76 2.76 30 at 50%F 2.52 2.52 25 at 50%F 2.68 2.68 100 1.54 1.57 75 1.69 1.70 65 1.78 1.80 50 50 1.96 1.96 40 2.18 2.18 30 2.52 2.52 30 at > 50%F 3.06 3.06 25 at > 50%F 3.36 3.36 30 at 50%F 2.93 2.93 25 at 50%F 3.33 3.33 TBVOOS FHOOS TBVOOS PLUOOS FHOOS PLUOOS TBVOOS FHOOS PLUOOS Operating Condition

  • All limits, including Base Case, support RPTOOS operation; operation is supported for any combination of 1 MSRVOOS, up to 2 TIPOOS (or the equivalent number of TIP channels), and up to 50% of the LPRMs out-of-service.

FFWTR and FHOOS assume the same value of temperature drop. Consequently, FHOOS limits are not provided for BOC to End of COAST due to redundancy. Thermal limits for the BOC to End of COAST exposure applicability window are developed to conservatively bound FHOOS limits for earlier exposure applicability windows.

Browns Ferry Unit 1 Cycle 11 Page 28 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 Table 4.6 MCPRP Limits for ATRIUM-10: Technical Specification Scram Time Basis*

BOC BOC BOC Pow er to to to End of

(% of rated)

NEOC EOCLB Coast 100 1.49 1.49 1.51 75 1.62 1.62 1.64 65 1.69 1.69 1.72 50 50 1.85 1.85 1.93 40 2.06 2.06 2.16 30 2.36 2.36 2.49 30 at > 50%F 2.36 2.36 2.49 25 at > 50%F 2.56 2.56 2.66 30 at 50%F 2.36 2.36 2.49 25 at 50%F 2.50 2.50 2.60 100 1.52 1.52 1.54 75 1.65 1.65 1.67 65 1.72 1.72 1.75 50 50 1.86 1.86 1.94 40 2.07 2.07 2.16 30 2.36 2.36 2.49 30 at > 50%F 2.90 2.90 3.00 25 at > 50%F 3.23 3.23 3.32 30 at 50%F 2.74 2.74 2.85 25 at 50%F 3.10 3.10 3.24 100 1.51 1.51 75 1.64 1.64 65 1.72 1.72 50 50 1.93 1.93 40 2.16 2.16 30 2.49 2.49 30 at > 50%F 2.49 2.49 25 at > 50%F 2.66 2.66 30 at 50%F 2.49 2.49 25 at 50%F 2.60 2.60 100 1.49 1.49 1.51 75 1.62 1.62 1.64 65 1.76 1.79 1.79 50 50 1.85 1.85 1.93 40 2.06 2.06 2.16 30 2.36 2.36 2.49 30 at > 50%F 2.36 2.36 2.49 25 at > 50%F 2.56 2.56 2.66 30 at 50%F 2.36 2.36 2.49 25 at 50%F 2.50 2.50 2.60 Operating Condition Base Case TBVOOS FHOOS PLUOOS

  • All limits, including Base Case, support RPTOOS operation; operation is supported for any combination of 1 MSRVOOS, up to 2 TIPOOS (or the equivalent number of TIP channels), and up to 50% of the LPRMs out-of-service.

FFWTR and FHOOS assume the same value of temperature drop. Consequently, FHOOS limits are not provided for BOC to End of COAST due to redundancy. Thermal limits for the BOC to End of COAST exposure applicability window are developed to conservatively bound FHOOS limits for earlier exposure applicability windows.

Browns Ferry Unit 1 Cycle 11 Page 29 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 Table 4.6 MCPRP Limits for ATRIUM-10: Technical Specification Scram Time Basis (continued)*

BOC BOC BOC Pow er to to to End of

(% of rated)

NEOC EOCLB Coast 100 1.54 1.54 75 1.67 1.67 65 1.75 1.75 50 50 1.94 1.94 40 2.16 2.16 30 2.49 2.49 30 at > 50%F 3.00 3.00 25 at > 50%F 3.32 3.32 30 at 50%F 2.85 2.85 25 at 50%F 3.24 3.24 100 1.52 1.52 1.54 75 1.65 1.65 1.67 65 1.76 1.79 1.79 50 50 1.86 1.86 1.94 40 2.07 2.07 2.16 30 2.36 2.36 2.49 30 at > 50%F 2.90 2.90 3.00 25 at > 50%F 3.23 3.23 3.32 30 at 50%F 2.74 2.74 2.85 25 at 50%F 3.10 3.10 3.24 100 1.51 1.51 75 1.64 1.64 65 1.76 1.79 50 50 1.93 1.93 40 2.16 2.16 30 2.49 2.49 30 at > 50%F 2.49 2.49 25 at > 50%F 2.66 2.66 30 at 50%F 2.49 2.49 25 at 50%F 2.60 2.60 100 1.54 1.54 75 1.67 1.67 65 1.76 1.79 50 50 1.94 1.94 40 2.16 2.16 30 2.49 2.49 30 at > 50%F 3.00 3.00 25 at > 50%F 3.32 3.32 30 at 50%F 2.85 2.85 25 at 50%F 3.24 3.24 TBVOOS FHOOS TBVOOS PLUOOS FHOOS PLUOOS TBVOOS FHOOS PLUOOS Operating Condition

  • All limits, including Base Case, support RPTOOS operation; operation is supported for any combination of 1 MSRVOOS, up to 2 TIPOOS (or the equivalent number of TIP channels), and up to 50% of the LPRMs out-of-service.

FFWTR and FHOOS assume the same value of temperature drop. Consequently, FHOOS limits are not provided for BOC to End of COAST due to redundancy. Thermal limits for the BOC to End of COAST exposure applicability window are developed to conservatively bound FHOOS limits for earlier exposure applicability windows.

Browns Ferry Unit 1 Cycle 11 Page 30 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 Table 4.7 MCPRP Limits for GE 14: Technical Specification Scram Time Basis*

BOC BOC BOC Pow er to to to End of

(% of rated)

NEOC EOCLB Coast 100 1.51 1.53 1.54 75 1.66 1.66 1.67 65 1.73 1.73 1.76 50 50 1.90 1.90 1.98 40 2.12 2.12 2.22 30 2.45 2.45 2.57 30 at > 50%F 2.45 2.45 2.57 25 at > 50%F 2.64 2.64 2.76 30 at 50%F 2.45 2.45 2.57 25 at 50%F 2.58 2.58 2.68 100 1.54 1.57 1.57 75 1.69 1.70 1.70 65 1.77 1.77 1.81 50 50 1.92 1.92 1.99 40 2.13 2.13 2.22 30 2.45 2.45 2.57 30 at > 50%F 2.96 2.96 3.06 25 at > 50%F 3.28 3.28 3.36 30 at 50%F 2.81 2.81 2.93 25 at 50%F 3.19 3.19 3.33 100 1.54 1.54 75 1.67 1.67 65 1.76 1.76 50 50 1.98 1.98 40 2.22 2.22 30 2.57 2.57 30 at > 50%F 2.57 2.57 25 at > 50%F 2.76 2.76 30 at 50%F 2.57 2.57 25 at 50%F 2.68 2.68 100 1.51 1.53 1.54 75 1.66 1.66 1.67 65 1.79 1.80 1.80 50 50 1.90 1.90 1.98 40 2.12 2.12 2.22 30 2.45 2.45 2.57 30 at > 50%F 2.45 2.45 2.57 25 at > 50%F 2.64 2.64 2.76 30 at 50%F 2.45 2.45 2.57 25 at 50%F 2.58 2.58 2.68 Operating Condition Base Case TBVOOS FHOOS PLUOOS

  • All limits, including Base Case, support RPTOOS operation; operation is supported for any combination of 1 MSRVOOS, up to 2 TIPOOS (or the equivalent number of TIP channels), and up to 50% of the LPRMs out-of-service.

FFWTR and FHOOS assume the same value of temperature drop. Consequently, FHOOS limits are not provided for BOC to End of COAST due to redundancy. Thermal limits for the BOC to End of COAST exposure applicability window are developed to conservatively bound FHOOS limits for earlier exposure applicability windows.

Browns Ferry Unit 1 Cycle 11 Page 31 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 Table 4.7 MCPRP Limits for GE 14: Technical Specification Scram Time Basis (continued)*

BOC BOC BOC Pow er to to to End of

(% of rated)

NEOC EOCLB Coast 100 1.57 1.57 75 1.70 1.70 65 1.80 1.81 50 50 1.99 1.99 40 2.22 2.22 30 2.57 2.57 30 at > 50%F 3.06 3.06 25 at > 50%F 3.36 3.36 30 at 50%F 2.93 2.93 25 at 50%F 3.33 3.33 100 1.54 1.57 1.57 75 1.69 1.70 1.70 65 1.79 1.80 1.81 50 50 1.92 1.92 1.99 40 2.13 2.13 2.22 30 2.45 2.45 2.57 30 at > 50%F 2.96 2.96 3.06 25 at > 50%F 3.28 3.28 3.36 30 at 50%F 2.81 2.81 2.93 25 at 50%F 3.19 3.19 3.33 100 1.54 1.54 75 1.67 1.67 65 1.79 1.80 50 50 1.98 1.98 40 2.22 2.22 30 2.57 2.57 30 at > 50%F 2.57 2.57 25 at > 50%F 2.76 2.76 30 at 50%F 2.57 2.57 25 at 50%F 2.68 2.68 100 1.57 1.57 75 1.70 1.70 65 1.80 1.81 50 50 1.99 1.99 40 2.22 2.22 30 2.57 2.57 30 at > 50%F 3.06 3.06 25 at > 50%F 3.36 3.36 30 at 50%F 2.93 2.93 25 at 50%F 3.33 3.33 TBVOOS FHOOS TBVOOS PLUOOS FHOOS PLUOOS TBVOOS FHOOS PLUOOS Operating Condition

  • All limits, including Base Case, support RPTOOS operation; operation is supported for any combination of 1 MSRVOOS, up to 2 TIPOOS (or the equivalent number of TIP channels), and up to 50% of the LPRMs out-of-service.

FFWTR and FHOOS assume the same value of temperature drop. Consequently, FHOOS limits are not provided for BOC to End of COAST due to redundancy. Thermal limits for the BOC to End of COAST exposure applicability window are developed to conservatively bound FHOOS limits for earlier exposure applicability windows.

Browns Ferry Unit 1 Cycle 11 Page 32 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 Table 4.8 Startup Operation MCPRP Limits for Table 3.1 Temperature Range 1 for ATRIUM-10: Nominal Scram Time Basis*

BOC BOC BOC Pow er to to to End of

(% of rated)

NEOC EOCLB Coast 100 1.49 1.49 1.49 75 1.62 1.62 1.62 65 1.75 1.77 1.77 50 50 2.06 2.06 2.06 40 2.35 2.35 2.35 30 2.74 2.74 2.74 30 at > 50%F 2.74 2.74 2.74 25 at > 50%F 2.92 2.92 2.92 30 at 50%F 2.74 2.74 2.74 25 at 50%F 2.85 2.85 2.85 100 1.51 1.52 1.52 75 1.66 1.66 1.66 65 1.75 1.77 1.77 50 50 2.06 2.06 2.06 40 2.35 2.35 2.35 30 2.74 2.74 2.74 30 at > 50%F 3.15 3.15 3.15 25 at > 50%F 3.48 3.48 3.48 30 at 50%F 3.03 3.03 3.03 25 at 50%F 3.46 3.46 3.46 Operating Condition TBVIS TBVOOS

  • Limits support RPTOOS operation; operation is supported for any combination of 1 MSRVOOS, up to 2 TIPOOS (or the equivalent number of TIP channels), and up to 50% of the LPRMs out-of-service.

Limits are applicable for all other EOOS scenarios, apart from TBV.

Limits are only valid up to 50% rated core power.

Browns Ferry Unit 1 Cycle 11 Page 33 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 Table 4.9 Startup Operation MCPRP Limits for Table 3.1 Temperature Range 1 for GE 14: Nominal Scram Time Basis*

BOC BOC BOC Pow er to to to End of

(% of rated)

NEOC EOCLB Coast 100 1.51 1.53 1.53 75 1.66 1.66 1.66 65 1.78 1.78 1.78 50 50 2.13 2.13 2.13 40 2.42 2.42 2.42 30 2.83 2.83 2.83 30 at > 50%F 2.83 2.83 2.83 25 at > 50%F 3.03 3.03 3.03 30 at 50%F 2.83 2.83 2.83 25 at 50%F 2.95 2.95 2.95 100 1.54 1.57 1.57 75 1.69 1.70 1.70 65 1.78 1.80 1.80 50 50 2.13 2.13 2.13 40 2.42 2.42 2.42 30 2.83 2.83 2.83 30 at > 50%F 3.21 3.21 3.21 25 at > 50%F 3.55 3.55 3.55 30 at 50%F 3.11 3.11 3.11 25 at 50%F 3.55 3.55 3.55 Operating Condition TBVIS TBVOOS

  • Limits support RPTOOS operation; operation is supported for any combination of 1 MSRVOOS, up to 2 TIPOOS (or the equivalent number of TIP channels), and up to 50% of the LPRMs out-of-service.

Limits are applicable for all other EOOS scenarios, apart from TBV.

Limits are only valid up to 50% rated core power.

Browns Ferry Unit 1 Cycle 11 Page 34 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 Table 4.10 Startup Operation MCPRP Limits for Table 3.1 Temperature Range 2 for ATRIUM-10: Nominal Scram Time Basis*

BOC BOC BOC Pow er to to to End of

(% of rated)

NEOC EOCLB Coast 100 1.49 1.49 1.49 75 1.62 1.62 1.62 65 1.75 1.77 1.77 50 50 2.07 2.07 2.07 40 2.36 2.36 2.36 30 2.76 2.76 2.76 30 at > 50%F 2.76 2.76 2.76 25 at > 50%F 2.98 2.98 2.98 30 at 50%F 2.76 2.76 2.76 25 at 50%F 2.87 2.87 2.87 100 1.51 1.52 1.52 75 1.66 1.66 1.66 65 1.75 1.77 1.77 50 50 2.07 2.07 2.07 40 2.36 2.36 2.36 30 2.76 2.76 2.76 30 at > 50%F 3.16 3.16 3.16 25 at > 50%F 3.49 3.49 3.49 30 at 50%F 3.04 3.04 3.04 25 at 50%F 3.47 3.47 3.47 Operating Condition TBVIS TBVOOS

  • Limits support RPTOOS operation; operation is supported for any combination of 1 MSRVOOS, up to 2 TIPOOS (or the equivalent number of TIP channels), and up to 50% of the LPRMs out-of-service.

Limits are applicable for all other EOOS scenarios, apart from TBV.

Limits are only valid up to 50% rated core power.

Browns Ferry Unit 1 Cycle 11 Page 35 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 Table 4.11 Startup Operation MCPRP Limits for Table 3.1 Temperature Range 2 for GE 14: Nominal Scram Time Basis*

BOC BOC BOC Pow er to to to End of

(% of rated)

NEOC EOCLB Coast 100 1.51 1.53 1.53 75 1.66 1.66 1.66 65 1.78 1.78 1.78 50 50 2.14 2.14 2.14 40 2.43 2.43 2.43 30 2.84 2.84 2.84 30 at > 50%F 2.84 2.84 2.84 25 at > 50%F 3.05 3.05 3.05 30 at 50%F 2.84 2.84 2.84 25 at 50%F 2.96 2.96 2.96 100 1.54 1.57 1.57 75 1.69 1.70 1.70 65 1.78 1.80 1.80 50 50 2.14 2.14 2.14 40 2.43 2.43 2.43 30 2.84 2.84 2.84 30 at > 50%F 3.22 3.22 3.22 25 at > 50%F 3.57 3.57 3.57 30 at 50%F 3.13 3.13 3.13 25 at 50%F 3.57 3.57 3.57 Operating Condition TBVIS TBVOOS

  • Limits support RPTOOS operation; operation is supported for any combination of 1 MSRVOOS, up to 2 TIPOOS (or the equivalent number of TIP channels), and up to 50% of the LPRMs out-of-service.

Limits are applicable for all other EOOS scenarios, apart from TBV.

Limits are only valid up to 50% rated core power.

Browns Ferry Unit 1 Cycle 11 Page 36 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 Table 4.12 Startup Operation MCPRP Limits for Table 3.1 Temperature Range 1 for ATRIUM-10: Technical Specification Scram Time Basis*

BOC BOC BOC Pow er to to to End of

(% of rated)

NEOC EOCLB Coast 100 1.51 1.51 1.51 75 1.64 1.64 1.64 65 1.76 1.79 1.79 50 50 2.09 2.09 2.09 40 2.39 2.39 2.39 30 2.79 2.79 2.79 30 at > 50%F 2.79 2.79 2.79 25 at > 50%F 2.92 2.92 2.92 30 at 50%F 2.79 2.79 2.79 25 at 50%F 2.85 2.85 2.85 100 1.54 1.54 1.54 75 1.67 1.67 1.67 65 1.76 1.79 1.79 50 50 2.09 2.09 2.09 40 2.39 2.39 2.39 30 2.79 2.79 2.79 30 at > 50%F 3.15 3.15 3.15 25 at > 50%F 3.48 3.48 3.48 30 at 50%F 3.03 3.03 3.03 25 at 50%F 3.46 3.46 3.46 Operating Condition TBVIS TBVOOS

  • Limits support RPTOOS operation; operation is supported for any combination of 1 MSRVOOS, up to 2 TIPOOS (or the equivalent number of TIP channels), and up to 50% of the LPRMs out-of-service.

Limits are applicable for all other EOOS scenarios, apart from TBV.

Limits are only valid up to 50% rated core power.

Browns Ferry Unit 1 Cycle 11 Page 37 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 Table 4.13 Startup Operation MCPRP Limits for Table 3.1 Temperature Range 1 for GE 14: Technical Specification Scram Time Basis*

BOC BOC BOC Pow er to to to End of

(% of rated)

NEOC EOCLB Coast 100 1.54 1.54 1.54 75 1.67 1.67 1.67 65 1.79 1.80 1.80 50 50 2.17 2.17 2.17 40 2.46 2.46 2.46 30 2.87 2.87 2.87 30 at > 50%F 2.87 2.87 2.87 25 at > 50%F 3.03 3.03 3.03 30 at 50%F 2.87 2.87 2.87 25 at 50%F 2.95 2.95 2.95 100 1.57 1.57 1.57 75 1.70 1.70 1.70 65 1.80 1.81 1.81 50 50 2.17 2.17 2.17 40 2.46 2.46 2.46 30 2.87 2.87 2.87 30 at > 50%F 3.21 3.21 3.21 25 at > 50%F 3.55 3.55 3.55 30 at 50%F 3.11 3.11 3.11 25 at 50%F 3.55 3.55 3.55 Operating Condition TBVIS TBVOOS

  • Limits support RPTOOS operation; operation is supported for any combination of 1 MSRVOOS, up to 2 TIPOOS (or the equivalent number of TIP channels), and up to 50% of the LPRMs out-of-service.

Limits are applicable for all other EOOS scenarios, apart from TBV.

Limits are only valid up to 50% rated core power.

Browns Ferry Unit 1 Cycle 11 Page 38 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 Table 4.14 Startup Operation MCPRP Limits for Table 3.1 Temperature Range 2 for ATRIUM-10: Technical Specification Scram Time Basis*

BOC BOC BOC Pow er to to to End of

(% of rated)

NEOC EOCLB Coast 100 1.51 1.51 1.51 75 1.64 1.64 1.64 65 1.76 1.79 1.79 50 50 2.10 2.10 2.10 40 2.40 2.40 2.40 30 2.80 2.80 2.80 30 at > 50%F 2.80 2.80 2.80 25 at > 50%F 2.98 2.98 2.98 30 at 50%F 2.80 2.80 2.80 25 at 50%F 2.87 2.87 2.87 100 1.54 1.54 1.54 75 1.67 1.67 1.67 65 1.76 1.79 1.79 50 50 2.10 2.10 2.10 40 2.40 2.40 2.40 30 2.80 2.80 2.80 30 at > 50%F 3.16 3.16 3.16 25 at > 50%F 3.49 3.49 3.49 30 at 50%F 3.04 3.04 3.04 25 at 50%F 3.47 3.47 3.47 Operating Condition TBVIS TBVOOS

  • Limits support RPTOOS operation; operation is supported for any combination of 1 MSRVOOS, up to 2 TIPOOS (or the equivalent number of TIP channels), and up to 50% of the LPRMs out-of-service.

Limits are applicable for all other EOOS scenarios, apart from TBV.

Limits are only valid up to 50% rated core power.

Browns Ferry Unit 1 Cycle 11 Page 39 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 Table 4.15 Startup Operation MCPRP Limits for Table 3.1 Temperature Range 2 for GE 14: Technical Specification Scram Time Basis*

BOC BOC BOC Pow er to to to End of

(% of rated)

NEOC EOCLB Coast 100 1.54 1.54 1.54 75 1.67 1.67 1.67 65 1.79 1.80 1.80 50 50 2.18 2.18 2.18 40 2.47 2.47 2.47 30 2.89 2.89 2.89 30 at > 50%F 2.89 2.89 2.89 25 at > 50%F 3.05 3.05 3.05 30 at 50%F 2.89 2.89 2.89 25 at 50%F 2.96 2.96 2.96 100 1.57 1.57 1.57 75 1.70 1.70 1.70 65 1.80 1.81 1.81 50 50 2.18 2.18 2.18 40 2.47 2.47 2.47 30 2.89 2.89 2.89 30 at > 50%F 3.22 3.22 3.22 25 at > 50%F 3.57 3.57 3.57 30 at 50%F 3.13 3.13 3.13 25 at 50%F 3.57 3.57 3.57 Operating Condition TBVIS TBVOOS

  • Limits support RPTOOS operation; operation is supported for any combination of 1 MSRVOOS, up to 2 TIPOOS (or the equivalent number of TIP channels), and up to 50% of the LPRMs out-of-service.

Limits are applicable for all other EOOS scenarios, apart from TBV.

Limits are only valid up to 50% rated core power.

Browns Ferry Unit 1 Cycle 11 Page 40 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 Table 4.16 MCPRP Limits for ATRIUM-10: Single Loop Operation for All Scram Times*

BOC to Pow er End of

(% of rated)

Coast 100 2.04 50 2.04 40 2.18 30 2.51 30 at > 50%F 2.51 25 at > 50%F 2.68 30 at 50%F 2.51 25 at 50%F 2.62 100 2.04 50 2.04 40 2.18 30 2.51 30 at > 50%F 3.02 25 at > 50%F 3.34 30 at 50%F 2.87 25 at 50%F 3.26 100 2.11 50 2.11 40 2.41 30 2.81 30 at > 50%F 3.17 25 at > 50%F 3.50 30 at 50%F 3.05 25 at 50%F 3.48 100 2.12 50 2.12 40 2.42 30 2.82 30 at > 50%F 3.18 25 at > 50%F 3.51 30 at 50%F 3.06 25 at 50%F 3.49 Operating Condition RCPOOS FHOOS RCPOOS TBVOOS PLUOOS FHOOS RCPOOS TBVOOS FHOOS1 RCPOOS TBVOOS FHOOS2

  • All limits, including Base Case, support RPTOOS operation; operation is supported for any combination of 1 MSRVOOS, up to 2 TIPOOS (or the equivalent number of TIP channels), and up to 50% of the LPRMs out-of-service.

FFWTR and FHOOS assume the same value of temperature drop.

RCPOOS limits are only valid up to 50% rated core power, 50% rated core flow, and an active recirculation drive flow of 17.73 Mlbm/hr.

Browns Ferry Unit 1 Cycle 11 Page 41 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 Table 4.17 MCPRP Limits for GE-14: Single Loop Operation for All Scram Times*

BOC to Pow er End of

(% of rated)

Coast 100 2.00 50 2.00 40 2.24 30 2.59 30 at > 50%F 2.59 25 at > 50%F 2.78 30 at 50%F 2.59 25 at 50%F 2.70 100 2.01 50 2.01 40 2.24 30 2.59 30 at > 50%F 3.08 25 at > 50%F 3.38 30 at 50%F 2.95 25 at 50%F 3.35 100 2.19 50 2.19 40 2.48 30 2.89 30 at > 50%F 3.23 25 at > 50%F 3.57 30 at 50%F 3.13 25 at 50%F 3.57 100 2.20 50 2.20 40 2.49 30 2.91 30 at > 50%F 3.24 25 at > 50%F 3.59 30 at 50%F 3.15 25 at 50%F 3.59 Operating Condition RCPOOS FHOOS RCPOOS TBVOOS PLUOOS FHOOS RCPOOS TBVOOS FHOOS1 RCPOOS TBVOOS FHOOS2

  • All limits, including Base Case, support RPTOOS operation; operation is supported for any combination of 1 MSRVOOS, up to 2 TIPOOS (or the equivalent number of TIP channels), and up to 50% of the LPRMs out-of-service.

FFWTR and FHOOS assume the same value of temperature drop.

RCPOOS limits are only valid up to 50% rated core power, 50% rated core flow, and an active recirculation drive flow of 17.73 Mlbm/hr.

Browns Ferry Unit 1 Cycle 11 Page 42 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 5 Oscillation Power Range Monitor (OPRM) Setpoint (Technical Specification 3.3.1.1)

Technical Specification Table 3.3.1.1-1, Function 2f, identifies the OPRM upscale function.

Instrument setpoints are established, such that the reactor will be tripped before an oscillation can grow to the point where the SLMCPR is exceeded. An Option III stability analysis is performed for each reload core to determine allowable OLMCPRs as a function of OPRM setpoint. Analyses consider both steady state startup operation, and the case of a two recirculation pump trip from rated power.

The resulting stability based OLMCPRs are reported in Reference 1. The OPRM setpoint (sometimes referred to as the Amplitude Trip, Sp) is selected, such that required margin to the SLMCPR is provided without stability being a limiting event. Analyses are based on cycle specific DIVOM analyses performed per Reference 26. The calculated OLMCPRs are shown in Table 5.1. Review of results shown in COLR Table 4.2 and Table 4.3 indicates an OPRM setpoint of 1.14 may be used. The successive confirmation count (sometimes referred to as Np) is provided in Table 5.2, per Reference 31.

Table 5.1 OPRM Setpoint Range*

Table 5.2 OPRM Successive Confirmation Count Setpoint OPRM OLMCPR OLMCPR Setpoint (SS)

(2PT) 1.05 1.18 1.23 1.06 1.20 1.24 1.07 1.22 1.26 1.08 1.24 1.28 1.09 1.26 1.30 1.10 1.28 1.33 1.11 1.30 1.35 1.12 1.32 1.37 1.13 1.34 1.39 1.14 1.36 1.41 1.15 1.39 1.44 Count 6

1.04 8

1.05 10 1.07 12 1.09 14 1.11 16 1.14 18 1.18 20 1.24 OPRM Setpoint

  • Extrapolation beyond a setpoint of 1.15 is not allowed Browns Ferry Unit 1 Cycle 11 Page 43 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 6 APRM Flow Biased Rod Block Trip Settings (Technical Requirements Manual Section 5.3.1 and Table 3.3.4-1)

The APRM rod block trip setting is based upon References 27 & 28, and is defined by the following:

SRB (0.66(W-W) + 61%)

Allowable Value SRB (0.66(W-W) + 59%)

Nominal Trip Setpoint (NTSP) where:

SRB

=

Rod Block setting in percent of rated thermal power (3458 MWt)

W

=

Loop recirculation flow rate in percent of rated W

=

Difference between two-loop and single-loop effective recirculation flow at the same core flow (W=0.0 for two-loop operation)

The APRM rod block trip setting is clamped at a maximum allowable value of 115%

(corresponding to a NTSP of 113%).

Browns Ferry Unit 1 Cycle 11 Page 44 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 7 Rod Block Monitor (RBM) Trip Setpoints and Operability (Technical Specification Table 3.3.2.1-1)

The RBM trip setpoints and applicable power ranges, based on References 27 & 28, are shown in Table 7.1. Setpoints are based on an HTSP, unfiltered analytical limit of 114%. Unfiltered setpoints are consistent with a nominal RBM filter setting of 0.0 seconds; filtered setpoints are consistent with a nominal RBM filter setting less than 0.5 seconds. Cycle specific CRWE analyses of OLMCPR are documented in Reference 1, superseding values reported in References 27, 28, and 30.

Table 7.1 Analytical RBM Trip Setpoints*

RBM Trip Setpoint Allowable Value (AV)

Nominal Trip Setpoint (NTSP)

LPSP 27%

25%

IPSP 62%

60%

HPSP 82%

80%

LTSP - unfiltered

- filtered 121.7%

120.7%

120.0%

119.0%

ITSP - unfiltered

- filtered 116.7%

115.7%

115.0%

114.0%

HTSP - unfiltered

- filtered 111.7%

110.9%

110.0%

109.2%

DTSP 90%

92%

As a result of cycle specific CRWE analyses, RBM setpoints in Technical Specification Table 3.3.2.1-1 are applicable as shown in Table 7.2. Cycle specific setpoint analysis results are shown in Table 7.3, per Reference 1.

Table 7.2 RBM Setpoint Applicability Thermal Power

(% Rated)

Applicable MCPR Notes from Table 3.3.2.1-1 Comment

> 27% and < 90%

< 1.70 (a), (b), (f), (h) two loop operation

< 1.74 (a), (b), (f), (h) single loop operation 90%

< 1.43 (g) two loop operation

  • Values are considered maximums. Using lower values, due to RBM system hardware/software limitations, is conservative, and acceptable.

MCPR values shown correspond with, (support), SLMPCR values identified in Reference 1.

Greater than 90% rated power is not attainable in single loop operation.

Browns Ferry Unit 1 Cycle 11 Page 45 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 Table 7.3 Control Rod Withdrawal Error Results RBM CRWE HTSP Analytical Limit OLMCPR Unfiltered 107 1.28 111 1.31 114 1.36 117 1.40 Results, compared against the base case OLMCPR results of Table 4.2, indicate SLMCPR remains protected for RBM inoperable conditions (i.e., 114% unblocked).

Browns Ferry Unit 1 Cycle 11 Page 46 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)

EDMS: L32 150813 800 NPG Reactor Engineering and Fuels - BWRFE 1101 Market Street, Chattanooga TN 37402 Date: August 13, 2015 8 Shutdown Margin Limit (Technical Specification 3.1.1)

Assuming the strongest OPERABLE control blade is fully withdrawn, and all other OPERABLE control blades are fully inserted, the core shall be sub-critical and meet the following minimum shutdown margin:

SDM > 0.38% dk/k Browns Ferry Unit 1 Cycle 11 Page 47 Core Operating Limits Report, (105% OLTP)

TVA-COLR-BF1C11, Revision 2 (Final)