HNP-15-060, License Amendment Request to Revise Technical Specification Table 3.3-4 Loss of Offsite Power 6.9 Kv Emergency Undervoltage Primary Setpoints Implementation

From kanterella
(Redirected from ML15181A007)
Jump to navigation Jump to search

License Amendment Request to Revise Technical Specification Table 3.3-4 Loss of Offsite Power 6.9 Kv Emergency Undervoltage Primary Setpoints Implementation
ML15181A007
Person / Time
Site: Harris 
(NPF-063)
Issue date: 06/30/2015
From: Waldrep B
Duke Energy Progress
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
HNP-15-060, TAC MF4294
Download: ML15181A007 (2)


Text

(-,DUKE ENERGY Serial: HNP-15-060 June 30,2015 ATTN: Document Control Desk U.S. Nuclear Regulatory Commission Washington, DC 20555-0001 Shearon Harris Nuclear pOWERpLANT,Unit 1 Docket No. 50-400/rENEWEDLicense No. npf-63 Benjamin C. Waldrep Vice President Harris Nuclear Plant 5413 sHEARONHarris Road New Hill NC 27562-9300 919.362.2000 10 CFR 50.90

Subject:

License Amendment Request to Revise Technical Specification Table 3.3-4 Loss of Offsite pOWER6.9 kV Emergency Undervoltage pRIMARYSetpoints Implementation (TAC No. MF4294)

Ladies and Gentlemen:

By letter dated June 19,2014,Duke Energy pROGRESS,iNC.(Duke Energy), requested an amendment to the Technical Specifications (TSs) for Shearon Harris Nuclear pOWERpLANT, Unit 1 (ADAMS Accession No. ML14174A118). Duke Energy proposed to revise TS 3.3.2, "Engineered Safety Features Actuation System Instrumentation," Table 3.3-4, "Engineered Safety Features Actuation System Instrumentation Trip Setpoints." Specifically, the Functional Unit 9.a, Loss of Offsite pOWER6.9 kV Emergency Bus Undervoltage Primary,instrument trip setpoint and associated allowable value are being revised to correct a non-conservative TS.

The letter above requested that the amendment be implemented within 120days of approval.

The proposed implementation schedule was based upon making field changes with the plant online during power operations. Duke Energy has determined that implementing the field changes online may introduce the risk of a plant trip, which would be averted by implementing the field changes during a refueling outage. Therefore, Duke Energy requests that the amendment be implemented by November 30,2016,which will allow the field changes to be made during the scheduled Fall 2016refueling outage.

The requested change to the implementation period does not impact the validity of the original Significant Hazards Consideration or the Environmental Consideration.

This document contains no new Regulatory Commitments.

U.S. Nuclear Regulatory Commission HNP-15-060 Page2 Please refer any questions regarding this submittal to John Caves at (919) 362-2406.

I declare under penalty of perjury that the foregoing is true and correct.

Executed on June 30, 2015.

Sincerely,

~ t.V..ff Benjamin C. Waldrep cc:

Mr. J.D. Austin, NRC Sr. Resident Inspector, HNP (email)

Mr. W. L. Cox, Ill, Radiation Protection Section Chief, N.C. DHSR (email)

Ms. M. Barillas, NRC Project Manager, HNP (email)

Mr. V. M. McCree, NRC Regional Administrator, Region II (EIE)