ULNRC-06200, Supplement to Licensing Document Change Notice (LDCN)12-0014 Application to Revise Technical Specification to Adopt TSTF-510, Revision to Steam Generator Program Inspection Frequencies and Tube Sample Selection, Using Consolidated

From kanterella
(Redirected from ML15098A575)
Jump to navigation Jump to search

Supplement to Licensing Document Change Notice (LDCN)12-0014 Application to Revise Technical Specification to Adopt TSTF-510, Revision to Steam Generator Program Inspection Frequencies and Tube Sample Selection, Using Consolidated
ML15098A575
Person / Time
Site: Callaway 
Issue date: 04/08/2015
From: Maglio S
Ameren Missouri, Union Electric Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
TSTF-510, ULNRC-06200
Download: ML15098A575 (38)


Text

~~

WAmeren MISSOURI Callaway Plant April 8, 2015 ULNRC-06200 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555-0001 Ladies and Gentlemen:

10 CFR 50.90 DOCKET NUMBER 50-483 CALLA WAY PLANT UNIT 1 UNION ELECTRIC CO.

FACILITY OPERATING LICENSE NPF-30 SUPPLEMENT TO LICENSING DOCUMENT CHANGE NOTICE (LDCN) 14-0014 APPLICATION TO REVISE TECHNICAL SPECIFICATIONS TO ADOPT TSTF -510, "REVISION TO STEAM GENERA TOR PROGRAM INSPECTION FREQUENCIES AND TUBE SAMPLE SELECTION," USING THE CONSOLIDATED LINE ITEM IMPROVEMENT PROCESS (CLIIP)

Reference:

1) Ameren Missouri Letter ULNRC-06174, "Application to Revise Technical Specifications to Adopt TSTF-510, 'Revision to Steam Generator Program Inspection Frequencies and Tube Sample Selection,' Using the Consolidated Line Item Improvement Process (CLIIP)," dated March 9, 2015 (Accession No. ML15068A422)

Pursuant to 10 CFR 50.90, Union Electric Company (Ameren Missouri) recently transmitted a request (Reference 1) for revising the Technical Specifications in order to adopt TSTF -510, "Revision to Steam Generator Program Inspection Frequencies and Tube Sample Selection," using the Consolidated Line Item Improvement Process (CLIIP). Subsequent to submittal of the license amendment request, it was identified that some wording was inadvertently omitted from the text of the proposed revision of Technical Specification (TS) 5.5.9, "Steam Generator (SG) Program."

PO Box 620 Fulton, MD 65251 AmerenMissouri.com **************

ULNRC-06200 April 8, 2015 Page2 In addition to the above, further review of the submittal identified some additional minor inconsistencies with TSTF -510 (Revision 2) and other minor errors of a typographical or editorial nature. For correction of these and the above, two attachments to the enclosure that were provided with the original submittal are to be revised and re-submitted. Accordingly, Attachment 1, "Technical Specification Page Markups," and Attachment 3, "Retyped Technical Specification Pages," as provided in the original submittal, are herewith revised and re-submitted as Attachments 1 and 2 to this letter, respectively.

Correcting the noted inconsistencies and minor errors requires changes to be made to the text of the affected Technical Specifications or to what was proposed to be changed for those Technical Specifications, as originally presented in Attachments 1 and/or 3 of the original submittal. The changes include adding the phrase "and that may satisfy the applicable tube plugging criteria" to the third sentence in proposed TS 5.5.9.d.2, as well as removing the word "active" from TS 5.6.10.e.

Additional items include the removal of several double spaces between words, as well as the use of a hyphenated form of"in-service" in TS 5.5.9.b.l, and making grammatical improvements toTS 5.6.10 by removing the second instance of "the" and putting "Steam Generator (SG) Program" in quotes.

Correction of these inconsistencies is reflected in the attached.

The Callaway Onsite Review Committee has reviewed and approved the changes proposed in this supplement to the amendment request and has approved the submittal thereof. In addition, in accordance with 10 CPR 50.91 "Notice for public comment: State consultation," Section (b)(l), a copy of this supplement to the amendment application is being provided to the designated Missouri State official.

This supplement to the amendment request involves no changes to the 10 CPR 50.92 (Basis for No Significant Hazards) evaluation or the environmental evaluation provided in Reference 1, nor does it contain new commitments. If there are any questions regarding this submittal, please contact Mr. Tom Elwood at 314-225-1905.

I declare under penalty of perjury that the foregoing is true and correct.

Very truly yours, Executed on: Lt l ~ f 2fJ 16

,(}[)ott~

Scott Maglio Manager, Regulatory Affairs DRB/nls

ULNRC-06200 April 8, 2015 Page 3 Attachments:

1-Technical Specification Page Markups 2-Retyped Technical Specification Pages

ULNRC-06200 April 8, 2015 Page4 cc:

Mr. Marc L. Dapas Regional Administrator U.S. Nuclear Regulatory Commission Region IV 1600 East Lamar Boulevard Arlington, TX 76011-4511 Senior Resident Inspector Callaway Resident Office U.S. Nuclear Regulatory Commission 8201 NRC Road Steedman, MO 65077 Mr. Fred Lyon Project Manager, Callaway Plant Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission Mail Stop 0-8B 1 Washington, DC 20555-2738

ULNRC-06200 April 8, 2015 Page 5 Index and send hardcopy to QA File A160.0761 Hardcopy:

Certrec Corporation 4150 International Plaza Suite 820 Fort Worth, TX 76109 (Certrec receives ALL attachments as long as they are non-safeguards and may be publicly disclosed.)

Electronic distribution for the following can be made via Tech Spec ULNRC Distribution:

F. M. Diya T. E. Herrmann D. W. Neterer L. H. Graessle B.L.Cox L. H. Kanuckel S. A. Maglio T. B. Elwood Corporate Communications NSRB Secretary T. A. Witt STARS Regulatory Affairs Mr. John O'Neill (Pillsbury Winthrop Shaw Pittman LLP)

Missouri Public Service Commission Ms. Leanne Tippett-Mosby (DNR) to ULNRC-06200 Page 1 of8 ATTACHMENT 1 TECHNICAL SPECIFICATION PAGE MARKUPS

3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.17 Steam Generator (SG) Tube Integrity LCO 3.4.17 SG tube integrity shall be maintained.

SG Tube Integrity 3.4.17 AND

//1_1'(}

All SG tubes satisfying the tube Fe~eir criteria shall be plugged in accordance with Steam Generator Program.

APPLICABIUTY:

MODES 1 2, 3, and 4.

ACTIONS


NOTE -----------------------------------------

Separate Condition entry is allowed for each SG tube.

CONDITION A

One or more SG tubes A.1 satisfying the tube ~

f / ~'I 1~

criteria and not plugged in (T 0 accordance with the Steam Generator Program.

CALLAWAY PLANT AND A.2 REQUIRED ACTION Verify tube integrity of the affected tube(s) is maintained until the next

  • refueling outage or inspection.

Plug the affected tube(s) in accordance with the Steam Generator Program.

3.4-42 COMPLETION TIME 7 days Prior to entering MODE 4 following the next refueling outage or SG tube inspection (contmued)

Amendment No. 168

SG Tube Integrity 3.4.17 SURVEILLANCE REQUIREMENTS SR 3.4.17.1 SR 3.4.17.2 CALLAWAY PLANT SURVEILLANCE FREQUENCY Verify SG tube integrity in accordance with the Steam In accordance with Generator Program.

the Steam Generator Program Verify that each inspected SG tube that satisfies the tube riteria is plugged in accordance with the Steam Ge erator Program.

3.4-44 Prior to entering MODE 4 following a SG tube inspection Amendment No. 168

5.5 Programs and Manuals (continued) 5.5.8 lnservice Testing Program Programs and Manuals 5.5 This program provides controls for inservice testing of ASME Code Class 1, 2, and 3 components. The program shall include the following:

a.

Testing frequencies applicable to the ASME Code for Operation and Maintenance of Nuclear Power Plants (ASME OM Code) and applicable Addenda as follows:

ASME OM Code and applicable Addenda terminology for inservice testing activities Weekly Monthly Quarterly or every 3 months Semiannually or every 6 months Every 9 months Yearly or annually Biennially or every 2 years Required Frequencies for performing inservice testing activities At least once per 7 days At least once per 31 days At least once per 92 days At least once per 184 days At least once per 276 days At least once per 366 days At least once per 731 days

b.

The provisions of SR 3.0.2 are applicable to the above required Frequencies and to other normal and accelerated Frequencies specified as 2 years or less in the lnservice Testing Program for performing inservice testing activities;

c.

The provisions of SR 3.0.3 are applicable to inservice testing activities; and

d.

Nothing in the ASME OM Code shall be construed to supersede the requirements of any TS.

5.5.9 Steam Generator (SGl Program A Steam Generator Program shall be established and implemented to ensure that SG tube integrity is maintained. In addition, the Steam Generator Program shall include the following~j!!IFevieieRs:

a.

Provisions for condition monitoring assessments. Condition monitoring assessment means an evaluation of the "as found" condition of the tubing (continued)

CALLAWAY PLANT 5.0-10 Amendment 187

Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.9 Steam Generator (SG) Program (continued) with respect to the performance criteria for structural integrity and accident induced leakage. The "as found" condition refers to the condition of the tubing during a SG inspection outage, as determined from the inservice inspection results or by other means, prior to the plugging of tubes.

Condition monitoring assessments shall be conducted during each outage during which the SG tubes are inspected or plugged to confirm that the performance criteria are being met.

b.

Performance criteria for SG tube integrity. SG tube integrity shall be maintained by meeting the performance criteria for tube structural integrity, accident induced leakage, and operational LEAKAG.

CALLAWAY PLANT lf1-Se.Yv1

1.

Structural integrity performance c:liiritteeirinOionii::lAijl~!!t6f:l~a..~

generator tubes shall retain structural integn y o\\l r the full range of normal operating conditions (including startu, operation in the power range, hot standby, and cooldow~.aA1 II anticipated transients included in the design specifica\\io and design basis accidents. This includes retaining a safety fac or of 3.0 (3DP) against burst under normal steady state full power operation primary-to-secondary pressure differential and a safety factor of 1.4 against burst applied to the design basis accident primary-to-secondary pressure differentials. Apart from the above requirements, additional loading conditions associated with the design basis accidents, or combination of accidents in accordance with the design and licensing basis, shall also be evaluated to determine if the associated loads contribute significantly to burst or collapse. In the assessment of tube integrity, those loads that do significantly affect burst or collapse shall be determined and assessed in combination with the loads due to pressure with a safety factor of 1.2 on the combined primary loads and 1.0 on axial secondary loads.

2.

Accident induced leakage performance criterion: The primary to secondary accident induced leakage rate for any design basis accident, other than a SG tube rupture, shall not exceed the leakage rate assumed in the accident analysis in terms of total leakage rate for all SGs and leakage rate for an individual SG.

Leakage is not to exceed 1 gpm total for all four steam generators.

3.

The operational LEAKAGE performance criterion is specified in LCO 3.4.13, "RCS Operational LEAKAGE."

(continued) 5.0-11 Amendment 187 I

Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.9 Steam Generator <SGl Program

c.

Provisions for SG tube riteria. Tubes fou by inservice inspection to contain flaws with a depth equal to or excee ng 40% of the nominal tube wall thickness shall be plugged.

d.

Provisions for SG tube inspections. Perio c SG tube inspections shall be performed. The number and portions of e tubes inspected and methods of inspection shall be performed with th objective of detecting flaws of any type (e.g., volumetric flaws, axial d circumferential cracks) that may be present along the length of the tub, from the tube-to-tubesheet weld at the tube inlet to the tube-to-tubesh et weld at the tube outlet, and that may satisfy the applicable tube

  • criteria. The tube-to-tubesheet weld is not part of the tube. In addition to meeting the requirements of d.1, d.2, and d.3 below, the inspection scope, inspection methods, and inspection intervals shall be such as to ensure that SG tube integrity is maintained until the next SG inspection. l\\R asseee"'ent of degradation t'I.SSesr11l&r/-

shall be performed to determine the type and location of flaws to which the tubes may be susceptible and, based on this assessment, to determine which inspection methods need to be employed and at what locations.

1.

Inspect 100% of the tubes in each SG durina thr first refueling outage following SG J"&plaseFReP'It. 1/Js.J-e,./t,;,h"Dn,

e.

Provisions for monitoring operational primary to sec (cont1nue CALLAWAY PLANT 5.0-12

INSERT 5.5.9.d.2

2.

After the first refueling outage following SG installation, inspect each SG at least every 72 effective full power months or at least every third refueling outage (whichever results in more frequent inspections). In addition, the minimum number of tubes inspected at each scheduled inspection shall be the number of tubes in all SGs divided by the number ofSG inspection outages scheduled in each inspection period as defmed in a, b, c and d below. If a degradation assessment indicates the potential for a type of degradation to occur at a location a nJ -f htit not previously inspected with a technique capable of detecting this type of iisff degradation at this locaho~ the minimum number of locations inspected with h"'.sa.

such a capable inspection {~chnique during the remainder of the inspection period 1

  • "';.~ t may be prorated. The fraction of locations to be inspected for this potential type

.-f; ne a, f f¥' 1 e of degradation at this location at the end of the inspection period shaH be no less f

I than the ratio of the number of times the SG is scheduled to be inspected in the

"'lJ e r.e. fC1t Y inspection period after the detennination that a new form of degradation could C y.j fe.YIC<..

potentially be occurring at this location divided by the total number of times the SG is scheduled to be inspected in the inspection period. Each inspection period defmed below may be extended up to 3 effective full power months to include a SG inspection outage in an inspection period and the subsequent inspection period begins at the conclusion of the included SG inspection outage.

a)

After the first refueling outage following SG installation, inspect 100% of the tubes during the next 144 effective full power months. This constitutes the first inspection period; b)

During the next 120 effective full power months, inspect 100% of the tubes. This constitutes the second inspection period; c)

During the next 96 effective full power months, inspect 100% of the tubes.

This constitutes the third inspection period; and d)

During the remaining life of the SGs, inspect 100% of the tubes every 72 effective full power months. This constitutes the fourth and subsequent inspection periods.

LDC. tJ I LJ -oo llf Reporting Requirements 5.6 5.6 Reporting Requirements (continued) 5.6.10 Steam Generator Tube lnsoection Report A report shall be submitted within 180 days after the initial entry into MODE 4 following completi~(l of an inspection performed in accordance with~

Specification 5,5.9."5team Generator (SG) Program.rhe report shall include:

a.

The scope of inspections performed on each SG;

b.

~fegradation mechanisms found;

c.

Nondestructive examination techniques utilized for each degradation mechanism;

d.

location. orientation (if linear). and measured sizes (if available) of service induced indications;

e.

Number of tubes plugged during the inspection outage for each asti*te degradation mechanism;

f.

Tetal RW~Iasr &AS fJ8FS8RlaS8 gf tw9&& ph:4iJ§J&a tg dale; eu id The results of condition monitoring, including the results of tube pulls and in-situ testing.

CALLAWAY PLANT 5.0-26 Amendment190 1 to ULNRC-06200 Page 1 of25 ATTACHMENT 2 RETYPED TECHNICAL SPECIFICATION PAGES

3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.17 Steam Generator (SG) Tube Integrity LCO 3.4.17 SG tube integrity shall be maintained.

SG Tube Integrity 3.4.17 All SG tubes satisfying the tube plugging criteria shall be plugged in accordance with Steam Generator Program.

APPLICABILITY:

MODES 1 2, 3, and 4.

ACTIONS


N 0 T E -----------------------------------------------------------

Separate Condition entry is allowed for each SG tube.

CONDITION A.

One or more SG tubes A.1 satisfying the tube plugging criteria and not plugged in accordance with the Steam Generator Program.

CALLAWAY PLANT AND A.2 REQUIRED ACTION COMPLETION TIME Verify tube integrity of 7 days the affected tube(s) is maintained until the next refueling outage or inspection.

Plug the affected tube(s) in accordance with the Steam Generator Program.

3.4-43 Prior to entering MODE 4 following the next refueling outage or SG tube inspection (contmued)

Amendment No.###

SG Tube Integrity 3.4.17 SURVEILLANCE REQUIREMENTS SR 3.4.17.1 SR 3.4.17.2 CALLAWAY PLANT SURVEILLANCE FREQUENCY Verify SG tube integrity in accordance with the Steam In accordance with Generator Program.

the Steam Generator Program Verify that each inspected SG tube that satisfies the tube plugging criteria is plugged in accordance with the Steam Generator Program.

3.4-45 Prior to entering MODE 4 following a SG tube inspection Amendment No. ###

5.5 Programs and Manuals (continued) 5.5.8 lnservice Testing Program Programs and Manuals 5.5 This program provides controls for inservice testing of ASME Code Class 1, 2, and 3 components. The program shall include the following:

a.

Testing frequencies applicable to the ASME Code for Operation and Maintenance of Nuclear Power Plants (ASME OM Code) and applicable Addenda as follows:

ASME OM Code and applicable Addenda terminology for inservice testing activities Weekly Monthly Quarterly or every 3 months Semiannually or every 6 months Every 9 months Yearly or annually Biennially or every 2 years Required Frequencies for performing inservice testing activities At least once per 7 days At least once per 31 days At least once per 92 days At least once per 184 days At least once per 276 days At least once per 366 days At least once per 731 days

b.

The provisions of SR 3.0.2 are applicable to the above required Frequencies and to other normal and accelerated Frequencies specified as 2 years or less in the lnservice Testing Program for performing inservice testing activities;

c.

The provisions of SR 3.0.3 are applicable to inservice testing activities; and

d.

Nothing in the ASME OM Code shall be construed to supersede the requirements of any TS.

5.5.9 Steam Generator CSGl Program A Steam Generator Program shall be established and implemented to ensure that SG tube integrity is maintained. In addition, the Steam Generator Program shall include the following:

a.

Provisions for condition monitoring assessments. Condition monitoring assessment means an evaluation of the lias foundn condition of the tubing (continued)

CALLAWAY PLANT 5.0-10 Amendment ###

Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.9 Steam Generator <SG> Program (continued) with respect to the performance criteria for structural integrity and accident induced leakage. The "as found" condition refers to the condition of the tubing during a SG inspection outage, as determined from the inservice inspection results or by other means, prior to the plugging of tubes.

Condition monitoring assessments shall be conducted during each outage during which the SG tubes are inspected or plugged to confirm that the performance criteria are being met.

b.

Performance criteria for SG tube integrity. SG tube integrity shall be maintained by meeting the performance criteria for tube structural integrity, accident induced leakage, and operational LEAKAGE.

CALLAWAY PLANT

1.

Structural integrity performance criterion: All in-service steam generator tubes shall retain structural integrity over the full range of normal operating conditions (including startup, operation in the power range, hot standby, and cooldown), all anticipated transients included in the design specification, and design basis accidents.

This includes retaining a safety factor of 3.0 (3DP) against burst under normal steady state full power operation primary-to-secondary pressure differential and a safety factor of 1.4 against burst applied to the design basis accident primary-to-secondary pressure differentials. Apart from the above requirements, additional loading conditions associated with the design basis accidents, or combination of accidents in accordance with the design and licensing basis, shall also be evaluated to determine if the associated loads contribute significantly to burst or collapse.

In the assessment of tube integrity, those loads that do significantly affect burst or collapse shall be determined and assessed in combination with the loads due to pressure with a safety factor of 1.2 on the combined primary loads and 1.0 on axial secondary loads.

2.

Accident induced leakage performance criterion: The primary to secondary accident induced leakage rate for any design basis accident, other than a SG tube rupture, shall not exceed the leakage rate assumed in the accident analysis in terms of total leakage rate for all SGs and leakage rate for an individual SG.

Leakage is not to exceed 1 gpm total for all four steam generators.

3.

The operational LEAKAGE performance criterion is specified in LCO 3.4.13, "RCS Operational LEAKAGE."

(continued) 5.0-11 Amendment #II#

Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.9 Steam Generator (SG) Program (continued)

c.

Provisions for SG tube plugging criteria. Tubes found by inservice inspection to contain flaws with a depth equal to or exceeding 40% of the nominal tube wall thickness shall be plugged.

d.

Provisions for SG tube inspections. Periodic SG tube inspections shall be performed. The number and portions of the tubes inspected and methods of inspection shall be performed with the objective of detecting flaws of any type (e.g., volumetric flaws, axial and circumferential cracks) that may be present along the length of the tube, from the tube-to-tubesheet weld at the tube inlet to the tube-to-tubesheet weld at the tube outlet, and that may satisfy the applicable tube plugging criteria. The tube-to-tubesheet weld is not part of the tube. In addition to meeting the requirements of d.1, d.2, and d.3 below, the inspection scope, inspection methods, and inspection intervals shall be such as to ensure that SG tube integrity is maintained until the next SG inspection. A degradation assessment shall be performed to determine the type and location of flaws to which the tubes may be susceptible and, based on this assessment, to determine which inspection methods need to be employed and at what locations.

CALLAWAY PLANT

1.

Inspect 1 00% of the tubes in each SG during the first refueling outage following SG installation.

2.

After the first refueling outage following SG installation, inspect each SG at least every 72 effective full power months or at least every third refueling outage (whichever results in more frequent inspections). In addition, the minimum number of tubes inspected at each scheduled inspection shall be the number of tubes in all SGs divided by the number of SG inspection outages scheduled in each inspection period as defined in a, b, c and d below. If a degradation assessment indicates the potential for a type of degradation to occur at a location not previously inspected with a technique capable of detecting this type of degradation at this location and that may satisfy the applicable tube repair criteria, the minimum number of locations inspected with such a capable inspection technique during the remainder of the inspection period may be prorated. The fraction of locations to be inspected for this potential type of degradation at this location at the end of the inspection period shall be no less than the ratio of the number of times the SG is scheduled to be inspected in the inspection period after the determination that a new form of degradation could potentially be occurring at this location divided by the total number of times the SG is scheduled to be inspected in the inspection (continued) 5.0-12 Amendment ###

Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.9 Steam Generator (SG) Program (continued) period. Each inspection period defined below may be extended up to 3 effective full power months to include a SG inspection outage in an inspection period and the subsequent inspection period begins at the conclusion of the included SG inspection outage.

(a)

After the first refueling outage following SG installation, inspect 1 00% of the tubes during the next 144 effective full power months. This constitutes the first inspection period; (b)

During the next 120 effective full power months, inspect 1 00% of the tubes. This constitutes the second inspection period; (c)

During the next 96 effective full power months, inspect 1 00°/o of the tubes. This constitutes the third inspection period; and (d)

During the remaining life of the SGs, inspect 100% of the tubes every 72 effective full power months. This constitutes the fourth and subsequent inspection periods.

3.

If crack indications are found in any SG tube, then the next inspection for each affected and potentially affected SG for the degradation mechanism that caused the crack indication shall not exceed 24 effective full power months or one refueling outage (whichever results in more frequent inspections). If definitive information, such as from examination of a pulled tube, diagnostic non-destructive testing, or engineering evaluation indicates that a crack-like indication is not associated with a crack(s), then the indication need not be treated as a crack.

e.

Provisions for monitoring operational primary to secondary LEAKAGE.

(continued)

CALLAWAY PLANT 5.0-13 Amendment ###

Programs and Manuals 5.5 5.5 Programs and Manuals (continued) 5.5.10 Secondary Water Chemistry Program This program provides controls for monitoring secondary water chemistry to inhibit SG tube degradation. The program shall include:

a.

Identification of a sampling schedule for the critical variables and control points for these variables;

b.

Identification of the procedures used to measure the values of the critical variables;

c.

Identification of process sampling points, which shall include monitoring the discharge of the condensate pumps for evidence of condenser in leakage;

d.

Procedures for the recording and management of data;

e.

Procedures defining corrective actions for all off control point chemistry conditions; and

f.

A procedure identifying the authority responsible for the interpretation of the data and the sequence and timing of administrative events, which is required to initiate corrective action.

5.5.11 Ventilation Filter Testing Program CVFTP)

A program shall be established to implement the following required testing of Engineered Safety Feature (ESF) filter ventilation systems at the frequencies specified in Regulatory Guide 1.52, Rev. 2, and uses the test procedure guidance in Regulatory Guide 1.52, Revision 2, Positions C.S.a, C.S.c and C.S.d.

a.

Demonstrate for each of the ESF systems that an in place test of the high efficiency particulate air (HEPA) filters shows a penetration and system bypass< 1.0°/o when tested at the system flowrate specified below.

CALLAWAY PLANT ESF Ventilation System Control Room Filtration Control Room Pressurization Emergency Exhaust System 5.0-14 Flowrate 2000 cfm, +/- 200 cfm 500 cfm, +500, -50 cfm 9000 cfm, +/- 900 cfm (continued)

Amendment### I

5.5 Programs and Manuals Programs and Manuals 5.5 5.5.11 Ventilation Filter Testing Program (VFTP) (continued)

b.

Demonstrate for each of the ESF systems that an in place test of the charcoal adsorber shows a penetration and system bypass < 1.0% when tested at the system flowrate specified below.

ESF Ventilation System Control Room Filtration Control Room Pressurization Emergency Exhaust System Flowrate 2000 cfm, +/- 200 cfm 500 cfm, +500, -50 cfm 9000 cfm, +/- 900 cfm

c.

Demonstrate for each of the ESF systems within 31 days after removal that a laboratory test of a sample of the charcoal adsorber, when obtained in accordance with Regulatory Position C.6.b of Regulatory Guide 1.52, Revision 2, shows the methyl iodide penetration less than the value specified below when tested in accordance with ASTM D3803-1989 at a temperature of 30°C and the relative humidity specified below.

ESF Ventilation System Control Room Filtration Control Room Pressurization Emergency Exhaust System Penetration 2.0%

2.0%

2.0o/o RH 70%

?OOfo

?Oo/o

d.

Demonstrate at least once per 18 months for each of the ESF systems that the pressure drop across the combined HEPA filters and the charcoal adsorbers is less than the value specified below when tested at the system flowrate specified below.

ESF Ventilation System Delta P Flowrate Control Room Filtration 5.4 11 WG 2000 cfm,

+/- 200 cfm Control Room Pressurization 5.4 11 WG 500 cfm,

+500,- 50 cfm Emergency Exhaust System 5.4 11 WG 9000 cfm,

+/- 900 cfm (continued)

CALLAWAY PLANT 5.0-15 Amendment ### I

Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.11 Ventilation Filter Testing Program (VFTP) (continued) 5.5.12

e.

Demonstrate at least once per 18 months that the heaters for each of the ESF systems dissipate the value specified below when tested in accordance with ANSI 510-1975 and corrected to design nameplate voltage settings.

ESF Ventilation System Control Room Pressurization Emergency Exhaust System Wattage 15 +/- 2 KW 37+/- 3 KW The provisions of SR 3.0.2 and SR 3.0.3 are applicable to the VFTP test frequencies.

Explosive Gas and Storage Tank Radioactivitv Monitoring Program This program provides controls for potentially explosive gas mixtures contained in the Gaseous Radwaste System, the quantity of radioactivity contained in gas storage tanks and the quantity of radioactivity contained in unprotected outdoor liquid storage tanks. The gaseous radioactivity quantities shall be determined following the methodology in Branch Technical Position (BTP) ETSB 11-5, "Postulated Radioactive Release due to Waste Gas System Leak or Failure, Revision 0". The liquid radwaste quantities shall be determined in accordance with Standard Review Plan, Section 15.7.3, "Postulated Radioactive Release due to Tank Failures, Revision 2".

The program shall include:

a.

The limits for concentrations of hydrogen and oxygen in the Gaseous Radwaste System and a surveillance program to ensure the limits are maintained. Such limits shall be appropriate to the system's design criteria (i.e., whether or not the system is designed to withstand a hydrogen explosion);

b.

A surveillance program to ensure that the quantity of radioactivity contained in each gas storage tank is less than the amount that would result in a whole body exposure of;?: 0.5 rem to any individual in an unrestricted area, in the event of an uncontrolled release of the tanks' contents; and

c.

A surveillance program to ensure that the quantity of radioactivity contained in the outdoor liquid radwaste tanks listed below that are not (continued)

CALLAWAY PLANT 5.0-16 Amendment ### I

Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.12 5.5.13 Explosive Gas and Storage Tank Radioactivitv Monitoring Program (continued) surrounded by liners, dikes, or walls, capable of holding the tanks' contents and that do not have tank overflows and surrounding area drains connected to the Liquid Radwaste System is less than the quantities determined in accordance with the Standard Review Plan, Section 15.7.3:

a.

Reactor Makeup Water Storage Tank,

b.

Refueling Water Storage Tank,

c.

Condensate Storage Tank, and

d.

Outside temporary tanks, excluding demineralizer vessels and the liner being used to solidify radioactive waste.

The provisions of SR 3.0.2 and SR 3.0.3 are applicable to the Explosive Gas and Storage Tank Radioactivity Monitoring Program surveillance frequencies.

Diesel Fuel Oil Testing Program A diesel fuel oil testing program to implement required testing of both new fuel oil and stored fuel oil shall be established. The program shall include sampling and testing requirements, and acceptance criteria, all in accordance with applicable ASTM Standards. The purpose of the program is to establish the following:

a.

Acceptability of new fuel oil for use prior to addition to storage tanks by determining that the fuel oil has:

1.

an API gravity or an absolute specific gravity within limits,

2.

a flash point and kinematic viscosity within limits for ASTM 2D fuel oil, and

3.

a water and sediment content within limits for ASTM 2D fuel oil.

b.

Other properties for ASTM 2D fuel oil are analyzed within 31 days following sampling and addition of new fuel oil to storage tanks; and

c.

Total particulate concentration of the stored fuel oil is ~ 10 mg/1 when tested every 31 days based on applicable ASTM D-2276 standards.

d.

The provisions of SR 3.0.2 and SR 3.0.3 are applicable to the Diesel Fuel Oil Testing Program test frequencies.

(contmued)

CALLAWAY PLANT 5.0-17 Amendment ### I

Programs and Manuals 5.5 5.5 Programs and Manuals (continued) 5.5.14 5.5.15 Technical Specifications (TS) Bases Control Program This program provides a means for processing changes to the Bases of these Technical Specifications.

a.

Changes to the Bases of the TS shall be made under appropriate administrative controls and reviews.

b.

Licensees may make changes to Bases without prior NRC approval provided the changes do not require either of the following:

1.

a change in the TS incorporated in the license; or

2.

a change to the updated FSAR or Bases that requires NRC approval pursuant to 10 CFR 50.59.

c.

The Bases Control Program shall contain provisions to ensure that the Bases are maintained consistent with the FSAR.

d.

Proposed changes that meet the criteria of Specification 5.5.14b above shall be reviewed and approved by the NRC prior to implementation.

Changes to the Bases implemented without prior NRC approval shall be provided to the NRC on a frequency consistent with 10 CFR 50.71(e).

Safety Function Determination Program (SFDP)

This program ensures loss of safety function is detected and appropriate actions taken. Upon entry into LCO 3.0.6, an evaluation shall be made to determine if loss of safety function exists. Additionally, other appropriate actions may be taken as a result of the support system inoperability and corresponding exception to entering supported system Condition and Required Actions. This program implements the requirements of LCO 3.0.6. The SFDP shall contain the following:

a.

Provisions for cross train checks to ensure a loss of the capability to perform the safety function assumed in the accident analysis does not go undetected;

b.

Provisions for ensuring the plant is maintained in a safe condition if a loss of function condition exists; (continued)

CALLAWAY PLANT 5.0-18 Amendment ### I

Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.15 5.5.16 Safety Function Determination Program <SFDP) (continued)

c.

Provisions to ensure that an inoperable supported system's Completion Time is not inappropriately extended as a result of multiple support system inoperabilities; and

d.

Other appropriate limitations and remedial or compensatory actions.

A loss of safety function exists when, assuming no concurrent single failure, a safety function assumed in the accident analysis cannot be performed. For the purpose of this program, a loss of safety function may exist when a support system is inoperable, and:

a.

A required system redundant to the system(s) supported by the inoperable support system is also inoperable; or

b.

A required system redundant to the system(s) in turn supported by the inoperable supported system is also inoperable; or

c.

A required system redundant to the support system(s) for the supported systems (a) and (b) above is also inoperable.

The SFDP identifies where a loss of safety function exists. If a loss of safety function is determined to exist by this program, the appropriate Conditions and Required Actions of the LCO in which the loss of safety function exists are required to be entered.

Containment Leakage Rate Testing Program

a.

A program shall be established to implement the leakage rate testing of the containment as required by 10 CFR 50.54(o) and 10 CFR 50, Appendix J, Option 8, as modified by approved exemptions. This program shall be in accordance with the guidelines contained in Regulatory Guide 1.163, "Performance-Based Containment Leak-Test Program," dated September 1995, as modified by the following exceptions:

1.

The visual examination of containment concrete surfaces intended to fulfill the requirements of 10 CFR 50, Appendix J, Option 8 testing, will be performed in accordance with the requirements of and frequency specified by ASME Section XI Code, Subsection IWL, except where relief has been authorized by the NRC.

(continued)

CALLAWAY PLANT 5.0-19 Amendment ### I

Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.16 Containment Leakage Rate Testing Program (continued)

2.

The visual examination of the steel liner plate inside containment intended to fulfill the requirements of 10 CFR 50, Appendix J, Option 8 testing, will be performed in accordance with the requirements of and frequency specified by ASME Section XI Code, Subsection IWE, except where relief has been authorized by the NRC.

3.

The unit is excepted from post-modification integrated leakage rate testing requirements associated with steam generator replacement during the Refuel 14 outage (fall of 2005).

4.

The first Type A test performed after the October 26, 1999 Type A test shall be performed no later than October 25, 2014.

b.

The peak calculated containment internal pressure for the design basis loss of coolant accident, pas is 48.1 psig.

c.

The maximum allowable containment leakage rate, La, at P a, shall be 0.20% of the containment air weight per day.

d.

Leakage rate acceptance criteria are:

1.

Containment leakage rate acceptance criterion is s; 1.0 La. During the first unit startup following testing in accordance with this program, the leakage rate acceptance criteria are< 0.60 La for the Type 8 and C tests and s; 0. 75 La for Type A tests;

2.

Air lock testing acceptance criteria are:

a)

Overall air lock leakage rate iss; 0.05 La when tested at

Pa; b)

For each door, leakage rate iss; 0.005 La when pressurized to;;::: 10 psig.

e.

The provisions of Technical Specification SR 3.0.2 do not apply to the test frequencies in the Containment Leakage Rate Testing Program.

f.

The provisions of Technical Specification SR 3.0.3 are applicable to the Containment Leakage Rate Testing Program.

(continued)

CALLAWAY PLANT 5.0-20 Amendment ### I

Programs and Manuals 5.5 5.5 Programs and Manuals (continued) 5.5.17 Control Room Envelope Habitability Program A Control Room Envelope (CRE) Habitability Program shall be established and implemented to ensure that CRE habitability is maintained such that, with an OPERABLE Control Room Emergency Ventilation System (CREVS), CRE occupants can control the reactor safely under normal conditions and maintain it in a safe condition following a radiological event, hazardous chemical release, or a smoke challenge. The program shall ensure that adequate radiation protection is provided to permit access and occupancy of the CRE under design basis accident (DBA) conditions without personnel receiving radiation exposures in excess of 5 rem whole body or its equivalent to any part of the body for the duration of the accident. The program shall include the following elements:

a.

The definition of the CRE, CRE boundary, control building envelope (CBE), and the CBE Boundary.

b.

Requirements for maintaining the CRE and CBE boundaries in their design condition, including configuration control and preventive maintenance.

c.

Requirements for (i) determining the unfiltered air inleakage past the CRE and CBE boundaries in accordance with the testing methods and at the Frequencies specified in Sections C.1 and C.2 of Regulatory Guide 1.197, "Demonstrating Control Room Envelope Integrity at Nuclear Power Reactors," Revision 0, May 2003, and (ii) assessing CRE habitability at the Frequencies specified in Sections C.1 and C.2 of Regulatory Guide 1.197, Revision 0.

The following exception is taken to Sections C.1 and C.2 of Regulatory Guide 1.197, Revision 0:

1.

The Tracer Gas Test based on the Brookhaven National Laboratory Atmospheric Tracer Depletion (ATD) Method is used to determine the unfiltered air in leakage past the CRE and CBE boundaries. The ATD Method is described in AmerenUE letters dated December 15, 2004 (ULNRC-051 04), June 6, 2006 (ULNRC-05298), July 16, 2007 (ULNRC-05427), and October 30, 2007 (ULNRC-05448).

d.

Measurement, at designated locations, of the CRE pressure relative to the outside atmosphere during the pressurization mode of operation by one train of the CREVS, operating at the flow rate required by the VFTP, at a Frequency of 18 months on a STAGGERED TEST BASIS. The results shall be trended and used as part of the periodic assessment of the CRE boundary.

(continued)

CALLAWAY PLANT 5.0-21 Amendment### I

Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.17 5.5.18 Control Room Envelope Habitability Program (continued)

e.

The quantitative limits on unfiltered air inleakage into CRE and CBE.

These limits shall be stated in a manner to allow direct comparison to the unfiltered air in leakage measured by the testing described in paragraph c.

The unfiltered air in leakage limit for radiological challenges is the inleakage flow rate assumed in the licensing basis analyses of DBA consequences. Unfiltered air leakage limits for hazardous chemicals must ensure that exposure of CRE occupants to these hazards will be within the assumptions in the licensing basis.

f.

The provisions of SR 3.0.2 are applicable to the Frequencies for assessing CRE habitability, determining CRE and CBE unfiltered inleakage, and measuring CRE pressure and assessing CRE and CBE as required by paragraphs c and d, respectively.

Surveillance Frequency Control Program This program provides controls for Surveillance Frequencies. The program shall ensure that Surveillance Requirements specified in the Technical Specifications are performed at intervals sufficient to assure the associated Limiting Conditions for Operation are met.

a.

The Surveillance Frequency Control Program shall contain a list of Frequencies of those Surveillance Requirements for which the Frequency is controlled by the program.

b.

Changes to the Frequencies listed in the Surveillance Frequency Control Program shall be made in accordance with NEI 04-10, "Risk-Informed Method for Control of Surveillance Frequencies," Revision 1.

c.

The provisions of Surveillance Requirements 3.0.2 and 3.0.3 are applicable to the Frequencies established in the Surveillance Frequency Control Program.

CALLAWAY PLANT 5.0-22 Amendment ### I

5.0 ADMINISTRATIVE CONTROLS 5.6 Reporting Requirements Reporting Requirements 5.6 The following reports shall be submitted in accordance with 10 CFR 50.4.

5.6.1 Not Used.

5.6.2 Annual Radiological Environmental Operating Report The Annual Radiological Environmental Operating Report covering the operation of the unit during the previous calendar year shall be submitted by May 1 of each year. The report shall include summaries, interpretations, and analyses of trends of the results of the radiological environmental monitoring program for the reporting period.

The material provided shall be consistent with the objectives outlined in the Offsite Dose Calculation Manual (ODCM), and in 10 CFR 50, Appendix I, Sections IV.B.2, IV.B.3, and IV.C.

The Annual Radiological Environmental Operating Report shall include the results of analyses of all radiological environmental samples and of all environmental radiation measurements taken during the period pursuant to the locations specified in the table and figures in the ODCM, as well as summarized and tabulated results of these analyses and measurements in a format similar to the table in the Radiological Assessment Branch Technical Position, Revision 1, November 1979. In the event that some individual results are not available for inclusion with the report, the report shall be submitted noting and explaining the reasons for the missing results. The missing data shall be submitted in a supplementary report as soon as possible.

5.6.3 Radioactive Effluent Release Report The Radioactive Effluent Release Report covering the operation of the unit during the previous year shall be submitted prior to May 1 of each year in accordance with 10 CFR 50.36a. The report shall include a summary of the quantities of radioactive liquid and gaseous effluents and solid waste released from the unit. The material provided shall be consistent with the objectives outlined in the ODCM and Process Control Program and in conformance with 10 CFR 50.36a and 10 CFR Part 50, Appendix I,Section IV.B.1.

5.6.4 Not used.

(continued)

CALLAWAY PLANT 5.0-23 Amendment ### I

Reporting Requirements 5.6 5.6 Reporting Requirements 5.6.5 CORE OPERATING LIMITS REPORT (COLR)

a.

Core operating limits shall be established prior to each reload cycle, or prior to any remaining portion of a reload cycle, and shall be documented in the COLR for the following:

1.

Moderator Temperature Coefficient limits in Specification 3.1.3,

2.

Shutdown Bank Insertion Limit for Specification 3.1.5,

3.

Control Bank Insertion Limits for Specification 3.1.6,

4.

Axial Flux Difference Limits for Specification 3.2.3,

5.

Heat Flux Hot Channel Factor, F0 (Z), F0 RTP, K(Z), W(Z) and Fa Penalty Factors for Specification 3.2.1,

6.

Nuclear Enthalpy Rise Hot Channel Factor F fH, F ~H RTP, and Power Factor Multiplier, PF ~H* limits for Specification 3.2.2,

7.

Shutdown Margin Limits for Specifications 3.1.1, 3.1.4, 3.1.5, 3.1.6, and 3.1.8,

8.

Reactor Core Safety Limits Figure for Specification 2.1.1,

9.

Overtemperature ~ T and Overpower~ T Setpoint Parameters for Specification 3.3.1, and

10.

Reactor Coolant System Pressure and Temperature DNB Limits for Specification 3.4.1.

b.

The analytical methods used to determine the core operating limits shall be those previously reviewed and approved by the NRC, specifically those described in the following documents:

CALLAWAY PLANT

1.

WCAP-9272-P-A, "WESTINGHOUSE RELOAD SAFETY EVALUATION METHODOLOGY."

2.

WCAP-10216-P-A, "RELAXATION OF CONSTANT AXIAL OFFSET CONTROL AND FQ SURVEILLANCE TECHNICAL SPECIFICATION."

3.

WCAP-10266-P-A, "THE 1981 VERSION OF WESTINGHOUSE EVALUATION MODEL USING BASH CODE."

(continued) 5.0-24 Amendment ### I

Reporting Requirements 5.6 5.6 Reporting Requirements

4.

WCAP-12610-P-A, "VANTAGE+ FUEL ASSEMBLY REFERENCE CORE REPORT."

5.

WCAP-11397-P-A, "REVISED THERMAL DESIGN PROCEDURE."

6.

WCAP-14565-P-A, "VIPRE-01 MODELING AND QUALIFICATION FOR PRESSURIZED WATER REACTOR NON-LOCA THERMAL-HYDRAULIC SAFETY ANALYSIS."

7.

WCAP-10851-P-A, "IMPROVED FUEL PERFORMANCE MODELS FOR WESTINGHOUSE FUEL ROD DESIGN AND SAFETY EVALUATIONS."

8.

WCAP-15063-P-A, "WESTINGHOUSE IMPROVED PERFORMANCE ANALYSIS AND DESIGN MODEL (PAD 4.0)."

9.

WCAP-8745-P-A, "DESIGN BASES FOR THE THERMAL OVERPOWER DT AND THERMAL OVERTEMPERATURE DT TRIP FUNCTIONS."

10.

WCAP-10965-P-A, "ANC: A WESTINGHOUSE ADVANCED NODAL COMPUTER CODE."

11.

WCAP-11596-P-A, "QUALIFICATION OF THE PHOENIX-P/ANC NUCLEAR DESIGN SYSTEM FOR PRESSURIZED WATER REACTOR CORES."

12.

WCAP-13524-P-A, "APOLLO: A ONE DIMENSIONAL NEUTRON DIFFUSION THEORY PROGRAM."

c.

The core operating limits shall be determined such that all applicable limits (e.g., fuel thermal mechanical limits, core thermal hydraulic limits, Emergency Core Cooling Systems (ECCS) limits, nuclear limits such as SDM, transient analysis limits, and accident analysis limits) of the safety analysis are met.

d.

The COLR, including any midcycle revisions or supplements, shall be provided upon issuance for each reload cycle to the NRC.

(continued)

CALLAWAY PLANT 5.0-25 Amendment### I

Reporting Requirements 5.6 5.6 Reporting Requirements 5.6.6 Reactor Coolant System (RCS) PRESSURE AND TEMPERATURE LIMITS REPORT (PTLR)

a.

RCS pressure and temperature limits for heat up, cooldown, low temperature operation, criticality, hydrostatic testing and PORV lift setting as well as heatup and cooldown rates shall be established and documented in the PTLR for the following:

1.

Specification 3.4.3, "RCS Pressure and Temperature (PIT) Limits,"

and

2.

Specification 3.4.12, "Cold Overpressure Mitigation System (COMS)."

b.

The analytical methods used to determine the RCS pressure and temperature and COMS PORV limits shall be those previously reviewed and approved by the NRC, specifically those described in WCAP-14040-NP-A, "Methodology Used to Develop Cold Overpressure Mitigating System Setpoints and RCS Heatup and Cooldown Limit Curves".

c.

The PTLR shall be provided to the NRC upon issuance for each reactor vessel fluence period and for any revision or supplement thereto.

5.6. 7 Not used.

5.6.8 PAM Report When a report is required by Condition 8 or F of LCO 3.3.3, "Post Accident Monitoring (PAM) Instrumentation," a report shall be submitted within the following 14 days. The report shall outline the preplanned alternate method of monitoring, the cause of the inoperability, and the plans and schedule for restoring the instrumentation channels of the Function to OPERABLE status.

5.6.9 Not used.

(continued)

CALLAWAY PLANT 5.0-26 Amendment### I

Reporting Requirements 5.6 5.6 Reporting Requirements (continued) 5.6.10 Steam Generator Tube Inspection Report A report shall be submitted within 180 days after the initial entry into MODE 4 following completion of an inspection performed in accordance with Specification 5.5.9, "Steam Generator (SG) Program." The report shall include:

a.

The scope of inspections performed on each SG;

b.

Degradation mechanisms found;

c.

Nondestructive examination techniques utilized for each degradation mechanism;

d.

Location, orientation (if linear), and measured sizes (if available) of service induced indications;

e.

Number of tubes plugged during the inspection outage for each degradation mechanism;

f.

The number and percentage of tubes plugged to date, and the effective plugging percentage in each steam generator; and

g.

The results of condition monitoring, including the results of tube pulls and in-situ testing.

CALLAWAY PLANT 5.0-27 Amendment ###

High Radiation Area 5.7 5.0 ADMINISTRATIVE CONTROLS 5.7 High Radiation Area As provided in paragraph 20.1601 (c) of 10 CFR Part 20, the following controls shall be applied to high radiation areas in place of the controls required by paragraph 20.1601 (a) and (b) of 1 0 CFR Part 20:

5. 7.1 High Radiation Areas with Dose Rates Not Exceeding 1.0 rem/hour at 30 Centimeters from the Radiation Source or from any Surface Penetrated by the Radiation:
a.

Each entryway to such an area shall be barricaded and conspicuously posted as a high radiation area. Such barricades may be opened as necessary to permit entry or exit of personnel or equipment;

b.

Access to, and activities in, each such area shall be controlled by means of Radiation Work Permit (RWP) or equivalent that includes specification of radiation dose rates in the immediate work area(s) and other appropriate radiation protection equipment and measures.

c.

Individuals qualified in radiation protection procedures and personnel continuously escorted by such individuals may be exempted from the requirement for an RWP or equivalent while performing their assigned duties provided that they are otherwise following plant radiation protection procedures for entry to, exit from, and work in such areas.

d.

Each individual or group entering such an area shall possess:

CALLAWAY PLANT

1.

A radiation monitoring device that continuously displays radiation dose rates in the area; or

2.

A radiation monitoring device that continuously integrates the radiation dose rates in the area and alarms when the device's dose alarm setpoint is reached, with an appropriate alarm setpoint, or

3.

A radiation monitoring device that continuously transmits does rate and cumulative dose rate information to a remote receiver monitored by radiation protection personnel responsible for controlling personnel radiation exposure within the area, or

4.

A self-reading dosimeter (e.g., pocket ionization chamber or electronic dosimeter) and (continued) 5.0-28 Amendment ### I

High Radiation Area 5.7

5. 7 High Radiation Area 5.7.1 High Radiation Areas with Dose Rates Not Exceeding 1.0 rem/hour at 30 Centimeters from the Radiation Source or from any Surface Penetrated by the Radiation: (continued)

(i)

Be under the surveillance, as specified in the RWP or equivalent, while in the area, of an individual qualified in radiation protection procedures, equipped with a radiation monitoring device that continuously displays radiation dose rates in the area; who is responsible for controlling personnel exposure within the area, or (ii)

Be under the surveillance as specified in the RWP or equivalent, while in the area, by means of closed circuit television, of personnel qualified in radiation protection procedures, responsible for controlling personnel radiation exposure in the area, and with the means to communicate with individuals in the area who are covered by such surveillance.

e.

Except for individuals qualified in radiation protection procedures, entry into such areas shall be made only after dose rates in the area have been determined and entry personnel are knowledgeable of them.

5.7.2 High Radiation Areas with Dose Rates Greater than 1.0 rem/hour at 30 Centimeters from the Radiation Source or from any Surface Penetrated by the Radiation. but less than 500 rads/hour at 1 Meter from the Radiation Source or from any Surface Penetrated by the Radiation:

a.

Each entryway to such an area shall be conspicuously posted as a high radiation area and shall be provided with a locked or continuously guarded door or gate that prevents unauthorized entry, and, in addition:

1.

All such door and gate keys shall be maintained under the administrative control of the Shift Manager/Operating Supervisor or Radiation Protection Department Supervision, or his or her designee.

2.

Doors and gates shall remain locked except during periods of personnel or equipment entry or exit.

b.

Access to, and activities in, each such area shall be controlled by means of an RWP or equivalent that includes specification of radiation dose rates in the immediate work area(s) and other appropriate radiation protection equipment and measures.

(Continued)

CALLAWAY PLANT 5.0-29 Amendment### I

High Radiation Area 5.7

5. 7 High Radiation Area 5.7.2 High Radiation Areas with Dose Rates Greater than 1.0 rem/hour at 30 Centimeters from the Radiation Source or from any Surface Penetrated by the Radiation. but less than 500 rads/hour at 1 Meter from the Radiation Source or from any Surface Penetrated by the Radiation: (continued)
c.

Individuals qualified in radiation protection procedures may be exempted from the requirement for an RWP or equivalent while performing radiation surveys in such areas provided that they are otherwise following plant radiation protection procedures for entry to, exit from, and work in such areas.

d.

Each individual or group entering such an area shall possess:

CALLAWAY PLANT

1.

A radiation monitoring device that continuously integrates the radiation rates in the area and alarms when the device's dose alarm setpoint is reached, with an appropriate alarm setpoint, or

2.

A radiation monitoring device that continuously transmits dose rate and cumulative dose information to a remote receiver monitored by radiation protection personnel responsible for controlling personnel radiation exposure within the area with the means to communicate with and control every individual in the area, or

3.

A self-reading dosimeter (e.g., pocket ionization chamber or electronic dosimeter) and (i)

Be under the surveillance, as specified in the RWP or equivalent, while in the area, of an individual qualified in radiation protection procedures, equipped with a radiation monitoring device that continuously displays radiation dose rates in the area; who is responsible for controlling personnel exposure within the area, or (ii)

Be under the surveillance as specified in the RWP or equivalent, while in the area, by means of closed circuit television, of personnel qualified in radiation protection procedures, responsible for controlling personnel radiation exposure in the area, and with the means to communicate with and control every individual in the area, or

4.

In those cases where options (2) and (3), above, are impractical or determined to be inconsistent with the "As Low As is Reasonably (Continued) 5.0-30 Amendment ### I

5. 7 High Radiation Area High Radiation Area 5.7 5.7.2 High Radiation Areas with Dose Rates Greater than 1.0 rem/hour at 30 Centimeters from the Radiation Source or from any Surface Penetrated by the Radiation. but less than 500 rads/hour at 1 Meter from the Radiation Source or from any Surface Penetrated by the Radiation: (continued)

Achievable" principle, a radiation monitoring device that continuously displays radiation dose rates in the area.

e.

Except for individual qualified in radiation protection procedures or personnel continuously escorted by such individuals, entry into such areas shall be made only after dose rates in the area have been determined and entry personnel are knowledgeable of them.

f.

Such individual areas that are within a larger area, such as PWR containment, where no enclosure exists for the purpose of locking and where no enclosure can reasonably be constructed around the individual area need not be controlled by a locked door or gate nor continuously guarded, but shall be barricaded, conspicuously posted, and a clearly visible flashing light shall be activated at the area as a warning device.

CALLAWAY PLANT 5.0-31 Amendment ### I