DISTRIBUTION Docket File C Parish NRC PDR raFie APR 1 5 1981 NRc PDR ARS (1 Local PDR CS{'
TERA
- 6. Parrish GrayeFie A CRSe (1 0).'o Mr. J. A. Jones B. Fe uson Senior Executive Vice President jes Carolina Power and Light Company OELD 336 Fayetteville Street I&E (3)
Raleigh, North Carolina 27602 S. Varga D. Neighbors
Dear Mr. Jones:
By letter dated January 19, 1981, you requested an exemption to 10 CFR 50, Appendix R, Item 111.0 for the H. B. Robinson Steam Electric PlAnt, Unit No. 2. This exemption would remove the requirement for an oil collection system in the Reactor Coolant Pump (RCP) bay based on the physicTalconfig uration of the RCP bays which isolates the effects of an oil fire in this area from any equipment needed for safe shutdown. Therefore, you assent that an oil collection system would not enhance fire protection safety at the H. B. Robinson 2 plant.
We have found that your request provides a sound technical basis warranting further staff review. In this regard, we have discussed with your staff.the possibility of visiting Robinson in May 1981, to further evaluate -the suscep tibility of equipment needed for safe shutdown to the effects of a fire in the RCP area.
The schedule requirements for this item are, therefore, suspended in-accord ance with 10 CFR 50.48(c)(6) until final Commission action on this request.
Sincerely, Original Signed 1h E. G. ca"e arold R. Denton, Director V) Office of Nuclear Reactor Regulation cc: See next page d'
8 1 0422 Oecl i ONCURRE NCES*
OFFICEO L
ORB#1:DL*
ORB#5:DL AD/OR:DL D/LD*
SURNAME)DNei h ors/r. S.Varqg*
TWambach*
TNovakA H
DEi ut DATEO 4/1 /8 1 4
F3FICI 3/13/81 4/
/814/
cRC saos FOM38108)NRcMo240 OFFICI.AL RECORD COPY USGPO: 1980-329-824
DISTRIBUTI.ON Z
Docket File C. Parrish NRC PDR Local PDR Gray File TERA ACRS (16)
NSIC ORB#l Rdg D. Eisenhut Docket No. 50-261 R. Purple H. Denton R. Tedesco G. Lainas Mr. J. A. Jones J. Heltemes Senior Executive Vice President OELD Carolina Power and Light Company I&E (3) 336 Fayetteville Street S. Varga Raleigh,.North Carolina 27602 D. Neighbors
Dear Mr. Jones:
By letter dated January 19, 1981, you requested an exemption to 10 CFR 50, Appendix R, Item III.0 for the H. B. Robinson Steam Electric Plant, Unit No. 2. This exemption would remove the requirement for an oil collection system in the Reactor Coolant Pump (RCP) bay based on the physical config uration of the RCP bays which isolates the effects of an oil fire in this area from any equipment needed for safe shutdown. Therefore, you conclude that an oil collection system would not enhance fire protection safety at the H. B. Robinson 2 plant.
We have found that your request has sufficient basis to wa'rrhnt our further review. In this regard, we have discussed with your staff-the possibility of visiting Rot4inson in May 1981, to further evaluate the susceptitility of dquipment needed for safe shutdown to the effects of a fire in the RCP area.
The schedule requirements for this item are, therefore, suspended in accord ance with 10 CFR 50.48(c)(6) until final Commission action on this request.
Sincerely, Harold R. Denton, Director Office of Nuclear Reactor Regulation cc: See next page SEE PREVIOUS CONCURRENCE SHEET FOR CONCURRENCES*
OFFCE OR ORB#1:DL ORB#5:DL AD/OR:DL D/DL D/NRR 0ELD SURNAMEO DN hbors/ sSVarga TWambach*
TNovak-DEisenhut HientonOLMSTEA BATE 81 3/
/81 3/13/81 3/ /81 3/ /81 3/ /81 3/18/81 NRC FORM 318(10/80) NRCM 0240 OFFICIAL RECORD COPY USGPO:1980-329-ma
DISTRIBUTION:
Docket File
-CParrish NRC PDR Gray File L PDR ACRS (16)
TERA NSIC Docket No. 50-261 ORB#l Rdg DEisenhut RPurple HDenton Mr. J. A. Jones RTedesco Senior Executive Vice President GLainas Carolina Power and Light Company JHeltemes 336 Fayetteville.Street OELD Raleigh, North Carolina 27602 I&E (3)
SVarga
Dear Mr. Jones:
DNeighbors By letter dated January 19, 1981, you requested an exemption to 10 CFR 50, Appendix R, Item III.0 for the H. B. Robinson Steam Electric Plant, Unit No. 2. This exemption would remove the requirement for an oil collection system in the Reactor Coolant Pump (RCP) bay.
We have found that your request has sufficient basis to warrant our fur ther review. In this regard, we have discussed with your staff the possibility of visiting Robinson in May, 1981, to further evaluate the susceptibility of equipment needed for safe shutdown to the effects of a fire in the RCP area.
The schedule requirements for this item are, therefore, suspended in accordance with 10 CFR 50.48(c)(6) until final Commission action on this request.
Sincerely, Harold R. Denton, Director Office of Nuclear Reactor Regulation cc: See next page OFFICE 1
- 1. DL........ 0R #5.:DL........
L/
L............ D/.NRR.........
SURNAME I~i rs S V TWambach TN k
DEisenhut HDenton uA IDATE 33 coDaTemoo.
OF C.
.A.L......
E.C.O..
.COPY USP.
80 NRC FORM 318(10/80) NRCM 0240 O
iCA RE RD OP.
-USGP0: 1980-329-82,
.AP R j 5 1981 Jr.
J. A. Jones Carolina Power and Light Company cc:
G. F. Trowbridge, Esquire Shaw, Pittman, Potts and Trow ridoe 1800 M Street, N.W.
Washington, D. C. 20036 Hartsville Memorial Library Home and Fifth Avenues Hartsville, South Carolina 29550
-U. S. Nuclear Regulatory Commission Resident Inspector's Office H. B. Robinson Steam Electric Plant Route 5, Box 266-1A Hartsville, South Carolina 29550 Richard S. Salzman Atomic Safety and Licensing Appeal Board Panel U. S. Nuclear Regulatory Commission Washington, D. C. 20555 Dr. W. Reed Johnson Atomic Safety and Licensing Appeal Board Panel U. S. Nuclear Reculatory Commission Washington, D. C. 20555