Text
ENCLOSURE 1 NOTICE OF VIOLATION Carolina Power and Light Company Docket No. 50-261 H. B. Robinson License No. DPR-23 During an NRC inspection conducted on August 24-28, 1992, a violation of NRC requirements was identified. In accordance with the "General Statement of Policy and Procedure for NRC Enforcement Actions," 10 CFR Part 2, Appendix C, the violation is listed below:
Technical Specification 6.5.1.1.1.a requires written procedures be established for activities referenced in Appendix A of Regulatory Guide 1.33 Revision 2, "Quality Assurance Program Requirements (Operation)". Appendix A paragraph 6.c requires that the licensee have procedures for combating emergencies (Loss of Electrical Power).
Procedure OP-603 Section 8.1.2 was established for restoration of normal power after loss of all AC power and turbine trip with Emergency Diesel Generator Operating. During the recovery phase of the Loss of Offsite Power Event of August 22, 1992 temporary change T-4633 to procedure OP-603 was being utilized for restoration of offsite power.
Contrary to the above, procedures were not adequately established in that on August 22, 1992 OP-603 temporary change T-4633 did not provide instructions for verifying that the generator lockout relays 86P and 86 BU were reset prior to closing the startup to 4kv Bus 2 breaker 52/12.
This is a Severity Level IV violation (Supplement 1).
Pursuant to the provisions of 10 CFR 2.201, Carolina Power and Light Company is hereby required to submit a written statement or explanation to the U.S.
Nuclear Regulatory Commission, ATTN: Document Control Desk, Washington, D.C.
20555 with a copy to the Regional Administrator, Region II, and a copy to the NRC Resident Inspector at the facility that is the subject of this Notice, within 30 days of the date of the letter transmitting this Notice of Violation (Notice). This reply should be clearly marked as a "Reply to a Notice of Violation" and should include:
(1) the reason for the violation, or, if contested, the basis for disputing the violation, (2) the corrective steps that have been taken and the results achieved, (3) the corrective steps that will be taken to avoid further violations, and (4) the date when full compli ance will be achieved. If an adequate reply is not received within the time specified in this Notice, an order or Demand for Information may be issued as to why the license should not.be modified, suspended, or revoked, or why such other action as may be proper should not be taken. Where good cause is shown, consideration will be given to extending the response time.
Dated at Atlanta, Georgia this 3oth day of September 1992 9210060238 920930 PDR ADOCK 05000261 G