Enclosure 3 FIR-NGGC-0009, NFPA 805 Transient Combustibles and Ignition Source Controls Program
DUKE ENERGY.
DUKE ENERGY PROGRESS ADMINISTRATIVE PROCEDURE FIR-NGGC-0009 NFPA 805 TRANSIENT COMBUSTIBLES AND IGNITION SOURCE CONTROLS PROGRAM REVISION 5 Information Use Effective Dates:
01/09/2014 Brunswick NA Crystal River 01/09/2014 Harris NA Robinson
NFPA 805 TRANSIENT COMBUSTIBLES AND FIR-NGGC-0009 IGNITION SOURCE CONTROLS PROGRAM Rev. 5 Page 2 of 26 REVISION
SUMMARY
PRR 576437 DESCRIPTION 1.0 - Added "Ignition Sources" to the Purpose statement.
2.2.6 - Added reference to OAP-033.
3.9 - Revised definition to account for the affected unit of multi-unit sites.
3.10 - Added "(Storage)" for clarity.
9.2.1.1., 9.2.1.2, 9.2.3.1, 9.2.3.2, 9.4.3.1 - Changed to an If/Then statement.
9.1.12 -Added section regards control of portable electric heaters.
9.2.2.4, 9.2.3.5 - Revised to state, 'When provided..." for combustible control drawings contained in the Job Aid.
9.4.2.3 - Deleted section as no longer applicable.
Various - Various editorial and format changes. - Corrected 12-A-5PICR1 to 12-A-6-PICR1. - Populated BNP Combustible Control Zones, changed to Attachment 2.
Attachments 2 Eliminated former Attachments 2 and 4. - Added exemption for in-use cribbing, PRR 588378 new Attachment 3. - Added hyperlink to BNP FPS website, new Attachment 5.
NFPA 805 TRANSIENT COMBUSTIBLES AND FIR-NGGC-0009 IGNITION SOURCE CONTROLS PROGRAM Rev. 5 Page 3 of 26 TABLE OF CONTENTS SECTION PAGE 1.0 P U R P O S E.....................................................................................................................
5 2.0 R E F E R E N C E S..............................................................................................................
5 3.0 D E F IN IT IO N S................................................................................................................
6 4.0 R ES PO N S IB ILIT IES..................................................................................................
7 5.0 PREREQUISITES..................................................................................................
8 6.0 PRECAUTIONS, LIMITATIONS AND NOTES...........................................................
8 7.0 SPECIAL TOOLS AND EQUIPMENT.......................................................................
8 8.0 ACCEPTANCE CRITERIA.........................................................................................
8 9.0 INSTRUCTIONS.....................................................................................................
9 9.1 G eneral Requirem ents................................................................................................
9 9.2 Transient Combustible Controls In The Power Block.............................................. 10 9.2.1 General Use of Transient Combustibles.....................................................
10 9.2.2 Use of Transient Combustibles in Non-Intervening Combustible Z o ne s.......................................................................................................
.. 1 1 9.2.3 Use of Transient Combustibles in No Storage Locations...........................
11 9.3 Permanent Staging Locations...................................................................................
12 9.4 Flammable / Combustible Liquids Controls In The Power Block............................. 12 9.4.1 General Use of Flammable/Combustible Liquids........................................ 12 9.4.2 Storage of Flammable/Combustible Liquids and Aerosols......................... 12 9.4.3 Use of Flammable/Combustible Liquids and Aerosols............................... 14 9.4.4 D ra in C a ns.................................................................................................
15 9.4.5 Storage C abinets.......................................................................................
15 9.5 Non-Pow er O perations.............................................................................................
16 10.0 R E C O R D S...................................................................................................................
16 ATTACHMENT 1
HNP COMBUSTIBLE CONTROL ZONES................................................................
17 2
BNP COMBUSTIBLE CONTROL ZONES................................................................
19 3
EXEMPTED COMBUSTIBLE MATERIALS.............................................................
22 4
TRANSIENT COMBUSTIBLE REFERENCE TABLE.............................................. 23
NFPA 805 TRANSIENT COMBUSTIBLES AND FIR-NGGC-0009 IGNITION SOURCE CONTROLS PROGRAM Rev. 5 Page 4 of 26 SECTIC ATTAC-TABLE OF CONTENTS (continued)
N PAGE
-IMENT FIRE PROTECTION SUITE - TRANSIENT MANAGER.......................................... 25 TRANSIENT COMBUSTIBLE PERMIT....................................................................
26 5
6
NFPA 805 TRANSIENT COMBUSTIBLES AND FIR-NGGC-0009 IGNITION SOURCE CONTROLS PROGRAM Rev. 5 Page 5 of 26 1.0 PURPOSE The purpose of this procedure is to establish controls of general housekeeping practices and the control of transient combustibles and ignition sources in the power block (plant). The procedure also provides guidance on the amount of transient combustible materials permitted in all plant areas.
2.0 REFERENCES
2.1 Developmental
- 1.
NFPA 805, Performance-Based Standard for Fire Protection for Light Water Reactor Electric Generating Plants, 2001 Edition
- 2.
CAP-NGGC-0200, Corrective Action Program
- 3.
CHE-NGGC-0045, NGG Chemical Control Program
- 4.
HNP-F/PSA-0071, Harris Fire PRA - Fire Ignition Frequency Calculation
- 5.
HNP-M/MECH-1 129, Fire Zone of Influence Calculation
- 6.
NFPA 30 Flammable and Combustible Liquids Code
- 7.
NFPA 30B Code for the Manufacture and Storage of Aerosol Products
- 8.
NFPA 704 Standard System for the Identification of the Hazards of Materials for Emergency Response
- 9.
Progress Energy Health and Safety Guidance Document, SAF-SUBS-0024, Flammable and Combustible Liquids
- 10.
SAF-NGGC-2172, Industrial Safety 2.2 Implementing
- 1.
10 CFR 50.48TM Fire Protection-National Fire Protection Standard NFPA 805
- 2.
NUREG/CR 6850, EPRI/NRC-RES, Fire PRA Methodology for Nuclear Power Facilities
- 3.
EGR-NGGC-0028, Engineering Evaluation
- 4.
FIR-NGGC-0130, NFPA 805 Monitoring HNP
- 5.
FPP-001, Fire Protection Program Manual
NFPA 805 TRANSIENT COMBUSTIBLES AND FIR-NGGC-0009 IGNITION SOURCE CONTROLS PROGRAM Rev. 5 Page 6 of 26 2.2 Implementing (continued)
BNP
- 6.
OAP-033, Fire Protection Program Manual 3.0 DEFINITIONS
- 1.
Approved: Acceptance, by the Fire Protection Engineering or the Fire Protection Staff. Devices having been tested and accepted for a specific purpose by a nationally recognized testing laboratory shall be deemed to be approved.
- 2.
Combustible Controlled Zones (Ccz): Areas designated in the Power Block where specific administrative controls limiting combustibles are applied in support of deterministic or performance based analysis and assumptions.
Specifics are described in 3.2.1 and 3.2..1 Non-Intervening Combustible Zone.
- a.
Non-Intervening Combustible Zone: Areas designated in the Power Block where unattended transient combustible material is not allowed, except as allowed by section 9.2.2 below.
- b.
No Storage Locations: Areas in the Power Block where transient combustible materials are allowed when work is in progress. Transient materials may only be left unattended during breaks and lunches for a single shift only, except as allowed by section 9.2.3 below.
- 3.
Combustible Liquid: A liquid having a flash point at or above 1 00°F (37.80C):
Class I1: Flash points at or above 1000F and below 140 0F.
Class IliA: Flash points at or above 140°F and below 200OF Class IIIB: Flash points at or above 200OF
- 4.
Combustible Material: A material that, in the form in which it is used and under the conditions anticipated will ignite and burn.
- 5.
Fire Protection Suite (FPS): The database used in the Fire Protection Program to maintain NFPA 805 program elements.
- 6.
Flammable Liquid: A liquid having a flash point below 100°F (37.80C) and having a vapor pressure not exceeding 40 pounds per square inch (absolute) at 100°F (37.81C):
Class IA: Flash point below 730F and boiling point below 100OF
NFPA 805 TRANSIENT COMBUSTIBLES AND FIR-NGGC-0009 IGNITION SOURCE CONTROLS PROGRAM Rev. 5 Page 7 of 26 3.0 DEFINITIONS (continued) 0 Class IB: Flash point below 730F and boiling point at or above 100°F Class IC: Flash point at or above 730F and below 100°F
- 7.
Fuel Package: Aggregate value of combustible materials entered into FPS for approved work.
- 8.
Ignition Sources: Any process or event that is capable of causing a fire or explosion, such as open flames, sparks and hot surfaces.
- 9.
Non-Power Operation: As applied to Fire Areas associated with the affected Unit, when that unit is in Mode 5, 6, or when the core is off-loaded for Pressurized Water Reactor (PWR), and Mode 4, 5 or when the core is off-loaded for Boiling Water Reactors (BWR).
- 10.
Permanent Staging (Storage) Locations: Fire Protection approved areas in the Power Block where placement of flammable or combustible materials is allowed. Compensatory Actions or Transient Combustible Permit are not required for storage in these areas.
- 11.
Power Block And Plant: As defined in plant fire protection program manual.
- 12.
Transient Combustibles: Flammable or combustible material not permanently installed or stored in a Permanent Staging Area.
4.0 RESPONSIBILITIES 4.1 Fire Protection - Operations / Work Control Center / STA
- 1.
Review and approve/reject temporary storage and/or use of transient flammable or combustible material in the Power Block that cannot meet the separation requirements of this procedure, and track the transient material until removed.
- 2.
Determine any Compensatory Actions required if separation criteria cannot be maintained.
- 3.
Ensure that general requirements of this procedure are being maintained. Enter any discrepancies noted into the Corrective Action Process.
4.2 Fire Protection Engineering
- 1.
Monitor and track transient control program performance.
- 2.
Approve permanent staging locations.
NFPA 805 TRANSIENT COMBUSTIBLES AND FIR-NGGC-0009 IGNITION SOURCE CONTROLS PROGRAM Rev. 5 Page 8 of 26 4.3 Plant Work Groups
- 1.
Maintain the work area in accordance with the procedure.
- a.
Limit transient combustibles to those necessary for the performance of assigned tasks.
- b.
Communicate with the Operations Fire Protection Coordinator/Work Control Center, as required to assess/understand maximum transient combustibles allowed in the area.
- c.
Assure transient combustibles are stored or removed within the time restrictions imposed by this procedure.
- d.
Ensure separation requirements are being maintained, approved storage is within guidance.
- e.
Ensure applicable compensatory measures are established.
4.4 Nuclear Plant Personnel
- 1.
Reduce or eliminate packaging material prior to the introduction of any item into the Power Block.
- 2.
Promptly place any waste transient combustible packaging material or waste combustible material from work activities in an approved waste container or promptly remove the material from the area.
5.0 PREREQUISITES N/A 6.0 PRECAUTIONS, LIMITATIONS AND NOTES N/A 7.0 SPECIAL TOOLS AND EQUIPMENT N/A 8.0 ACCEPTANCE CRITERIA N/A
NFPA 805 TRANSIENT COMBUSTIBLES AND FIR-NGGC-0009 IGNITION SOURCE CONTROLS PROGRAM Rev. 5 Page 9 of 26 9.0 INSTRUCTIONS 9.1 General Requirements
- 1.
Maintain the work area neat and clean.
- 2.
Waste, debris, scrap, packing materials, or other combustibles shall be removed from an area immediately following the completion of work or at the end of the shift, whichever comes first.
- 3.
Containers are emptied on a schedule that removes the combustibles prior to exceeding container capacity, but should a specific work activity approach container capacity, notify housekeeping.
- 4.
Keep aisles and doors clear at all times. Tags and signage shall be installed in such a way that does not block normal access/egress paths, safe shutdown walk paths or emergency lights.
- 5.
Stairwells shall not be used for storage of combustible materials, except for approved Permanent Staging Locations.
- 6.
Do not block access to firefighting equipment.
- 7.
Maintain clearance of 18 inches below sprinkler heads.
NOTE The term "pressure-impregnated" refers to the method of application of the fire retardant chemical.
- 8.
Wood used within the Power Block shall be listed pressure-impregnated or coated with a listed fire-retardant application. Exception: Cribbing timbers 6 in.
by 6 in. (15.2 cm by 15.2 cm) or larger shall not be required to be fire-retardant treated.
- 9.
Plastic sheeting materials used in the Power Block shall be fire-retardant types that have passed NFPA 701, Standard Methods of Fire Tests for Flame Propagation of Textiles and Films, large-scale tests, or equivalent.
- 10.
Permanent Staging Locations shall be designated, and limits shall be established on the types and quantities of stored materials.
- 11.
Portable fuel fired heaters shall not be permitted in plant areas containing equipment important to nuclear safety or where there is a potential for radiological releases resulting from a fire.
NFPA 805 TRANSIENT COMBUSTIBLES AND FIR-NGGC-0009 IGNITION SOURCE CONTROLS PROGRAM Rev. 5 Page 10 of 26 9.1 General Requirements (continued)
- 12.
Use of portable electric heaters shall be in accordance with the manufactures recommendations, including adequate clearance and separation from combustible materials.
- 13.
Adequate clearance, free of combustible material, shall be maintained around energized electrical equipment. Refer to Section 9.2.1.3 for separation of Combustibles from Plant Equipment and Cabling.
- 14. lists exempted materials not considered as transient combustibles under this procedure. Exempted items in Non-Intervening Combustible Areas are limited to those identified in Attachment 3, by an asterisk(*).
- 15.
The following applies to vehicles located in the Power Block buildings:
- 16.
No fluid/fuel leaks
- 17.
A valid fire extinguisher readily accessible
- 18.
Tractor trailer trucks shall not be left unattended in the power block
- 19.
The tractor must be removed if the trailer is to be left unattended
- 20.
Aerosol cans used in the RCA shall be disposed of by placing them in a designated flammable liquid locker.
9.2 Transient Combustible Controls In The Power Block 9.2.1 General Use of Transient Combustibles
- 1.
IF the material is to be used during a shift and left unattended only during breaks and lunches and removed at the end of the shift, THEN no transient combustible tracking is required.
- 2.
IF the material is to remain in the power block unattended beyond the work shift, and is not exempted by Attachment 3, Exempted Combustible Materials, THEN a transient combustible permit is required for the material with the following compensatory actions:
Fuel Package Compensatory Action
<3 Million BTUs No Fire Watch Required 3-6 Million BTUs Hourly Fire Watch
>6 Million BTUs Continuous Fire Watch
NFPA 805 TRANSIENT COMBUSTIBLES AND FIR-NGGC-0009 IGNITION SOURCE CONTROLS PROGRAM Rev. 5 Page 11 of 26 9.2.1 General Use of Transient Combustibles (continued)
Individual fuel packages should be separated by a minimum of 20 feet (edge-to-edge) within a single fire area. Where separation of individual fuel packages is not achieved, then the material shall be considered one fuel package. BTU values for typical combustible materials are listed in Attachment 4.
- 3.
Material not exempted by Attachment 3, Exempted Combustible Materials, shall be separated from energized equipment, vertical and horizontal conduit and cable trays by an adequate distance as described below. If separation distances cannot be maintained, and the material will be left unattended beyond the work shift, provide an hourly fire watch.
Fuel Package Separation Distances
<3 Million BTUs 3'-0" horizontal, 6'-0" vertical 3-6 Million BTUs 6'-0" horizontal, 8'-0" vertical
>6 Million BTUs Review w/ Fire Protection Engineering 9.2.2 Use of Transient Combustibles in Non-Intervening Combustible Zones
- 1.
Transient materials may not be left unattended in Non-Intervening Combustible Zones. No material may remain after work is completed or left unattended, including breaks and lunch, without a transient combustible permit and a Continuous Fire Watch.
- 2.
Exempted items in Non-Intervening Combustible Areas are identified in, by an asterisk(*).
- 3.
Non-Intervening Combustible Zones are listed in Attachments land 2.
- 4.
When provided, see job aid for drawings showing Non-Intervening Combustible Zones, see job aid (HNP-Combustible Control Zones) 9.2.3 Use of Transient Combustibles in No Storage Locations
- 1.
IF the material is to be used during a shift and left unattended only during breaks and lunches and removed at the end of the shift, THEN no transient combustible permit is required.
- 2.
IF material is to remain in the No Storage Area unattended beyond breaks and lunches, THEN a transient combustible permit and an Hourly Fire Watch are required.
- 3.
Material must be separated by an adequate distance as described in 9.2.1.3. If separation distances cannot be maintained, the material is not exempted by and will be left unattended beyond the work shift, then a Continuous Fire Watch is required.
NFPA 805 TRANSIENT COMBUSTIBLES AND FIR-NGGC-0009 IGNITION SOURCE CONTROLS PROGRAM Rev. 5 Page 12 of 26 9.2.3 Use of Transient Combustibles in No Storage Locations (continued)
- 4.
No Storage Locations are listed in Attachment 1 and 2.
- 5.
When provided, Fire Protection Engineering shall maintain drawings showing No Storage Locations, see job aid (HNP-Combustible Control Zones).
9.3 Permanent Staging Locations NOTE The Fire PRA uses weighting factors for storage which are associated with the amount of combustible material typically stored in specific fire compartments.
Permanent Staging Locations and amounts of combustibles have been analyzed and approved by Fire Protection Engineering. New areas and changes to existing areas may be approved by Engineering Evaluation in accordance with EGR-NGGC-0028 or other approved methods. Fire Protection Engineering shall maintain a list of approved permanent staging areas in the plant, see job aid (HNP-Permanent Staging Locations).
9.4 Flammable I Combustible Liquids Controls In The Power Block 9.4.1 General Use of Flammable/Combustible Liquids
- 1.
Combustible liquids, including high flashpoint lubricating oils, shall be kept from coming in contact with hot pipes and surfaces, including insulated pipes and surfaces.
- 2.
Any flammable or combustible liquids accidentally spilled shall be promptly cleaned up and materials disposed of properly (particularly oil spills on insulation materials). Proper disposal methods (in self-closing metal safety containers) shall be utilized to prevent spontaneous combustion of liquid soaked rags and/or materials. Refer to CHE-NGGC-0045, for spill reporting requirements.
9.4.2 Storage of Flammable/Combustible Liquids and Aerosols The following requirements shall apply to the storage of flammable or combustible liquids and aerosols, unless a specific written exemption has been granted by Fire Protection Engineering and documented on a transient combustible permit:
- 1.
Only approved flammable or combustible liquid storage cabinets, portable tanks, container drums, and safety cans shall be used for the storage of flammable or combustible liquids and aerosols.
- 2.
All storage containers shall be labeled in accordance with CHE-NGGC-0045.
NFPA 805 TRANSIENT COMBUSTIBLES AND FIR-NGGC-0009 IGNITION SOURCE CONTROLS PROGRAM Rev. 5 Page 13 of 26 9.4.2 Storage of Flammable/Combustible Liquids and Aerosols (continued)
- 3.
Glass containers for transporting flammable liquids are permitted only when required for material quality reasons. Allowable glass container size is as follows:
Flammable Liquids Combustible Liquids Class IA Class lB Class IC Class II Class III 1 pint 1 quart 1 gallon 1 gallon 5 gallon
- 4.
Glass containers may be used by the Chemistry Unit in lab areas.
- 5.
When not in use, containers, safety cans, and aerosol cans, containing flammable or combustible liquids, should be stored in approved storage cabinets.
- 6.
The quantity of flammable liquids in safety cans located outside a storage cabinet in any one fire area of a building shall not exceed 2 gallons for Class 1A flammable liquids, or 5 gallons for all other flammable liquids or one safety can.
- 7.
No more than 60 gallons of flammable or combustible liquids shall be stored in any one cabinet; and, no more than 660 gallons shall be stored in any one portable tank.
- 8.
No more than three storage cabinets shall be located in any one fire area, except that an additional cabinet or group of not more than three cabinets may be located in the same fire area if separated from any other cabinets or group of cabinets by at least 100 feet.
- 9.
The quantity of combustible liquids in safety cans located outside a storage cabinet in any one fire area of a building shall not exceed 10 gallons or two safety cans.
- 10.
The quantity of combustible liquids in safety cans located outside a storage cabinet in any one fire area of a building shall not exceed 10 gallons or two safety cans.
- 11.
The quantity of combustible liquids in drums located in any one fire area shall not exceed 120 gallons.
- 12.
No more than one portable tank containing flammable or combustible liquids shall be located in any one fire area.
NFPA 805 TRANSIENT COMBUSTIBLES AND FIR-NGGC-0009 IGNITION SOURCE CONTROLS PROGRAM Rev. 5 Page 14 of 26 9.4.2 Storage of Flammable/Combustible Liquids and Aerosols (continued)
- 13.
Portable tanks shall be closed and an approved emergency relief vent in place for the protection against overpressure and potential rupture during fire exposure.
- 14.
Transfer of flammable and combustible liquids from one tank or container to another container shall be separated from other operations in the building by adequate distance or by construction having adequate fire resistance.
- 15.
Pressurized gas shall not be used to transfer flammable or combustible liquids.
- 16.
Containers with over 30 gallons of flammable or combustible liquids shall not be stacked one upon another.
- 17.
NO SMOKING signs shall be posted in areas where flammable liquids are stored. Signs are not required in buildings where smoking is prohibited.
- 18.
Original DOT Approved shipping containers may be used for storage of flammable or combustible liquids and aerosols.
9.4.3 Use of Flammable/Combustible Liquids and Aerosols The following requirements shall apply to the use of flammable or combustible liquids and aerosols, unless a specific written exemption has been granted by Fire Protection Engineering and documented on a transient combustible permit:
- 1.
IF any flammable or combustible liquid is to remain inside power block buildings longer than one shift, THEN it must be stored in an approved cabinet.
- 2.
Flammable or combustible liquids shall only be used when contained in an approved container.
- 3.
Flammable or combustible liquids placed in an approved container shall be labeled as to its contents and the requirements of NFPA 704 and CHE-NGGC-0045.
- 4.
Dispensing of flammable or combustible liquids from metal containers shall be by approved pump or self-closing valve.
- 5.
Metal containers and portable metal tanks used for flammable or combustible liquids shall be electrically grounded during transfer of liquids.
- 6.
When transferring flammable liquids, a grounding strap shall be connected between the containers involved whenever the possibility of electrical sparking exists.
NFPA 805 TRANSIENT COMBUSTIBLES AND FIR-NGGC-0009 IGNITION SOURCE CONTROLS PROGRAM Rev. 5 Page 15 of 26 9.4.3 Use of FlammablelCombustible Liquids and Aerosols (continued)
- 7.
When left unattended no more than 2 gallons for Class 1A flammable liquids or 5 gallons for all other flammable liquids or one safety can, shall be located in any one fire area.
- 8.
When left unattended no more than 10 gallons of combustible liquids or two safety cans shall be located in any one fire area.
- 9.
When left unattended no more than 10 aerosol containers shall be located outside a storage cabinet in any one fire area of a building.
- 10.
Use of flammable or combustible liquids will be such that leakage of the liquid is controlled and accidental spills are prevented.
- 11.
Any flammable or combustible liquids accidentally spilled shall be cleaned up and materials disposed of promptly. Proper disposal methods (in self closing metal safety containers) shall be utilized to prevent spontaneous combustion of liquid soaked rags and/or materials.
9.4.4 Drain Cans Drain cans may be used where combustible liquids are present during maintenance activities or when equipment is operating and there is a need for a collecting container.
If a drain can is used, the following restrictions apply:
- 1.
For maintenance activities, the maintenance work crew is responsible for removing the drain can and properly disposing of the combustible liquid.
- 2.
For operating equipment, the drain can shall be checked by an operator on a periodic basis to ensure the container does not over flow.
- 3.
When a drain can is removed, the contents shall be properly stored or disposed of at the time of removal.
9.4.5 Storage Cabinets
- 1.
Storage cabinets shall be approved, located and inspected in accordance with CHE-NGGC-0045.
- 2.
Each Storage Cabinet shall be structurally intact. To be considered structurally intact, all of the following must be met:
The metal shell is in good condition without rust and holes.
The vent/drain plugs are in place and tightly secured.
The door hardware is in good operating order.
NFPA 805 TRANSIENT COMBUSTIBLES AND FIR-NGGC-0009 IGNITION SOURCE CONTROLS PROGRAM Rev. 5 Page 16 of 26 9.4.5 Storage Cabinets (continued)
The doors are latched shut with cabinet latch (NOT hasp and lock).
The cabinet is clearly marked in conspicuous lettering "FLAMMABLE/COMBUSTIBLE - KEEP FIRE AWAY", or similar wording.
No material is stored on top of the cabinet.
The area surrounding the cabinet is clean and free of obstructions to fire fighting access.
The total capacity of the storage cabinet is not exceeded.
- 3.
Each Storage Cabinet shall have a fixed label designating the following:
0 Cabinet Number Maximum Storage Capacity Location (Building, column, room, etc.)
Responsible Organization (Operations, Maintenance, Chemistry &
Environmental, Radiation Protection, etc.)
9.5 Non-Power Operations
- 1.
When the plant is in Non-Power Operations as defined in section 3.9:
- a.
The No Storage Locations and Non-Intervening Combustible Area requirements are suspended.
- b.
The requirements of Sections 9.2 and 9.3 are not required if regularly scheduled Hourly Fire Watches patrol the area for all areas of the power block with the exception of Containment.
- c.
The requirements of Sections 9.2 and 9.3 are not required for the Containment building if a roving Continuous Fire Watch patrol has been established.
- d.
All other sections of this procedure and other plant procedures remain in effect during Non-Power Operations.
10.0 RECORDS N/A
NFPA 805 TRANSIENT COMBUSTIBLES AND FIR-NGGC-0009 IGNITION SOURCE CONTROLS PROGRAM Rev. 5 Page 17 of 26 ATTACHMENT 1 Page 1 of 2 HNP COMBUSTIBLE CONTROL ZONES Fire Area Fire Zone Room CCZ Type Description Numbers 1-A-BAL-A 1-A-2-MP A661 Non-Intervening Misc Equip Rm RAB 216 =31-36/ E-G Combustible Zone 1-A-BAL-A 1-A-3-MP A461 Non-Intervening M-Pen Area RAB 236=31-36/E-FW Combustible Zone 1-A-BAL-A 1-A-3-COR A458 Non-Intervening Access Corr. - RAB 236=13-15/E-G Combustible Zone 1-A-BAL-A 1-A-3-PB A459 Non-Intervening Pump Area - RAB 236 15 / B-C Combustible Zone 1-A-BAL-B 1-A-4-CHLR A104 Non-Intervening Chiller Room-RAB 261 28-31 / B-E Combustible Zone 1-A-BAL-B 1-A-4-CHLR A104 Non-Intervening Chiller Room-RAB 261 18-39 / B-E Combustible Zone 1-A-BAL-B 1-A-4-COMB 126A Non-Intervening Misc Equip Area-RAB 261 = 41-42/ E Combustible Zone 1-A-BAL-B 1-A-4-COME A128C Non-Intervening Equip. Area - RAB 261 = 42-43 / GX Combustible Zone 12-A-CR 12-A-6-RT1 A370, A371 No Storage Relay/Termination Room - RAB 305 12-A-6-CRC1 12-A-6-ARP1 A384 No Storage ARP Room - RAB 305 12-A-6-CRC1 12-A-6-PICR1 A387 No Storage PlC Room - RAB 305 12-A-6-CRC1 12-A-6-RCC1 A374 No Storage Rod Drive Set Room - 305' RAB 1-A-BAL-A 1-A-2-MP A661 No Storage Misc Equip Rm RAB 216 =31-36/ E-G 1-A-BAL-A 1-A-2-PT A663, A664, No Storage Service Water Pipe Tunnel 216' RAB A665 1-A-BAL-J 1-A-5-BATN A250 No Storage Battery Room Non-Safety - 286' RAB 1-A-ACP 1-A-ACP A256 No Storage ACP Room - RAB 286 1-A-BAL-A 1-A-4-TA A101 No Storage CST Area 261' RAB, Col 8/12-BIG 1-A-BAL-A 1-A-3-MP A461 No Storage M-Pen Area RAB 236 1-A-BAL-A 1-A-3-PB A459 No Storage Pump Area - RAB 236 1-A-BAL-A 1-A-3-COMB A475 No Storage Misc Equip Area-RAB 236 1-A-BAL-A 1-A-3-COME ALL No Storage Misc Equip Area - RAB 236 1-A-BAL-A 1-A-3-COMI A509 No Storage RAB 236 Corridor 1-A-BAL-B 1-A-4-COR ALL No Storage Corridor-RAB 261 1-A-BAL-B 1-A-4-COMB A126A No Storage Chlr. Surge RAB 261' COL 41/43-B/C 1-A-BAL-B 1-A-4-COMB A128A No Storage Chir. Surge RAB 261' Col 41/43-C/E 1-A-BAL-B 1-A-4-COME ALL No Storage Access Aisle - RAB 261 1-A-BAL-C 1-A-5-HVB A257A No Storage H&V & Elect Room-RAB 286 1-A-BAL-G 1-A-BAL-G A463, A463A No Storage 1C-CSIP-SAB Transfer Switch Room 1-A-BAL-H 1-A-BAL-H A465, A465A No Storage 1C-CSIP-SAB Charging Pump Room
NFPA 805 TRANSIENT COMBUSTIBLES AND FIR-NGGC-0009 IGNITION SOURCE CONTROLS PROGRAM Rev. 5 Page 18 of 26 ATTACHMENT 1 Page 2 of 2 HNP COMBUSTIBLE CONTROL ZONES Fire Area Fire Zone Room CCZ Type Description Numbers 1-A-BAL-J 1-A-5-HVA A246A No Storage H&V & Elect Room-RAB 286 1-A-BATA 1-A-BATA A249 No Storage Battery Room A - 286' RAB 1-A-BATB 1-A-BATB A255 No Storage Battery Room B - 286' RAB 1-A-CSRA 1-A-CSRA A273 & A275 No Storage Cable Spread Room A - 286' RAB 1-A-CSRB 1-A-CSRB A274A No Storage Cable Spread Room B - 286' RAB 1-A-EPA 1-A-EPA A102 No Storage A Elect Pen Room - RAB 261 1-A-EPB 1-A-EPB A110 No Storage B Elect Pen Room - RAB 261 1-A-SWGRA 1-A-SWGRA A251 No Storage Switchgear Room A - 286' RAB 1-A-SWGRB 1-A-SWGRB A252 No Storage Switchgear Room B - 286' RAB 1-C 1-C R101, R102, No Storage Containment Building All Elevations R103 I
I I
5-W-BAL 5-W-4-SWG1 W173 No Storage WPB Switchgear Room 1 - 276' 5-W-BAL 5-W-4-SWG2 W174 No Storage WPB Switchgear Room 2 - 276'
NFPA 805 TRANSIENT COMBUSTIBLES AND FIR-NGGC-0009 IGNITION SOURCE CONTROLS PROGRAM Rev. 5 Page 19 of 26 ATTACHMENT 2 Page 1 of 3 BNP COMBUSTIBLE CONTROL ZONES Fire Area Fire Zone Room CCZ Type Description Numbers CB-1 CB-01A NA No Storage Unit 1 Cable Access Way (North East Rattle Space)'23' Elevation CB-1 CB-01 B NA No Storage Unit 1 Cable Access Way (North West Rattle Space)'23' Elevation CB-2 CB-02A NA No Storage Unit 2 Cable Access Way (South East Rattle Space)'23' Elevation CB-2 CB-02B NA No Storage Unit 2 Cable Access Way (South West Rattle Space)'23' Elevation CB-23E CB-05 NA No Storage Unit 1 Cable Spreading Room'23' Elevation CB-23E CB-06 NA No Storage Unit 2 Cable Spreading Room'23' Elevation CB-23E CB-14 NA No Storage Unit 1 Computer Room North'49' Elevation CB-23E CB-15 NA No Storage Unit 2 Computer Room South'49' Elevation CB-23E CB-16 NA No Storage Auxiliary Operator Briefing Room CB-23E CB-17 NA No Storage Operator Break Room CB-23E CB-18 NA No Storage Ladies Washroom CB-23E CB-22 NA No Storage Mens Washroom CB-23E CB-23 NA No Storage Control Room'49' Elevation DG-8 DG-08 NA Non-Intervening E7 Switchgear Room, 23ft Combustible Zone RB1-1 RB1-01A NA No Storage Reactor Building Southwest Core Spray, minus 17ft RB1-1 RB1-01B NA No Storage Reactor Building Northwest Core Spray, minus 17ft RB1-1 RB1-01C NA No Storage Reactor Building Northeast RHR Room, minus 17ft RB1-1 RB1-01D NA No Storage Reactor Building Southeast RHR Room, minus 17ft RB1-1 RB1-01E NA No Storage Reactor Building Northeast RHR Heat Exchanger, 20ft RB1-1 RB1-01F NA No Storage Reactor Building Southeast RHR Heat Exchanger, 20ft RB1-1 RB1-01G(EC)
NA Non-Intervening Reactor Building East Central, 20ft Combustible Zone RB1-1 RB1-01G(NC)
NA No Storage Reactor Building North Central, 20ft RB1-1 RB1-01G(SW)
NA Non-Intervening Reactor Building Southwest Corner, 20ft Combustible Zone RB1-1 RB1-01H(EC)
NA Non-Intervening Reactor Building East Central, 50ft Combustible Zone RB1-1 RB1-01H(NC)
NA No Storage Reactor Building North Central, 50ft RB1-1 RB1-01H(NE)
NA No Storage Reactor Building Northeast Corner, 50ft RB1-1 RB1-01H(NW)
NA No Storage Reactor Building Northwest Corner, 50ft RB1-1 RB1-01H(SE)
NA No Storage Reactor Building Southeast Corner, 50ft RB1-1 RB1-01H(SW)
NA No Storage Reactor Building Southwest Comer, 50ft RB1-1 RB1-01H(WC)
NA No Storage Reactor Building West Central, 50ft
NFPA 805 TRANSIENT COMBUSTIBLES AND FIR-NGGC-0009 IGNITION SOURCE CONTROLS PROGRAM Rev. 5 Page 20 of 26 ATTACHMENT 2 Page 2 of 3 BNP COMBUSTIBLE CONTROL ZONES Fire Area Fire Zone Room CCZ Type Description Numbers RB1-1 RB1-011 NA No Storage Reactor Building RWCU Access Room, 77ft RB1-1 RB1-01J NA No Storage Reactor Building West, 80ft RB1-1 RB1-01K NA No Storage Reactor Building East, 80ft RB1-1 RB1-01N NA Non-Intervening Reactor Building HPCI Roof Mezzanine, 5ft Combustible Zone RB1-1 RB1-010 NA Non-Intervening Reactor Building ECCS Tunnel Roof, 36ft Combustible Zone RBI-1 RB1-05 NA No Storage Reactor Building HP Field Office, Decontamination Room, 20ft RB1-1 RB1-07 NA Non-Intervening Reactor Building Drywell Entry, 20ft Combustible Zone RB1-1 RB1-12 NA No Storage Reactor Building RWCU Backwash Tank Room, 77ft RB1-1 RB1-13 NA No Storage Reactor Building CRD Repair Room, 80ft East RB1-1 RB1-20 NA No Storage Reactor Building RWCU Valve Room, 77ft RB1-1 RB1-21 NA No Storage Reactor Building Resin Storage Room, 80ft East RB2-1 RB2-01A NA No Storage Reactor Building Southwest Core Spray, minus 17ft RB2-1 RB2-01 B NA No Storage Reactor Building Northwest Core Spray, minus 17ft RB2-1 RB2-01C NA No Storage Reactor Building Northeast RHR Room, minus 17ft RB2-1 RB2-01D NA No Storage Reactor Building Southeast RHR Room, minus 17ft RB2-1 RB2-01G(EC)
NA Non-Intervening Reactor Building East Central, 20ft Combustible Zone RB2-1 RB2-01 G(NC)
NA No Storage Reactor Building North Central, 20ft RB2-1 RB2-01G(SE)
NA No Storage Reactor Building Southeast Corner, 20ft RB2-1 RB2-01 H(EC)
NA Non-Intervening Reactor Building East Central, 50ft Combustible Zone RB2-1 RB2-01 H(NC)
NA No Storage Reactor Building North Central, 50ft RB2-1 RB2-01 H(NE)
NA No Storage Reactor Building Northeast Corner, 50ft RB2-1 RB2-01 H(NW)
NA No Storage Reactor Building Northwest Corner, 50ft RB2-1 RB2-01 H(SE)
NA No Storage Reactor Building Southeast Corner, 50ft RB2-1 RB2-01 H(SW)
NA No Storage Reactor Building Southwest Corner, 50ft RB2-1 RB2-01 H(WC)
NA No Storage Reactor Building West Central, 50ft RB2-1 RB2-011 NA No Storage Reactor Building RWCU Access Room, 77ft RB2-1 RB2-01J NA No Storage Reactor Building West, 80ft RB2-1 RB2-01 K NA No Storage Reactor Building East, 80ft RB2-1 RB2-01 N NA Non-Intervening Reactor Building HPCI Roof Mezzanine, 5ft Combustible Zone RB2-1 RB2-010 NA Non-Intervening Reactor Building ECCS Tunnel Roof, 36ft Combustible Zone
NFPA 805 TRANSIENT COMBUSTIBLES AND FIR-NGGC-0009 IGNITION SOURCE CONTROLS PROGRAM Rev. 5 Page 21 of 26 ATTACHMENT 2 Page 3 of 3 BNP COMBUSTIBLE CONTROL ZONES Fire Area Fire Zone Room CCZ Type Description Numbers RB2-1 RB2-04 NA No Storage Reactor Building MSIV Pit, 50ft RB2-1 RB2-05 NA No Storage Reactor Building HP Field Office, Decontamination Room, 20ft RB2-1 RB2-09 NA No Storage Reactor Building Elevator Shaft RB2-1 RB2-10 NA No Storage Reactor Building RWCU Pump and Heat Exchanger Room, 50ft RB2-1 RB2-12 NA No Storage Reactor Building RWCU Backwash Tank Room, 77ft RB2-1 RB2-13 NA No Storage Reactor Building CRD Repair Room, 80ft East RB2-1 RB2-18 NA No Storage Reactor Building Supply Room, 98ft RB2-1 RB2-18GA NA No Storage Reactor Building Platform, 98ft RB2-1 RB2-19 NA No Storage Reactor Building Clothing Change room, 98ft RB2-1 RB2-20 NA No Storage Reactor Building Resin Storage Room, 80ft East RB2-1 RB2-21 NA No Storage Reactor Building RWCU Valve Room, 77ft RB2-6 RB2-06 NA No Storage Reactor Building ECCS Mini Steam Tunnel, 20ft
NFPA 805 TRANSIENT COMBUSTIBLES AND FIR-NGGC-0009 IGNITION SOURCE CONTROLS PROGRAM Rev. 5 Page 22 of 26 ATTACHMENT 3 Page 1 of 1 EXEMPTED COMBUSTIBLE MATERIALS NOTE Items denoted below by an Asterisk (*) and Bolded are exempted in Non-Intervening Combustible Areas.
- Fiberglass ladders (with associated rope(s))
- Signs, Postings, Permits, Cautions Tags, Clearance Tags, Warnings
- Tape, Ty-wraps, and other similar attachment or incidental items
- Drip Bags and spill containment materials including tubing
- Non-combustible carts with rubber/plastic wheels
- Step-off Pad with 2 PPE containers
- Work site barriers (ropeltape) and signs
- Camera configurations and associated remote telemetry monitoring cable(s)
- Safety Barrier Netting (unrolled/installed)
- Combustibles in closed metal containers such as cabinets, tool boxes, gang boxes, metal drums necessary for work performance Procedures located in the area to support the use of plant equipment Operator notebooks Portable Electric Heaters (120V or less)
Portable Air Compressors Portable HEPA Units (w/ <10ft of Hose)
Computers, test equipment and leads, limited to single PC or equal amounts of smaller test devices and leads
" Vacuum cleaners, floor polishers HP Portable Radiation Monitors Welding Machines including wheels Power cords on portable equipment (extended)
Extension cords/cable, or welding leads (extended)
Portable Power Supply Buggies Housekeeping/cleaning supplies (e.g., floor signs, mops, buckets, towels, brooms, oil absorbent pads) in use and removed from normal storage location Plastic sleeving and spill blockers Rubber mats (unrolled) on concrete Flammable or combustible material while being transported or when stored in a metal container with a tight fitting lid or any UL Listed or Factory Mutual (FM) approved storage cabinet Combustibles in metal receptacles equipped w/ self-closing or self-extinguishing type lids Incidental combustible item(s) in quantities <105,000 BTUs In-Use Wood Cribbing (fire retardant treated, or as allowed under section 9.1.8)
" Wooden insulation blocks used for cable as part of plant design.
NFPA 805 TRANSIENT COMBUSTIBLES AND FIR-NGGC-0009 IGNITION SOURCE CONTROLS PROGRAM Rev. 5 Page 23 of 26 ATTACHMENT 4 Page 1 of 2 TRANSIENT COMBUSTIBLE REFERENCE TABLE Description Weight BTUILB
& FT 3 Acetone 1 lb 13,300 Acetylene (Gas) 1 ft3 1,500 Alcohol 1 lb 12,800 Blue Matting 0.2 lb/ t2 12,000 Cardboard B10 Drum 5 lbs each 7,900 Charcoal 55 Gallon Drum of Dry 235 lbs 14,500 Cords Drop and Extension
.175 lb/ft 21,000 Cotton (PCs) 1 lb 9,500 Electric Cable 10/3 SOW
.28 lb/ft 21,000 Electric Cable 10/3 Type XLPI
.19 lb/ft 21,000 Electric Cable 10/4 SO
.155 lb/ft 21,000 Electric Cable 10/4 SOW
.35 lb/ft 21,000 Electric Cable 12/3 SO
.175 lb/ft 21,000 Electric Cable 12/4 SOW
.21 lb/ft 21,000 Electric Cable 14/3 SO
.136 Ib/ft 21,000 Electric Cable 4/4 Type W
.585 lb/ft 21,000 Electric Cable 6/4 Type W 480V drop cord
.566 lb/ft 21,000 Electric Cable 8/4 Type W
.52 lb/ft 21,000 Electric Cable #16/32
.25 lb/ft 21,000 Electric Cable #2/3 Type K
.448 lb/ft 21,000 Electric Cable #3/4 Type W 1.495 lb 21,000 Ethyl Ether 1 lb 22,000 FYQUEL 220 MSDS sheet 275 1 lb 1,100 Gasoline (Flammable Liquid) 1 lb 19,900 Herculite
.017 lb/ft2 21,000 Hose %" Red Rubber
.4 lb/ft 21,000 Hose 1" Red Rubber
.5 lb/ft 21,000 Hose Clear HEPA Hose
.08 lb/ft or 2 lb per 25 foot 21,000 Hose Orange or Black HEPA
.4 lb/ft or 10 lb per 25 foot 21,000 Hydraulic Oil 1 lb 20,400 Hydrogen (Gas) 1 ft3 325 Kerosene (Combustible Liquid) 1 lb 19,900 Liquids Combustible Flash point greater 1 lb 20,000 than 100 degrees F.
NFPA 805 TRANSIENT COMBUSTIBLES AND FIR-NGGC-0009 IGNITION SOURCE CONTROLS PROGRAM Rev. 5 Page 24 of 26 ATTACHMENT 4 Page 2 of 2 TRANSIENT COMBUSTIBLE REFERENCE TABLE Description Weight BTUILB
& CUBIC FT Liquids Flammable Flash point less than 1 lb 20,000 100 degrees F.
Lubricating Oil, SA 40 1 lb 20,400 Lumber (Pine) 1 lb 8,500 Man Lifts (oil) 70 lbs 20,400 Nylon Lift Straps 1" x 6'
.80 lbs 21,000 Nylon Lift Straps 1" x 4'
.62 Ibs 21,000 Nylon Lift Straps 2"x 10' 4.77 lbs 21,000 Nylon Lift Straps 2" x 20' 5.11 lbs 21,000 Paper 1 lb 7,900 Paint 1 lb 21,000 Plastic for HP Tents
.017 lb/ft 21,000 Propane (Gas) 1 ft3 2,500 Rad Rope (Spool)
.03 lb/ft 21,000 Ray Wall (UV Shield) per piece 7,000 Rubber Mats 1lb/ ft2 12,000 Safety Harness w/lanyard 5 Ib 21,000 Tygon Tube
.1 lb/ft 21,000 Welding Leads
.1 lb/ft 21,000 Wood 1 lb 8,500
NFPA 805 TRANSIENT COMBUSTIBLES AND FIR-NGGC-0009 IGNITION SOURCE CONTROLS PROGRAM Rev. 5 Page 25 of 26 ATTACHMENT 5 Page 1 of 1 FIRE PROTECTION SUITE - TRANSIENT MANAGER The Fire Protection Suite (FPS) is a web-based application and the Transient Manager T'm is utilized for Combustible Tracking in the Power Block or Plant. A hardcopy printout of the Transient Combustible Permit, Attachment 6 (or facsimile) may be used for approvals, and entered into FPS when available. Only those "open or active" manually generated permits (Attachment 6) need be entered into FPS when it becomes initially available or returned to service in the future. Also, manually generated permits may be discarded once entered into FPS, or the task is closed / complete.
http://fps.nexus-tech.com/hnp/
http://fps.nexus-tech.com/bnpl TM allows fire protection engineers to track both fixed and transient combustible loading by fire zone and fire area. They take into account the type and quantities of material available within the area.
The Transient Manager tracks Transient Combustible Loading, creates and tracks the Transient Permits, and generates various reports.
NFPA 805 TRANSIENT COMBUSTIBLES AND FIR-NGGC-0009 IGNITION SOURCE CONTROLS PROGRAM Rev. 5 Page 26 of 26 ATTACHMENT 6 Page 1 of 1 TRANSIENT COMBUSTIBLE PERMIT PERMIT NO.
Requestor / Responsible Person Phone Date Issued Estimated Duration ESR, WR/JO (Not to exceed 6 months)
Location: Unit Building_
Fire Area Fire Zone Elev.
Reason for Storage/Use Is Fuel Package Separated from other Fuel Packages by a Minimum of 20 feet within a Single Fire Area?
Yes
-I No E--
Type of Material Quantity BTU/LB Line Total BTU/FT3 BTU
!SumTotal BTU General Transient Combustibles:
0I Transient Combustible in Non-Intervening Combustible Zones (Non-Exempt Items):
0]
Transient Combustible in No Storage Locations:
-I Fire Watch: EI None EI Hourly-Roving LI Continuous Comments/Special Provisions:
Approved By:_
Date Fire Protection Coordinator or Designee