05000219/LER-2013-002, Regarding Manual Scram Due to Lowering Vacuum

From kanterella
(Redirected from ML14008A097)
Jump to navigation Jump to search
Regarding Manual Scram Due to Lowering Vacuum
ML14008A097
Person / Time
Site: Oyster Creek
Issue date: 12/05/2013
From: Peak R
Exelon Generation Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
RA-13-117 LER 13-002-00
Download: ML14008A097 (4)


LER-2013-002, Regarding Manual Scram Due to Lowering Vacuum
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)(i)

10 CFR 50.73(a)(2)(vii), Common Cause Inoperability

10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded

10 CFR 50.73(a)(2)(viii)(A)

10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition

10 CFR 50.73(a)(2)(viii)(B)

10 CFR 50.73(a)(2)(iii)

10 CFR 50.73(a)(2)(ix)(A)

10 CFR 50.73(a)(2)(iv)(A), System Actuation

10 CFR 50.73(a)(2)(x)

10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor

10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat

10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown

10 CFR 50.73(a)(2)(v), Loss of Safety Function

10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications
2192013002R00 - NRC Website

text

PA.¶34.¶ 7 10 C94 50,131ý DecTembo5,,201,3 Attn: Docufwi Conro D WasWpgo, DC 2M65 - OD)t Oys Cregk Nuck Gewfrv~ Smton Renewe FacUky Opratog Utose W, OPR4O-P Subject:w L~seL-MRpolt (LER) 201ý 3-0O2-X, Vanu Sma Du toLwr wnedlis LER 2013-M-0), Mauai 8cia Ds to i-oe*

Vacuum Th Mdi

~l~

Wft heafth wid safl of1 the I

P4w or* Ord lA pePmai 'Th 4d nA rout*

in a -aet system IcfionaIJ *Wre Ther are m~ regtky commkwme ma* in LER subm".

Should you mew any qusstbis concmiur #w WW p~s MMMeM~na Riegut.4y Asurw* ff~

at (6% 971 -43V9 RusO R. NaOk Pbew CnmrO uk wit w

Enckowre: NRC Form 3W, tER 2013002~-00 Oc:

Adukthr~kx NRC R,0Om I NAC Swtkx Resid Inepwwr Oysr C~oo Nuie Gwrdng S~t NAC Prooc Mmnaom - Oy*

Creek Nula GeraWng ftWi

NRC FORM 366 (1 0-2010) p.----------

I I

  • LII I*1 *A * *AI II i*ID
  • IIIII*I*LI¸ U.S. N'UCLEAR REGULATOIRY COMMISSION APPROVED BY OMB: NO. 3150-0104 EXPIRES: 10/31/2013

, the NRC may not conduct or sponsor, and a person is not required to respond to, the information collection.

LICENSEE EVENT REPORT (LER)

(See reverse for required number of digits/characters for each block)

3. PAGE Oyster Creek, Unit 1 05000219 1 OF 3
4. TITLE Manual Scram Due to Lowering Vacuum
5. EVENT DATE
6. LER NUMBER
7. REPORT DATE
8. OTHER FACILITIES INVOLVED R

FACILITY NAME DOCKET NUMBER MONTH DAY YEAR YEAR SEQUENTIAL REV MONTH DAY YEAR N/A N/A FACILITY NAME DOCKET NUMBER 10 06 2013 2013 002 00 12 5

2013 N/A N/A

9. OPERATING MODE
11. THIS REPORT IS SUBMI'rrED PURSUANT TO THE REQUIREMENTS OF 10 CFIR §: (Check all that apply)

[E 20.2201(b)

[I 20.2203(a)(3)(i)

El 50.73(a)(2)(i)(C)

[I 50.73(a)(2)(vii)

N [1 20.2201(d)

El 20.2203(a)(3)(ii)

[I 50.73(a)(2)(ii)(A)

[I 50.73(a)(2)(viii)(A)

[E 20.2203(a)(1)

El 20.2203(a)(4)

El 50.73(a)(2)(ii)(B)

El 50.73(a)(2)(viii)(B)

[I] 20.2203(a)(2)(i)

El 50.36(c)(1)(i)(A)

El 50.73(a)(2)(iii)

El 50.73(a)(2)(ix)(A)

10. POWER LEVEL [I 20.2203(a)(2)(ii)

El 50.36(c)(1)(ii)(A) 0 50.73(a)(2)(iv)(A)

El 50.73(a)(2)(x)

E] 20.2203(a)(2)(iii)

El 50.36(c)(2)

El 50.73(a)(2)(v)(A) 0l 73.71(a)(4) 20 El 20.2203(a)(2)(iv)

El 50.46(a)(3)(ii)

El 50.73(a)(2)(v)(B)

El 73.71(a)(5)

[I 20.2203(a)(2)(v)

[E 50.73(a)(2)(i)(A)

El 50.73(a)(2)(v)(C)

El OTHER El 20.2203(a)(2)(vi)

El 50.73(a)(2)(i)(B)

El 50.73(a)(2)(v)(D)

Specify in Abstract below or in Analysis of Event Continued on October 2012 during 1R24, likely resulted in an unseen accidental impact of tools or equipment.

Corrective Actions

A temporary leak repair was performed on the 1" hole on Y-1-26, 'B' Condenser Steam Inlet Expansion Joint on the south side of 'B' Condenser. A replacement of the Y-1 -26 Expansion Bellows is planned for a future outage.

Previous Occurrences

There have been no similar Licensee Event Reports associated with this component failure submitted at OCNGS in the last two years.

Component Data Component IEEE 805 System ID IEEE 803A Component Expansion Joint SM EXJ