ATTACHMENT 2 PROPOSED TECHNICAL SPECIFICATIONS 900619?0080 90)061L!b I:DR ADOC::

K 0500C)k)6 p

PDC

TABLE 3.5.1-1 (Continued)

REACTOR TRIP SYSTEM INSTRUMENTATION MINIMUM TOTAL NO.

CHANNELS CHANNELS APPLICABLE Z

FUNCTION UNIT OF CHANNELS TO TRIP OPERABLE MODES ACTION 0

10. Reactor Coolant Flow A. Single Loop 1/loop 1/loop in any 1/loop in each 1

6#

C (Above 50% of Full Power) operating loop operating loop B. Two Loops 1/loop I/loop in two 1/loop in each 1####

6#

(Below 50% of Full Power) operating loops operating loop

11.

Steam/Feedwater Flow Mismatch 3

2 2

1#####

6#

12.

Turbine Trip-Low Fluid 3

2 2

1####

6#

Oil Pressure

13.

Reactor Coolant Pump Breaker Position A.. Single Loop 1/loop 1/loop in any I/loop in each 1

6#

(Above 50% of Full Power) operating loop operating loop B. Two Loops 1/loop 1/loop in two I/loop in each 1####

6#

(Below 50% of Full Power) operating loops operating loop

14.

Reactor Trip Breakers 2

1 2

1, 2 30 2

1 2

3*, 4*, 5*

7

15. Sequencer Input to 2

1 2

1, 2 29****

Reactor Trip W

00

TABLE 3.5.1-1 (Continued)

TABLE NOTATION With the reactor trip system breakers in the closed position, the control rod drive system capable of rod withdrawal.

A "TRIP" will stop all rod withdrawal.

Startup rate circuit enabled at 10% reactor power.

Comply with the provisions of Specification 3.5.5 for any portion of the channel required to be OPERABLE by Specification 3.5.5.

The provisions of Specification 3.0.4 are not applicable.

Below the Source Range High Voltage Cutoff Setpoint.

      1. Below the P-7 (At Power Reactor Trip Defeat) Setpoint.

Above the P-7 (At Power Reactor Trip Defeat) Setpoint.

          1. Above the P-8 Setpoint.

ACTION STATEMENTS ACTION 1 -

With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, restore the inoperable channel to OPERABLE status within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or be in HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

ACTION 2 -

With the number of OPERABLE channels one less than the Total Number of Channels, STARTUP and/or POWER OPERATION may proceed provided the following conditions are met:

a. The inoperable channel is placed in the tripped condition within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.
b. The Minimum Channels OPERABLE requirement is met; however, the inoperable channel may be returned to the untripped condition for up to 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> for surveillance testing channels per Specification 4.1.

ACTION 3 -

With the number of channels OPERABLE one less than the Minimum Channels OPERABLE requirement and with the THERMAL POWER level:

a. Below the Source Range High Voltage Cutoff Setpoint, restore the inoperable channel to OPERABLE status prior to increasing THERMAL POWER above the Source Range High Voltage Cutoff Setpoint.
b. Above the Source Range High Voltage Cutoff Setpoint but below 10 percent of RATED THERMAL POWER, restore the inoperable channel to OPERABLE status prior to increasing THERMAL POWER above 10 percent of RATED THERMAL POWER.
However, one channel may be bypassed for up to 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> for surveillance testing per Specification 4.1, provided the other channel is OPERABLE.

ACTION 4 -

With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement suspend all operations involving positive reactivity changes.

SAN ONOFRE - UNIT 1 3.5-4 AMENDMENT NO:

55, 58, 83, 117, 118, 121, 128, 130

ACTION 5 -

With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, verify compliance with the SHUTDOWN MARGIN requirements of Specification 3.5.2 as applicable, within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> thereafter.

ACTION 6 -

With the number of OPERABLE channels one less than the Total Number of Channels, STARTUP and/or POWER OPERATION may proceed until performance of the next required OPERATIONAL TEST provided the inoperable channel is placed in the tripped condition within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />.

ACTION 7 -

With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, restore the inoperable channel to OPERABLE status within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or open the reactor trip breakers within the next hour.

ACTION 28 - With the number of OPERABLE channels less than the Minimum Channels OPERABLE requirements, within one hour reduce THERMAL POWER such that T. is less than or equal to 551.5*F, and place the rod control system in manual mode.

ACTION 29 - With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirements, be in at least HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />; however, one channel may be removed from service for up to 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> for surveillance testing per Specification 4.1, provided the other channel is OPERABLE.

ACTION 30 - With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, be in at least HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and apply ACTION 7.

SAN ONOFRE - UNIT 1 3.5-5 AMENDMENT NO: 83, 117, 130

TABLE 4.1.1 REACTOR TRIP SYSTEM INSTRUMENTATION SURVEILLANCE REQUIREMENTS TRIP ACTUATING DEVICE CHANNEL CHANNEL CHANNEL OPERATIONAL ACTUATION FUNCTIONAL UNIT CHECK CALIBRATION TEST TEST LOGIC TEST

1.

Manual Reactor Trip N.A.

N.A.

N.A.

R (7)

N.A.

2.

Power Range, Neutron Flux S

D (2,3)

M N.A.

N.A.

R (3,4)

3.

Power Range, Neutron Flux, N.A.

N.A.

M N.A.

N.A.

Dropped Rod Rod Stop

4.

Intermediate Range, S

R (3,4)

S/U (1),

N.A.

N.A.

Neutron Flux M

5.

Source Range, Neutron Flux S

R (3)

S/U (1),

N.A.

N.A.

M

6.

NIS Coincidentor Logic N.A.

N.A.

N.A.

N.A.

M (5)

7.

Pressurizer Variable Low S

R M

N.A.

N.A.

Preisure

8.

Pressurizer Pressure S

R M

N.A.

N.A.

9.

Pressurizer High Level S

R M

N.A.

N.A.

10.

Reactor Coolant Flow S

R Q

N.A.

N.A.

M

11.

Steam/Feedwater Flow S

R M

N.A.

N.A.

rn Mismatch

12.

Turbine Trip-Low Fluid N.A.

N.A.

N.A.

S/U (1,6)

N.A.

C Oil Pressure

    • 1 00

TABLE 4.1.1 (Continued)

REACTOR TRIP SYSTEM INSTRUMENTATION SURVEILLANCE REQUIREMENTS TRIP ACTUATING DEVICE CHANNEL CHANNEL CHANNEL OPERATIONAL ACTUATION FUNCTIONAL UNIT CHECK CALIBRATION TEST TEST LOGIC TEST

13.

Reactor Coolant Pump Breaker S

R R

N.A.

N.A.

Position*

14.

Reactor Trip Breakers N.A.

N.A.

N.A.

R(8)

N.A.

15.

Sequencer Input to Reactor Trip N.A.

N.A.

N.A.

R(9)

N.A.

  • Applicable to Item 6 in Table 2.1 TABLE NOTATION (1) -

If not performed in previous 31 days.

(2) -

Heat balance only, above 15% of RATED THERMAL POWER. Adjust channel if absolute difference greater than 2 percent.

(3) -

Neutron detectors may be excluded from CHANNEL CALIBRATION.

(4) -

The provisions of Specification 4:0.4 are not applicable for entry into MODE 2 or 1.

(5) -

Each train shall be tested at least every 62 days on a STAGGERED TEST BASIS.

(6) -

Setpoint verification is not applicable.

(7) -

The TRIP ACTUATING DEVICE OPERATIONAL TEST shall independently verify the OPERABILITY of the undervoltage and shunt trip circuits for the a

Manual Reactor Trip Function.

(8) -

The TRIP ACTUATING DEVICE OPERATIONAL TEST shall independently verify the OPERABILITY of the undervoltage and shunt trip attachments of the Reactor Trip Breakers.

(9) -

Comply with the surveillance requirements of Specification 4.1.4 for any portion of the channel required to be OPERABLE by Specification 3.5.5.

CD)