Southern California Edison Company P. 0. BOX 800 2244 WALNUT GROVE AVENUE ROSEMEAD. CALIFORNIA 91770 DAVID F.

PILMER TELEPHONE MANAGER. NUCLEAR ENGINEERING September 22, 1988 (818) 302-1989 U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D.C. 20555 Gentlemen:

Subject:

Docket Nos. 50-206, 50-361 and 50-362 NRC Bulletin 88-05, Supplement 2 Report San Onofre Nuclear Generating Station, Units 1, 2 and 3 Provided as an enclosure to this letter is the 120-day report for San Onofre Units 1, 2 and 3 required by NRC Bulletin 88-05 Supplement 2. If you have any questions regarding this report, please so advise.

Very truly yours, Enclosure cc: J. B. Martin, Regional Administrator, NRC Region V F. R. Huey, NRC Senior Resident Inspector, San Onofre Units 1, 2 and 3 80,,C9270 129 SSO922 X PDR ADOCK 05000206 Q

Subscribed on this

--"'day of

, 1988.

Respectful ly submi tted, SOUTHERN CALIFORNIA EDISON COMPANY By: ;i7 D. F.-

Timer Manager, Nuclear Engineering Subscr bed and sworn o

thiseethi

_2_

day of "fore met OFFICIAL SEAL S. C. SALLY SEBO Notary Public-California U.

MLOS ANGELES COUNTY

.MY Comm. Exp. Apr. 20, 1990 Notary Public 1 and for the County of Los Angeles, State of California Charles R. Kocher James A. Beoletto Attorneys for Southern California Edison Company By:

NRC Bulletin 88-05 120-Day Report San Onofre Units 1, 2 and 3 Docket Nos. 50-206, 50-361 and 50-362 August 1988 Southern California Edison Company Rosemead, California

NRC Bulletin 88-05 120 Day Report The purpose of this report is to provide the results of the records review, testing and analysis performed in response to NRC Bulletin 88-05 and Supplements 1 and 2 for San Onofre Units 1, 2 and 3. This report documents status as of the date of issue of NRC Bulletin 88-05, Supplement 2 (8/3/88).

On May 6, 1988, the NRC issued Bulletin 88-05 regarding nonconforming materials supplied by Piping Supplies Incorporated (PSI) and West Jersey Manufacturing Company (WJM).

This bulletin required licensees to take actions to assure that materials comply with ASME Code and design specification requirements, are suitable for their intended service or replace the material. In addition, a written report was required within 120 days of receipt of the bulletin to detail the actions taken by the licensee.

The Nuclear Management and Resources Council (NUMARC) established an industry program to coordinate an industry response to NRC Bulletin 88-05.

Under this program NUMARC is compiling the results of records searches and field testing of suspect flanges by individual utilities, and conducting laboratory testing on a sample of these components to determine their acceptability in support of a coordinated industry response to the NRC.

Southern California Edison (SCE) contracted Bechtel Construction, Inc. to conduct the records search and on July 1, 1988, the initial list of approximately 1,000 suspect items was provided. By August 3, 1988, a total of 1,051 suspect items (flanges) were Identified to be installed in San Onofre Units 1, 2 and 3. Out of this total, 219 of these flanges were determined to be inaccessible. Of the remaining flanges, all 103 stainless-steel flanges were tested satisfactorily using a magnetic test. Accessible carbon steel flanges were tested using EQUOTIP hardness testing.

All were specified as ASME SA-105 material.

The results were that 269 of the 716 flanges tested were outside the nominal 137-187 BHN hardness range. A total of 13 flanges were not included in the testing as a result of the issuance of Supplement 2 (8/3/88) when all testing was stopped.

For each item outside the nominal range, an appropriate non-conformance report (NCR) was written which included analysis justifying continued operation (JCO).

It should be noted that this approach is very conservative in light of the EQUOTIP/hardness/strength correlations described in the NUMARC Generic Testing Program Interim Report dated July 29, 1988.

The status of San Onofre efforts regarding NRC Bulletin 88-05 is provided in Table 1 which is a complete listing of the data provided to NUMARC by SCE.

Included are all suspect items - installed in the operating units and located in the warehouse -

identified through August 3, 1988. SCE is continuing to analyze the results of tests performed through August 3rd.

Final resolution of issues raised by NRC Bulletin 88-05 will depend on results of this analysis and the NUMARC generic program.

Table 1 NRC Bulletin 88-05 Results The column heading codes are identified as follows:

Code Description Item Specific item number 1-12 Plant Location of specific item, for example:

SOACCW - San Onofre Common Component Cooling Water System SOACHW - San Onofre Common Chilled Water System SO-WHS -

San Onofre Warehouse SO-PWH -

San Onofre Project Warehouse SO1AFW - San Onofre Unit 1 Auxiliary Feedwater System SO1CCW - San Onofre Unit 1 Component Cooling Water System SO1CRS - San Onofre Unit 1 Containment Recirculation System SO2RCS - San Onofre Unit 2 Reactor Coolant System SO2CCW - San Onofre Unit 2 Component Cooling Water System SO2SIS - San Onofre Unit 2 Safety Injection System S02CSS - San Onofre Unit 2 Containment Spray System SO2VCC - San Onofre Unit 2 Volume and Chemical Control System S02FSS - San Onofre Unit 2 Fuel Storage System SO2STM - San Onofre Unit 2 Main Steam System SO2FWS - San Onofre Unit 2 Auxiliary Feedwater System S02SCS

- San Onofre Unit 2 Saltwater Cooling System SO2ACS - San Onofre Unit 2 Containment Penetrations SO2NGS - San Onofre Unit 2 Nitrogen Gas System SO20AS - San Onofre Unit 2 Emergency Diesel Generator S02FOS - San Onofre Unit 2 Fuel Oil Storage SO3RCS - San Onofre Unit 3 Reactor Coolant System SO3CCW - San Onofre Unit 3 Component Cooling Water System SO3SIS - San Onofre Unit 3 Safety Injection System S03CSS - San Onofre Unit 3 Containment Spray System SO3VCS - San Onofre Unit 3 Volume and Chemical Control System S03FSS.-

San Onofre Unit 3 Fuel Storage System

Table I -

Continued Code Description SO3STM - San Onofre Unit 3 Main Steam System SO3FWS - San Onofre Unit 3 Auxiliary Feedwater System S03SCS

- San Onofre Unit 3 Saltwater Cooling System SO3ACS - San Onofre Unit 3 Containment Penetrations SO3CHW - San Onofre Unit 3 Chilled Water System SO3DAS - San Onofre Unit 3 Emergency Diesel Generator S03FOS - San Onofre Unit 3 Fuel Oil Storage Trans Transaction-A-Add, C-Change, 0-Delete Diameter Diameter of item Commodity Type of item -

Flange, Fitting, etc.

Rating Pressure rating of item in psi.

Type Material description of item -

Elbow, Blind, Cap, etc.

Spec.

ASME material specification (Section II)

Grade Specific grade of material Schedule Piping schedule for item Vendor West Jersey or Piping Supplies, Inc.

Heat/Lot Heat number associated with item Date Date installed Quantity Number of items in stock Source Original material manufacturer before sold to vendor ASME ASME Code Class Line Isometric drawing containing item Test Specific field test number M.O. Number -

Maintenance order number for prep and test T-Hard Brinnel hardness of item or P for Passing Magnetic Test KSI Cony.

Strength in KSI equivalent to Brinnel hardness NCR Number -

Non-conformance report number for items out of tolerance 9878F

Page No.

1 09/08/88 NCR SONGS REPORT (BY LOCATION)

ITEM PLANT TRANS DIAMETER COMMODITY RATING TYPE SPEC GRADE SCHEDULE VENDOR HEAT LOT DATE QUANTITY SOURCE ASME LINE TEST 0 NUMBER T-NARD KSICONV NCRNLNBER 1217 SO-WHS 0.50 FLG 300.0 BL 105 N/A U

CBL 17 2

0 1218 SO-WHS 0.50 FLG 300.0 BL 105 N/A U

CBL 1

2 0

1219 SO-WHS 1.50 FLG 150.0 B1 105 N/A U

GKH 12 2

0 1220 SO-MS 1.00 FLG 600.0 SW 105 N/A 160 U

CEW 5

2 0

1221 SO-UHS 0.50 FLG 0.0 SW 105 N/A 160 U

GDED 10 2

0 1222 SO-UNS 0.50 FLG 0.0 sU 105 N/A 160 U

GDED 2

2 0

1223 SO-WHS 1.00 FLG 300.0 SWRF 105 N/A W

CBL 10 2

0 24 SO-WHS 0.50 FLG 600.0 SWRF 105 N/A 160 U

CHV 2

2 0

25 SO-WS 0.50 FLG 600.0 SWRF 105 N/A 160 U

GDDF 1

2 0

1226 SO-WHS 0.50 FLG 600.0 SWRF 105 N/A 160 W

GDDF 5

2 0

1227 SO-WHS 0.75 FLG 600.0 SWRF 350 N/A 160 U

83811 4

2 0

1228 SO-WHS 0.50 FLG 0.0 SWRF 350 N/A 160 W

53811 4

2 0

1229 SO-UHS 0.75 FLG 0.0 SWRF 350 N/A 160 W

83811 6

2 0

1230 SO-WHS 1.00 FLG 600.0 SWRF 350 N/A 160 W

63811 4

2 0

1231 SO-WHS 1.50 FLG 600.0 SURF 350 N/A 160 W

83811 3

2 0

1232 SO-WHS 1.50 FLG 0.0 SURF 350 N/A 160 U

63811 4

2 0

1233 SO-WHS 1.00 FLG 0.0 SWRF 350 N/A 160 W

53811 4

2 0

1243 SO-PWN A 25.00 FLG 0.0 BL W

UNKNOWN 2

0 1244 SO-PWH A 18.00 FLG 150.0 BL 105 N/A W

9478723 1

0 1245 SO-PWH A 2.00 FLG 600.0 RFWN 105 N/A 80 W

COP 8

0 1246 SO-PWH A 2.00 FLG 600.0 BL 105 N/A W

COP 7

0 1247 SO-PWH A 2.50 FLG 150.0 RFWN 182 N/A 105 U

2730 1

0 1248 SO-PWH A 20.00 FLG 0.0 BL 35313 2

0 1249 SO-PWH A 20.00 FLG 0.0 BL 46019 2

0 250 SO-PWH A 6.00 FLG 150.0 RFWN 182 54949 8

0 W

68 SO1AFW A 1.00 FLG 600.0 RFUN 105 N/A 40 U

?

0 SI-AFW-RO-143, UP(S01-87-054) 0 140.5 1267 SO1AFW A 1.00 FLG 600.0 RFWN 105 N/A 40 U

?

0 S1-AFW-RO*143,LWR(S01-87-05 4 )

0 147.5 1213 SO1CRS C 4.00 FLG 300.0 RFWN 105 N/A 40 W

JSG 0

Sl-TRV S01-044*86, G45A 0 140 1214 SO1CRS C 6.00 FLG 150.0 RFWN 105 N/A 40 W

CND 0

51-TRV S01-044-86, G45A 0 150 1215 SO1CRS C 4.00 FLG 300.0 RFWN 105 N/A 40 W

J5G 0

51-TRV So1-045-86, G458 0 122*

1216 SO1CRS C 6.00 FLG 150.0 RFWN 105 N/A 40 U

CMD 0

S1-TRV S01-045-86, G45B 0 144 1212 SO1CCW C 1.00 FLG 150.0 RFUN 105 N/A 40 U

M920901 0

s1-TRV S01-159-84 LINE 16214 0 169 797 SO2RCS 6.00 FLG 600.0 RFWN 182 F316 40 W

62919 01/24/79 0

2 521201ML017-2RC017038 0

1115 2RCS 6.00 FIG 600.0 RPUN 182 F316 40 U

82919 01/24/79 0

2 S21201ML017-2RC017038 0

Page No.'

2 09/08/88 NCR SONGS REPORT (BY LOCATION)

ITEM PLANT TRANS DIAMETER COMMODITY RATING TYPE SPEC GRADE SCHEDULE VENDOR HEAT.LOT DATE QUANTITY SURCE ASME LINE TEST A0NUMBER TNHARD KSI.CONy NCR.NUMBER 1276 SO2RCS A 6.00 FLG 600.0 RFBL 182 F316 N/A U

83296 N/A 0

2 521201ML017-2RC161001 0

841 SO2CCU 2.50 FLG 150.0 RFWN 105 N/A 40 U

T4696 11/01/76 0

3 S21203ML006-2CC006009 0

842 SO2CCW 2.50 FLG 150.0 RFWN 105 N/A 40 T4696 11/01/76 0

3 S21203ML006-2CC006010 0

843 SO2CCW 2.50 FLG 150.0 RFWN 105 N/A 40 U

T4696 11/01/76 0

3 S21203MLOD6-2CC006010 0

844 S02CCW 2.50 FLG 150.0 RFUN 105 N/A 40 U

74696 11/01/76 0

3 S21203ML008-2CCO08001 0

845 S02CCU 2.50 FLG 150.0 RFUN 105 N/A 40 U

T4696 11/01/76 0

3 S21203ML008-2CCO08001 0

849 S02CCW 2.50 FLG 150.0 RFUN 105 N/A 40 U

T4696 05/09/77 0

3 S21203ML008-2CC008010 0

Q 6 S02CCU 2.50 FLG 150.0 RFUN 105 N/A 40 U

74696 11/01/76 0

3 521203ML008-2CCD08011 0

47 SO2CCW 2.50 FLG 150.0 RFUN 105 N/A 40 U

T4696 11/01/76 0

3 S21203ML008-2CC008011 0

850 S02CCU 2.50 FLG 150.0 RFWN 105 N/A 40 U

14696 05/09/77 0

3 S21203ML008-2CC008012 0

955 SO2CCW 2.50 FLG 150.0 RFWN 105 N/A 40 U

T4902 02/09/77 0

3 521203ML012-2CC012003 0

956 SO2CCU 2.50 FLG 150.0 RFWN 105 N/A 40 w

74902 02/09/77 0

3 S21203ML012*2CC012004 0

954 S02CCW 2.50 FLG 150.0 RFWN 105 N/A 40 U

T4902 02/09/77 0

3 S21203ML014-2CCD14001 0

848 SO2CCU 2.50 FLG 150.0 RFWN 105 N/A 40 U

T4696 11/01/76 0

3 S21203ML014-2CC014002 0

298 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 U

2190 11/01/76 0

3 521203ML064-2CC064004 0

673 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

3 S21203ML064-2CCO64008 0

1121 SO2CCw 4.00 FLG 150.0 RFUN 105 N/A 40 U

J61D 03/10/80 0

3 521203ML070-ITEM #32 0

964 SO2CCW 5.00 FLG 150.0 RFWN 105 N/A 40 w

H598 01/17/78 0

3 S21203ML072-2CC072001 0

763 S02CCW 4.00 FLG 150.0 RFWN 105 N/A 40 W

J61D 01/21/77 0

3 S21203ML072-2CCO72002 0

1126 S02CCU 4.00 FLG 150.0 RFWN 105 N/A 40 w

J610 12/14/74 0

3 521203ML072-2CC072007 0

587 SO2CCW 4.00 FLG 150.0 RFWN 105 N/A 40 w

T4696 10/21/76 0

3 S21203ML074-2CCO74002 0

749 S02CCW 5.00 FLG 150.0 RFUN 105 N/A 40 U

K764701 09/08/78 0

3 S21203ML074-2CCO74007 0

1161 SO2CCw 4.00 FLG 150.0 RFWN 105 N/A 40 U

T4228 09/08/78 0

3 S21203ML074-2CC074007 0

447 SO2CCU C 5.00 FLG 150.0 RFWN 105 N/A 40 w

H598 07/29/77 0

3 S21203ML078-2CCO78001 0

36 So2CCW 4.00 FLG 150.0 RFWN 105 N/A 40 w

7097642 02/09/77 0

3 S21203ML078-2CCO78002 0

3 SO3CCW 5.00 FLG 150.0 RFUN 105 N/A 40 U

H598 10/14/77 0

3 S21203MLO78-ITEM 41 0

449 S02CCW 5.00 FLG 150.0 RFWN 105 N/A 40 U

H598 01/21/77 0

3 S21203ML080-2CC080001 0

937 SO2CCW 4.00 FLG 150.0 RFWN 105 N/A 40 U

1097642 02/09/77 0

3 S21203ML080-2CC080002 0

448 SO2CCW 5.00 FLG 150.0 RFWN 105 N/A 40 w

H598 10/14/77 0

3 S21203ML080-ITEM 44 0

934 SO2CCW 4.00 FLG 150.0 RFWN 105 N/A 40 U

1097642 02/09/77 0

3 S21203ML082-2CC082001 0

935 So2CCW 4.00 FLG 150.0 RFWN 105 N/A 40 w

T097642 02/09/77 0

3 S21203ML082-2CC082001 0

1274 SO2CCW A 4.00 FLG 150.0 RFWN 150 N/A 40 U

1097642 2/9/77 0

3 S21203ML082-2CCO82002 0

450 SO2CCW 5.00 FLG 150.0 RFWN 105 N/A 40 w

H598 02/09/77 0

3 S21203ML084-2CCD84001 0

764 S02CCu 4.00 FIG 150.0 RFno 105 N/A 40 U

.61 01/21/77 0

3 S21203ML084-2CCOb4001 0

Page No.

3 09/08/88 NCR SONGS REPORT (BY LOCATION)

ITEM PLANT TRANS DIAMETER COMMODITY RATING TYPE SPEC GRADE SCHEDULE VENDOR HEAT LOT DATE QUANTITY SOURCE ASME LINE TEST M 0 NUMBER T-KARO KSI CONy NCR NUMBER 765 So2CCW 4.00 FLG 150.0 RFW 105 N/A 40 U

J61D 01/21/77 0

3 S21203ML084-2CCOS4002 0

674 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S21203ML090-2CC090004 0

746 SO2CCW 6.00 FLG 150.0 RFSO 105 N/A 40 U

LAG 12/14/76 0

3 S21203ML090-2CCO90006 0

759 SO2CCU 3.00 FLG 150.0 RFWN 105 N/A 40 w

T2190 10/21/76 0

3 521203ML090-2CCD90006 0

675 SO2CCW C 3.00 FLG 150.0 RFW 105 N/A 40 U

JAE 06/17/77 0

3 S21203ML092-2CCO92007

-1 88071307 138 676 SO2CCW C 3.00 FLC 150.0 RFWN 105 N/A 40 U

JAE 06/17/77 0

3 S21203MLO92-2CCO92008

  • 3 88071307 174 116 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 12/14/76 0

3 S21203ML092-2CCD92008 0

7 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

3 S21203ML092-2E370001 4

88071307 176 427 SO2CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

3 521203ML092-2E370001

-5 88071307 167 87 SO2CCU 3.00 FLG 150.0 RFUN 105 N/A 40 U

J4E 06/17/77 0

3 521203MLO92-ITEM 40

-2 88071307 237*

299 SO2CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 W

2190 11/01/76 0

3 S21203ML093-2CCO93006

-1 88071308 219*

2-2440 85 S02CCU C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

3 S21203ML093-2E371001

-2 88071308 173 428 S02CCU C 3.00 FLG 150.0 RFuN 105 N/A 40 U

JAE 06/17/77 0

3 521203ML093-2E371001

-3 88071308 186 679 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 W

J4E 06/17/77 0

3 S21203ML094-2CCO94008

-3 88071310 173 28 502CCW C 3.00 FLG 150.0 RFWN 105 W/A 40 w

J4E 06/17/77 0

3 S21203ML094-2E370002

-1 88071310 205**

2-2441 429 SO2CCV C 3.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 06/17/77 0

3 S21203ML094-2E370002

-2 88071310 167 300 S02CCW C

3.00 FLG 150.0 RFWN 105 N/A 40 w

2190 11/01/76 0

3 521203ML095-2CCO95007

-1 88071311 173 86 SO2CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

3 521203ML095-2E371002

-2 88071311 225**

2-2442 682 SO2CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

3 521203ML095-2E371002

-3 88071311 192**

2-2442 1210 S02CCW 12.00 FLG 150.0 RFWN 105 N/A 40 w

T4205 12/14/76 0

3 S21203ML102-2CC102001

-2 88071312 156 1211 S02CCW 12.00 FLG 150.0 RFWN 105 N/A 40 w

14205 12/14/76 0

3 S21203ML102-2CC102001

-3 88071312 159 520 SO2CCW C 12.00 FLG 150.0 RFWN 105 N/A 40 w

T4205 12/14/76 0

3 S21203ML102-2CC102002

-3 88071312 137 580 S02CCW 12.00 FLG 150.0 RFWN 105 N/A 40 U

74205 12/14/76 0

3 521203ML103-2CC103002

-1 88071313 131*

2-2472 924 S02CCW C 12.00 FLG 150.0 RFWN 105 N/A 40 w

M771115 09/30/77 0

3 521203ML106-2CC106001

-1 88071314 133*

2-2475 5 SO2CCW C 12.00 FLG 150.0 RFWN 105 N/A 40 W

M771115 09/30/77 0

3 S21203ML106-2CC106001

-2 88071314 124' 2-2475 1 S02CCW C 12.00 FLC 150.0 RFUN 105 N/A 40 U

T4205 12/14/76 0

3 s21203ML106-2CC106002

-3 88071314 125*

2-2475 550 S02CCW C 10.00 FLG 150.0 RFWN 105 N/A 40 U

NJ 10/21/76 0

3 S21203ML137-2CC137002

-1 88071315 143 463 502CCW C 10.00 FLG 150.0 RFWN 105 N/A 40 U

HJ 10/21/76 0

3 521203ML137-2CC137003

-3 88071315 137 464 SO2CCW C 10.00 FLG 150.0 RFWN 105 N/A 40 U

KJ 10/21/76 0

3 S21203ML137-2CC137003

-2 88071315 123*

2-2462 931 S02CCW C 28.00 FLG 125.0 FFWN 105 N/A 40 U

W9666 03/23/78 0

3 S21203ML140-2CC140005

-1 88071317 150 462 SO2CCW C 10.00 FLG 150.0 RFWN 105 N/A 40 U

NJ 10/21/76 0

3 521203ML151-2CC151002

-1 88071318 139 461 S02CCW C 10.00 FLG 150.0 RFWN 105 N/A 40 U

HJ 10/21/76 0

3 521203ML155-2CC155002

-1 88071320 136*

2-2467 460 S02CCW 10.00 FLG 150.0 RFWN 105 N/A 40 U

NJ 10/21/76 0

3 521203ML157-2CC157004

-1 88071321 134*

2-2473 1252 S02CCW A 4.00 ViO 150.0 R

.WN 105 N/A 402 U

J61D 6/30/77 0

3 S21203ML158-2CC158001

-1 88071322 130*

2-2466

Page No.

4 09/08/88 NCR SONGS REPORT (BY LOCATION)

ITEM PLANT TRANS DIAM4ETER COMMODITY RATING TYPE SPEC GRADE SCHEDULE VENDOR MEAT.LOT DATE QUANTITY SOURCE ASMqE LINE TEST N 0 NUMBER T:HARD KSI CONV NCR-NLR4BER 452 So2CCW c 4.00 FLG 150.0 RFBL 105 N/A N/A w

H904 09/08/78 0

3 S21203ML158-2CC158004

.2 88071322 147.5 1164 SO2CCW 4.00 FLG 150.0 RFuN 105 N/A 40 W

T4696 11/01/76 0

3 S21203ML159-2CC159001 0

814 SO2CCW C 4.00 FLG 150.0 RFBL 105 N/A N/A w

N904 09/08/78 0

3 S21203ML159-2CC159007

-1 88071364 1'37 929 S02CCW C 28.00 FLG 125.0 FFWN 105 N/A 40 H

W9666 03/23/78 0

3 521203ML164-2CC164004

-1 88071365 147.5 930 SO2CCW C 28.00 FLG 125.0 FFW 105 N/A 40 H

W9666 03/23/78 0

3 S21203ML164-2CC164004

-2 88071365 150 833 S02CCW C 8.00 FLG 150.0 RFWN 105 N/A 40 H

74298 10/21/76 0

3

$21203ML210-2CC210027

-1 88071366 122*

2-2460 834 SO2CCW C 8.00 FLG 150.0 RFWN 105 N/A 40 w

T4298 10/21/76 0

3 S21203ML210-2CC210028

  • 2 88071366 119*

2-2460 528 SO2CCW 10.00 FLG 150.0 RFWN 105 N/A 40 w

T4205 12/14/76 0

3 S21203ML228-2CC228002 0

529 S02CCW 10.00 FLG 150.0 RFWN 105 N/A 40 w

74205 12/14/76 0

3 521203ML228-2CC228002 0

1205 So2CCW 10.00 FLG 150.0 RFWN 105 N/A 40 H

T4205 12/14/76 0

3 521203ML228-2CC228003 0

1177 SO2CCS 8.00 FLG 150.0 FFWN 105 N/A 40 w

T30266 05/09/77 0

3 521203ML228-2CC243001 0

1278 502CC2 A 10.00 FLG 150.0 RFWN 105 N/A 40 w

NJ 10/21/76 0

3 521203ML231-2CC231002

-1 88071368 134*

2-2471 459 S02CCW C 10.00 FLG 150.0 RFWN 105 N/A 40 H

NJ 10/21/76 0

3 S21203ML231-2CC231003

-3 88071368 132*

2-2471 1279 S02CCW A 10.00 FLG 150.0 RFWN 105 N/A 40 w

NJ 10/21/76 0

3

$21203ML231-2CC231003

-2 88071368 140 2-2471 1162 S02CCW C 8.00 FLG 150.0 RFWN 105 N/A 40 H

T4298 10/21/76 0

3 521203ML243-2CC2 43025

-1 88071369 134*

2-2469 835 S02CCW C 8.00 FLG 150.0 RFWN 105 N/A 40 H

74298 10/21/76 0

3 521203ML243-2CC243026

-2 88071369 130*

2-2469 533 S02CCW 10.00 FLG 150.0 FFWN 105 W/A 40 w

74205 01/21/77 0

3 S21203ML247-2cC247009 0

532 S02CCW 10.00 FLO 150.0 FFWN 105 N/A 40 H

T4205 12/14/76 0

3 521203ML252-2CC252009 0

29 SD2Cou 3.00 FLO 150.0 RFUN 105 N/A 40 U

J4E 06/17/77 0

2 S21203ML273-2E402004A 0

30 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 H

J4E 06/17/77 0

2 S21203ML273-2E402004A 0

31 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 H

JAE 06/17/77 0

2 S21203ML273-2E402004B 0

32 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 521203ML273-2E4020048 0

33 SO2CCH 3.00 FLG 150.0 RFWN 105 N/A 40 H

JAE 06/17/77 0

2 521203ML273-2E402004C 0

34 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 H

J4E 06/17/77 0

2 521203ML273-2E402004C 0

35 so2CCU 3.00 FLO 150.0 RFuN 105 N/A 40 U

JAE 06/17/77 0

2 S21203ML273-2E402004D 0

U 36 502CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 521203ML273-2E402004D 0

142 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 H

J4E 06/17/77 0

2 521203ML273-2E402004E 0

143 S02CCU 3.00 FLG 150.0 RFWN 105 N/A 40 H

J4E 06/17/77 0

2 S21203ML273-2E402004E 0

106 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 H

JAE 06/17/77 0

2 521203ML273-2E402N011 0

107 SOZCCW 3.00 FLG 150.0 RFWN 105 N/A 40 H

J4E 06/17/77 0

2 S21203ML273-2E402N012 0

108 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 521203ML273-2E402N013 0

109 502CCW 3.00 FLG 150.0 RFWN 105 N/A 40 H

JAE 06/17/77 0

2 521203ML273-2E402N014 0

110 502CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 521203ML273-2E402N015 0

535 S02CCW 10.00 PLO 150.0 R.WN 105 N/A 40 a

T4205 12/14/76 0

2 521203ML273-ITEM 28 0

Page No.

5 09 /08/8.8 NCR SONGS REPORT (BY LOCATION)

ITEM PLANT TRANS DIAMIETER COMMODITY RATING TYPE SPEC GRADE SCHEDULE VENDOR NEAT LOT DATE QUANTITY SOURCE ASKE LINE TEST M 0 NUMBER T-NARD KSI COWV NCR.NUMBER 531 S02CCW 10.00 FLG 150.0 RFWN 105 N/A 40 U

T4205 12/14/76 0

2 S21203ML275-2CC275009 0

88 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 S21203ML275-2E402003A 0

89 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 06/17/77 0

2 S21203ML275-2E402003A 0

90 S02CCW 3.00 FLG 150.0 RFUN 105 N/A 40 JAE 06/17/77 0

2 S21203ML275-2E4020038 0

91 SO2CCw 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S21203ML275-2E402003B 0

92 S02CCU 3.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 06/17/77 0

2 S21203ML275-2E402003C 0

93 S02CCw 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 S21203ML275-2E402003C 0

94 S02CCU 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S21203ML275-2E4020030 0

95 S02CCW 3.00 FLG 150.0 RFUN 105 N/A 40 U

J4E 06/17/77 0

2 521203ML275-2E402003D 0

96 S02CCU 3.00 FLG 150.0 RFUN 105 N/A 40 U

JAE 06/17/77 0

2 S21203ML275-2E402003E 0

97 S02CCW 3.00 FLG 150.0 RFUN 105 N/A 40 U

JAE 06/17/77 0

2 S21203ML275-2E402003E 0

111 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 06/17/77 0

2 S21203ML275-2E402L001 0

112 SO2CCU 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 521203ML275-2E402L002 0

113 SO2CCW 3.00 FLO 150.0 RFWN 105 N/A 40 U

JAE 06/17/77 0

2 S21203ML275-2E402L003 0

114 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 S21203ML275-2E402L004 0

115 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 06/17/77 0

2 S21203ML275-2E402L005 0

116 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 S21203ML275-2E402N016 0

117 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 06/17/77 0

2 521203ML275-2E402N017 0

118 So2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S212031L275-2E402N018 0

119 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 U

JE 06/17/77 0

2 S21203ML275-2E402N019 0

120 S02CCW 3.00 FLC 150.0 RFWN 105 N/A 40 U

JAE 06/17/77 0

2 521203ML275-2E402N020 0

522 S02CCW C 10.00 FLG 150.0 RFUN 105 N/A 40 w

T4205 12/14/76 0

2 S21203ML277-2CC277009 0

534 S02CCW 10.00 FLG 150.0 RFWN 105 N/A 40 L

T4205 12/14/76 0

2 S21203ML277-2CC277009 0

524 S02CCW 10.00 FLG 150.0 RFWN 105 N/A 40 U

14205 12/14/76 0

2 S21203ML277-2CC277010 0

0 525 S02CCW 10.00 FLG 150.0 RFWN 105 N/A 40 W

74205 12/14/76 0

2 S21203ML277-2CC277010 0

1117 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 08/24/77 0

2 521203ML277-2E399M004A 0

1118 SO2CCU 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 08/24/77 0

2 S21203ML277-2E399M004A 0

98 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S21203ML277-2E399M004B 0

99 S02CCU 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 S21203ML277-2E399MOD4B 0

100 SO2cCU 3.00 FLG 150.0 RFWN 105 N/A 4D U

J4E 06/17/77 0

2 S21203ML277*2E399MOD4C 0

101 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/7 0

2 S21203ML277-2E399M004C 0

102 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 s21203ML277-2E399MDD4D 0

103 S02CCw 3.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 06/17/77 0

2 S21203ML277-2E399M004D 0

104 S02CCW 3.00 PLG 150.0 R.WN 105 N/A 40 u

r4E 06/17/77 0

2 S21203ML277-2E399MOD4E 0

09/8/

o.

NCR SONGS REPORT (BY LOCATION)

SPECGRAE SHEDLE ENDO HET LT DTE UANTTY OURE AKE INETEST M 0 NUMBER 1-HARD KSI COWy NCR NLR48ER ITEM PLANT TRANS DIAMETER COMODITY RATING TYPE SPEC.RA.E SCHE...E EO HEA OT DATE

.AT RCS E

105 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 06/17/77 0

2 S21203ML277-2E399M004E 0

121 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 S21203ML277-2E399W011 0

122 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 06/17/77 0

2 S21203ML277-2E399N012 0

123 S02CCW 3.00 FLC 150.0 RFWN 105 N/A 40 U

JAE 06/17/77 0

2 521203ML277-2E399N013 0

124 SO2CCU 3.00 FLG 150.0 RFWUN 105 N/A 40 w

JAE 06/17/77 0

2 521203ML277-2E399N014 0

125 SO2CCW 3.00 FLO 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 S21203ML277-2E399N015 0

36 SO2CCW 10.00 FLG 150.0 RFWN 105 N/A 40 w

74205 12/14/76 0

2 S21203ML277-ITEM 32 0

23 SO2CCU 10.00 FLG 150.0 RFWN 105 N/A 40 U

T4205 12/14/76 0

2 S21203ML279-2CC279008 0

126 SO2CCU 3.00 FLG 150.0 RPUN 105 N/A 40 A

JE 06/17/77 0

2 S21203ML279-2E399L001 0

127 SO2CCW 3.00 FLG 150.0 RFUN 105 N/A 40 U

J4E 06/17/77 0

2 S21203ML279-2E399L002 0

128 SD2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 06/17/77 0

2 S21203ML279-2E399L003 0

129 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S21203ML279-2E399L003A 0

130 S02CCU 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 S21203ML279-2E399L003A 0

131 SO2CCU 3.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 06/17/77 0

2 521203ML279-2E399L003B 0

132 SO2CCU 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 521203ML279-2E399L0038 0

43 SO2CCU 3.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 06/17/77 0

2 S21203ML279-2E399L003C 0

44 S02CCU 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S21203ML279-2E399L003C 0

45 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 S21203ML279-2E399L003D 0

46 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S21203ML279-2E399L003D 0

47 SO2CCU 3.00 FLG 150.0 RFPN 105 N/A 40 U

J4E 06/17/77 0

2 S21203ML279-2E399L003E 0

48 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S21203ML279-2E399L003E 0

49 SO2CCU 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 521203ML279-2E399L004 0

50 SO2CCU 3.00 FLG 150.0 RFN 105 N/A 40 w

J4E 06/17/77 0

2 S21203ML279-2E399L005 0

51 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 521203ML279-2E399N016 0

52 S02CCU 3.00 FLG 150.0 RFUN 105 N/A 40 U

JAE 06/17/77 0

2 521203ML279-2E399N017 0

53 SO2CCU 3.00 FLG 150.0 RFWH 105 N/A 40 W

JAE 06/17/77 0

2 521203ML279-2E399N018 0

54 SO2CCU 3.00 FLG 150.0 RFWN 105 N/A 40 W

J4E 06/17/77 0

2 521203ML279-2E399N019 0

55 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 521203ML279-2E399NO20 0

836 S02CCW 10.00 FLG 150.0 RFWN 105 N/A 40 U

T443192 05/09/77 0

2 S21203ML281-2CC281015 0

526 S02CCU 10.00 FLG 150.0 RFWN 105 N/A 40 U

14205 12/14/76 0

2 521203ML281-2CC281016 0

527 S02CCW 10.00 FLG 150.0 RFWN 105 N/A 40 U

74205 12/14/76 0

2 S21203ML281-2CC281016 0

837 S02CCU 10.00 FLG 150.0 RFWN 105 N/A 40 w

T443192 05/09/77 0

2 S21203ML281-2CC281017 0

838 SO2CCW 10.00 FLC 150.0 RFWN 105 N/A 40 U

T443192 05/09/77 0

2 521203ML281-2CC281017 0

56 S02CCW 3.00 PLO 150.0 RPUN 105 N/A 40 U

JIE 06/17/77 0

2 S21203ML281-2E401004A 0

Page No.

7 09/08/88 NCR SONGS REPORT (BY LOCATION)

ITMPATTRANS DIAMETER COMMODITY RATING TYPE SPEC GRADE SCHEDULE VENDOR HEAT.LOT DATE QUANTITY SOURCE ASME LINE TEST 11 0 NUMBER T:HARD KSI CONy NCR NUMBER 57 502CCU 3.00 FLG 150.0 RFWN 105 N/A 40 J AE 06/17/77 0

2 S21203ML281-2E401004A 0

58 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 06/17/77 0

2 S21203ML281-2E401b04B 0

59 S02CCy 3.00 FLG 150.0 RFWN 105 N/A 40 W

J4E 06/17/77 0

2 S21203ML281-2E401004C 0

60 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S21203ML281-2E401004C 0

61 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 S21203ML281-2E401004C 0

62 SO2CCU 3.00 FLC 150.0 RFWN 105 N/A 40 W

J4E 06/17/77 0

2 S21203ML281-2E401004E 0

63 SO2CCu 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 521203ML281-2E401004E 0

64 S02CCU 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S21203ML281*2E401004E 0

65 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

JE 06/17/77 0

2 S21203HL281-2E401004E 0

66 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 s21203ML281-2E401N006 0

67 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 06/17/77 0

2 S21203ML281-2E401N007 0

68 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S21203ML281-2E401N1008 0

69 SO2CCU 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 521203ML281-2E4010039 0

70 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 U

AE 06/17/77 0

2 521203ML2812E401N010 0

1 SO2CCW 3.00 FLC 150.0 RFWN 105 N/A 40 w

4E 06/17/77 0

2 521203ML283-2E401003A 0

2 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 06/17/77 0

2 S21203ML283-2E401003A 0

3 sO2CCw 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 521203ML283-2E401003B 0

4 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 521203ML283-2E401003C 0

5 SO2CCU 3.00 FLG 150.0 RFWN 105 N/A 40 w

J jE 06/17/77 0

2 521203ML283-2E401003C 0

6 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S21203ML283-2E401003C 0

7 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 s21203ML283-2E401003E 0

8 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 J AE 06/17/77 0

2 521203ML283-2E401003E 0

9 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S21203ML283-2E401003E 0

10 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S21203ML283-2E401003E 0

13 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 W

J4E 06/17/77 0

2 521203ML283-2E401L003 0

12 SO2CCW 3.00 FLG 150.0 RFUN 105 N/A 40 w

JAE 06/17/77 0

2 521203ML283-2E401L002 0

13 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 521203ML283-2E401L003 0

14 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 J4E 06/17/77 0

2 S21203ML283-2E401L014 0

15 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 s21203ML283-2E401L005 0

16 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S21203ML283-2E401N016 0

17 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S21203ML283-2E401N017 0

18 S02CCW 3.00 FLG 150.0 RFN.

105 N/A 40 U

.4E 06/17/77 0

2 521203ML283-2E401NO018 0

19 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S21203ML283-2E401N019 0

20 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2

$21203ML283-2E401N020 0

00)8/688 NCR SONGS REPORT (BY LOCATION)

ITEM PLANT TRANS DIAMETER COMMODITY RATING TYPE SPEC GRADE SCHEDULE VENDOR HEAT LOT DATE QUANTITY SOURCE ASME LINE TEST M 0 NUMBER 1-HARD KSI CONy NCR NUM~BER 839 SO2CCW 10.00 FLG 150.0 RFUN 105 N/A 40 w

T443192 05/09/77 0

2 S21203ML285-2CC285006 0

828 SO2CCU 10.00 FLG 150.0 RFWN 105 N/A 40 U

14205 12/14/76 0

2 S21203ML285-2CC285007 0

1155 So2CCW 10.00 FLG 150.0 RFUN 105 N/A 40 U

T4205 01/21/77 0

2 S21203ML285-2CC285007 0

21 SD2CCW 3.00 FLG 150.0 RFUN 105 N/A 40 U

J4E 06/17/77 0

2 S21203ML285-2E400004A 0

22 S02CCW 3.00 FLC 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 521203ML285-2E400004A 0

23 SO2CCU 3.00 FLG 150.0 RFUN 105 N/A 40 U

JAE 06/17/77 0

2 S21203ML285-2E400004B 0

24 S02CCU 3.00 FLG 150.0 RFWN 105 N/A 40 U

JE 06/17/77 0

2 S21203ML285-2E4000046 0

25 S02CCU 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S21203ML285-2E400004C 0

26 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S21203ML285-2E400004C 0

27 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 S21203ML285-2E400004D 0

71 SO2CCW 3.00 FLG 150.0 RFUN 105 N/A 40 U

JAE 06/17/77 0

2 S21203ML285-2E400DD4D 0

72 SO2CCU 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 521203ML285-2E400004E 0

73 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 06/17/77 0

2

$21203ML285-2E400004E 0

133 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S21203ML285-2E400N006 0

134 SO2CCU 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S21203ML285-2E400N007 0

135 So2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 521203ML285-2E400N008 0

136 S02CCW 3.00 FLC 150.0 RFWN 105 N/A 40 w

JE 06/17/77 0

2 s21203ML285-2E400N009 0

137 S02CCW 3.00 FLG 150.0 RFUN 105 N/A 40 U

AE 06/17/77 0

2 S21203ML285-2E400N010 0

74 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 06/17/77 0

2 S21203ML287-2E400003A 0

75 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S21203ML287-2E400003A 0

76 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 521203ML287-2E400003B 0

77 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S21203ML287-2E4000036 0

78 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 S21203ML287-2E400003C 0

79 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S21203ML287-2E400003C 0

80 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 W

J4E 06/17/77 0

2 521203ML287-2E400003D 0

81 S02CCW 3.00 FLG 150.0 RFUN 105 N/A 40 w

J4E 06/17/77 0

2 S21203ML287*2E400003D 0

82 SO2CCW 3.00 FLG 150.0 RFWU 105 N/A 40 U

J4E 06/17/77 0

2 S21203ML287*2E400003E 0

83 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 521203ML287-2E400003E 0

138 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 14E 06/17/77 0

2 521203ML287-2E400L001 0

139 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 521203ML287-2E400L002 0

140 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 06/17/77 0

2 521203ML287-2E400LD03 0

141 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S21203ML287-2E400L004 0

37 SO2CCW 3.00 FLG 150.0 RFWN 105 N/A 40 W

J4E 06/17/77 0

2 S21203ML287-2E400L005 0

38 S02CCW 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 521203ML287-2E400N016 0

0908/88 NCR SONGS REPORT (BY LOCATION)

TRANS DIAMETER COMODITY RATING TYPE SPEC GRADE SCHEDULE VENDOR HEAT LOT DATE QUANTITY SORCE ASME LINE TEST M 0 NUMBER T-HARD KSI CONV NCR NUMBER ITEM PLANT TRANS.. DIMEE CO.OIT RATING. TYPE SP... GRADE.

U..

S.......

39 S02CCU 3.00 FLG 150.0 RFUN 105 N/A 40 U

JAE 06/17/77 0

2 S21203ML287-2E400N017 0

40 SO2ccW 3.00 FLC 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 521203ML287-2E400N018 0

41 S02CCU 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S21203ML287-2E400N019 0

42 S02CCU 3.00 FLG 150.0 RFW 105 N/A 40 U

J4E 06/17/77 0

2 S21203ML287-2E400N020 0

537 S02CCU 10.00 FLG 150.0 RFWN 105 N/A 40 U

74205 12/14/76 0

2 S21203ML287-ITEM 22 0

530 S02CCu C 12.00 FLG 150.0 RFWN 105 N/A 40 w

T4205 12/14/76 0

3 S21203ML293-2CC293002

  • 1 88071370 128*

2-2447 8 57 SO2SIS C 24.00 FLG 150.0 RFWN 182 F304 10 U

T55511 01/28/77 0

2 521204MLODl-251001003

-1 0 P 58 S02SIS C 24.00 FLG 150.0 RFWN 182 F304 10 w

755511 01/28/77 0

2 S21204ML002-2SIO02002

  • 2 0 P 1207 S02SIS C 24.00 FLG 150.0 RFWN 182 F316 10 U

w08507 06/10/77 0

2 S21204ML002-2SIO02003

-1 0 P 1263 S02SIS A 24.00 FLG 150.0 RFWN 182 F304 10 w

755511 1/28/77 0

2 S21204ML002-251109002 0

582 S02SIS C 14.00 FLG 150.0 RFWN 182 F316 10 w

82616 10/14/77 0

2 521204ML003-2S1003001

-1 0 P 1176 S02SIS 24.00 FLG 150.0 RFWN 182 F316 10 w

W08507 06/10/77 0

2 S21204ML003-2S]003013 0

584 S02SIS 24.00 FLG 150.0 RFUN 182 F304 10 w

E05305 01/13/78 0

2 S21204MLOD4-2S004014 0

959 S02SIS 24.00 FLG 150.0 RFWN 182 F304 10 U

755511 01/28/77 0

2 S21204ML004-2S1004018 0

962 S02SIS C 8.00 FLG 150.0 RFUN 182 F304 10 U

T62378T 01/28/77 0

2 S21204MLOD9-2S1009002

-1 0 P 439 S02SIS C 4.00 FLG 900.0 RFWN 182 F316 80 U

83329 06/09/80 0

2 S21204ML013-ITEM 50

-1 0 P 440 SO2SIS C 4.00 FLG 900.0 RFWN 182 F316 80 U

B3329 06/09/80 0

2 521204ML013-ITEM 51

-2 0 P 441 S02SIS C 4.00 FLC 900.0 RFWN 182 F316 80 U

B3329 06/09/80 0

2 521204ML014-ITEN 52

-1 0 P 442 S02SIS C 4.00 FLG 900.0 RFWN 182 F316 80 U

B3329 06/09/80 0

2 S21204ML014-ITEM 53

-2 0 P 585 S02SIS C 8.00 FLG 300.0 RFWN 182 F316 20 U

HH657 10/16/77 0

2 S21204ML034-2S1034008

-1 0 P 1251 S02SIS A 8.00 FLG 300.0 RFWN 182 F316 20 w

B2717 3/23/78 0

2 521204ML036-2Sl036007 0

583 S02SIS C 8.00 FLG 300.0 RFWN 182 F316 20 U

s2827 08/18/78 0

2 521204ML036-2S1036012

-1 0 P 960 S02SIS C 8.00 FLG 300.0 RFUN 182 F316 20 U

755518 05/06/77 0

2 521204ML037-ITEM 7

-1 0 P 941 S02SIS C 8.00 FLG 300.0 RFN 182 F316 10 U

762834 01/28/77 0

2 S21204ML038-2S1038025

-1 0 P 87 502SIS A 8.00 FLC 300.0 RFWN 182 F316 10 w

82827 8/18/78 0

3 S21204ML133-2S1133037

-1 0 P W 80 S02SIS A 8.00 FLC 300.0 RFWN 182 F316 20 H657 10/16/77 0

2 521204ML145-2S1145005

-2 0 P 1019 502FSS C 8.00 FLG 300.0 RWWN 182 F316 20 w

762834 05/06/77 0

2 521204ML145-ITEM 6

-1 0 P 581 S02SIS C 1.00 FLG 600.0 RFWN 182 F316 40 U

81345 07/14/78 0

2 521204ML149-2S1149006

-1 0 P 940 SO2CSS C 8.00 FLG 300.0 RFWN 182 F316 10 U

T62834 01/28/77 0

2 S21206ML001-2CS056001

-1 0 P 939 502CSS C 8.00 FLG 300.0 RFWN 182 F316 10 U

162834 01/28/7 0

2 521206MLD01-2CS056002

-2 0 P 1172 502CSS 8.00 FLG 300.0 RFWN 182 F316 20 U

162834 01/21/77 0

2 S21206ML003-ITEM 13 0

961 502CSS C 8.00 FLG 300.0 RFWN 182 F316 20 w

755518 05/06/77 0

2 S21206ML004-2CS004035

-1 0 P 938 SO2CSS C 4.00 FLG 300.0 RFWN 182 F316 10 U

162834 01/28/77 0

2 S21206ML030-2CS030003

-2 0 P 1281 S02CSS A 4.00 FLO 300.0 RPBL 182 F316 N/A H

82753 N/A 0

2.

S21206ML030-2CS030005

-1 0 P

Page No.

10 09/08/88 NCR SONGS REPORT (BY LOCATION)

ITEM PLANT TRANS DIAMETER COMMOITY RATING TYPE SPEC GRADE SCHEDULE VENDOR HEAT LOT DATE QUANTITY SOURCE ASME LINE TS UBRTHR

~.OVWRNME 827 S02CSS C 4.00 FLG 300.0 RFBL 182 F316 40 w

S654357 06/10/77 0

2 521206ML031-2CS031004

-1 0 P 1060 SO2SCS C 4.00 FLG 300.0 RFWN 182 F316 10 U

wA1877 06/10/77 0

3 S21206ML031-2SC031003

.2 0 P 735 S02CSS C 12.00 FLG 300.0 RFWN 182 F316 20 w

82764 04/05/78 0

2 S21206MLO33-ITEN 3

-1 0 P 736 S02CSS C 12.00 FLG 300.0 RFUN 182 F316 20 U

B2764 04/05/78 0

2 S21206ML033-ITEM 4

  • 2 0 P 731 SO2CSS 8.00 FLG 300.0 RFWN 182 F316 20 w

B2717 03/23/78 0

2 S21206ML041-2CS041032 0

732 502CSS 8.00 FLG 300.0 RFWN 182 F316 20 W

82717 03/23/78 0

2 S21206ML041-2CS041033 0

8 733 502CSS 8.00 FLG 300.0 RFWN 182 F316 20 w

B2717 03/23/78 0

2

$21206ML041-2CS041033 0

815 502CSS 8.00 FLG 300.0 RFWN 182 F316 20 U

H657 09/16/77 0

2 521206ML047-2CS047020 0

816 502CSS 8.00 FLG 300.0 RFWN 182 F316 20 w

HH657 09/16/77 0

2 521206ML047-2CS047033 0

817 SO2CCW 8.00 FLC 300.0 RFWN 182 F316 20 w

HH657 09/16/77 0

2 521206ML047-2CS047033 0

734 S02CSS C 8.00 FLG 300.0 RFWN 182 F316 20 w

62827 08/18/78 0

2 S21206ML053-3CS053002

.1 0 P 551 SO2VCC C 3.00 FLG 150.0 RFWN 182 F304 40 w

82502 10/14/77 0

2

$21208ML035-2VC035002

-1 0 P 1271 S02FSS A 10.00 FLG 150.0 RFUN 182 304 10 w

762378T 1/28/77 0

3 S21219ML013-ITEM 31 0

819 S02STM C 4.00 FLG 900.0 RFWN 105 N/A 80 U

T4205 04/04/78 0

3 521301ML017-ITEM 51

-1 88071345 105*

743 SO2STM 0.50 FLG 600.0 RFSW 350 LF2 160 U

83811 07/05/83 0

2 521301ML921-ITEM 10 0

742 SO2STM 0.50 FLG 600.0 RFSW 350 LF2 160 w

63811 07/05/83 0

2 521301ML921-ITEM 6 0

744 502STM 0.50 FLG 600.0 RFSW 350 LF2 160 U

83811 07/05/83 0

2 521301ML924-ITEM 11 0

1169 SO2FWS C 8.00 FLG 150.0 RFW 182 F304 10 w

T62378T 01/28/77 0

3 521305ML047-2FW047010

-1 0 P 284 S02FWS C 0.00 FLG 150.0 REDRFSO 182 F316 N/A w

83044 05/18/79 0

3 521305ML048-ITEM 25

-1 0 P 283 S02FWS C 0.00 FLG 150.0 REDRFSO 182 F316 N/A H

83044 05/18/79 0

3 S21305ML050-ITEM 38

-1 0 P 297 SO2FWS C 8.00 FLG 150.0 RFWN 182 F304 10 w

762378T 01/28/77 0

3 521305ML053-2FW053001

-1 0 P 437 S02FU C 2.00 FLG 0.0 RFSW 350 LF2 160 w

83811 07/05/83 0

3 S21305ML078-ITEM 13

-1 88061326 134*

2-2448 829 SO2FS C 4.00 FLG 900.0 RFWN 105 N/A 40 U

T4205 06/30/77 0

3 S21305ML098-2FW098025

-1 88071328 150 830 S02FWS C 4.00 FLG 900.0 RFWN 105 N/A 40 w

T4205 06/30/77 0

3 S21305ML099-2FW099028

-1 88061329 141 268 S02FWS C 3.00 FLG 150.0 RFBL 182 F316 N/A W

83425 10/24/80 0

3 S21305ML144-ITEM 29

-1 0 P 269 S02FWS C 3.00 FLG 150.0 RF8L 182 F316 N/A U

B3425 10/24/80 0

3 S21305ML144-ITEM 30

  • 2 0 P 1107 SO2FWS 6.00 FLG 900.0 RFWN 105 N/A 120 U

A03641 10/06/80 0

3 s21305ML331-2FW331001 0

1131 S02FWS 6.00 FLG 900.0 RFWN 105 N/A 120 U

A03641 10/06/80 0

3 S21305ML331-2FW331001 0

290 S02FWS C 6.00 FLG 900.0 RFBL 105 N/A N/A w

56989 10/06/80 0

3 S21305ML331-2FW331008 2

88071337 154 296 S02FWS C 6.00 FLG 150.0 RFSO 105 N/A 80 U

3453 10/10/80 0

3 521305ML335-2FW335002

-1 88071342 145 276 S02FWS C 8.00 FLG 150.0 RFWN 182 F316 10 w

83355 06/27/80 0

3 S21305ML335-2FW335004

-2 0 P 275 S02FWS C 8.00 FLG 150.0 RFW 182 f316 10 H

53371 08/15/80 0

3 521305ML335-2FW335015

.1 0 P 438 S02FW5 C 6.00 FLG 300.0 RFSW 182 F316 10 w

53329 09/24/80 0

3 521305ML335-2FW33501 7

-2 0 P 506 S02SC. C 2.50 PLO 150.0 PPUN 105 N/A 40 H

14696 10/21/76 0

3 S21413ML001-2SC001001

.5 88071344 150

Page No.

11 09/08/8 8 NCR SONGS REPORT (BY LOCATION)

ITEM PLANT TRANS DIAMETER COMMODITY RATING TYPE SPEC GRADE SCHEDULE VENDOR HEAT LOT DATE QUANTITY SOU.RCE ASME LINE TEST N 0 NUMBER T-HARD KSI CONV NCR NUMiBER 502 SO2SCS C 2.50 FLO 150.0 FFUN 105 N/A 40 w

T4696 10/21/76 0

3 521413ML001-2SC001006

-4 88071344. 153 509 SO2SCS C 2.50 FLO 150.0 FFWN 105 N/A 40 U

14696 10/21/76 0

3 521413ML001-2SCOD1010

-3 88071344 160 503 SO2SCS C 2.50 FLO 150.0 FFN 105 W/A 40 U

74696 10/21/76 0

3 S21413ML001-2SC001014

-2 88061344 144 507 S02SCS C 2.50 FLO 150.0 FFWN 105 N/A 40 w

T4696 10/21/76 0

3 521413ML001-25C001018

-2 88071344 138 1285 502SCS A 2.50 FLO 150.0 FFWN 105 N/A 40 U

74696 10/21/76 0

3

$21413ML001-25C001022

-3 88071348 150 510 S02SCS C 2.50 FLC 150.0 FFUN 105 N/A 40 U

T4696 10/21/76 0

3 S21413ML001-ITEM 10

-6 88071344 141 504 S02SCS C 2.50 FLO 150.0 FFWN 105 N/A 40 U

T4696 10/21/76 0

3 S21413ML002-2SC002002

-1 88071346 138 284 S02SCS A 2.50 FLG 150.0 FFWN 105 N/A 40 U

T4696 10/21/76 0

3

$21413ML002-2SC002006

-2 88071346 168 1064 S02SCS C 2.50 FLG 150.0 FFWN 105 N/A 40 U

T4696 10/21/76 0

3 521413ML003-2SC003001

-1 88071347 150 508 S02SCS C 2.50 FLO 150.0 FFW 105 N/A 40 U

T4696 10/21/76 0

3

$21413ML003-2SC003006

-4 88071347 157 1166 S02SCS 2.50 FLO 150.0 FFWN 105 N/A 40 w

T4696 10/21/76 0

3 521413ML003-2S0003009 0

1165 SO2SCS 2.50 FLO 150.0 FFWN 105 N/A 40 w

T4696 10/21/76 0

3 521413ML003-2SC003020 0

512 S02SCS C 2.50 FLG 150.0 FFWN 105 N/A 40 U

14696 10/21/76 0

3 S21413ML003-ITEM 2

-3 88071347 143 511 S02SCS C 2.50 FLG 150.0 FFUN 105 N/A 40 U

T4696 10/21/76 0

3 S21413ML003-ITEM 6

-2 88071347 151 885 S02SCS C 2.50 FLO 150.0 FFWN 105 N/A 40 w

7415 04/18/78 0

3 521413ML004-2SCDD4008

-2 88071348 141 1167 S02SCS C 2.50 FLG 150.0 FFWN 105 N/A 40 U

T4696 10/21/76 0

3

$21413ML004-2SC004012

-7 88071348 158 1286 SO2SCS A 2.50 FLG 150.0 FFWN 105 N/A 40 w

14696 10/21/76 0

3 521413ML004-2SC004015

-8 88071348 162 840 S02SCS 2.50 FLG 150.0 RFUN 105 N/A 40 U

T4696 10/21/76 0

3 S21413ML004-25C004016

-4 88071348 153 886 S02SCS C 2.50 FLG 150.0 FFUN 105 N/A 40 U

1415 04/18/78 0

3 521413ML004-2SC004021

-5 88071348 163 887 SO2SCS C 2.50 FLG 150.0 FFUN 105 N/A 40 w

1415 04/18/78 0

3

$21413ML004-2SC004021

-6 88071348 137 505 SO2SCS C 2.50 FLG 150.0 FFWN 105 N/A 40 U

14696 10/21/76 0

3 521413ML004-ITEM 19

-1 88071348 156 519 S02SCS C 2.50 FLG 150.0 FFWN 105 N/A 40 U

14696 10/21/76 0

3 521413ML005-2S0005006

-3 88071350 150 513 S02SCS C 2.50 FLG 150.0 FFWN 105 N/A 40 w

T4696 10/21/76 0

3 521413ML005-ITEM 1

-2 88071350 137 303 SO2SCS C 2.50 FLG 150.0 FFUN 105 N/A 40 U

74696 10/21/76 0

3 S21413ML005-ITEM 18

-1 88071350 138 304 S02SCS C 2.50 FLG 150.0 FFWN 105 N/A 40 U

14696 10/21/76 0

3 S21413ML020-2SC019001

-1 88071556 138 305 S02SCS C 2.50 FLG 150.0 FFWN 105 N/A 40 w

T4696 10/21/76 0

3 S21413ML025-2SCO25003

-1 88071232 140 552 S02ACS 6.00 FLO 150.0 RFWN 182 F304 10 U

B2502 09/08/78 0

2 521500ML013-2AC013003 0

1112 SO2ACS 6.00 FLG 150.0 RFWN 182 F3D4 10 w

B2505 09/20/78 0

2 S21500ML013-2AC013003 0

553 SO2ACS 6.00 FLG 150.0 RFWN 182 F304 10 W

62502 09/08/78 0

2 521500ML015-2AC015003 0

1113 SO2ACS 6.00 FLG 150.0 RFWN 182 F304 10 w

62505 09/20/78 0

2 521500ML015-2AC015003 0

1272 SOZACS A 10.00 FLG 150.0 RFWN 105 N/A 40 U

T4205 12/21/77 0

2 521500ML023-ITEM 32 0

1072 SO2ACS 10.00 FLO 150.0 RFWN 105 N/A 40 w

14205 12/21/77 0

2 S21500ML023-ITEM 35 0

923 S02ACS 10.00 FLC 150.0 RFBL 105 N/A N/A U

H18A3T 01/17/78 0

2 521500ML023-ITEM 36 0

1133 S02.GS 2.00 PLO 150.0 PP.N 105 N/A 40 U

Co 09/12/85 0

2 S22418ML335-ITEM 23 (1 OF 3) 0

Page No.

12 0 9/08/ 88 NCRSONGS.REPORT (BY.LOCATION)

ITEM PLANT TRANS DIAMETER C OMODITY RATING TYPE SPEC GRADE SC EDULE VENDOR NEAT LOT DATE UANTITY S ORCE ASME LINE T S

. -U B R T H R S

O V N R N M E 1134 SO2NGS 2.00 FLG 150.0 FFWN 105 N/A 40 U

Cox 09/12/85 0

2 S22418ML335-ITEM 23 (2 OF 3) 0 1135 S02UGS 2.00 FLG 150.0 FFWN 105 N/A 40 w

Cox 09/12/85 0

2

$22418ML335-ITEM 23 (3 OF 3) 0 974 SO2DAS C 3.00 FLG 150.0 FFUN 105 N/A 40 U

1415 04/18/78 0

3 s22420ML002-2DA002007

-2 88071233 130*

2-2445 975 SO2AS C 3.00 FLG 150.0 FFUN 105 N/A 40 w

T415 04/18/78 0

3 S22420ML002-2DA002008

.3 88071233 136*

2-2445 976 SO2DAS C 3.00 FLG 150.0 FFWN 105 N/A 40 U

T415 04/18/78 0

3 S22420ML002-2DA002008

-4 88071233 134' 977 S02DAS C 3.00 FLG 150.0 RFN 105 N/A 40 M 7415 04/18/78 0

3 S22420ML002-ITE 5

-1 88071233 142 2-2445 25 S02DAS C 6.0 FLG 150.0 FFUN 105 N/A 40 U

M908701 04/18/78 0

3 S22420ML007-20A007006

.1 88061237 126*

2-2459 26 SO2DAS C 8.00 FLG 150.0 FFWN 105 N/A 40 w

M974801 09/23/77 0

3 522420ML007-2DA007005

-2 8071241 138 946 SO2DAS C 8.00 FLG 150.0 FFUN 105 N/A 40 U

M765401 04/18/78 0

3 22420ML007-2DA007006 3

88071241 141 947 S2DAS C 8.00 FIG 150.0 FF4N 105 N/A 40 U

M765401 04/18/78 0

3 S22420ML007-2DA007006

-3 88071241 942 SO2DAS C 8.00 FLG 150.0 FFUN 105 N/A 40 U

M765401 04/18/78 0

3 S22420ML008-2DA008002

-1 88071243 130 2-2446 943 S02DAS C 8.00 FLG 150.0 FFWN 105 N/A 40 U

T765401 04/18/78 0

3 S22420ML008-2DA008005

-3 88071243 133*

2-2446 945 SO2DAS C 8.00 FLG 150.0 FF N 105 N/A 40 w

M765401 04/18/78 0

3 S22420ML008-2DA008002

-2 88071243 138 1139 S020AS 8.00 FLG 150.0 RFUN 105 N/A 40 U

-30266 02/09/8 1

0 3

222420M-00822A008 65 0

1208 S02DAS 8.00 FLG 150.0 RFWN 105 N/A 40 U

M765401 04/18/78 0

3 S22420ML008-20A008006 0

1209 502DAS 8.00 FLG 150.0 RFWN 105 N/A 40 U

M76501 04/18/78 0

3 S22420ML008-2DA008006 0

1027 S02DAS C 6.00 FIG 150.0 FFUN 105 N/A 40 U

M908701 04/18/78 0

3 522420ML008-2DA008007

-4 88071247 129*

2-2461 1063 SO2DAS C 8.00 FLG 150.0 RFN 105 N/A 40 U

M613601 06/30/77 0

3 522420ML008-2DA008007

-3 88071247 14 1028 SO2DAS C 6.00 FLG 150.0 FFWN 105 N/A 40 U

m908701 10/08/78 0

3 S22420ML016-2DA008008

-5 88071247 121 2-2461 1029 S02DAS C 6.00 FLG 150.0 FFUN 105 N/A 40 U

4908701 10/08/78 0

3 S22420ML016-2DA008008

-6 88071247 124 2-2461 973 S02DAS C 3.00 FLG 150.0 FFUN 105 N/A 40 U

1415 04/18/78 0

3 522420ML016-2DA016008

-2 88071257 138 971 S02DAS C 3.00 FLG 150.0 FFWN 105 N/A 40 U

1415 04/18/78 0

3 S22420ML016-2DA016009

-3 88071257 145 972 S02DAS C 3.00 FIG 150.0 FFUN 105 N/A 40 U

T415 04/18/78 0

3 S22420ML016-20A016009

-4 8807257 138 978 S02DAS C 3.00 FIG 150.0 RPFJN 105 N/A 40 U

T415 04/18/78 0

3 S22420ML016-ITEM 5

-1 88071257 136.5*

2-2451 30 S02DAS C 6.00 FIG 1 50.0 FPN 105 N/A 40 U

M908701 04/18/78 0

3 S22420ML021-2DA021001

-1 88071261 125*

2-2474 1033 S02DAS C 8.00 FLG 150.0 FFUN 105 N/A 40 U

M765 4 01 04/18/78 0

3 S22420ML021-2DA021006

-2 88071261 134 949 S02DAS C 8.00 FIG 150.0 FFUN 105 N/A 40 U

m765401 04/18/78 0

3

$22420MI021-2DA021006

-3 88071261 129*

1129 S02DAS C 8.00 FIG 150.0 BFWN 105 N/A 40 U

m765401 04/18/78 0

3 S22420ML021-ITEM 25

-4 88071261 129' 1031 SOZOAS C 8.00 FIG 150.0 FPUN 105 N/A 40 U

m765401 04/18/78 0

3 S22420ML022-20A022001

-1 88071266 129*

2-2476 1032 S02DAS C 8.00 FLG 150.0 FFUN 105 N/A 40 U

m4765401 04/18/78 0

3 S22420ML022-2DA022001

.2 88071266 126*

2-2476 1033 S02DAS C 8.00 FIG 150.0 FFUN 105 N/A 40 w

m765401 04/18/78 0

3 522420ML022-20A022002

-3 88071266 162 1020 S02DAS 8.00 FLG 150.0 RFUN 105 N/A 40 U

A11404 09/08/78 0

3 S22420ML022-2DA022007 0

1127 S02DAS 8.00 FLG 150.0 RFWN 105 N/A 40 U

m613601 06/30/77 0

3 S22420M-022-ITE8 16 0

1151 S02DAS C 6.00 FIG 150.0 FFWN 105 N/A 40 U

m908701 09/D8/78 0

3 S22420ML022-IIEM 17

-4 88071267 130' 2-2468

Page No.

13 09/08/a8 NCR SONGS REPORT (BY LOCATION)

ITEM PLANT TRANS DIAMETER COMMODITY RATING TYPE SPEC GRADE SCHEDULE VENDOR HEAT LOT DATE QUANTITY SOURCE ASME LINE TEST M.0_NUMBER 1-HARD KSINCOWV NCR HUMBER 969 SO2DAS 3.00 FLG 150.0 FFWN 105 N/A 40 U

T415 04/18/78 0

3 S22420ML036-2DA036008

-3 88071327 144 970 SO2DAS 3.00 FLG 150.0 FFUN 105 N/A 40 U

7415 04/18/78 0

3 S22420ML036-2DAO36008

-4 88071327 137 980 SO2DAS 3.00 FLG 150.0 RFWN 105 N/A 40 U

T415 04/18/78 0

3 S22420ML036-ITEM 14

-2 88071327 135*

2-2458 979 SO2DAS 3.00 FLG 150.0 RFWN 105 N/A 40 U

7415 04/18/78 0

3 S22420MLO36-ITEM 6

-1 88071327 142 1152 SO2DAS 6.00 FLG 150.0 RFWN 105 N/A 40 U

M908701 04/18/78 0

3 S22420ML041-2DA041001 0

1061 SO2DAS 8.00 FLG 150.0 FFWN 105 N/A 40 U

M974801 09/23/77 0

3 S22420ML041-20AD41005

-1 88071330 140 034 SO2DAS 8.00 FLG 150.0 FFWN 105 N/A 40 w

M765401 04/18/78 0

3 522420ML041-2DAD41006

-2 88071330 140 035 So2DAS 8.00 FLG 150.0 FFWN 105 N/A 40 U

M765401 04/18/78 0

3 522420ML041-20A041006

  • 3 88071330 124*

2-2452 1036 S02DAS C 8.00 FLG 150.0 FFWN 105 N/A 40 U

M765401 04/18/78 0

3 522420ML042-2DA042001

-1 88071336 135*

2-2450 1037 S02DAS C 8.00 FLG 150.0 FFWN 105 N/A 40 U

M765401 04/18/78 0

3 S22420ML042-2DA042001

-2 88071336 133*

2-2450 1038 502DAS 8.00 FLG 150.0 FFWN 105 N/A 40 w

M765401 04/18/78 0

3 522420ML042-20A042002

-6 88071333 129*

2-2449 1239 S02DAS A 8.00 FLG 150.0 RFUN 105 N/A 40 U

A11404 09/08/78 0

3 S22420ML042-2A042006

-5 88071333 152 1240 S02DAS A 8.00 FLG 150.0 RFWN 105 N/A 40 U

K765401 04/18/78 0

3 522420ML042-2DA042006

-3 88071333 140 944 SO2DAS C 8.00 FLG 150.0 RFWN 105 N/A 40 U

M613601 06/30/77 0

3 S22420ML042-2DA042007

-7 88071333 143 1062 S02DAS C 6.00 FLG 150.0 FFWN 105 N/A 40 U

M908701 04/18/78 0

3 522420ML042-2DA042007

-8 88071333 148 1128 502DAS 8.00 FLC 150.0 RFWN 105 N/A 40 U

m613601 06/30/77 0

3 S22420ML042-ITEM 17

-4 88071333 145 968 SOZDAS C 3.00 FLG 150.0 FFWN 105 N/A 40 U

T415 09/08/78 0

3 522420ML049-20AQ49007

-1 88071339 130*

2-2470 966 S02DAS C 3.00 FLG 150.0 FFWN 105 N/A 40 U

7415 04/18/78 0

3 522420ML049-2DA049008

-2 88071339 144 967 So2DAS C 3.00 FLG 150.0 FFWN 105 N/A 40 U

7415 04/18/78 0

3 S22420ML049-2DA049008

-3 88071339 137.5 965 SO2DAS C 3.00 FLG 150.0 RFWN 105 N/A 40 U

1415 04/18/88 0

3 S22420ML049-ITEM 5

-1 88071338 147 1149 502DAS 6.00 FLG 150.0 FFWN 105 N/A 40 w

M908701 09/08/78 0

3 S22420ML054-2DA054001 0

1039 S02DAS C 8.00 FLG 150.0 FFUN 105 N/A 40 U

M765401 04/18/78 0

3 S22420ML054-2DA054006

-1 88071340 147 1040 S02DAS C 8.00 FLG 150.0 FFWN 105 N/A 40 U

M765401 04/18/78 0

3 522420ML054-2DA054006

-2 88071340 148 1130 502DAS 8.00 FLG 150.0 RFWN 105 N/A 40 U

M765401 04/18/78 0

3 S22420ML054-ITEM 11 0

0 41 S02DAS C 8.00 FLG 150.0 FFWN 105 N/A 40 U

m765401 04/18/78 0

3 S22420ML055-2DA055001

-1 88071341 144 042 S02DAS C 8.00 FLG 150.0 FFWN 105 N/A 40 w

M765401 04/18/78 0

3 S22420ML055-2DA055001

-2 88071341 140 1043 SO2DAS C 8.00 FLG 150.0 FFWN 105 N/A 40 U

M765401 04/18/78 0

3 522420ML055-2DA055002

-3 88071341 134*

2-2443 1148 S02DAS C 8.00 FLG 150.0 FFWN 105 N/A 40 w

M613601 06/30/77 0

3 S22420ML055-2DA055005

.5 88071343 140 1292 S02DAS A 8.00 FLG 150.0 FFWN 105 N/A 40 U

A11404 09/08/78 0

3 S22420ML055-2DA055006

-6 88071343 169 1293 SO2DAS A 8.00 FLG 150.0 FFWN 105 N/A 40 w

?

0 3

S22420ML055-2DA055006

-5 88071343 168 1021 S02DAS C 8.00 FLG 150.0 RFWN 105 N/A 40 U

A11404 09/08/78 0

3 522420ML055-2DA055007

-7 88071343 189**

2-2465 1045 S02DAS C 6.00 FLG 150.0 FFWN 105 N/A 40 w

M908701 04/18/78 0

3 522420ML055-2DA055008

-9 88071343 144 1150 5020AS C 6.00 FLG 150.0 FFWN 105 N/A 40 U

m908701 09/08/78 0

3 522420ML055-2DA055008

-8 88071343 136*

2-2464 1153.O0AS C 6.00 FLG 150.0 FF..

105 N/A 40 U

m908701 09/08/78 0

3 522420ML055-ITEM 10

-7 88071343 133*

2-2464

Page No.

14 09/08/88 NCR SONGS REPORT (BY LOCATION)

ITEM PLANT TRANS DIAM4ETER COMMODITY RATING TYPE SPEC GRADE SCHEDULE VENDOR HEAT LOT DATE QUANTITY SOURCE ASME LINE TEST M.0 NUMBER T:HARD KSI-CONV NCR.NUMBER 831 SO2FOS 4.00 FLG 150.0 RFWN 105 N/A 40 w

T4228 09/08/78 0

3 S22421ML017-ITEM 14

-1 88071349 157 981 SO2FOS C 3.00 FLG 150.0 RFUN 105 N/A 40 w

T415 09/08/78 0

3 S22421ML018-2F0018001

-1 88071351 143 1046 S02FOS C 2.00 FLG 300.0 RFSW 105 N/A 80 w

COP 0

3 S22421ML018-ITEM 44

-2 88071351 146 1047 SOZFOS C 2.00 FLG 300.0 RFSW 105 N/A 80 w

COP 0

3 S22421ML018-ITEM 45

-3 88071351 144 982 SO2FOS C 3.00 FLG 150.0 RFWN 105 N/A 40 w

T415 09/08/78 0

3 S22421ML020-2F0020001

-1 88071352 145 1002 S02FOS C 3.00 FLG 150.0 RFWN 105 N/A 40 w

T415 09/08/78 0

3 S22421ML022-2Fo022002

-1 88071353 137 a

8 502FOS C 3.00 FLG 150.0 RFWN 105 N/A 40 w

T415 09/08/78 0

3 522421ML023-2F0023001

-1 88071354 144

.9 S02FOS C 3.00 FLG 150.0 RFWN 105 N/A 40 U

T415 09/08/78 0

3 S22421ML023-2F0023002

-3 88071354 143 997 502FOS C 3.00 FLG 150.0 RFBL 105 N/A 40 w

1415 09/08/78 0

3 522421ML023-2F0023003

-2 88071354 137 832 S02FOS C 4.00 FLG 150.0 RFWN 105 N/A 40 w

T4228 09/08/78 0

3 S22421ML026-ITEM 14

-1 88071355 140.5 1000 502F0S C 3.00 FLG 150.0 RFWN 105 N/A 40 w

T415 09/08/78 0

3 522421ML027-2F0027001

-1 88071357 133.5*

2-2463 1048 S02FOS 2.00 FLG 300.0 RFSW 105 N/A 80 w

COP 0

3 522421ML027-ITEM 57 0

1184 502FOS 2.00 FLG 600.0 RFWN 105 N/A 80 w

COP 03/04/86 0

3 522421ML027-ITEM 58 0

983 S02FOS C 3.00 FLG 150.0 RFWN 105 N/A 40 w

1415 09/08/78 0

3 S22421ML029-2Foo29001

-1 88071358 151 1001 SO2FOS C 3.00 FLG 150.0 RFWN 105 N/A 40 w

T415 09/08/78 0

3 S22421ML031-ITEM 5

-1 88071359 141 994 S02FOS C 3.00 FLG 150.0 RFWN 105 N/A 40 w

T415 09/08/78 0

3 522421ML032-2F0032001

-1 88071360 153 986 502FOS C 3.00 FLG 150.0 RFWN 105 N/A 40 w

T415 09/08/78 0

3 S22421ML032-2F0032002

-3 88071360 145 985 S02FOS C 3.00 FLG 150.0 RFBL 105 N/A 40 U

T415 09/08/78 0

3 522421ML032-2Foo32003

-2 88071360 123*

2-2456 1181 502FOS C 3.00 FLG 150.0 RFWN 105 N/A 40 w

1415 09/08/78 0

3 522421ML066-2F0066006

-1 88071361 143 989 SO2FOS C 3.00 FLG 150.0 RFWN 105 N/A 40 w

1415 09/08/78 0

3 522421ML066-2Foo66007

.2 88071361 143 990 S02FOS C 3.00 FLG 150.0 RFWN 105 N/A 40 w

7415 09/08/78 0

3 S22421ML066-2F0066007

-3 88071361 137 1182 502FOS 3.00 FLG 150.0 RFWN 105 N/A 40 U

7415 09/08/78 0

3 522421ML066-2FD66008 0

984 502FOS 3.00 FLG 150.0 RFWN 105 N/A 40 w

T415 09/08/78 0

3 522421ML066-2F0066010 0

993 502FDS 3.00 FLG 150.0 RFWN 105 N/A 40 H

T415 09/08/78 0

3 522421ML068-2FO068004

-1 88071363 151 9

91 502F0S 3.00 FLG 150.0 RFUN 105 N/A 40 W

7415 09/08/78 0

3 S22421ML068-2F0068005

  • 2 88071363 W

92 S02FOS C 3.00 FLG 150.0 RFwN 105 N/A 40 w

T415 09/08/78 0

3

$22421ML068-2FOD68005

-3 88071363 147 995 502Fos C 3.00 FLG 150.0 RFWN 105 N/A 40 w

7415 09/08/78 0

3 522421ML068-2F0068006

-4 88071363 143 996 502FOS C 3.00 FLG 150.0 RFWN 105 N/A 40 U

T415 09/08/78 0

3 522421ML068-2F0068006

-5 88071363 153 987 SO2FOS C 3.00 FLG 150.0 RFWN 105 N/A 40 w

7415 09/08/78 0

3 522421ML068-2F0068007

-6 88071363 150 988 SO2FOS C 3.00 FLG 150.0 RFUN 105 N/A 40 U

T415 09/08/78 0

3 S22421ML068-2Foo68008

-7 88071363 136*

2-2457 795 S03RCS C 6.00 FLG 600.0 RFWN 182 F316 40 w

83070 05/18/79 0

2 S31201ML017-3RC017038

-1 0 P 1125 SO3RCS 6.00 FLG 600.0 RFWU 182 F316 40 U

63070 05/18/79 0

2 531201ML017-3RC017038 0

1183 S03RCS 6.00 FLG 600.0 RFBL 182 F316 N/A w

B3296 N/A 0

2 S31201ML017-3RC161001 0

1122 so3RCS 6.00 FIG 0.0 IC GROOVE 182 F316 160 w

118613 06/30/78 0

1 S31201ML032-ITEM #29 0

098

/88 NCR SONGS REPORT (BY LOCATION)

ITEM PLANT TRANS DIAMETER COMMODITY RATING TYPE SPEC GRADE SCHEDULE VENDOR HEAT LOT DATE QUANTITY SOURCE ASME LINE TEST 0 NUMBER 7-HARD KSI COWy NCR NUMBER 1123 S03RCS 6.00 FLG 0.0 LG GROOVE 182 F316 160 w

L18613 06/30/78 0

1 S31201ML033-ITEM #30 0

556 S03CC C

18.00 0 150.0 RFWN 105 N/A 40 w

T27K 10/21/76 0

3 531203ML005-3CC005004

-2 88070513 140 67.5 557 SO3CCW C 28.00 FLG 125.0 FFWN 105 N/A 40 w

W9820 05/12/78 0

3 S31203ML005-3CCO05015

-1 88070512 148 70.6 558 So3CCW C 18.00 PLG 150.0 RFWN 105 N/A 40 w

1 7 10/21/76 0

3 S31203ML007-3CC007004

-1 88070519 142 68.3 76 S03CCW C 2.50 PLO 150.0 RPHN 105 N/A 40 H

T4696 10/21/76 0

3 531203ML008-3CC008009

-1 88075260 125*

3-2174 SO3CCW C 2.50 FLG 150.0 RFWN 105 N/A 40 H

T415 05/04/79 0

3 531203ML008-3CC008010

-2 88075260 172 SO3CCH 2.50 PLO 150.0 RPHN 105 N/A 40 H

T73519 06/06/79 0

3 S31203ML012-ITEM 11 0

0 S03CCW C 2.50 PLG 150.0 RPJ 105 N/A 40 H

74902 05/09/77 0

3 S31203ML012-ITEM 12

-1 88070535 146 69.7 775 SO3CCW C 2.50 FLG 150.0 RFWN 105 N/A 40 H

T415 05/04/79 0

3 531203ML013-ITEM 36

-2 88070532 140 67.5 785 S03CCW C 2.50 FLG 150.0 RFWN 105 N/A 40 H

14902 05/09/77 0

3 531203ML013-ITEM 51

-1.

88070532 137 66 772 SO3CCW 2.50 FLG 150.0 RFWN 105 N/A 40 w

T4902 05/09/77 0

3 531203ML014-3CC014002

-2 88070537 154 922 SO3CCW C 2.50 FLG 150.0 RFWN 105 N/A 40 H

T415 04/08/78 0

3 531203ML014-3CC014003

-1 88070537 138 1282 SO3SIS A 8.00 FLC 300.0 RFWN 182 F316 20 w

NH657 01/12/78 0

2 S31204ML037-ITEM 9

-2 0 P 570 So3CCW C 3.00 FLG 150.0 RFWN 105 N/A.

40 H

T415 09/23/77 0

3 531203ML064-3CCO64004

-1 88070538 156 77 571 S03CCU C 3.00 FLG 150.0 RFWN 105 N/A 40 H

J4E 10/21/76 0

3 531203ML064-3CCO64005

-3 88070538 164 81.5 3-2152 683 S03CCU C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

3

$31203ML06.4-3CCD6.005

-2 88070538 180 88 760 So3CCW C 3.00 FLC 150.0 RFWN 105 N/A 40 w

T2190 10/21/76 0

3 S31203ML064-ITEM 26

-4 88070538 204** 97.6 776 503CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 H

7415 05/04/79 0

3 S31203ML065-ITEM 23

-1 88070540 143.5 68.9 572 SO3CCW C 4.00 FLG 150.0 RFWN 105 N/A 40 w

J61D 01/21/77 0

3 531203ML070-3CCO70003

-1 88070542 153 750 S03CCW C 5.00 FLG 150.0 RFWN 105 N/A 40 w

M764701 09/08/78 0

3 S31203ML070-3CC070004

-3 88070542 134*

3-2165 769 SO3CCW C 4.00 FLO 150.0 RPUN 105 N/A 40 TL4696 10/21/76 0

3 S31203ML070-3CCO70004

-2 88070542 153 559 S03CCU C 5.00 FLG 150.0 RFUN 105 N/A 40 w

H598 01/17/78 0

3 531203ML072-3CCO72001

-1 88070542 140 302 S03CCW C 4.00 FLG 150.0 RFWN 105 N/A 40 w

T4696 10/21/76 0

3 S31203ML072-3CCO72002

-2 88070542 153 60 503CCU C 4.00 FLG 150.0 RFUN 105 N/A 40 w

7415 04/04/78 0

3 S31203ML072-3CCO72006

-3 88070542 133*

3-2194 1 503CCw C 5.00 FLG 150.0 RFWN 105 N/A 40 U

m764701 09/08/78 0

3 531203ML074-ITEM 29

-3 88070545 134*

3-2139 770 S03CCW C 4.00 FLG 150.0 RFWN 105 N/A 40 w

T4696 10/21/76 0

3 531203ML074-ITEM 31

-1 88070545 151 782 SD3CCW C 4.00 FLG 150.0 RFWN 105 N/A 40 w

T4228 09/08/78 0

3 531203ML074-ITEM 32

-2 88070545 150 752 SO3CCW C 5.00 FLG 150.0 RFWN 105 N/A 40 U

M764701 09/08/78 0

3 S31203ML076-ITEM 18

-1 88070545 140 932 SO3CCU C 5.00 FLO 150.0 RFWN 105 N/A 40 w

H598 10/14/77 0

3 S31203ML078-3CCO78001

-1 88070588 13.4*

3-2166 573 S03CCW C 4.00 FLG 150.0 RFWN 105 N/A 40 w

J61D 01/21/77 0

3 S31203ML078-3CCO78002

-2 88070588 144 561 $03CCW C 5.00 PLO 150.0 RPHN 105 N/A 40 H

m595 10/14/77 0

3 S31203ML078-ITEM 23

-3 88070588 153 554 S03CCW C 5.00 FLG 150.0 RPUN 105 N/A 40 H

H598 10/14/76 0

3 S31203ML080-3CC080001

-1 88070588 128' 3-2167 771 SO3CCW C 4.00 FLG 150.0 RFWN 105 N/A 40 U

T4696 10/21/76 0

3 S31203ML080-3CC080001

-2 88070545 147 451 S02CCW C 5.00 FLG 150.0 RUN 105 N/A 40 U

598 10/14/77 0

3 531203ML082-3CCD82001

-3 88070589 126*

61.5 3-2125

Page No.

16 09/08/88 NCR SONGS REPORT (BY LOCATION)

ITEM PLANT TRANS DIAMETER COMMODITY RATING TYPE SPEC GRADE SCHEDULE VENDOR HEAT LOT DATE QUANTITY SOUIRCE ASME LINE TEST M 0 NUMBER T-HARD KSICONV NCR.NUMBER 777 S03CCW C 4.00 FLG 150.0 RFWN 105 N/A 40 U

T415 05/04/79 0

3 S31203ML082-3CCO82001

-2 88070589 133*

64.3 3-2125 574 SO3CCU C 4.00 FLG 150.0 RFUN 105 N/A 40 U

1097642 02/09/77 0

3 S31203ML082-3CCO82002

-1 88070589 153 73 562 S03CCW C 5.00 FLG 150.0 RFWN 105 N/A 40 U

H598 10/14/77 0

3 S31203ML084-3CCOS4001

-1 88070589 130*

63 3-2127 778 S03CCW C 4.00 FLG 150.0 RFWN 105 N/A 40 U

T415 05/04/79 0

3 S31203ML084-3CCO84001

-2 88070589 143 68.7 555 S03CCW C 4.00 FLG 150.0 RFWN 105 N/A 40 w

T097642 02/09/77 0

3 531203ML084-3CCO84002

-3 88070589 165 82 563 SO3CCU 5.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 01/21/77 0

3 531203ML090-3CCO90005 88070591 174.5 85 8

64 SO3CCU C 3.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 01/21/77 0

3 531203ML090-3CCD90005

-3 88070591 190** 90 3-2151 47 S03CCU C 6.00 FLG 150.0 RFSO 105 N/A 40 w

LAG 01/21/77 0

3 531203ML090-3CCO90006

-5 88070591 167 82.5 779 SO3CCU C 3.00 FLG 150.0 RFWN 105 N/A 40 U

T415 05/04/79 0

3 531203ML090-3CCO90006

-4 88070591 140 67.5 684 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 06/17/77 0

3 S31203ML090-ITEM 48

-1 88070591 206**

98.3 3-2151 780 SO3CCW C 3.00 FLG 150.0 RFUN 105 N/A 40 U

T415 05/04/79 0

3 S31203ML091-3CCO91008

-1 88070592 147 70 565 S03CCU C 3.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 01/21/77 0

3 S31203ML092-3CCO92007

-1 88070593 198*

3-2154 566 503CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 01/21/77 0

3 531203ML092-3CCO92008

-2 88070593 178 567 SO3CCW C 3.00 FLG 150.0 RFW 105 N/A 40 U

JAE 01/21/77 0

3

$31203ML092-3CCO92008

-3 88070593 174 199 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 06/17/77 0

3 S31203ML092-3E370001X

-4 88070593 172 327 SD3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

3 531203ML092-3E370001X

-5 88070593 198*

3-2154 1119 so3ccw C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 01/21/77 0

3 S31203ML093-3CCO93006

-1 88070594 205-3-2153 568 503CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 01/21/77 0

3 S31203ML093-3CCO93007

-2 88070594 194**

3-2153 686 S03CCU C 3.00 FLC 150.0 RFWN 105 N/A 40 U

JAE 06/17/77 0

3 531203MLO93-3CCD93007

-3 88070594 156 200 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

3 531203ML093-3E371001x

-4 88070594 189**

3-2153 329 s03CCw C 3.00 FLC 150.0 RFWN 105 N/A 40 14E 06/17/77 0

3

$31203ML093-3E371001X

-5 88070594 181 569 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 01/21/77 0

3 531203ML094-3CCO94008

-3 88070593 174 328 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

3 531203MLO94-3E370002X

-1 88070593 177 2201 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

3 S31203ML094-3E370002X

-2 88070593 175 0

8 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 06/17/77 0

3 S31203ML095-3CCO95007

-3 88070594 159 202 S03CCW 3.00 FLG 150.0 FWN 105 N/A 40 w

J4E 06/17/77 0

3

$31203ML095-3E371002X

-1 88070594 172 330 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

3 S31203ML095-3E371002X

-2 88070594 172 456 SO3CCW 8.00 FLG 150.0 RFWN 105 N/A 40 w

730266 02/09/77 0

3 531203MLO99-3CCO99001

-1 88070619 138 472 SO3CCW C 12.00 FLG 150.0 RFWN 105 N/A 40 U

14205 01/21/77 0

3 S31203ML102-3CC102002

-1 88070605 137 66 473 SO3CCU C 12.00 FLG 150.0 RFUN 105 N/A 40 U

T4205 01/21/77 0

3 531203ML103-3CC103001

-1 88070605 137 66 474 So3CCW C 12.00 FLG 150.0 RFWN 105 N/A 40 w

74205 01/21/77 0

3 531203ML103-3CC103001

-2 88070605 140 67.5 470 S03CCW C 12.00 FLG 150.0 RFWN 105 N/A 40 U

74205 12/14/76 0

3 S31203ML103-3CC103002

-3 88070605 136*

65.5 3-2129 475 S03CCW C 12.00 FLG 150.0 RFUN 105 N/A 40 U

74205 01/21/77 0

3 531203ML106-3CC106001

-1 88070607 133*

64.7 3-2130 476 S03CCU C 12.00 PLC 150.0 SPUN 105 N/A 40 U

T4205 01/21/77 0

3 S31203ML106-3CC106001

-2 88070607 137 66

Page No.

17 09/08/588 NCR SONGS REPORT (BY LOCATION)

ITEM PLANT TRANS DIAMETER CMODITY RATING TYPE SPEC GRADE SCHEDULE VENDOR HEAT LOT DATE QUANTITY SORCE ASME LINE M

NM A

N M

469 SO3CCW C 10.00 FLG 150.0 RFUN 105 N/A 40 u

T4205 01/21/77 0

3 S31203ML106-3CC10.6002

-3 88070607 134*

64.9 3-2130 468 SO3CCw C 10.00 FLG 150.0 RFUN 105 N/A 40 w

74205 01/21/77 0

3 S31203ML137-3CC137002

-1 88070608 138 471 SO3CCW C 10.00 FLG 150.0 RFWN 105 N/A 40 w

T4205 01/21/77 0

3 S31203ML137-3CC137003

-2 88070608 142 465 S03CCW C 10.00 FLC 150.0 RFWN 105 N/A 40 w

T4205 01/21/77 0

3 S31203ML137-3CC137004

-3 88070608 141 577 So3CCW C 28.00 FLG 125.0 FFWN 105 N/A 40 H

W9666 03/23/78 0

3

$31203ML145-3CC145004

-1 88070609 143 68.7 578 S03CCW C 28.00 FLG 125.0 FFWN 105 N/A 40 H

W9820 05/12/78 0

3 531203ML147-3CC147001

-1 88070610 147 70 62 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

T2578 09/13/79 0

3 S31203ML147-3CC147002

.3 88070610 148 70.6 454 S03CCW C 6.00 FLG 150.0 RFWN 105 N/A 40 H

T1830 09/28/79 0

3 S31203ML147-3CC147004.

-2 88070610 169 83 748 SO3CCW C 3.00 FLG 150.0 RFBLND 105 N/A 40 w

M1223 05/04/79 0

3 S31203ML147-ITEM 90

-4 88070610 143 68.7 576 S03CCW 28.00 FLG 125.0 FFUN 105 N/A 40 H

W9666 02/23/78 0

3 S31203ML149-3CC149001 0

546 S03CCU C 10.00 FLG 150.0 RFuN 105 N/A 40 U

NJ 10/21/76 0

3 S31203ML151-3CC151002

-1 88070613 129*

62.9 3-2126 477 SO3CCW C 10.00 FLG 150.0 RFWN 105 N/A 40 U

T4205 01/21/77 0

3 531203ML151-3CC151003

-1 88070613 138 66.5 545 S03CCW C 10.00 FLG 150.0 RFWN 105 N/A 40 H

NJ 10/21/76 0

3 531203ML153-3CC153002

-1 88070614 136*

65.5 3-2132 1264 S03CCW A 10.00 FLG 150.0 RFWN 105 N/A 10 U

NJ 10/21/76 0

2 S31203ML155-3CC155002 0

466 SO3CCW C 10.00 FLG 150.0 RFWN 105 N/A 40 U

74205 01/21/77 0

3 531203ML157-3CC157002

-8 88070614 140 67.5 467 S03CCU C 10.00 FLG 150.0 RFWN 105 N/A 40 U

74205 01/21/77 0

3 S31203ML157-3CC157002

-9 88070614 147 70 547 SO3CCU C 10.00 FLG 150.0 RFWN 105 N/A 40 H

NJ 10/21/76 0

3 S31203ML157-3CC157003

-6 88070614 136*

65.5 3-2131 548 SO3CCu C 10.00 FLG 150.0 RFWN 105 N/A 40 H

NJ 10/21/76 0

3 S31203ML157-3CC157003

-7 88070614 133*

64.7 3-2131 1265 S03CCW A 10.00 FLG 150.0 RFWN 105 N/A 10 W

HJ 10/21/76 0

3 S31203ML157-3CC157004 0

543 SO3CCU C 10.00 FLG 150.0 RFUN 105 N/A 40 H

NJ 10/21/76 0

3 S31203ML157-3CC157005

-5 88070614 125*

61 3-2131 544 S03CCW C 10.00 FLG 150.0 RFWN 105 N/A 40 w

NJ 10/21/76 0

3 S31203ML157-3CC157005

-4 88070614 128*

62.5 3-2131 541 SO3CCU C 10.00 FLG 150.0 RFWN 105 N/A 40 w

NJ 10/21/76 0

3 531203ML157-3CC157006

-3 88070614 129*

62.9 3-2131 542 S03CCW C 10.00 FLG 150.0 RFWN 105 N/A 40 U

NJ 10/21/76 0

3 S31203ML157-3CC157006

-2 88070614 138 66.5 540 S03CCW C 10.00 FLG 150.0 RFWN 105 N/A 40 w

NJ 10/21/76 0

3 S31203ML157-3CC157007

.1 88070614 128*

62.5 3-2131 73 S03CCW C 4.00 FLG 150.0 RFWN 105 N/A 40 U

797642 02/09/77 0

3

$31203ML158-3CC158001

-1 88070615 157 921 SO3CCW 4.00 FLC 150.0 RFBL 105 N/A N/A w

H904 09/08/78 0

3 531203ML158-3CC158004 0

575 SO3CCW C 4.00 FLG 150.0 RFWN 105 N/A 40 w

1097642 02/03/77 0

3 531203ML159-3CC159001

-1 88070616 145 453 SO3CCW C 28.00 FLG 125.0 FFW 105 N/A 40 H

N1321 5/12/78 0

3 S31203ML164-3CC164003

-1 88070617 148 70.6 457 SO3CCW C 8.00 FLG 150.0 RFUN 105 N/A 40 w

T30266 01/21/77 0

3 S31203ML210-3CC210027

-1 88070618 140 67.5 458 S03CCW C 8.00 FLG 150.0 RFUN 105 W/A 40 w

T30266 01/21/77 0

3 S31203ML210-3CC210028

-2 88070618 144 69 538 S03CCW 10.00 FLG 150.0 RFWN 105 N/A 40 U

HJ 10/21/76 0

3 531203ML228-3CC228001 0

1124 SO3CCW 10.00 FLG 150.0 RFWN 105 N/A 40 U

NJ 10/21/76 0

3 531203ML228-3CC228002 0

539 S03CCW 8.00 FLG 150.0 RFWN 105 N/A 40 W

730266 01/21/77 0

3 531203ML228-3CC243001

-2 88070619 140 492 S03CCW C 10.00 PLG 150.0 R..N 105 N/A 40 U

14205 01/21/77 0

3 531203ML231-3CC231002

-1 88070620 139

Page No.

18 09/08/88 NCR SONGS REPORT (BY LOCATION)

ITEM PLANT TRANS DIAMETER COMMODITY RATING TYPE SPEC GRADE SCHEDULE VENDOR NEAT LOT DATE OUANTITY SOURCE ASME LINE TEST M 0 NUMBER T-NARD KSI CONV NCR.NUMBER 493 S03CCW C 10.00 FLG 150.0 RFWN 105 N/A 40 U

74205 01/21/77 0

3 S31203ML231-3CC231003

-2 88070620 142 483 so3CCW C 10.00 FLG 150.0 RFUN 105 N/A 40 U

T4205 01/21/77 0

3 S31203ML231-3CC2310D4

-3 88070620 141 783 so3CCw C 8.00 FLG 150.0 RFWN 105 N/A 40 U

T4298 10/21/76 0

3 S31203ML243-3CC243025

-1.

88070621 145 69.3 500 So3CCW C 10.00 FLG 150.0 RFuN 105 N/A 40 w

T4205 01/21/77 0

3 S31203ML247-3CC247009

-1 88070622 132*

3-2142 1156 S03CCU 10.00 FLG 150.0 FFWN 105 N/A 40 U

T4205 12/14/76 0

3 S31203ML252-3CC252009 0

767 S03CCW C 10.00 FLG 150.0 RFWN 105 N/A 40 w

T4205 01/21/77 0

3 531203ML273-3CC273009

.1 88072794 144 69 494 SO3CCW C 10.00 FLG 150.0 RFWN 105 N/A 40 w

T4205 01/21/77 0

3 531203ML273-3CC273010

-2 88072794 141 68

  • '95 SO3CCW C 10.00 FLG 150.0 RFWN 105 N/A 40 w

74205 01/21/77 0

3 S31203ML273-3CC273010

-3 88072794 157 78 86 SO3CCW C 10.00 FLG 150.0 RFWN 105 N/A 40 U

74205 01/21/77 0

3 S31203ML273-3CC273011

-4 88072794 145 69.3 1157 So3CCW C 10.00 FLG 150.0 RFUN 105 N/A 40 U

T4205 01/21/77 0

2 531203ML273-3CC273011

-5 88072794 140 67.5 1186 SO3CCW C 10.00 FLG 150.0 RFWN 105 N/A

.40 w

T36330 02/09/77 0

2 S31203ML273-3E401002

-6 88072794 154 74 333 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML273-3E402001

-2 88070920 184**

334 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML273-3E402001

-5 88070920 189*

335 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML273-3E402001

-6 88070920 179 336 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

JE 06/17/77 0

2

$31203ML273-3E402001

-9 88070920 171 337 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

AE 06/17/77 0

2 S31203ML273-3E402001

-11 88070920 199**

338 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 531203ML273-3E402001

-14 88070920 184 339 scCCU C 3.00 FLC 150.0 RFUN 105 N/A 40 U

J4E 06/17/77 0

2 531203ML273-3E402001

-15 88070920 183 340 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML273-3E402001

-19 88070920 166 341 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 531203ML273-3E402001

-20 88070920 200**

1254 SO3CCW A 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 6/17/77 0

2 S31203ML273-3E402001

-23 88070920 222**

205 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML273-3E402004A

-22 88070920 141 206 s03CCw 3.00 FLG 150.0 RFUN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML273-3E402004A 0

207 SO3CCW C 3.00 FLG 150.0 RFUN 105 N/A 40 W

J4E 06/17/77 0

2 S31203ML273-3E402004B

-18 88070920 208**

208 S03CCw 3.00 FLG 150.0 RFWN 105 N/A 40 w

JE 06/17/77 0

2 S31203ML273-3E402004B 0

0 09 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 S31203ML273-3E402004C

-13 88070920 175 210 SO3CCw 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2

$31203ML273-3E402004C 0

211 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 S31203ML273-3E402004D

-8 88070920 213**

212 SO3CCW 3.00 FLG 150.0 RFWN 105 N/A 40 W

J4E 06/17/77 0

2 531203ML273-3E402004D 0

144 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 531203ML273-3E402004E

-4 88070920 195**

213 S03CCW 3.00 FLG 150.0 RFW 105 N/A 40 U

J.E 06/17/77 0

2 S31203ML273-3E402004E 0

342 so3CCU C 3.00 FLO 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML273-3E402005A

-21 88070920 218**

343 SO3CCw C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML273-3E402005B

-16 88070920 176 344 SO3CC. C 3.00 PLO 150.0 RF.N 105 N/A 40 148 06/17/77 0

2 S31203ML273-3E402005C

-12 88070920 190-

P age No.

19 09/05/88 NCR SONGS REPORT (BY LOCATIDN)

ITEM PLANT TRANS DIAMETER COMMODITY RATING TYPE SPEC GRADE SCHEDULE VENDOR HEAT LOT DATE QUANTITY SOURCE ASKE LINE TEST N_0 NUMBER 1-HARD KSI CO~y NCR.NUMBER 332 S03CCW C 3.00 FLG 150.0 RFUN 105 N/A 40 U

JAE 06/17/77 0

2 S31203ML273-3E402005D

-7 88070920 202*

331 S03CCW C 3.00 FLG 150.0 RFW 105 N/A 40 U

JE 06/17/77 0

2

$31203ML273-3E402005E

-1 88070920 194**

203 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J.E 06/17/77 0

2 S31203ML273-ITEM 20

.-3 88070920 205*

204 S03CCU C 3.00 FLG 150.0 RFun 105 N/A 40 J AE 06/17/77 0

2 S31203ML273-ITEM 23

-17 88070920 236*

350 SO3CCU C 3.00 FLG 150.0 RFuN 105 N/A 40 w

JE 06/17/77 0.

2

$31203ML275-3E402002

-28 88070920 242*

351 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

JE 06/17/77 0

2 S31203ML275-3E402002

-33 88070920 178 52 So3CCU C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML275-3E402002

-38 88070920 186 S03CW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2

$31203ML275-3E402002

-42 88070920 190**

354 S03CCW C 10.00 FLG 150.0 RFWN 105 N/A 40 U

T36330 02/19/77 0

2 S31203ML275-3E402002

-1 88072794 141 68 639 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML275-3E402002

-48 88070920 174 230 S03CCU 3.00 FLG 150.0 RFWN 105 N/A 40 U

JE 06/17/77 0

2 S31203ML275-3E402003A 0

231 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML275-3E402003A

-25 88070920 225**

232 SO3CCW 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML275-3E402003B 0

233 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML275-3E402003B

-30 88070920 167 214 SO3CCU 3.00 FLG 150.0 RFUN 105 N/A 40 U

JE 06/17/77 0

2 531203ML275-3E402003C 0

216 503CCW 3.00 FLG 150.0 RFuN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML275-3E402003D 0

217 SO3CCW C 3.00 FLG 150.0 RFUN 105 W/A 40 U

J4E 06/17/77 0

2 S31203ML275-3E402003D

-40 88070920 228**

218 S03CCW 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 531203ML275-3E402003E 0

219 S03CCW C 3.00 FLC 150.0 RFUN 105 N/A 40 U

JE 06/17/77 0

2 531203ML275-3E402DO3E

-45 88070920 213**

349 SO3CCU C 3.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 06/17/77 0

2 S31203ML275-3E402005F

-27 88070920 175 348 SO3CCW C 3.00 FLG 150.0 RFWN 105 W/A 40 U

JAE 06/17/77 0

2 531203ML275-3E402005G

-32 88070920 193**

347 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 S31203ML275-3E402005H

-37 88070920 246' 346 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 531203ML275-3E4020051

.43 88070920 215*

345 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

JE 06/17/77 0

2 S31203ML275-3E402005J

.47 88070920 179 46 SO3CCW C 3.00 FLC 150.0 RFUN 105 N/A 40 U

J4E 06/17/77 0

2 531203ML275-ITEM 10

-29 88070920 220*

47 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 531203ML275-ITEM 11

-34 88070920 198*

148 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 W

J4E 06/17/77 0

2 S31203ML275-ITEM 12

-39 88070920 185 149 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A

'.0 U

J4E 06/17/77 0

2 S31203ML275-ITEM 13

-44 88070920 245**

150 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML275-ITEM 14

-26 88070920 211**

151 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML275-ITEM 15

-31 88070920 208**

152 SO3CCW C 3.00 FLG 150.0 RFUN 105 N/A

'0 U

JE 06/17/77 0

2 S31203ML275-ITEM 16

-36 88070920 251**

153 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML275-ITEM 17

-41 88070920 222**

154 S03CCW C 3.00 FLG 150.0 RFWN 105 H/A 40 U

J4E 06/17/77 0

2 S31203ML275-ITEM 18

-46 88070920 201**

215 S03CCW C 3.00 PLC 150.0 RFN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML275-ITEM 19

-35 88070920 230**

Page No.

20 09/08/88 NCR SONGS REPORT (BY LOCATION)

ITEM PLANT TRANS DIAMETER COMMODITY RATING TYPE SPEC GRADE SCHEDULE VENDOR HEAT LOT DATE QUANTITY SOURCE ASME LINE TEST M 0 NUMBER T-HARO KSI COW NCR NUMBER 549 S03CCW C 10.00 FLG 150.0 RFWN 105 N/A 40 U

T4205 01/21/77 0

2 S31203ML275-ITEM 26

-2 88072794 154 74 145 SO3CCW C 3.00 FLG 150.0 RFW 105 N/A 40 w

J4E 06/17/7 0

2 S31203ML275-ITEM.9

-24 88070920 162 478 S03CCW C 10.00 FLG 150.0 RFWN 105 N/A 40 w

T4205 01/21/77 0

3 S31203ML277-3CC277008

-1 88072791 145 69.3 490 S03CCW C 10.00 FLG 150.0 RFWN 105 N/A 40 U

T4205 01/21/77 0

3 531203ML277-3CC277009

-2 88072791 145 69.3 491 SO3CCU C 10.00 FLG 150.0 RFUN 105 N/A 40 U

T4205 01/21/77 0

3 S31203ML277-3CC277009

-3 88072791 148 70.6 484 S03CCW C 10.00 FLG 150.0 RFWN 105 N/A 40 U

14205 01/21/77 0

3 531203ML277-3CC277010

-4 88072791 148 70.6 485 SO3CCU C 10.00 FLG 150.0 RFWN 105 N/A 40 w

74205 01/21/77 0

3 531203ML277-3CC277010

-5 88072791 144.5 69.1 60 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 W

JAE 06/17/77 0

2 S31203ML277-3E399001

-24 88070917 195 1

61 S03CCU C 3.00 FLG 150.0 RFUN 105 N/A 40 U

JAE 06/17/77 0

2 S31203ML277-3E399001

-34 88070917 177 362 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

JE 06/17/77 0

2 S31203ML277-3E399001

-27 88070917 220**

363 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 S31203ML277-3E399001

-35 88070917 175 364 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 06/17/77 0

2

$31203ML277-3E399001

-29 88070917 180 365 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/f7 0

2 S31203ML277-3E399001

-36 88070917 174 366 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 W

JAE 06/17/77 0

2 S31203ML277-3E399001

-31 88070917 192**

367 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML277-3E399001

-37 88070917 192**

368 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 06/17/77 0

2 S31203ML277-3E399001

-33 68070917 1891*

369 SO3CCU C 3.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 06/17/77 0

2 S31203ML277-3E399001

-38 88070917 180 370 SO3CCW C 10.00 FLG 150.0 RFWN 105 N/A 40 w

736330 02/09/77 0

2 S31203ML277-3E399001

-6 88072791 150.5 72.1 359 503CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 531203ML279-399005E

-23 88070917 184 480 SO3CCw C 10.00 FLG 150.0 RFUN 105 N/A 40 w

74205 01/21/77 0

3 531203ML279-3CC279008

-2 88072791 153 73 376 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML279-3E399002

-40 88070917 195**

377 SO3CCV C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML279-3E399002

-42 88070917 180 378 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 W

J4E 06/17/77 0

2 531203ML279-3E399002

-44 88070917 189 379 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2

$31203ML279-3E399002

-46 88070917 213" 380 S03CCU C 10.00 FLG 150.0 RFWN 105 N/A 40 U

T36330 02/09/77 0

2 531203ML279-3E399002

-1 88072791 151.5 72.5 55 SO3CCW A 3.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 6/17/77 0

2 S31203ML279-3E399002

-47 88070917 165 157 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML279-3E399003A

-2 88070917 182 158 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 06/17/77 0

2 S31203ML279-3E399003A

-1 88070917 196*

3-2150 159 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 531203ML279-3E399003B

-6 88070917 186**

3-2150 160 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML279-3E3990038

-6 88070917 220**

3-2150 161 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 531203ML279-3E399003C

-11 88070917 215-*

3-2150 162 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML279-3E399003C

-10 88070917 226**

3-2150 163 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 531203ML279-3E399003D

-16 88070917 171 165 S03CC. C 3.00 PLO 150.0 RPUN 105 N/A 40 U

.I4E 06/17/77 0

2 S31203ML279-3E399003E

-20 88070917 174

Page No.

21 09/08/88 NCR SONGS REPORT (BY LOCATION)

ITEM PLANT TRANS DIAMETER COMMODITY RATING TYPE SPEC GRADE SCHEDULE VENDOR NEAT LOT DATE QUANTITY SOURCE ASME LINE TEST M.0 NUMBER T-NARD ESI CONV NCR NUMBER 166....

3.

!L 150....N 105./A 40

.^ANOAAU A//

7 0

2 0.M. 2.9.

.E3.9...E-19.0 1

226.

21.0 166 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 S31203ML279-3E399003E

-19 88070917 226*1 3-2150 220 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 06/17/77 0

2 S31203ML279-3E399004A

-4 88070917 211*

3-2150 221 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML279-3E399004A

-3 88070917 231 3-2150 222 SO3CcU C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML279-3E399004B

-8 88070917 168 223 SO3CCU C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML279-3E3990048

-7 88070917 172 224 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML279-3E399004C

-13 88070917 181 25 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML279-3E399004C

-12 88070917 248*

3-2150 26 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 1

J4E 06/17/77 0

2 S31203ML279-3E399004D

.17 88070917 216 3-2150 228 SO3CCU C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2

$31203ML279-3E399004D

-17 88070917 207 3-2150 229 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2

$31203ML279-3E399004E

-22 88070917 168 229 SO3CCW C 3.00 FLG 150.0 RFuN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML279-3E399004E

-22 88070917 1683 356 S03CCU C 3.00 FLG 150.0 RFUN 105 N/A 40 U

JAE 06/17/77 0

2 S31203ML279-3E399005A

-32 88070917 12 357 S03CCW C 3.00 FLG 150.0 RFUN 105 N/A 40 U

J4E 06/17/77 0

2 531203ML279-3E399005C

-32 88070917 172 358 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML279-3E399005C

-26 88070917 192 358 So3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML279-3E399005D

-26 88070917 12 375 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML279-3E399005F

-41 88070917 171 373 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 531203ML279-3E399005G

-43 88070917 171 372 503CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML279-3E399005H

-43 88070917 17 3723 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML279-3E3990051

-45 88070917 17 12 S03CCU C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML279-3E3990051 88070917 173 156 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML279-ITEM 15

-9 88070917 17 3-2150 156 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML279-ITEM 15

-2 88070917 1 3-2150 168 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML281 IT.12

-20 88070919 221 168 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML281 IT.13

-20 88070919 19 16 03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 531203ML281 IT.15

-19 88070919 22 17 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML281 IT.15

-4 88070919 217 172 503CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML281 IT.17

-7 88070919 212 172 S03CCU C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML281 IT.17

-7 88070919 2 69.3 41 SO3CCW C 10.00 FLG 150.0 RFWN 105 N/A 40 U

J4205 01/21/77 0

3 531203ML281-3CC281015

-2 88072793 147 69 482 S03CCW C 10.00 FLG 150.0 RFWN 105 N/A 40 U

74205 01/21/77 0

3 531203ML281-3CC281016

-3 88072793 147 66.5 487 S03CCW C 10.00 FLG 150.0 RFWN 105 N/A 40 U

14205 01/21/77 0

3 S31203ML281-3CC281016

-3 88072793 134 66.5 488 503CCW C 10.00 FLC 150.0 RFWN 105 N/A 40 w

74205 01/21/77 0

3 S31203ML281-3CC281017

-5 88072793 134 69.8 488 S03CCW C 10.00 FLG 150.0 RFWN 105 N/A 40 U

74205 01/21/77 0

3 S31203ML281-3CC281017

-5 88072793 144 69 82 S03CCW. C 3.0 FG 0.0n RmW.

105 N/A 4n u

J4E n6i17/77 0

2 531203ML281-3E401001

-1 88070919 169

Page No.

22 09/08/88 NCR SONGS REPORT (BY LOCATION)

ITEM PLANT TRANS DIAMETER COMMODITY RATING TYPE SPEC GRADE SCHEDULE VENDOR NEAT LOT DATE GUANTITY SOURCE ASME LINE TEST M.0-NUMBER T:HARD KSI.CONV NCR NIJBER 383 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML281-3E401001

.2 88070919 161 384 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 V

J4E 06/17/77 0

2 S31203ML281-3E401001

-8 88070919 178 385 SO3CCU C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML281-3E401001

-11 88070919 208-*

386 S03CCW C 3.00 FLG 150.0 RFUN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML281-3E401001

-12 88070919 189" 387 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML281*3E401001

-17 88070919 172 388 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML281-3E401001

-18 88070919 184 389 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML281-3E401001

-22 88070919 166 W

90 S03CCW C 10.00 FLG 150.0 RFWN 105 N/A 40 w

T36330 02/09/77 0

2 531203ML281-3E401001

-6 88072793 143 68.7 618 S03CCW C 3.00 FLG 150.0 RFUN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML281-3E401001

-23 88070919 179 173 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML281-3E401004A

-27 88070919 180 174 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML281-3E401004A

-28 88070919 175 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML281-3E401004B

-21 88070919 235" 176 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2

$31203ML281-3E401004B

-25 88070919 213" 177 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 531203ML281-3E401004C

-15 88070919 182 178 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML281-3E401004C

-16 88070919 224*"

179 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 J4E 06/17/77 0

2 S31203ML281-3E401004D

-10 88070919 237' 180 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML281-3E401004E

.6 88070919 199" 181 SO3CCU C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML281*3E401004E

-5 88070919 206" 381 S03CCw C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML281-3E401005A

  • 24 88070919 189" 1257 SO3CCW A 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 6/17/77 0

2 S31203ML281-3E401005B

-19 88070919 2411" 1258 SO3CCW A 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 6/17/77 0

2 S31203ML281-3E401005C

-13 88070919 247" 1260 SO3CCW A 3.00 FLG 150.0 RFWN 105 W/A 40 U

J4E 6/17/77 0

2 S31203ML281-3E401005E

-3 88070919 179 162 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML283 11.12

-31 88070919 171 183 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML283 IT.14

-36 88070919 179 184 SO3CCW C 3.00 FLC 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 531203ML283 IT.16

-41 88070919 169 9

85 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML283 IT.18

-46 88070919 195" 186 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML283 IT.19

-49 88070919 224 187 SO3CCU C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML283 IT.20

-52 88070919 207" 188 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML283 IT.22

-50 88070919 173 189 SO3CCw C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML283 IT.23

-39 88070919 233" 497 SO3CCU C 10.00 FLG 150.0 RFWN 105 N/A 40 U

14205 01/21/77 0

3

$31203ML283-3CC283015

-2 88072793 151 72.3 395 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML283-3E401002

-33 88070919 182 396 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML283-3E401002

-38 88070919 171 397 S03CC. C 3.00 PLO 150.0 RFN 105 N/A 40 U

J4E 06/17/77 0

2 531203ML283-3E401002

-43 88070919 209"

pcce No.

23 Do /188 NCR SONGS REPORT (BY LOCA1ION)

IEM PLANT TRANS DIAMETER COMMODITY ATING TYPE SPEC GRADE SCHEDULE VENDOR EAT LOT DATE QUIAN7TY SORCE ASME LINE EST N 0 NUMBER 7-HARD SlCOWiV NCR.JUMER 398 SC3CCW C 3.00 res 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML283-3E401002

.4s 88070919 181 11E5 SC3CCW C 10.00 FLG 150.0 RFuN 105 N/A N/A w

736330 02/09/77 0

2 5312C3ML283-3E401002

  • 1 88072793 147 70 1261 S.3CCW A 3.00 FLG 150.0 RFWN 105 K/A 40 w

JAE 6/17/77 0

2 S31203ML283-3E401002

-54 88070919 192' 234 SO3CCH C 3.00 FLG 150.0 RFWH 105 N/A 40 JAE 06/17/77 0

2 531203ML283-3E401003A

-29 88070919 216" 235 S03CCW C 3.00 FLG 150.0 RPHN 105 N/A 40 w

J4E 06/17/77 0

2 s31203ML283-3E401003A

-30 88070919 241.

236 S03CCW C 3.00 FLG 150.0 RFUN 105 N/A 40 w

JE 06/17/77 0

2 S31203ML2M3-3E4010038

.34 88070919 173 0

37 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

JE 06/17/77 0

2 S31203ML253-3E4010036

-35 88070919 175 90 S03CCw C 3.00 FLG 150.0 RFWN 105 N/A 40 JAE 06/17/77 0

2

$31203ML283-3E401003C.

-40 88070919 177 238 S03CCW C 3.00 FLC 150.0 RFWN 105 W/A 40 H

JAE 06/17/77 0

2

$31203ML283*3E401003D

-44 88070919 224" 239 S03CCW C 3.00 FLG 150.0 ErUN 105 N/A 40 H

J4E 06/17/77 0

2 S31203ML213-3E401003D

.45 88070919 224" 191 S3cCH C 3.00 FLG 150.0 RFWH 105 W/A 40 J AE 06/17/77 0

2 s31203ML283-3E401003E

-51 88070919 180 394 53CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 H

JAE 06/17/77 0

2 S31203ML2E3-3E401005F

-32 88070919 163 33 503CCW C 3.00 FLG 150.0 RFW 105 N/A 40 H

J4E 06/17/77 0

2 531203ML283-3E401005G

-37 88070919 207**

1262 S03CCW A 3.00 FLG 150.0 RFWN 105 N/A 40 V

JE 6/17/77 0

2 531203ML2E3-3E401005K

.42 88070919 227" 392 SD3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 H

J4E 06/17/77 0

2 531203ML283-3E4010051

-47 88070919 181 391 53CCu C 3.00 FLC 150.0 RFLN 105 N/A 40 w

JAE 06/17/77 0

2 531203ML283-3E401005J

.53 88070919 191" 192 S3CCW C 3.00 FLG 150.0 RFN 105 N/A 40 w

JAE 06/17/77 0

2 531203ML285 17.13

-27 88070918 189" 193 503CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 5312C3ML285 IT.14

-21 88070918 196" 194 53CCLw C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML285 11.15

-15 88070918 194" 195 s3ccu C 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 S31203ML285 IT.16

-9 88070918 193" 196 SC3CCW C 3.00 FLG 150.0 RFLN 105 N/A 40 w

JAE 06/17/77 0

2 531203ML285 17.17

-3 88070918 242" 1158 SO3CCW C 10.00 FLG 150.0 RFWN 105 N/A 40 H

74205 01/21/77 0

2 5312C3ML285-3CC285006

-1 88072792 148 70.6 L98 S03CCW C 10.00 FLG 150.0 RFWN 105 W/A 40 H

74205 01/21/77 0

3 531203ML285-3CC285007

-2 88072792 136*

65.5 3-2114 499 SC3CCw c 10.00 FLG 150.0 RFWN 105 W/A LO w

14205 01/21/77 0

3 531203ML285-3CC285007

.3 88072792 1L4.5 69.A 9

9 503CCV C 10.00 FLO 150.0 RFuN 105 N/A 40 W

136330 02/09/77 0

2

$31203ML285-3E 400001

-4 88072792 145 69.3 LOS Sc3CC/ C 3.00 FLG 150.0 NFW 105 N/A 40 w

JAE 06/17/77 0

2 E31203ML285-3E400001

-1 88070918 175 406 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 H

JE 06/17/77 0

2 S31203ML2e5-3E400001

-6 85070918 237" 407 S3CCW C 3.00 FLG 150.0 PFUN 105 N/A 40 H

JAE 06/17/77 0

2 S31203ML285-3E400001

-7 88070918 174 408 s03CCW C 3.00 FLG 150.0 RFN 105 N/A 40 w

J4E 06/17/77 0

2 531203ML285-3E400001

-12 88070918 199" 409 S03CCW C 3.00 FLG 150.0 RFPN 105 N/A 0

H JAE 06/17/77 0

2 S31203ML285-3E400001

-13 88070918 189" 410 SO3CCW C 3.00 FLG 150.0 RFL 105 N/A 40 H

JAE 06/17/77 0

2 531203ML285.3E400001

.18 88070918 197" 411 503CCW C 3.00 FLO 150.0 RFN 105 N/A 40 w

JAE 06/17/77 0

2 531203ML285-3E400001

-19 88070918 174 412 S3CCV C 3.00 FLG 150.0 RFLN 105 N/A 40 w

JAE 06/17/77 0

2 531203ML285-3E4000D1

-24 88070918 199" 413 SC3CCH C 3.00 PLO 150.0 FLN 105 N/A 40 H

AE 06/17/77 0

2 S31203ML2M5-3E400001

-25 88070918 222"

Paae NO.

21 09708/88 NCR SONGS REPORT (BY LOCATION)

ITEM PLANT TRANS DIAMETER COMMODITY RATING TYPE SPEC GRADE SCHEDULE VENDOR HEAT LOT DATE QUANTITY SJRCE ASME LINE TEST MR0NNUMBER T-HARD ESI CONV NCR NUMBER

1. SO3C..

3......0 FLG..........0.0 RF.N

..05

../A.

0 J.....E.

06 0

2.

50 8

1 2

414 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 W

J4E 06/17/77 0

2 s31203ML285-3E40000A

-30 88070918 207*

2410 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML285-3E400004A

  • 28 88070918 187 241 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML285-3E400004A

-29 880709186 242 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 S31203ML285-3E400004B

-22 88070918 206*

243 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML285-3E400004B

-23 88070918 8

244 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML285-3E400004C

-16 88070918 189" 9

245 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 S31203ML285-3E400004C

-17 88070918 246 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 S31203ML285-3E400004D

-10 88070918 185 247 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML285-3E400004E

-11 88070918 179 248 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 10 U

J4E 06/17/77 0

2 S31203ML285-3E400004E

-5 88070918 19 249 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML285-3E400004E

-2 88070918 19**

40 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 W

J4E 06/17/77 0

2 S31203ML285-3E400005B

-26 88070918 185 403 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 W

J4E 06/17/77 0

2 S31203ML285-3E400005C

-20 88070918 195**

402 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML285-3E400005D

-14 88070918 175 401 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 531203ML285-3E400005E

-1 88070918 135**

198 SO3CCw C 3.00 FLG 150.0 RFWN 105 N/A 40 W

J4E 06/17/77 0

2 531203ML285-3E400005E

.1 88070918 2073 198 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML287 IT.10

-1.3 88070918 209" 252 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML287 IT.12

-43 88070918 209" 253 SC3CCW' C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML287 IT.13

-37 88070918 205 255 53CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 W

JAE 06/17/77 0

2 531203ML287 IT.13

-31 88070918 215" 256 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML287 IT.15

-5 88070918 2133 256 So3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML287 IT.16

-52 88070918 286 257 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML287 IT.17

-4 88070918 19" 258 S03CCW C 3.00 FLG 150.0 RFwN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML287 IT.17

-4 88070918 218" 5 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML287 IT.1

-4 88070918 19 2 SO3CCW C 3.00 FLG 150.0 RFUN 105 N/A 40 W

J4E 06/17/77 0

2 531203ML287 3E.00

-60 88070918 2102 422 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 531203ML287-3E400002

-55 88070918 157 423 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML287-3E400002

-48 88070918 180 421 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 S31203ML287-3E400002

-42 88070918 168 425 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML287-3E400002

  • 36 88070918 178 426 SO3CCW C 10.00 FLG 150.0 RFWN 105 N/A 40 U

736330 02/09/77 0

2 S31203ML287-3E400002

-1 88072792 156.5 77.5 250 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 J4E 06/17/77 0

2 531203ML287-3E400003A

-56 88070918 181

Fage No.

2 09/08/88 NCR SONGS REPORT (BY LOCATION)

ITEM PLANT TRANS DIAMETER COMMODITY RATING TYPE SPEC GRADE SCHEDULE VENDOR NEAT LOT DATE GUANTITY SORCE ASME LINE TEST M0 NUMBER T:NARO KSI.CONV NCR.NUMBER 251 S03CCU C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML287-3E400003A

-57 88070918 179 260 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML287-3E4000036

-50 88070918 199**

261 S03CCU C 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 S31203ML287-3E400003B

-51 88070918 198*

262 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 S31203ML287-3E400003C

-AS 88070918 163 263 SO3CCW C 3.00 FLG 150.0 RFUN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML287-3E400003C

-45 88070918 189**

264 So3CCU C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML287-3E400003D

-38 88070918 191**

W65 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 W

J4E 06/17/77 0

2 S31203ML287-3E400003D

-39 88070918 188**

66 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

JAE 06/17/77 0

2 S31203ML287-3E400003E

-32 88070918 228**

267 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

JE 06/17/77 0

2 531203ML287-3E400003E

-33 88070918 235**

420 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 S31203ML287-3E400005F

-59 88070918 197**

419 S03CCW C 3.00 FLG 150.0 RFUN 105 N/A 40 w

J4E 06/17/77 0

2 531203ML287-3E400005G

-53 88070918 180 418 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

J4E 06/17/77 0

2 S31203ML287-3E400005H

-47 88070918 192*

417 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 531203ML287-3E4000051

-41 88070918 1T7 416 S03CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

JAE 06/17/77 0

2 S31203ML287-3E400005J

-35 88070918 227**

489 S03CCW C 12.00 FLG 150.0 RFWN 105 N/A 40 w

74205 01/21/77 0

3 531203ML293-3CC293002

-1 88070623 136*

65.5 3-2128 164 SO3CCW C 3.00 FLG 150.0 RFWN 105 N/A 40 U

J4E 06/17/77 0

2 S31203ML279-3E399003D

-15 88070917 175 893 S03SIS C 24.00 FLO 150.0 PFwN 182 F304 10 w

T51511 01/28/77 0

2 531204ML0013S1001003

-1 0 P 790 SO3SIS C 24.00 FLG 150.0 RFWN 182 F304 10 U

755511 01/28/77 0

2 S31204ML002-351002003

-1 0 P 851 S03SIS C 24.00 FLG 150.0 RFWN 182 F304 10 U

E05353 11/18/77 0

2 S31204ML002-351109002

-2 0 P 739 S03SIS 16.00 FLG 150.0 RFWN 182 F304 10 U

BRB 09/13/79 0

2 531204ML003-351003002 0

740 503SIS 16.00 FLG 150.0 RFWN 182 F304 10 U

SRB 09/13/79 0

2 531204ML003-3S)003002 0

1187 S03SIS 2.00 FIT 0.0 N/A 403 304 N/A A8785 07/20/79 0

2 S31204ML003-3S1003002 0

1206 S03SIS 24.00 FLG 150.0 FFUN 182 F304 10 U

55511 01/28/77 0

2 531204ML003-3S1003013 0

789 S03SIS C 24.00 FLG 150.0 RFWN 182 F304 10 U

155511 01/28/77 0

2 531204ML003-351003017

-1 0 P 92 503SS C 24.00 FLG 150.0 FFUN 182 F304 10 w

755511 01/28/77 0

2 531204ML004-3SIO04014

-1 0 P 88 SO3SIS C 24.00 FLG 150.0 R FW 182 P304 10 U

755511 01/28/77 0

2

$31204ML004-351004018

-2 0 P 891 503515 C 8.00 FLG 150.0 RFWN 182 F304 10 U

T62378T 01/28/77 0

2 S31204ML009-3SIO09002

-1 0 P 755 S03SIS C 4.00 FLG 900.0 RFUN 182 F316 F.0 U

E3329 06/09/80 0

2 S31204ML013

-1 0 P 756 S03SIS C 4.00 FLG 900.0 RFWN 182 F316 80 U

£3329 06/09/80 0

2 531204ML013

-2 0 P 757 SO3SIS C 4.00 FLG 900.0 RFWN 182 F316 80 U

63329 06/09/80 0

2 S31204PLOR4

-1 0 P 758 S03SIS C 4.00 FLG 900.0 RFWN 182 F316 80 U

63329 06/09/80 0

2 S31204ML014

-2 0 P 443 S03SIS C 4.00 FLG 900.0 RFWN 182 F316 80 U

63329 06/09/80 0

2 S31204MLO20

.1 0 P 444 SO3SIS C 4.00 FLO 900.0 RFWN 182 F316 80 U

63329 06/09/80 0

2 S31204ML020

-2 0 P 1296 S03SIS A 1.00 PLO 0.0 RP N 182 316 80 U

62496 6/30/77 0

2 S3120LML020-3S]020032 0

Pace No.

26 09708/88 NCR SONGS REPORT (BY LOCATION)

ITEM PLANT TRANS DIAMETER COMMODITY RATING TYPE SPEC GRADE SCHEDULE VENDOR HEAT.LOT DATE QUANTITY SOUJRCE ASME LINE TEST M.0 NUMBER T:HARD KSI CONy NCR NUMBER 730 S03SIS C 8.00 FLG 300.0 RFWN 182 F316 20 w

82818 06/08/78 0

2 S31204ML036-3SI036007

-1 0 P 738 SO3SIS C 8.00 FLG 300.0 RFWN 182 F316 20 H

B2870 11/15/78 0

2 S31204ML037-3SI137003

-1 0 P 888 SO3SIS C 8.00 FLG 300.0 RFWN 182 F316 20 H

762834 01/21/77 0

2 S31204ML038-3SI038025

-1 0 P 753 S03SIS C 3.00 FLG 0.0 RFWN 182 F316 160 H

63252 02/22/80 0

2 S31204ML087-3SISO87015

-1 0 P 754 SO3SIS C 3.00 FLG 0.0 RFWN 182 F316 160 w

B3252 02/22/80 0

2 S31204ML087-3SIS087016

-2 0 P 798 S03SIS C 3.00 FLG 0.0 RFW 182 F316 160 H

63252 02/22/80 0

2 S31204ML089-3SIO89012

-1 0 P 799 SO3SIS C 3.00 FLG 0.0 RFWN 182 F316 160 H

B3252 02/22/80 0

2 531204ML089-35I089013

-2 0 P 7 SO35WS C 8.00 FLG 300.0 RFWN 182 N/A 20 H

HN657 09/16/77 0

2 S31204ML145-3SI145004

-1 0 P 173 S03SIS C 8.00 FLG 300.0 RFWN 182 F316 20 H

T62834 01/21/77 0

2 S31204ML145-ITEM 7

-2 0 P 737 SO3SIS C 1.00 FLG 600.0 RFWN 182 F316 80 H

62829 08/18/78 0

2 S31204ML149-3SI149006

-1 0 P 786 S03SIS C 2.50 FLG 300.0 RFWN 182 N/A 10 H

82938 01/12/79 0

3 S31204ML180-3S1180001

-1 0 P 818 So3CSS C 8.00 FLG 300.0 RFWN 182 F316 20 H

HH657 01/12/78 0

2 S31206ML003-3CS003027

-1 0 P 1174 S03CSS 8.00 FLG 300.0 RFWN 182 F316 20 H

162834 01/21/77 0

2 S31206ML004-3CS004035 0

894 S03CSS C 4.00 FLG 300.0 RFBL 182 F316 H

762834 03/14/77 0

2 S31206ML030-3CS030004

-1

.0 P 896 SO3CSS C 4.00 FLG 300.0 RFWN 182 F316 10 H

762834 01/28/77 0

2 S31206ML031-3CS031003

-1 0 P 895 S03CSS C 4.00 FLG 300.0 RFBL 182 F316 w

762834 01/28/77 0

2 S31206ML031-3CS031004

-2 0 P 591 SO3CSS C 12.00 FLG 300.0 RPFN 182 F316 20 w

52712 04/18/78 0

2 S31206ML033-3CS033003

-1 0 P 588 SO3CSS C 8.00 FLO 300.0 RFWN 182 F316 20 H

62706 01/12/78 0

2 S31206ML041-3CS041003

  • 3 0 P 592 S03CSS C 8.00 FLG 300.0 RFWN 182 F316 20 H

62717 03/23/78 0

2 S31206ML041-3CS041032

-1 0 P 595 S03CSS C 8.00 FLG 300.0 RFWN 182 F316 20 U

62818 06/08/78 0

2 S31206ML041-3CS041033

-2 0 P 589 SO3CSS C 8.00 FLG 300.0 RFWN 182 F316 20 H

82706 01/12/78 0

2 S31206ML047-3CS047032

-1 0 P 590 so3CSS C 8.00 FLG 300.0 RFWN 182 F316 20 H

62706 01/12/78 0

2 S31206ML047-3CS047032

-2 0 P 593 SO3CSS 8.00 FLG 300.0 RFSO 182 F316 N/A w

62764 04/05/78 0

2 531206ML047-3CS047040 0

594 SO3CSS 8.00 FLG 300.0 RFSO 182 P316 N/A w

62764 04/05/78 0

2 S31206ML047-3CS047040 0

94 503VCS C 2.00 FLO 150.0 RFWN 182 F316 10 w

62528 06/10/77 0

2 S31208ML005-3VC005008

-1 0 P 4 S03VCS C 4.00 FLG 150.0 RFWN 182 F304 40 H

B3011 05/04/79 0

2 S31208ML007

-1 0 P 292 503VCS C 4.00 PLO 150.0 RFWN 182 F316 40 H

62470 10/14/77 0

2 S31208MLO55

-1 0 P 293 S03VCS C 4.00 FLG 150.0 RFWN 182 F316 40 H

62470 10/14/77 0

2 S31208ML056

-1 0 P 889 SO3FSS C 10.00 FLG 150.0 RFWN 182 F304 10 w

1623781 01/28/77 0

3 S31219ML02-3FS012002

-1 0 P 890 SO3FSS C 10.00 FLG 150.0 RFWN 182 F304 10 w

162378T 01/28/77 0

3 S31219ML012-3FS012002

-2 0 P 1171 SO3FSS C 10.00 FLG 150.0 RFWN 182 F304 10 w

762378T 01/28/77 0

3 531219ML031-ITEM 8

-2 0 P 1170 S03FSS C 10.00 FLG 150.0 RFWN 182 F304 10 w

7623781 01/28/77 0

3 531219ML031-ITEM 9

-1 0 P 792 S03FSS C 6.00 FLG 150.0 RFWN 182 F316 10 w

62995 05/04/79 0

2 S31219ML067-3FS067001

-1 0 P 793 S3FSS C 3.00 LO 150.0 RP N 182 P316 TO H

62995 05/04/79 0

2 S31219ML072-3FS072001

-1 0 P

Pao.e No.

27 09/08/88 NCR SONGS REPORT (BY LOCATION)

ITEM PLANT TRANS DIAMETER COMMODITY RATING TYPE SPEC GRADE SCHEDULE VENDOR HEAT LOT DATE OUANTITY SOURCE ASME LINE TEST M 0 NUMBER T-HARD.KSI CONy NCR NUMBER 291 S03STM C 4.00 FLG 900.0 RFWN 105 N/A 80 H

T4205 04/04/78 0

3 S31301ML017-35T017010

-1 88070935 154 1288 S03STM A 1.00 FLG 600.0 RFWN 105 N/A 80 w

CL2 0

0 S31301ML843A

-1 0 121*

3-2195 1289 SO3STM A 1.00 FLG 600.0 RFWN 105 N/A 80 w

CL2 0

0 S31301ML843A

-2 0 122*

3-2195 1105 SO3STM 0.50 FLG 600.0 RFSW 350 LF2 160 H

B3811 07/05/83 0

2 S31301ML921-ITEM #16 0

741 SO3FWS C 6.00 FLG 300.0 RFWN 182 F316 10 w

62919 11/15/78 0

3 531305ML047-3FW047001

-2 0 P 282 SO3FWS C 8.00 FLG 150.0 RFWN 182 F316 10 w

83035 05/05/79 0

3 S31305ML047-3FW047010

.1 0 P 728 S03FWS C 0.00 FLG 150.0 RFWN 182 F316 40 w

B2911 08/20/79 0 TMW 3

S31305ML048-ITEM 24

-1 0 P 81 SO3FWS C 8.00 FLG 150.0 RFWN 182 F316 10 H

83035 05/04/79 0

3 S31305ML049-3FW049005

-1 0 P 729 503FWS C 7.50 FLG 150.0 RFWN 182 F316 40 w

62911 08/20/79 0 TMW 3

531305ML050-3FW050001

-1 0 P 791 S03FWS C 8.00 FLG 150.0 RFWN 182 F316 10 w

82919 12/15/78 0

3 S31305ML053-3FW053001

-1 0 P 726 S03FWS C 6.00 FLG 900.0 RFWN 105 N/A 120 H

P86861 07/26/79 0

3 531305ML098-3FW098026

-1 88070936 158 295 503FWS C 6.00 FLG 900.0 RFWN 105 N/A w

P86861 07/26/79 0

3 S31305ML099-3FW099029

-1 88070939 157 727 503FWS C 6.00 FLG 900.0 RFWN 105 N/A 120 H

P86861 07/26/79 0

3 531305ML099-3FW099034

-2 88070939 159 278 S03FWS C 6.00 FLG 900.0 RFBL 105 N/A N/A w

L0768 04/27/81 0

3 S31305ML100

-2 88070940 119*

3-2137 285 S03FWS C 6.00 FLG 900.0 RFWN 105 N/A 120 w

A41234 04/06/81 0

3 S31305ML100

-1 88070940 137 445 SO3FWS C 3.00 FLG 150.0 RFBL 182 F316 N/A w

B3425 06/18/81 0

3 S31305ML144

-1 0 P 46 S03FIJS C 3.00 FLG 150.0 RF8L 182 F316 N/A H

83425 06/18/81 0

3 531305ML144

-2 0 P 279 S03F61S C 8.00 FLG 150.0 RFWN 182 F316 10 w

62764 05/12/78 0

3 S31305ML301-3FW301003

.1 0 P 280 SC3FWS C 8.00 FLG 150.0 RFWN 182 F316 10 w

83035 05/04/79 0

3 S31305ML302-3FW302003

-1 0 P 1294 503FW5 A 6.00 FLG 150.0 RFWN 182 F316 10 w

B3036 N/A 0

3 S31305ML303-3FW303001

-1 0 P 1111 S03FWS 6.00 FLG 900.0 RFWN 105 N/A 120 H

A41234 08/04/80 0

3 S31305ML331-3FW331001 0

286 SC3F/S C 6.00 FLG 900.0 RFWN 105 N/A 120 w

A41234 04/06/81 0

3 531305ML331-3FW331002

-1 88071185 136*

3-2159 287 503FWS C 6.00 FLG 900.0 RFW 105 N/A 120 w

A41234 04/06/81 0

3 531305ML331-3FW331006

.2 88071185 141 288 S03FWS C 6.00 FLG 900.0 RFWN 105 N/A 120 w

A41234 04/06/81 0

3 531305ML331-3FW331007

.3 88071185 154 89 S03FWS C 6.00 FLG 900.0 RFWN 105 N/A 120 W

A41234 04/06/81 0

3 531305ML331-3FW331007

-4 88071185 144 77 503FWS C 6.00 FLG 900.0 RFBL 105 N/A N/A w

L0784 04/27/81 0

3 531305ML331-3FW331008

-5 88071185 126*

3-2159 274 503FWS C 8.00 FLG 150.0 RFuN 182 F316 10 w

53539 04/23/81 0

3 531305ML335-3FW335013

-1 0 P 272 503FWS C 8.00 FLG 150.0 RFWN 182 F316 10 w

83539 04/23/81 0

3 531305ML335-3FW335014

-2 0 P 273 SO3FWS C 8.00 FLG 150.0 RFWN 182 F316 10 w

83539 04/23/81 0

3 S31305ML335-3FW335014

-3 0 P 270 SO3FWS C 6.00 FLG 300.0 RFWN 182 F316 10 w

63539 04/23/81 0

3 S31305ML335-3FW335015

-5 0 P 271 503FWS C 8.00 FLG 150.0 RFWN 182 F316 10 H

B3539 04/23/81 0

3 S31305ML335*3FW335015

-4 0 P 579 503FWS C 0.00 FLG 150.0 REDRFSW 182 F316 H

63425 0

3 S31305ML340

-1 0 P 307 5035CS C 2.50 FLG 150.0 FFWN 105 N/A 40 w

T4696 10/21/76 0

3

$31413ML001-35C001001

-6 88070624 143 1080 5035C5 C 2.50 PLG 150.0 FrN 105 N/A 40 H

14696 10/21/76 0

3 S31413ML001-3SC001006

  • 4 88070624 154

Poge NO.

28 09/08/88 NCR SONGS REPORT (BY LOCATION)

ITEM PLANT TRANS DIAMETER COMMDDITY RATING TYPE SPEC GRADE SCHEDULE VENDOR HEAT LOT DATE QUANTITY SOURCE ASME LINE TEST 9 0 NUMBER 1-HARD KSI.COWy NCR.NUMBER 308 SO3sC5S C 2.50 FLG 150.0 FFWN 105 N/A 40 w

74696 10/21/76 0

3 S31413ML001-3SC001010

-3 88070624 160 312 503SCS C 2.50 FLG 150.0 FFWN 105 N/A 40 w

14696 10/21/76 0

3 S31413ML001-3SC001014

-2 88070624 146 311 SO3SCS C 2.50 FLG 150.0 FFWN 105 N/A 40 w

T4696 10/21/76 0

3 531413ML001-3SC001018

-1 88070624 181 320 S03SCS C 2.50 FLG 150.0 FFWN 105 N/A

'0 U

T4696 10/21/76 0

3 S31413ML001-3SC001022

.5 88070624 159 306 SO3SCS C 2.50 FLG 150.0 FFWN 105 N/A 40 U

74696 11/01/76 0

3 S31413ML001-ITEM 27

  • 7 88070624 153 1198 S03SCS C 2.50 FLG 150.0 FFUN 105 N/A 40 U

74696 10/21/76 0

3 S31413ML002-3SC002001

-1 88070625 148 10 S03SCS C 2.50 FLG 150.0 FFUN 105 W/A 40 U

T4696 10/21/76 0

3 531413ML002-3SC002006

.2*

88070625 151 14 So3SCS C 2.50 FLG 150.0 FFWN 105 N/A 40 w

14696 10/21/76 0

3 531413ML003

-1 88070625 125*

3-2196 1081 503SCS C 2.50 FLG 150.0 FFWN 105 N/A 40 W

T4696 10/21/76 0

3 S31413ML003-3SC003001

-6 88060625 122*

3-2173 1101 SO3SCS C 2.50 FLG 150.0 FFWN 105 N/A 40 U

14696 10/21/76 0

3 S31413ML003-3SC003001

-7 88060625 126*

3-2173 322 SO3SCS C 2.50 FLG 150.0 FFWN 105 N/A 40 w

74696 10/21/76 0

3 531413ML003-3SCO03005

-2 88060625 179 321 S03SCS C 2.50 FLG 150.0 FFWN 105 N/A 40 U

14696 10/21/76 0

3 531413ML003-35C003006

.4 88070625 157 316 S03SCS C 2.50 FLG 150.0 FFWN 105 N/A 40 w

14696 10/21/76 0

3 531413ML003-3SCO03009

,3 88060625 125*

3-2173 1168 SO3SCS C 2.50 FLG 150.0 FFWN 105 N/A 40 w

74696 10/21/76 0

531413ML003-35C003017

-5 88060625 154 318 SO3SCS 2.50 FLG 150.0 FFWN 105 N/A 40 w

14696 10/21/76 0

3 S31413ML003-3SC003020 0

317 SO3SCS C 2.50 FLG 150.0 FFWN 105 N/A 40 w

T4696 10/21/76 0

3 S31413ML004-3SC004002

-1 88070626 121*

59 3-2136 501 S03scs C 2.50 FLG 150.0 FFWN 105 N/A 40 w

14696 10/21/76 0

3 531413ML004-3SCO04006

-2 88070626 132.5* 64.1 3-2136 1188 SOTSCS 2.50 FLG 150.0 FFUN 105 N/A 40 w

1415 04/18/78 0

3 S31413ML004-3SC004008 0

314 S03SCS C 2.50 FLG 150.0 FFWN 105 N/A 40 U

14696 10/21/76 0

3 S31413ML004-3SC004012

-4 88070626 131*

324 S03SCS C 2.50 FLG 150.0 FFWN 105 N/A 40 w

74696 10/21/76 0

3 S31413ML004-35C004015

.5 88070626 152 313 SO3sCS C 2.50 FLG 150.0 FFWN 105 N/A 40 U

74696 10/21/76 0

3 S31413ML004-3SC004016

-6 88070626 159 309 SO3SCS C 2.50 FLG 150.0 FFWN 105 N/A 40 w

T4696 10/21/76 0

3 S31413ML004-3SC004021

-7 88070626 135*

3-2136 516 503SCS C 2.50 FLG 150.0 FFWN 105 N/A 40 U

T4696 10/21/76 0

3 S31413ML004-3SC004021

-8 88070626 143 515 S03SCS C 2.50 FLG 150.0 FFWN 105 N/A 40 U

14696 10/21/76 0

3 531413ML004-IIEM 28

-3 88070626 136*

3-2136 8 19 503SCS C 2.50 FLG 150.0 F:WN 105 N/A 40 U

14696 10/21/76 0

3 S31413ML005-3SC005002

-2 88070626 131*

63.5 5 503SCS 2.50 FLG 150.0 FFUN 105 N/A 40 w

74696 10/21/76 0

3 531413ML005-3SC005006 0

323 S03SCS C 2.50 FLG 150.0 FFWN 105 N/A 40 w

14696 10/21/76 0

3 S31413ML005-35C005010

-3 88070626 142 517 SO3SCS C 2.50 FLG 150.0 FFWN 105 N/A 40 w

14696 10/21/76 0

3 531413ML005-ITEM 27

-1 88070626 130*

63 315 SO3SCS C 2.50 FLG 150.0 FFWN 105 N/A 40 U

74696 10/21/76 0

3 531413ML020-3SC019001

.1 88070627 153 518 SO3SCS C 2.50 FLG 150.0 FFWN 105 N/A 40 7 14696 10/21/76 0

3 531413ML025-3SCO25003

-1 88061194 1.24*

1114 S03ACS 6.00 FLG 150.0 RFWN 182 F304 10 U

B2505 09/20/78 0

2

$31500ML013-3Ac013003 0

725 S03ACS C 10.00 FLG 150.0 RFBL 105 W/A N/A U

18A3T 01/08/88 0

2 531500ML023-3AC023007

-1 88072103 125*

3-2175 1159 503ACS C 10.00 FLG 150.0 RFWN 105 N/A 40 U

74205 01/21/77 0

2 531500ML023-3AC023008

-2 88072103 151 3-2175 1163 S03ACS C 10.00 FLO 150.0 RPUN 105 N/A 40 U

1443192 05/09/77 0

2 S31500ML023-3AC023009

-4 88072103 121*

3-2175

Page No.

29 09/08/88 NCR SONGS REPORT (BY LOCATION)

ITEM PLANT TRANS DIAMETER COMiMODITY RATING TYPE SPEC GRADE SCHEDULE VENDOR HEAT LOT DATE QUANTITY SOUJRCE ASME LINE TEST 14 0 NUI4BER T-NARD KSICONV NCR.NUMBER 724 S03ACS C 10.00 FLG 150.0 RFBL

.105 N/A N/A w

18A3T 01/08/88 0

2 S31500ML023-3AC023010

-3 88072103 128*

1290 SO3CCW A 3.00 FLG 150.0 FRUN 105 N/A 40 w

J4E 6/17/77 0

2 S31501ME402 AT 3EL02004C

-10 88070920 176 812 SO3CHU C 6.00 FLG 150.0 RFSO 105 N/A 40 U

T1830 05/04/79 0

3 S31513ML061-3CH061010

-1 88071196 138 1238 SO3CHW A 6.00 FLG 150.0 RFUN 105 N/A 40 U

TA07194 09/23/77 0

3 S31513ML061-3CN061010 0

926 SO3CHU 4.00 FLG 150.0 RFBL 105 N/A N/A U

TO 10/12/79 0

3 S31513ML150-3C1150017 0

586 S03CHU C 4.00 FLG 150.0 RFWN 105 N/A 40 U

74696 10/21/76 0

3 S31513ML255-3CH255019

-1 88071200 158

  • 7 503CHU C 4.00 FLG 150.0 RFBL 105 N/A N/A W

TO 10/12/79 0

3 531513ML255-3CH255021

.2 88071200 160 1 S03CHW A 4.00 FLG 150.0 RFWN 105 N/A 40 w

74696 10/21/76 0

3 S31513ML259-3CH259017

  • 1 88071202 145 928 S03CHW C 4.00 FLG 150.0 'RFBL 105 N/A N/A U

TO 10/12/79 0

3 S31513ML259-3CH259019

-2 88071202 151 1189 S03DAS 2.50 FLG 150.0 FFUN 105 N/A 40 U

T415 09/08/78 0

3 S32420ML002-3DA002001 0

907 S03DAS C 3.00 FLG 150.0 FFUN 105 N/A 40 U

T415 09/08/78 0

3 532420ML002-3DA002007

  • 1 88061207 132*

3-2156 904 S03DAS C 3.00 FLG 150.0 FFWN 105 N/A 40 U

7415 09/08/78 0

3 532420ML002-3DA002008

-2 88071207 129*

3-2156 905 S03DAS C 3.00 FLG 150.0 FFWN 105 N/A 40 U

7415 09/08/78 0

3 532420ML002-3DA002008

.3 88061207 134*

3-2156 913 SO3DAS C 6.00 FLG 150.0 FFWN 105 N/A 40 w

m908701 09/08/78 0

3 S32420KLO07-3DA007001

-1 88070943 120*

1082 S03DAS C 8.00 FLG 150.0 FFWN 105 N/A 40 w

A11404 09/08/78 0

3 532420ML007-3DA007005

-2 88070943 158 1083 S03DAS C 8.00 FLG 150.0 FFUN 105 N/A 40 U

A11404 09/08/78 0

3 532420ML007-3DA007006

-3 88070943 153 1084 S03DAS C 8.00 FLG 150.0 FFWN 105 N/A 40 U

A11404 09/08/78 0

3 532420ML007-3DA007006

-4.

88070943 11.7 1085 503DAS C 8.00 FLG 150.0 FFWN 105 N/A 40 U

A11404 09/08/78 0

3 S32420ML008-3DA008001

-1 88070944 162 1086 503DAS C 8.00 FLG 150.0 FFWN 105 N/A 40 U

A11404 09/08/78 0

3 S32420ML008-3DA008001

-2 88070944 172 1087 SO3DAS C 8.00 FLG 150.0 FFWN 105 N/A 40 U

A11404 09/08/78 0

3 532420ML008-3DA008002

-3 88070944 166 1088 503DAS C 8.00 FLG 150.0 RFWN 105 N/A 40 U

A11404 09/08/78 0

3 S32420ML008-3DA008005

-4 88070944 140 1089 S03DAS C 8.00 FLG 150.0 RFWN 105 N/A 40 w

A11404 09/08/78 0

3 S32420ML008-3DA008006

-5 88070944 137 1090 S03DAS C 8.00 FLG 150.0 RFWN 105 N/A 40 w

A11404 09/08/78 0

3 S32420ML008-3DA008006

-6 88070944 147 1024 S03DAS C

6.00 FLG 150.0 FFWN 105 N/A 40 U

11256 03/13/79 0

3 532420ML008-3DA008007

-8 88070944 134*

1 SO3DAS C 8.00 FLG 150.0 RFWN 105 N/A 40 V

A11404 09/08/78 0

3

$32420ML008-3DA008007

-7 88070944 137 6 S03DAS C 6.00 FLG 150.0 FFWN 105 W/A 40 U

71256 03/13/79 0

3 532420ML008-3DA008008

-9 88070944 137 917 S03DAS C 6.00 FLG 150.0 FFWN 105 N/A 40 w

11256 03/13/79 0

3 532420ML008-3DA008008

-10 88070944 128*

899 S03DAS C 3.00 FLG 150.0 FFWN 105 N/A 40 w

1415 09/08/78 0

3 S32420ML016-3DA016001

-1 88070945 138 906 SO3DAS C 3.00 FLG 150.0 FFWN 105 N/A 40 U

1415 09/08/78 0

3 532420ML016-3DA016008

-2 88070945 126*

902 S03DAS C 3.00 FLG 150.0 FFWN 105 N/A 40 U

T415 09/08/78 0

3 532420ML016-3DA016009

.3 88070945 145 903 S03DAS C 3.00 FLG 150.0 FFWN 105 N/A 40 U

1415 09/08/78 0

3 S32420ML016-3DA016009

-4 88070945 143 1197 S03FOS 3.00 FLG 150.0 RFWN 105 N/A 40 w

1415 09/08/78 0

3 532420ML016-ITEM 11 0

1092 SO3DAS C 8.00 FLG 150.0 FFWN 105 N/A 40 U

A11404 09/08/78 0

3 532420ML021-3DA021005

-1 88070947 143 1093 S03DAS C 8.00 F.G 150.0 FFN 105 N/A 40 U

A11404 09/08/78 0

3 S32420ML021-3DA021006

-2 88070947 145

Page No.

30 09/08/88 NCR SONGS REPORT (BY LOCATION)

ITEM PLANT TRANS DIAMETER COMMODITY RATING TYPE SPEC GRADE SCHEDULE VENDOR HEAT LOT DATE QUANTITY SOURCE ASME LINE TEST K 0 NUMBER T-ARD KSI COWV NCR NUMBER 1094 S03DAS C 8.00 FLG 150.0 FFWN 105 N/A 40 w

A11404 09/08/78 0

3 S32420ML021-3DA021006

-3 88070947 153 1095 S03DAS C 8.00 FLG 150.0 FFWN 105 N/A 40 W

A11404 09/08/78 0

3 S32420ML022*3DA022001

-1 88070948 143 1096 S03DAS C 8.00 FLG 150.0 FFWN 105 N/A 40 w

A11404 09/08/78 0

3 S32420ML022-3DA022001

.2 88070948 126*

1097 SO3DAS C 8.00 FLG 150.0 FFWN 105 N/A 40 w

A11404 09/08/78 0

3 S32420ML022-3DA022002

-3 88070948 144 910 S03DAS C 6.00 FLO 150.0 FFWN 105 N/A 40 w

A114D4 09/08/78 0

3 S32420ML022-3DA022005

  • 4 88070948 145 1098 S03DAS C 8.00 FLG 150.0 RFWN 105 N/A 40 I

A11404 09/08/78 0

3 S32420ML022-3DA022006

-5 88070948 150 9 S03DAS C 8.00 FLO 150.0 RFWN 105 N/A 40 W

A11404 09/08/78 0

3 S32420ML022-3DA022006

-6 88070948 124-3-2145 W 0 S03DAS C 8.00 FLG 150.0 RFWN 105 N/A 40 I

A11404 09/08/78 0

3 532420ML022-3DA022007

-7 88070948 148 1022 503DAS C 6.00 FLG 150.0 FFWN 105 N/A 40 U

11256 03/13/79 0

3 532420MLO22-3DA022008

-9 88070948 140 1023 S03DAS C 6.00 FLO 150.0 FFWN 105 N/A 40 w

T1256 03/13/79 0

3 S32420ML022-3DA022008

-10 88070948 137 1154 So3DAS C 6.00 FLG 150.0 RFWN 105 N/A 40 w

M908701 04/18/78 0

3 532420ML022-ITEM 13

-8 88070948 165 898 S03DAS C 3.00 FLG 150.0 FFWN 105 N/A 40 U

1415 09/08/78 0

3 S32420ML036-3DA036001

-1 88070949 143 1201 SO3DAS C 3.00 FLG 150.0 FFWN 105 N/A 40 I

7415 09/08/78 0

3 S32420ML036-3DA036007

-2 88070949 136*

3-2148 900 SO3DAS C 3.00 FLG 150.0 FFWN 105 N/A 40 w

T415 09/08/78 0

3 532420ML036-3DA036008

-3 88070949 133*

3-2149 901 S03DAS C

3.00 FLG 150.0 FFWN 105 N/A 40 w

T415 09/08/78 0

3 S32420ML036-3DA036008

  • 4 88070949 141 912 503DAS C 6.00 FLG 150.0 FFWN 105 N/A 40 U

M908701 09/08/78 0

3 S32420ML041-3DA041001

-1 88070950 136-3-2140 1003 503DAS C 8.00 FLO 150.0 FFWN 105 N/A 40 w

A11404 09/08/78 0

3 S32420ML041-3DA01005

-2 88070950 158 1004 SO3DAS C 8.00 FLG 150.0 FFWN 105 N/A 40 A11404 09/08/78 0

3 S32420ML041-3DA041006

-3 88070950 163 1005 S03DAS C 8.00 FLG 150.0 FFWN 105 N/A 40 w

A11404 09/08/78 0

3 532420ML041-3DA041006

-4 88070950 156 1109 S03DAS C 8.00 FLG 150.0 FFWN 105 N/A 40 U

411404 09/08/78 0

3 S32420ML042-3DA042001

-1 88070951 148 1110 S03DAS C 8.00 FLG 150.0 FFWN 105 N/A 40 U

A11404 09/08/78 0

3 S32420ML042-3DA042001

-2 88070951 158 1006 S03DAS C 8.00 FLG 150.0 FFWN 105 N/A 40 w

A 1404 09/08/78 0

3 532420ML042-3DA042002

.3 88070951 147 1007 S03DAS C 8.00 FLG 150.0 RFWN 105 N/A 40 U

A11404 09/08/78 0

3 S32420ML042-3DA042005

-4 88070951 145 1008 S03DAS C

8.00 FLG 150.0 RFWUN 105 N/A 40 U

A11404 09/08/78 0

3 S32420ML042-3DA042006

-5 88070951 154 9 S03DAS C

8.00 FLO 150.0 RFUN 105 N/A 40 U

A11404 09/08/78 0

3 532420ML042-3DA042006

-6 88070951 162 W

2 S03DAS C

8.00 FLG 150.0 RF N 105 N/A 40 U

A 11404 09/08/78 0

3 S32420ML042-3DA042007

-7 88070951 914 SO3DAS C 6.00 FLG 150.0 FFWN 105 N/A 40 U

71256 03/13/79 0

3 532420ML042-3DA042008

-8 88070951 141 915 S03DAS C 6.00 FLG 150.0 FF4W 105 N/A 40 U

T1256 03/13/79 0

3 532420ML042-3DA042008

.9 88070951 134*

3-2137 1136 S03DAS C 6.00 FLG 150.0 RFWN 105 N/A 40 U

71256 03/13/79 0

3 532420ML042-ITEM 13

-10 88070951 138 1190 SC3DAS 3.00 FLG 150.0 RFWN 105 N/A 40 w

1415 09/08/78 0

3 532420ML049-3DA049001 0

897 503DAS C 3.00 FLG 150.0 FFWN 105 N/A 40 v

7415 09/08/78 0

3 S32420ML049-3DA049007

-1 88071033 132*

3-2138 908 503DAS C 3.00 FLG 150.0 FF WN 105 N/A 40 U

7415 09/08/78 0

3 532420ML049-3DA049008

-2 88071033 137 909 S03DAS C

3.00 FLG 150.0 FF WN 105 N/A 40 U

1415 09/08/78 0

3 S32420ML049-3DA049008

.3 88071033 129*

3-2138 920 S03DAS C 6.00 FLG 150.0 FFUN 105 N/A 40 U

T1256 03/13/79 0

3 32420ML054-3A054001

-1 88061034 134*

3-2143

Page No.

31 09/08/88 NCR SONGS REPORT (BY LOCATION)

ITEM PLANT TRANS DIAMETER COMMODIT RATING TYPE SPEC GRADE SCHEDULE VENDOR NEAT.LOT DATE QUANTITY SO RCE ASME LINE 1132 S03DAS C 8.00 FLG 150.0 FFWN 105 N/A 40 w

A11404 09/08/78 0

3 S32420ML054-3DA054005

.2 88071034 163 1010 S03DAS C 8.00 FLG 150.0 FFWN 105 N/A 40 w

A11404 09/08/78 0

3 S32420ML054-3DA054006

.3 88061034 160 1011 SO3DAS C 8.00 FLG 150.0 FFUN 105 N/A 40 w

A11404 09/08/78 0

3 S32420ML054-3DA054006

-4 88071034 152 1012 SO3DAS C 8.00 FLG 150.0 FFWN 105 N/A 40 I

A11404 09/08/78 0

3 532420ML055-3DA055DO1

-1 88071035 157 1013 SO3DAS C 8.00 FLG 150.0 FFWN 105 N/A 40 I

A11404 09/08/78 0.

3 S32420ML055-3DA055001

-2 88071035 154 1014 SO3DAS C 8.00 FLG 150.0 FFWN 105 N/A 40 w

A11404 09/08/78 0

3 S32420ML055-3DA055002

-3 88071035 147 15 S03DAS C 8.00 FLG 150.0 RFWN 105 N/A 40 w

A11404 09/08/78 0

3 S32420ML055-3DA055005

-4 88071035 149 03 SO3DAS C 8.00 FLG 150.0 FFWN 105 N/A 40 w

A11404 09/08/78 0

3 S32420ML055-3DA055006

-6 88071035 143 1204 S03DAS C 8.00 FLG 150.0 FFWN 105 N/A 40 w

A11404 09/08/78 0

3 532420ML055-3DA055006

-7 88071035 149 911 S03DAS C 6.00 FLG 150.0 F FWN 105 N/A 40 w

M908701 09/08/78 0

3 532420ML055-3DA055007

-8 88071035 126*

3-2149 1016 SO3DAS C 8.00 FLG 150.0 RFWN 105 N/A 40 U

A11404 09/08/78 0

3 532420MLO55-3DA055007

.5 88071035 149 918 S03DAS C 6.00 FLG 150.0 FFWN 105 N/A 40 w

T1256 03/13/79 0

3 532420ML055-3DA055008

-9 88071035 136*

3-2149 919 SO3DAS C 6.00 FLG 150.0 FFWN 105 N/A 40 U

11256 03/13/79 0

3 S32420ML055-3DA055008

-10 88071035 138 1137 S03FOS 4.00 FLG 150.0 RFWN 105 N/A 40 w

11830 05/04/79 0

3 S32421ML017-ITEM 12 0

1059 S03FOS C 3.00 FLG 150.0 RFWN 105 N/A 40 w

1415 09/08/78 0

3 S32421ML018-3F0018001

-1 88071038 133*

3-2157 1236 SO3FOS A 2.00 FLG 600.0 RFWN 105 N/A 80 w

COP 03/04/86 0

3 S32421ML018-ITEM 36 0

1237 SO3F05 A 2.00 FLG 600.0 RFWN 105 N/A 80 W

COP 03/04/86 0

3 532421ML018-ITEM 37 0

1055 SO3FOS C 3.00 FLG 150.0 RFWN 105 N/A 40 W

7415 09/08/78 0

3 532421ML020-3F0020001

-1 88071039 143.5 1191 S03FOS 3.00 FLG 150.0 RFWN 105 N/A 40 U

T415 09/08/78 0

3 532421ML022-ITEM 5 0

722 S03FOS 4.00 FLG 150.0 RFWN 105 N/A 40 U

04224 12/04/80 0

3 532421ML023 0

1049 S03FOS C 3.00 FLG 150.0 RFWN 105 N/A 40 U

7415 09/08/78 0

3 532421ML023-3F0023001

-1 88071377 151 1053 SO3FOS C 3.00 FLG 150.0 RFWN 105 N/A 40 U

T415 09/08/78 0

3 S32421ML023-3F0023002

-2 88071377 124.5*

3-2158 951 S03FOS C 3.00 FLG 150.0 RF8L 105 N/A N/A w

7415 09/08/78 0

3 532421ML023-3F0023003

-3 88071377 134*

3-2158 1138 SO3FOS 4.00 FLG 150.0 RFUN 105 N/A 40 w

11830 05/04/79 0

3 S32421MLO26-ITEM 12 0

0 2 S03FOS 3.00 FLG 150.0 RFWN 105 N/A 40 w

T415 09/08/78 0

3 532421ML027-3F0027001 0

,34 503105 A 2.00 FLG 600.0 RF N 105 N/A 80 w

COP 03/04/86 0

3 S32421MLC27-ITEM 14 0

1235 503FOS A 2.00 FLG 600.0 RFUN 105 N/A 80 w

COP 03/04/86 0

3 532421ML027-ITEM 15 0

1277 S03FOS A 3.00 FLG 150.0 RFUN 105 N/A I40 w

1415 09/08/78 0

3 532421ML029-3F0029001 0

1054 SC3FOS C 3.00 FLG 150.0 RFUN 105 N/A 40 w

7415 09/08/78 0

3 S32421ML031-3F0031002

-1 88071084 146 723 S03FOS C 4.00 FLG 150.0 RFUN 105 N/A 40 w

04224 12/04/80 0

3 S32421ML032

-1 88071085 153.5 953 So3FOS C 3.00 FLG 150.0 RFW 105 N/A 40 U

T415 09/08/78 0

3 S32421ML032-3F0032001

-2 88071085 150.5 1052 S03FOS C 3.00 FLC 150.0 RFUN 105 N/A 40 w

1415 09/08/78 0

3 S32421ML032-3F0032002

-3 88071085 146 950 503FOS C 3.00 FLG 150.0 RFBL 105 N/A N/A w

T415 09/08/78 0

3

$32421ML032-3F0032003

-4 88071085 136*

3-2177 952 S03FOS C 3.00 FLG 150.0 RFUN 105 N/A 40 1415 09/08/78 0

3 532421ML066-3F066007

-1 88071086 147

P-oe No.

32 09708/88 NCR SONGS REPORT (BY LOCATION)

ITEM PLANT TRANS DIAM4ETER COMMODITY RATING TYPE SPEC GRAE SCHEDULE VENDOR HEAT LOT DATE QUANTITY SOURCE ASME LINE TEST K C NUMBER 1-HARD KSI CONV NCR.WNUMBER 93 SO FO 00...

FLG......

1...0.0 RF..

..0.

5 09/

3.

32.2.MLO6 -

F 8

8 1193 S03FOS C 3.00 FLG 150.0 RFWN 105 N/A 40 U

7415 09/08/78 0

3 S32421ML066-3F0066008

-2 88071086 155 1195 S03Fos C 3.00 FLG 150.0 RFWN 105 N/A 40 w

7415 09/08/78 0

3 S32421ML066-3F0066008

-3 88071086 148 1058 503FOS C 3.00 FLG 150.0 RFWN 105 N/A 40 U

7415 04/08/78 0

3 S32421ML066-3F0066009

-6 88071086 151 1051 S03FOS C 3.00 FLG 150.0 RFWN 105 N/A 40 U

7415 09/08/78 0

3 S32421ML066-3FO066010

-5 88071086 161 1057 S03FOS C 3.00 FLG 150.0 RFWN 105 N/A 40 415 09/08/78 0

3 S32421ML068-3F0068005

  • 1 88071376 148 1050 SO3FOS C 3.00 FLG 150.0 RFWN 105 N/A 40 U

T415 09/08/78 0

3 532421ML068-3F0068006

-2 88071376 147 4

96 503Fos C 3.00 FLG 150.0 RFWN 105 N/A 40 U

T415 09/08/78 0

3 S32421ML068-3F0068006

-4 88071376 150.5 56 S 03F0S C 3.00 FLG 150.0 RFWN 105 N/A 40 U

T415 09/08/78 0

3 S32421ML068-3F0068007

-3 88071376 146 1194 503FOS C 3.00 FLG 150.0 RFWN 105 N/A 40 U

7415 09/08/78 0

3 S32421ML068-ITEM 19

.5 88071376 136*

3-2176 1160 SOACCW 10.00 FLG 150.0 RFWN 105 N/A 40 U

74205 01/21/77 0

3 SA1203ML305-ACC305002 0

1178 SOACCW C 8.00 FLG 150.0 RFWN 105 N/A 40 U

T30266 01/21/77 0

3 SA1203ML305-ACC305002

-2 88071088 144 811 SOACCW C 8.00 FLG 150.0 RFWN 105 N/A 40 w

130266 02/09/77 0

3 SA1203ML305-ITEM 28

-1 88071088 128*

G-879 1179 SOACCW 8.00 FLG 150.0 RFWN 105 N/A 40 w

730266 01/21/77 0

3 SA1203ML307-ACC307001 0

1295 SOACCW A 10.00 FLG 150.0 RFWN 105 N/A 40 U

HJ 10/21/76 0

3 SA1203ML307-ACC307001

. 0 1180 SOACCW 8.00 FLG 150.0 RFWN 105 N/A 40 U

730266 01/21/77 0

3 SA1203ML307-ACC307002 0

596 SOACHU C 6.00 FLG 300.0 RFWN 105 N/A 40 U

m964301 09/23/77 0

3 SA1513ML070-ACH070010

-1 88071121 141 597 SOACHW C 6.00 FLG 300.0 RFWN 105 N/A 40 U

M964301 09/23/77 0

3 SA1513KLO73-ACH073001

-1 88071305 133*

807 SOACHW C 8.00 FLG 150.0 RFWN 105 N/A 40 U

730266 02/09/77 0

3 SA1513ML073-ACH073004

-2 88071114 132*

G-878 808 SOACHW C 8.00 FLG 150.0 RFWN 105 N/A 40 U

730266 02/09/77 0

3 SA1513ML073-ACH073004

-3 88071114 134*

G-878 810 SOACHW C 8.00 FLG 150.0 RFWN 105 N/A 40 U

730266 02/09/77 0

3 SA1513ML073-ITEM 25

-1 88071114 134*

G-878 856 SOACHW C 2.50 FLG 150.0 RFWN 105 N/A 40 U

T4902 02/09/77 0

3 SA1513ML076-ACH076004

-1 88071123 138 857 SOACHW C 2.50 FLG 150.0 RFWN 105 N/A 40 U

74902 02/09/77 0

3 SA1513ML076-ACHO7600S

-2 88071123 150 858 SOACHW C

2.50 FLG 150.0 RFWN 105 N/A 40 U

14902 02/09/77 0

3 SA1513ML076-ACH076005

-3 88071123 146 859 SOACHW C 2.50 FLG 150.0 RFWN 105 N/A 40 w

74902 02/09/77 0

3 SA1513MLO77-ACH077004

-3 88071125 142 60 SOACHW C 2.50 FLG 150.0 RFWN 105 N/A 40 U

74902 02/09/77 0

3 SA1513ML077-ACHO77005

-1 88071125 129*

6-875 61 SOACHW C 2.50 FLG 150.0 RFWN 105 N/A 40 w

74902 02/09/77 0

3 SA1513ML077-ACH077005

-2 88071125 130*

G-875 963 SOACHW C 2.50 FLG 150.0 RFWN 105 N/A 40 U

74902 02/09/77 0

3 SA1513ML081-ITEM 6

-1 88071126 144 1077 SOACHW C 2.50 FLG 150.0 RFWN 105 N/A 40 U

14696 11/01/76 0

3 SA1513ML093-ITEM 38

-1 88071128 128*

G-891 1078 SOACHW C 2.50 FLG 150.0 RFWN 105 N/A 40 U

T4696 11/01/76 0

3 SA1513ML126-ITEM 36

-1 88071130 122*

G-890 1079 SOACHW C 2.50 FLG 150.0 RFWN 105 N/A 40 U

74696 11/01/76 0

3 SA1513ML131-ITEM 2

-1 88061132 134*

G-889 866 SOACHW C 2.50 FLG 150.0 RFWN 105 N/A 40 U

74902 02/09/77 0

3 SA1513ML132-ACH13.2027

-3 88071134 138 854 SOACHW C 2.50 FLG 150.0 RFWN 105 N/A 40 w

74902 02/09/77 0

3 SA1513ML132-ACH132028

-4 88071134 148 855 SOACHW C 2.50 FLG 150.0 RFWN 105 N/A 40 U

74902 02/09/77 0

3 SA1513ML132-ACH132028

-5 88071134 140 823 SOACH. C 3.00 FLO 150.0 RPUN 105 N/A 40 U

1415 09/23/77 0

3 SA1513ML132-ITEM 2

-1 88071134 147

Psoe Le.

33 NCR SONGS REPORT (BY LOCATION)

ITMP41TRANS DIAMETER COMMODITY RA71UG TYPE SPEC GRADE SCHEDULE VENDOR HEAT L07 DATE DUAQYITY SOURCE kSME LINE TS UBR7!R S.OVNRWME 824 SOACHU C 3.00 FLG 150.0 RruN 105 N/A 40 U

J4E 09/23/77 0

3 SA1513ML132-ITEM &

-2 88061134 214 862 SOACHW C 2.50 FLG 150.0 RFW 105 W/A 40 U

14902 02/09/77 0

3 SA1513ML137-ACHM137025 88071212 143 863 SOACHU C 2.50 FLG 150.0 RFW 105 W/A 40 U

14902 02/09/77 0

3 SA1513ML137-ACH137026 88071212 158 864 SOACHW C 2.50 FIG 150.0 rTUN 105 N/A

'0 U

14902 02/09/77 0

3 5A1513ML137-ACH137026 88071212 USB 25 SOACHU C 3.00 FIG 150.0 RFun 105 W/A 40 U

7415 09123/77 0

3 SA1513ML137-ITEM I S/I

-4 88071210 151 6

05ACHW C 3.00 FLG 150.0 RFUW 105 W/A

/0 U

7415 09/23/77 0

3 SA1513ML137-31EN 5 S/2

-5 88071210 160 S73 0ACHU A 2.50 FLG 150.0 RFUN 105 W/A 40 U

14902 2/9/77 0

3 SA1T513ML14t-ACCTD008

-2 88071213 153 1065 SOACHW C 2.50 FIG 150.0 arUN 105 W/A 40 U

14696 11/01/76 0

3 SAl513ML144-ACH"0O9

-1 88071213 140 1068 SOACHW C 2.50 FLG 150.0 RFUN 105 H/A 40 U

14696 11/01/76 0

3 SA1513ML149-ACH149001

.1 88071215 156 1275 SDACuW A 2.50 FIG 150.0 RFun 105 W/A 40 U

T4902 2/9/77 0

3 SA1513ML149-ACH149002

-2 88071215 147 601 SOACHW C 4.00 FIG 150.0 RFWK 105 N/A

'0 w

1097642 02/09/77 0

3 SA1513ML180-IIEM 18

-1 88071218 165 602 SOACHU C 4.00 FIG 150.0 RFWN 105 H/A 40 U

7097642 02/09/77 0

3 SA1513MLTSO-ITEM 19

-2 88071218 152 603 50ACHW C

'.00 FIG 150.0 RFWN 105 H/A 40 U

1097642 02/09/77 0

3 SA1513ML180-IlEM 38

-3 88071218 181 600 SOACHW C 4.00 FIG 150.0 RFWN 105 H/A 40 U

7097642 02/09/77 0

3 SA1513MLIt-ACH185007

-1 88071219 173 867 SDACHW C 2.50 FIG 150.0 RFWN 105 H/A

'0 w

14902 02/09/77 0

3 SA1513ML192-ACH192007

  • 1 88071221 141 665 50ACHW C 2.50 FIG 150.0 aRun 105 H/A 40 w

74902 02/09/77 0

3 SA1513ML192*ACM192008

-1 88071221 143 668 05ACHu C 2.50 FIG 150.0 RSw 105 H/A 40 U

74902 02/09/77 0

3 SA1513ML197-ACH197007

-1 88071222 151 869 SOACHU C 2.50 FLG 150.0 RFUN 105 N/A 40 U

14902 02/09/77 0

3 SA1513ML197-ACH197008

-2 88071222 144 1066 50ACHW C 8.00 FIG 150.0 RFUN 105 W/A 40 U

74298 10/21/76 0

3 SA1513ML227-ACH227007

.1 88071115 14S 800 SOACHW C 8.00 FIG 150.0 RFWN 105 H/A 40 U

130266 02/09/77 0

3 SA1513ML227*ACH227008

-2 88061115 140 801 S0ACHW C 8.00 FIG 150.0 RFUN 105 H/A 40 U

130266 02/09/77 0

3 SA1513ML227-ACh227008

  • 3 88071115 136*

G-886

!98 SOACHW C 6.00 FLG 300.0 RFUN 105 W/A

'0 U

M964301 09/23/77 0

3 SA1513ML239*ACK239005

-1 88071223 139 250ACHW C 8.00 FIG 150.0 RFWN 105 N/A

'0 U

730266 02/09/77 0

3 SA1513ML2t2-ACH242004

-1 58071119 139 9 50ACHW C 6.00 FIG 300.0 RFU 105 N/A 40 U

.96L301 09/23/77 0

3 SA1513ML242-ACK242006

  • 1 88061378 134*

G-882 803 SOACHW C 8.00 FIG 150.0 RFWN 105 H/A 40 w

730266 02/09/77 0

3 5A1513ML242-ACH?42007

.3 88071119 130-G-888 804 SOACHW C 8.00 FIG 150.0 RFWN 105 H/A

'0 w

130266 02/09/77 0

3 SA1513ML242-ACK242007

-2 88071119 128*

G-888 805 SOACHW C 8.00 FIG 150.0 RFun 105 W/A 40 U

130266 02/09/77 0

3 SA1513ML244-ACH244005

-1 88071120 129.5*

G-L876 806 SOAHW C 8.00 FLG 150.0 RFWH 105 N/A 40 w

130266 02/09/77 0

3 SA1513ML244-ACH244005

-2 88071120 140 1067 SDACHW 8.00 FIG 150.0 rTUN 105 W/A 40 w

1IL298 10/21/76 0

3 SA1513ML244-ACH2440D 0

1073 SOACHW C 2.50 FIG 150.0 RFWN 105 N/A

'0 U

14696 11/01/76 0

3 SAIS13ML271I-1EM 8

-1 88061224 129 1074 SOACHW C 2.50 FIG 150.0 arFW 105 N/A LO U

14696 11/01/76 0

3 SA1513ML276-ITEM 12

-1 88061226 154 1142 SOACHW 8.00 FIG 150.0 RFWN 105 H/A 40 U

130266 02/09/77 0

3 SAS13ML277-ACH227008 0

1143 SoAOHU 8.00 FIG 150.0 RFUN 105 N/A 40 w

130266 02/09/77 0

3 SA1513ML277*ACH227008 0

E74 SOA.HW C 2.50 FIG 150.0 RFW 105 H/A 40 U

71902 02/n9/77 0

3 SA1513ML325-ACN325023

-3 88071228 14

Pa-e No.

34 0908/88 NCR SONGS REPORT (BY LOCATION)

ITEM PLANT TRANS DIAMETER COMMODITY RATING TYPE SPEC GRADE SCHEDULE VENDOR HEAT LOT DATE QUANTITY SOURCE ASME LINE TEST M_0 NUMBER 7-HARD KSI.CONy NCR.NUMBER 875 SOACHW C 2.50 FLG 150.0 RFWN 105 N/A 40 w

14902 02/09/77 0

3 SA1513ML325-ACH325024

-4 88061228 137 876 SOACHW C 2.50 FLG 150.0 RFWN 105 N/A 40 W

74902 02/09/77 0

3 SA1513ML325-ACH325024

.5 88061228 137 820 SOACHW C 3.00 FLG 150.0 RFWN 105 N/A 40 W

7415 09/23/77 0

3 SA1513ML325-ITEM 10

-2 88061227 217-*

719 SOACCW C 3.00 FLG 150.0 RF N 105 N/A 40 w

J4E 06/17/77 0

3 SA1513ML325-ITEM 6

-1 88061227 143.5 873 SOACHW C 2.50 FLG 150.0 RFWN 105 N/A 40 w

74902 02/09/77 0

3 SA1513ML330-ACH330023

-1 88071093 149 871 SOACHW C 2.50 FLG 150.0 RFWN 105 N/A 40 w

74902 02/09/77 0

3 SA1513ML330-ACH330024

.2 88071093 147.5 4

72 SOACHW C 2.50 FLG 150.0 RFWN 105 N/A 40 w

74902 02/09/77 0

3 SA1513ML330-ACH330024

.3 88071093 142 1 SOACHW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

7415 09/23/77 0

3 SA1513ML330-ITEM 10

-1 88071089 150 822 SOACHW C 3.00 FLG 150.0 RFWN 105 N/A 40 w

7415 09/23/77 0

3 SA1513ML330-ITEM 14

-2 88071089 150 852 SOACHW C 2.50 FLG 150.0 RFWN 105 N/A 40 W

14902 02/09/77 0

3 SAI513ML331-ACH331008

-1 88071098 144 1069 SOACHW C 2.50 FLG 150.0 RFWN 105 N/A 40 w

74902 11/01/76 0

3 SA1513ML331-ACH331009

.2 88071098 162 1070 SOACHW C 2.50 FLG 150.0 RFWN 105 W/A 40 U

74696 11/01/76 0

3 SA1513ML336-ACH336001

-1 88071099 158 G-887 853 SOACHW C 2.50 FLG 150.0 RFN 105 N/A 40 U

14902 02/09/77 0

3 SA1513ML336-ACH336002

,-2 88071099 132*

877 SOACHW C 2.50 FLG 150.0 RFWN 105 N/A 40 w

74902 02/09/77 0

3 SA1513ML367-ACH367004

-2 88071100 130 G-883 1199 SOACHW C 2.50 FLG 150.0 RFWN 105 W/A 40 T4902 02/09/77 0

3 SA1513ML367-ACH367005

-1*

88071100 144 1200 SOACHW C 2.50 FLG 150.0 RFWN 105 N/A 40 7 14902 02/09/77 0

3 SA1513ML367-ACH367005

-3 88071100 146 881 SOACHW C 2.50 FLC 150.0 RrUN 105 N/A 40 U

T4902 02/09/77 0

3 5A1513ML372-ACh372004

-1 88071102 144 878 SOACHW C 2.50 FLG 150.0 RFWN 105 N/A 40 U

14902 02/09/77 0

3 SA1513ML372-ACH372005

  • 2 88071102 142 879 SOACHW C 2.50 FLG 150.0 RFWN 105 N/A 40 U

T4902 02/09/77 0

3 SA1513ML372-ACH372005

-3 88071102 146 880 SOACHW C 2.50 FLG 150.0 RFWN 105 N/A 40 U

14902 02/09/77 0

3 SA1513ML373-AC H373007

-1 88071106 144.5 882 SOACHW C 2.50 FLG 150.0 RFWN 105 N/A 40 U

14902 02/09/77 0

3 SA1513ML373-ACH373008

-2 88071106 140 884 SOACHW C 2.50 FLG 150.0 RFWN 105 N/A 40 U

14902 02/09/77 0

3 SA1513ML378-ACH378007

-1 88071108 144.5 883 SOACHW C 2.50 FLG 150.0 RFWN 105 N/A 40 T

14902 02/09/77 0

3 SA1513ML378-ACH378008

-2 88071108 145 1071 S0ACHW C 4.00 FLG 150.0 RFWN 105 N/A 40 U

T4696 11/01/76 0

3 SA1513ML385-ACH385004

-3 88061110 143.5 5 5OACHW C 4.00 FLG 150.0 RFWN 105 N/A 40 w

14696 11/01/76 0

3 SA1513ML385-ITEM 44

-1 88071110 159 6 SOACHW C 4.00 FLG 150.0 RFWN 105 N/A 40 U

14696 11/01/76 0

3 SA1513ML385-ITEM 46

.2 88061110 171.5 1120 SOACHW C 4.00 FLG 150.0 RFWN 105 N/A 40 U

i61D 06/30/77 0

3 SA1513ML390-AC4390001

-1 88071112 148