Re-evaluation Criteria for Anchorage & Support of Safety- Related Electrical Equipment
ML13317B083
Person / Time
Site: San Onofre 
Issue date: 05/01/1981
From:
BECHTEL GROUP, INC.
To:
Shared Package
ML13317B080 List:
References
TASK-03-06, TASK-3-6, TASK-RR NUDOCS 8204160316
Download: ML13317B083 (16)


Text

SAN ONOFRE NUCLEAR GENERATING STATION UNIT I REEVALUATION CRITERIA FOR ANCHORAGE AND SUPPORT OF SAFETY RELATED ELECTRICAL EQUIPMENT JOB 14000-086 BECHTEL POWER CORPORATION NORWALK, CALIFORNIA MAY 1, 1981 8204160316 820412 PDR ADOCK 05000206 P

.: PDR

Table of Contents Page

1. INTRODUCTION.........

-... 1

2. SCOPE OF WORK................

2

3. GOVERNING
CODES, REGULATIONS, AND REFERENCE DOCUMENTS 3

3.1 Governing Codes, Specifications and Standards.

3 3.2 NRC Regulatory Guides.

3

4. DESIGN REQUIREMENTS....

4 4.1 Seismic Withstand Capacity 4

4.2 Design Life.

4

5. LOADS AND LOAD COMBINATIONS 9

5.1 Normal Loads.............

9 5.2 Extreme Environmental Loads...........

9

6. ALLOWABLE LOADS AND STRESSES...

1 6.1 Structural Steel, Cold Form Steel, Bolts....

11 6.2 Hilti Kwik Concrete Expansion Anchors.......

11

7. CONSTRUCTION MATERIALS........

14

1. INTRODUCTION This document describes the seismic reevaluation for the anchorage and support of Safety Related Electrical Equipment. The criteria covers the evaluation and modifications as referenced in the NRC letter dated January 1, 1980, from Darrel G. Eisenhut to James H. Drake and IE Information Notice No. 80-21.

1

2. SCOPE OF WORK Seismic reevaluation shall be performed on safety related electrical equipment, identified by SCE, to determine the adequacy of their anchorage and support. The analysis and design will be limited to only the structural adequacy of the supports and anchors, and not to the equipments' functional ability. The engineering effort will include record search at the station (BPC and SCE) for pertinent data, field "As-Built" information gathering, as required, and determination of the structural design parameters such as embedment length of the anchorages, concrete strength, etc.
3.

GOVERNING CODES, REGULATIONS AND REFERENCE DOCUMENTS Unless specifically stated otherwise, the design of anchorages and supports shall be based on the following codes, specifications, standards, regulations and other reference documents.

3.1 Governing Codes, Specifications and Standards The following codes, specifications and standards, when appli cable, shall govern the reevaluation and any subsequent design of modifications.

ACI-318-77 Building Code Requirements for Reinforced Concrete.

AISC-1978 Specification for Design, Fabrication and Erection of Structural Steel for Buildings.

AWS D1.1 1980 Structural Welding code.

IEEE 344-1975 Seismic Qualification of Class IE Equipment for Nuclear Power Generating Stations.

Bechtel Design Concrete Expansion Anchors Guide No. C-2.40 Standard Review Plan, Section 3.8.4 ANSI N45-2 1977 Nuclear Quality Assurance Standards ANSI N45-2-11 1974 Quality Assurance Requirements for the Design of Nuclear Power Plants 3.2 NRC Regulatory Guides.

The following NRC Regulatory Guides shall be implemented.

Guide Number Title 1.29 Seismic Design Classification.

1.61 Damping values for Seismic Design of Nuclear Power Plants.

4.

REEVALUATION AND DESIGN REQUIREMENTS The reevaluation and design to be accomplished under this criteria shall be subject to the following requirements.

4.1 Seismic Withstand Capability:

Analysis and design of the anchorage and support of safety related electrical equipment will be accomplished using the equivalent static load method of analysis.

Provisions of subsections 4.1.1 and 4.1.2 are applicable to the equipment support and anchorages.

4.1.1 Seismic Response Spectra The design response spectra for horizontal motion for the Design Basis Earthquake (DBE) corresponds to the Bousner spectra, as described in Section 9.2 of the San Onofre Unit 1 FSAR, normalized to 0.67 g. The vertical design response spectra are defined as 2/3 of the horizontal spectra.

The spectra to be used for all the items located at or below plant grade and the appropriate floor spectra to be used for all the items located above plant grade are shown in Figures 4.1, 4.2 and 4.3. The recommended damp ing factors are given in Table 4.1.

4.1.2 Equivalent Static Load Methods of Analysis.

The static load equivalent analysis method involves the multiplication of the total weight of the subsystem by the specified seismic acceleration coefficient. The magnitude of the seismic acceleration coefficient is established on the basis of the fundamental frequency of the system or subsystem. In determining the dynamic characteristics of the system, support base plate flexibility will be taken into account. Structural subsystem which can be adequately characterized as single-degree-of-freedom systems are considered to have a modal participation factor of one. Seismic acceleration coefficients for multi-degree of freedom systems which may be in the resonance region of the amplified response spectra, are increased by 50 percent to account conservatively for the increased modal participation.

4.2 Design Life The design life for all items will be 35 years.

4

TABLE 4.1 DBE DAMPING VALUES USED FOR SEISMIC REEVALUATION DBE DAMPING ITEM (Percent of Critical)

Welded Steel Structures 4

Bolted and/or Riveted Steel Structures 7

Reinforced Concrete Structures 7

FREQUENCY (cycies per wond) 100 50 25 10 521j.2 l

2 PERID (EC

~

SCMTELPOWECOPORATION Sc, DIS.PLACEMENT RESPONSE (IN'CHES)

O NEE IIIN N

T

-PRO(SCISOUTH4ERN CALIFORNVIA EDISON COMPANY SAN ONOFRE NUC,LAFI GOLN[ATING STATION S -ACCELERATION RESPONSE (0a,S)

~

NI DAM IN VA UE

____BSIERT_

0AK f2RZ1ITLA-EEAINRSOS ASPRETOFCIIA0 SPCR.FRMS pAVN 4

OOTI ET CLRSOS CEL A O UTPYB U7

.02~~~~r r-T I 2

12 3

F PtEQUE NCY (cydks pw twm we50

s.

sc 10 T 2 S, 4 -

K-CHT4L "ER~ CORP0RATIo,0 sd -DISPLACEMENT RESPONSE (IodCMES)

T rtlIitto (SEC.)

SOUTHERN CALIFORNIA EDISON COMPANY SAN ONOFRE NU)CLEARt GENERtATING STATION~

S ACC IE[RA T bO4A SEWONSE (2' )

UIT~r AS PERCENT OF CRITtCAL DESG16 BASIS E2$I7-'4'rE NoR/ZOAJ7AL ACCELEEATIOAI

=4--

RESPCAJSE,9PECTkA A7' TO 08STA/k' s/E,?/CAL.RE5P2A,/E EL EV (24? 1'-O" C1 ACCELERqA7T/0, AI1LT,-Pt-Y 6~Y 0,O4/676FAT/'~-c'~TO

-T

~~-~i1 J-~

FREQJANCY Wcyclu pe ndw)

S 0

5 d SISrHTIE "ER~ CONIORATIGN 9 DISPLACEMENT RESOW~E (INdCHES)

ANLUDVSO

.SOUTHERN CALIFORNVIA 11Ot[SN COMPANY S -~LER~lON

-~LA)N OOFRE NUCLEAR GUENEATIG STATION AS PICENT OfCRITICAL

~FPWFS~rAA icFV A O0O-ro 42 0"OF REAC TOR 86f4.V/NG I-I 4;A p16 wY I0.'5-

0 0

5. LOADS AND LOAD COMBINATIONS The anchorages and supports for safety related electrical equipment will consider the occurrence of a DBE during normal plant operation.

The loading combinations that will be considered are shown in Table 5.1.

The normal loads and extreme environmental loads are described in the following paragraphs.

5.1 Normal Loads (Loads encountered during normal plant operation.)

Normal load includes dead load (D) and live loads (L) as defined in Table 5.1.

The design parameters such as approximate weight, location of center of gravity, and dynamic characteristics of equipment shall be obtained from the following.

A. SONGS 1 BOP Seismic Re-Evaluation Program, Photographic Description of Electrical, Control and Instrumentation Systems, Volume 2.

B. SONGS 1 Seismic Re-Evaluation Program, Phase IB, Site Survey Reports.

C. When design parameters are not obtainable from A and B, a conservative estimate shall be obtained from the original equipment suppliers and from field surveys.

5.2 Extreme Environmental Loads (Loads that are credible, but are highly improbable).

The extreme environmental loads considered are the Design Basis Earthquake (DBE) loads (E'). The DBE seismic loads will be generated in accordance with the provisions of Section 4.1.

TABLE 5.1 LOADS AND LOAD COMBINATIONS Definitions and Nomenclature for Load Combination.

D = Dead load of equipment including weight of all permanent attachments.

L = Live load.

E I= Loads Generated by the Design Basis Earthquake (DBE).

S = Required section strength based on elastic design method and the allowable stresses defined in Part I of the AISC "Specification for the Design, Fabrication, and Erection of Structural Steel for Buildings".

Load Combinations The following loading combinations shall be satisfied.

S > D + L 1.6S > D + L + E'

6. ALLOWABLE LOADS AND STRESSES Allowable loads for different types of material are as follows.

6.1 Structural Steel, Cold Form Steel, Bolts.

The allowable stresses are as per AISC specification, depending on type of steel and bolt used.

6.2 Hilti Kwik Concrete Expansion Anchors.

The following criteria should be used in the design. Allowable design loads are shown in Table 6.1.

6.2.1 Expansion anchors shall be at least 1/2 inch diameter, except that 1/4 inch and 3/8 inch diameter expansion anchors may be used for attachment of conduits, instrument sensing lines, or similar lightly loaded installations.

6.2.2 A minimum of two expansion anchors shall be used at each attachment.

6.2.3 The allowable design loads per Table 6.1 shall be reduced to 25 percent of the specified values when designing for dynamic shock or vibratory loads.

This reduction does not apply to seismic loads.

6.2.4 A reduction in the minimum center to center spacing and edge distance for anchors is acceptable provided that the allowable design loads (tension and shear) are reduced by the same proportion (i.e.:

25 percent reduction in spacing -*25 percent reduction in allowable design loads).

The reduction in spacing may not exceed 50 percent in any case.

6.2.5 A reduction in the minimum embedment for anchors is acceptable provided that the allowable design load (shear and tension) is reduced in proportion to the square of the reduced embedment (i.e.:

embedment reduced to 80 percent of mi imum specified -*allowable design load reduced to (.80) = 0.64 times allowable load specified).

The reduced embedment may not be less than 70 percent of the specified minimum embedment.

6.2.6 For evaluation of simultaneous tension and shear loading, the loads shall be combined by the following interaction formulas:

-2+

< 1.0 T

S where:

(t, s) = actual design (tension, shear) loads, respectively.

(T, S) = specified allowable (tension, shear) loads, respectively.

Table 6-1.

Allowable Design Loads for Concrete Expansion Anchors Torque at Installation Allow Min.

(ft.

lb. )

Design Min.

Edge Min.

Test Anchor Loads Embed.

Dist.

Spacing Wedge Sleeve Loa d Diameter (Kips)

(inches)*

(inches)

(inches)

Anchor Anchor (Kips) 1/4 0.30 1-1/8 3

3 5-10 5-10 NA 3/8 0.60 1-1/2 4

4-1/2 25-35 20-35 NA 1/2 1.0 2-1/2 6

5 45-65 35-50 2.0 5/8 2.0 3

6 6

80-90 50-75 4.0 3/4 3.0 3-1/2 6

7-1/2 125-175 75-100 6.0 7/8 3.5 4

6 9

200-250 NA 7.0 1

4.0 4-1/2 6

10 250-300 NA 8.0 A

Load in shear, tension or combined. Allowable design loads are for 4000 psi concrete.

B Threads not lubricated.

NA= Not Applicable

=

After tightening.

7. CONSTRUCTION LATERIALS All construction materials shall be classified Safety Related unless otherwise specified on the design drawing.

7.1 Structural steel shall be ASTM A36.

7.2 Bolts shall be of the following specifications.

7.2.1 Standard connections shall be ASTM A307 or as specified on the design drawing.

7.2.2 Anchor bolts shall be Kwik Bolts manufactured by Hilti Fastening Systems, Inc., or as specified on the design drawing.

7.3 Grout shall be Five Star Non-Shrink grout or approved equal.

7.4 All structural welding shall be done with low hydrogen electrodes E7015, E7016, or E7018 per AWS Code.

7.5 Miscellaneous material not specified in these criteria shall be per design drawing.