ML12348A272

From kanterella
Jump to navigation Jump to search
12Q0108.30-R-001, Rev. 1, Seismic Walkdown Report in Response to the 50.54(f) Information Request Regarding Fukushima Near-Term Task Force Recommendation 2.3: Seismic for the Dresden Nuclear Power Station, Unit 2, Part 7 of 7
ML12348A272
Person / Time
Site: Dresden Constellation icon.png
Issue date: 11/15/2012
From: Delaney M
Exelon Generation Co, Stevenson & Associates
To:
Office of Nuclear Reactor Regulation
References
RS-12-167 12Q0108.30-R-001, Rev 1
Download: ML12348A272 (102)


Text

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Sheet 1 of 6 Status: F N U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

AWC-22 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.

Additional space is provided at the end of this checklist for documenting other comments.

1.

Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?

2.

Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?

Overhead light at west end (Column Line 42) contains broken chain; judged to not be of concern.

3.

Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,

condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?

4.

Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

5.

Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?

6.

Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?

7.

Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and

.temporary installations (e.g., scaffolding, lead shielding)?

D-78

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Sheet 2 of 6 Status: r N U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

AWC-22

8.

Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?

Comments Seismic Walkdown Team: D. Carter & J. Griffith - 7/19/2012 AWC 22 Evaluated by:

).JVO*"

David Carter Date:

10/24/2012 e

James Grffith 10/24/2012 Photos MG 0610 MG 0611 D-79

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Sheet 3 of 6 Status: 7 N U Area Walk-By Checklist (AWC)

MG_0612 MG 0614 D-80

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Sheet 4 of 6 Status: F N U Area Walk-By Checklist (AWC)

MG_0616 MG 0617 MG 0618 D-81

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Sheet 5 of 6 Status: L7Y N U Area Walk-By Checklist (AWC)

MG_0621 MG_0622 D-82

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Sheet 6 of 6 Status: l N U Area Walk-By Checklist (AWC)

MG 0623 MG 0625 MG 0625 D-83

12Q0108.30-R-OO1, Rev. 1 Correspondence No.: RS-12-167 Sheet 1 of 8 Status: 7 N U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

AWC-23 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.

Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?
2.

Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?

3.

Based on a visual inspection froni the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,

condition of supports is adequate and fill conditions of cable trays appears to be inside acceptable limits)?

4.

Does it appear that the area is free of potentially adverse seismic spatial' Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Overhead light fixtures judged to be acceptable.

Masonry wall in vicinity is safety related.

5.

Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?

6. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?
7.

Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Tools and ladder far enough away from soft targets judged not to be of concern.

2 valve wrenches hung from duct opening at back of room judged not to be of concem.

D-84

12QO108.30-R-001, Rev. I Correspondence No.: RS-12-167 Sheet 2 of 8 Status: F N U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

AWC-23

8.

Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?

Comments Seismic Walkdown Team: D. Carter & J. Griffith - 7/19/2012 - 7/20/2012 AWC 23 Evaluated by:

V4JAlk David Carter Date:

10/2/2012 James Griffith 10/2/2012 Photos MG 0707 MG 0708 D-85

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Sheet 3 of 8 Status:

Y N U Area Walk-By Checklist (AWC)

MG 0709 MG_0710 D-86

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Sheet 4 of 8 Status: LY N U Area Walk-By Checklist (AWC)

MG_071 MG_0712ir MG_0713 MG_0714 D-87

12Q0108.30-R-001, Rev. I Correspondence No.: RS-12-167 Sheet 5 of 8 Status: [-1 N U Area Walk-By Checklist (AWC)

Location BdElev, Room/Area:

AWC-23 MG 0715 MG 0719 MG_0721 I

MG 0720 D-88

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Sheet 6 of 8 Status:

Y N U Area Walk-By Checklist (AWC)

Location Bid Elev Room/Area AWC-23 MG 0722 MG 0723 SI MG_0812 MG 0811 D-89

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Sheet 7 of 8 Status: F N U Area Walk-By Checklist (AWC)

MG_0814 MG 0816 MG 0818 D-90

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Sheet 8 of 8 Status: [Y N U Area Walk-By Checklist (AWC)

MG_0819 MG 0820 D-91

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Sheet I of 2 Status: [Y] N U

Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

AWC-24 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.

Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?

Yes

2.

Does anchorage of equipment in the area appear to be free of significant degraded conditions?

Yes

3.

Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,

condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?

Yes

4.

Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Yes

5.

Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?

Yes

6.

Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?

Yes

7.

Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Yes D-92

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Sheet 2 of 2 Status: 111 N

U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

AWC-24

8.

Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?

Comments Seismic Walkdown Team: D. Carter & J. Griffith - 7/16/2012 AWC 24 For photographs, see SWCs of components included in this area walk-by.

Evaluated by:

9JI/O,4-David Carter Date:

10/24/2012 James Griffith 10/24/2012 Photos D-93

12Q-108.30-R-O01, Rev.

I Correspondence No.: RS-12-167 Sheet 1 of 2 Status: F N

U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

AWC-25 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.

Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?

Yes

2.

Does anchorage of equipment in the area appear to be free of significant degraded conditions?

Yes

3.

Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,

condition of supports.is adequate and fill conditions of cable trays appear to be inside acceptable limits)?

Yes

4.

Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Yes

5.

Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?

Yes

6.

Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?

Yes

7.

Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Yes D-94

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Sheet 2 of 2 Status: F N

U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

AWC-25

8.

Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?

Comments Seismic Walkdown Team: D. Carter & J. Griffith - 7/16/2012 AWC 25 Evaluated by:

'-Q-k, David Carter Date:

10/24/2012 James Griffith 10/24/2012 Photos D-95

12Q0108.30-R-OO1, Rev. 1 Correspondence No.: RS-12-167 Sheet 1 of 2 Status: F--

N U

Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

AWC-26 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.

Additional space is provided at the end of this checklist for documenting other comments.

1.

Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?

2.

Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?

3.

Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,

condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?

4.

Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

5.

Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?

6.

Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?

7.

Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

D-96

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Sheet 2 of 2 Status: [-

N U

Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

AWC-26

8.

Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?

Temporary cables stored in area near Cabinet 902-63C judged acceptable as-is.

Comments Seismic Walkdown Team: D. Carter & J. Griffith - 7/16/2012 AWC 26 For photographs; see SWCs of components included in this area walk-by.

Evaluated by:

David Carter Date:

10/24/2012 James Griffith 10/24/2012 Photos D-97

12Qo108.30-R-oo1, Rev. 1 Correspondence No.: RS-12-167 Sheet 1 of 2 Status: F N U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

AWC-27 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.

Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?
2.

Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?

3.

Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,

condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?

4.

Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

5.

Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?

Threaded fire pipe well supported. Judged acceptable.

6.

Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?

7.

Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Scaffold adequately restrained.

D-98

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Sheet 2 of 2 Status: F N U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

AWC-27

8.

Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?

Comments Seismic Walkdown Team: D. Carter & J. Griffith - 7/18/2012 AWC 27 For photographs, see SWCs of components included in this area walk-by.

Evaluated by:

QJA/04k David Carter Date:

10/24/2012 James Griffith 10/24/2012 Photos D-99

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Sheet 1 of 2 Status: F N

U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

AWC-28 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.

Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?

Yes

2.

Does anchorage of equipment in the area appear to be free of significant degraded conditions?

Minor rod support bend on heating steam line judged to be acceptable.

3.

Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,

condition of supports is adequate and fill conditions of cable trays appears to be inside acceptable limits)?

Yes Yes

4.

Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Yes

5.

Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?

Yes

6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?

Yes

7.

Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Yes D-100

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Sheet 2 of 2 Status: r-Y N

U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

AWC-28

8.

Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?

Comments Seismic Walkdown Team: D. Carter & J. Griffith - 7/17/2012 AWC 28 Evaluated by:

QJ&iQ" David Carter Date:

10/2/2012

'P$IJames Griffith 10/2/2012 MU.U UjlU MUj_Ulti1 D-101

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167

.Sheet 1 of 3 Status: F N

U Area Walk-By Checklist (AWC)

Location (Blda, Elev, Room/Area):

AWC-29 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.

Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?

Yes

2.

Does anchorage of equipment in the area appear to be free of significant degraded conditions?

Yes

3.

Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,

condition of supports is adequate and fill conditions of cable trays appears to be inside acceptable limits)?

Yes

4.

Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Yes

5.

Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?

Threaded fire pipe well supported. Judged acceptable.

Yes

6.

Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?

Yes

7.

Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Scaffold adequately restrained.

Yes D-102

1200108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Sheet 2 of 3 Status: F-7 N U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

AWC-29

8.

Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?

Comments Seismic Walkdown Team: D. Carter & J. Griffith - 7/17/2012 AWC 29 Evaluated by:

Q2JA/Q--

David Carter Date:

10/2/2012 A"

James Griffith 10/2/2012 Photos MG 0202 MG 0203 MG 0204 MG 0205 D-103

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Sheet 3 of 3 Status: F N U Area Walk-By Checklist (AWC)

M(G 0206 MU 0201 U 0206 mu Uzut D-1 04

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Sheet 1 of 2 Status:

Y N U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

AWC-30 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.

Additional space is provided at the end of this checklist for documenting other comments.

1.

Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?

Yes

2.

Does anchorage of equipment in the area appear to be free of significant degraded conditions?

3.

Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,

condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?

Yes Yes Yes

4.

Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

5.

Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?

Yes

6.

Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?

Yes

7.

Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Yes D-105

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Sheet 2 of 2 Status: F N U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

AWC-30

8.

Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?

Security position less than 24 inches from Bus 24, Considered to be at design location.

Comments Seismic Walkdown Team: D. Carter & J. Griffith - 7/16/2012 AWC 30 For photographs, see SWCs of components included in this area walk-by.

Evaluated by:

9 J,,(k David Carter Date:

10/24/2012 James Griffith 10/24/2012 Photos D-1 06

12Q0108.30-R-001, Rev. I Correspondence No.: RS-12-167 Sheet 1 of 2 Status: F N

U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

AWC-31 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.

Additional space is provided at the end of this checklist for documenting other comments.

1.

Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?

Yes

2.

Does anchorage of equipment in the area appear to be free of significant degraded conditions?

Yes

3.

Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,

condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?

Yes

4.

Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

5.

Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?

Yes Yes Yes

6.

Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?

7.

Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Baker scaffold stored in room is adequate. Adequate tip and slide clearance per DAP.

Yes D-107

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Sheet 2 of 2 Status: F N

U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

AWC-31

8.

Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?

Masonry walls all edge-supported and judged acceptable.

Comments Seismic Walkdown Team: D. Carter & J. Griffith - 7/16/2012 AWC 31 For photographs, see SWCs for D00-5741-0048BV72, D00-9400-0102-Ri 5, and DOO-9400-0104BF05.

Evaluated by:

David Carter Date:

10/24/2012 James Griffith 10/24/2012 Photos D-108

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Sheet 1 of 5 Status: -7 N U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

AWC-32 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.

Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?

Yes

2.

Does anchorage of equipment in the area appear to be free of significant degraded conditions?

3.

Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,

condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?

Yes Yes Yes

4.

Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

5.

Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?

Minor bend in fire protection line support judged to be acceptable. Threaded fire pipe well supported and judged to be acceptable.

IR 1389712:

Bent fire piping hanger that is in the area above the Unit 2 LEFM panel.

6.

Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?

Yes Yes

7.

Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffoldinq, lead shieldina)?

Yes D-109

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Sheet 2 of 5 Status:

Y-] N U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

AWC-32

8.

Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?

Comments Seismic Walkdown Team: D. Carter & J. Griffith - 7/17/2012 AWC 32 Evaluated by:

David Carter Date:

10/24/2012 James Griffith 10/24/2012 Photos MG_0188 MG 0189 D-110

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Sheet 3 of 5 Status: EY N

U Area Walk-By Checklist (AWC)

MG_0191 MG_0190 D-111

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Sheet 4 of 5 Status: F N U Area Walk-By Checklist (AWC)

MG_0192 MG_0194 MG_0195 D-112

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Sheet 5 of 5 Status: FT N U Area Walk-By Checklist (AWC)

MG 0196 D-113

12Q0108.30-R-0O1, Rev. 1 Correspondence No.: RS-12-167 Sheet 1 of 2 Status: [-* N. U Area Walk-By Checklist (AWC)

Location (Bid30, Elev, Room/Area):

AWC-33 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.

Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?

Yes

2.

Does anchorage of equipment in the area appear to be free of significant degraded conditions?

Yes

3.

Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,

condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?

Yes

4.

Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Yes

5.

Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?

Yes

6.

Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?

Yes

7.

Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Yes D-114

12Q0108.30-R-OO1, Rev. 1 Correspondence No.: RS-12-167 Sheet 2 of 2 Status: F N

U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

AWC-33 8.. Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?

Comments Seismic Walkdown Team: D. Carter & J. Griffith - 7/16/2012 AWC 33 Evaluated by:

David Carter Date:

10/24/2012 Jl James Griffith 10/24/2012 Photos D-115

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Sheet 1 of 3 Status:

Y N

U Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

AWC-34 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.

Additional space is provided at the end of this checklist for documenting other comments.

1.

Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?

Yes

2.

Does anchorage of equipment in the area appear to be free of significant degraded conditions?

Yes

3.

Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,

condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?

Yes

4.

Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Yes

5.

Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?

Threaded fire piping is well-supported and judged to be acceptable.

6.

Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?

Yes Yes

7.

Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Yes D-116

12Q0108.30-R-OO1, Rev. 1 Correspondence No.: RS-1 2-1 67 Sheet 2 of 3 Status: [-1 N U

Area Walk-By Checklist (AWC)

Location (Bldg, Elev, Room/Area):

AWC-34

8.

Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?

Comments Seismic Walkdown Team: J. Griffith & B. Weight - 10/15/2012 Evaluated by:

ý,

e James Griffith Date:

10/24/2012 Y

Bryan Weight 10/2412012 Photos D-117

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Sheet 3 of 3 Status: F N U Area Walk-By Checklist (AWC)

D-118

12Q0108.30-R-oo1, Rev. 1 Correspondence No.: RS-12-167 E

Plan for Future Seismic Walkdown of Inaccessible Equipment Thirteen (13) items could not be walked down during the 180-day period following the issuance of the 1 OCFR50.54(f) letter since they are located in areas that are normally inaccessible. The items will be walked down during a unit outage or time when the equipment is accessible, as appropriate. Table E-1 summarizes the reasons each item is inaccessible during normal plant operation and notes the Dresden Station Issue Report (IR) that has been written to track completion of the Seismic Walkdowns (and Area Walk-bys) for these items. It is noted that SSCs identified on Table E-1 require a complete inspection including, as applicable, internal inspections of electrical cabinets for other adverse seismic conditions, as required.

Certain cabinets require supplemental internal inspection for other adverse seismic conditions as summarized in Table E-2. Supplemental internal inspections of these cabinets are required due to clarifications provided by the NRC after the online seismic walkdowns were completed. These Supplemental inspections will be completed during a unit outage or another time when the equipment is accessible, as appropriate. It is noted that SSCs identified on Table E-1 do not appear on Table E-2.

E-1

12Qo108.30-R-OO1, Rev. I Correspondence No.: RS-12-167 Table E-1. Inaccessible and Deferred Equipment List Component Reason for Action Resolution Milestone ID Description Inaccessibility IDReque Status Completion REACTOR Located in D02-0202-.

RECIRCULATION/

drywell 0005AV20 Recirc Pump A 1403580 Open D2R23 Discharge Valve D02-0203-MAIN STEAM/

Located in 1403580 0001AV05 Isolation Valve drywell Open D2R23 D02-0203-ADS/ Target Rock Located in 1403580 0003AV26 Valve drywell Open D2R23 D02-0203-ADS/ Electromatic Located in 1403580 0003BV26 Relief Valve drywell Open D2R23 ADS/REACTOR Located in 0004AV26 OVERPRESSURE drywell 1403580 Open D2R23 RELIEF VALVE ISOLATION Located in D02-1301-CONDENSER/ Steam drywell 1403580 0004-V20 Return Line Isolation Open D2R23 Valve D02-1541---

CCSW/ CCSW Pump Located in torus

--A-FE "A" and "B" Discharge basement /

1403580 Open D2R23 Flow Element catwalk PRESSURE' Located in torus D02-1601-SUPPRESSION/

basement !

0021-V05 Drywell Purge Line catwalk Open D2R23 Valve PRESSURE Located in torus D02-1601-SUPPRESSION/

basement 1403580 0022-VO5 Drywell/Torus Purge catwalk Open D2R23 Line Valve PRESSURE Located in torus D02-1601-SUPPRESSION/

basement 1403580 0057-V20 Drywell/Torus Nitr.

catwalk Open D2R23 Makeup Valve E-2

12Q-108.30-R--oo, Rev. 1 Correspondence No.: RS-12-167 Component Reason for Action Resolution Milestone DescrptionRequest ID Description Inaccessibility ID (IR)

/ Status Completion RB EQUIPMENT Located in torus D02-2001-DRAIN/ Drywell basement /

0005-VO5 Equipment Drain Line catwalk 1403580 Open D2R23 Valve D02-2001 -

RB EQUIPMENT Located in torus 0105-V05 DRAIN/ Drywell Floor basement /

1403580 Open D2R23 Drain Line Valve catwalk D02-2301-HPCI/ HPCI Pump Located in X-1403580 0008-V20 Injection Line Valve AREA Open D2R23 E-3

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Table E-2. Supplemental Cabinet Internal Inspection List COMPONENT EQUIPMENT ACCESSIBLE IF NOT MILESTONE TRACKING STATUS/

ID DESCRIPTION CLASS (Y/N)

ACCESSIBLE, COMPLETION NUMBER (IR INSPECTION WHY?

No.)

RESULTS Energized D02-7828-7---

480V AC/ MCC (01) Motor 480VAC IR 1440224 M05 28-7 Control No cabinets.

D2R24 WO 631303 Open Centers Electrical safety hazard.

Tight 250V DC/ MCC (01) Motor thumbscrews.

D0 A

Bus #2A (ROB-Control Yes Will require 1Q2013 1427700 Open RB MCC #2)

Centers screwdriver to open.

Tight 250V DC/ MCC (01) Motor thumbscrews.

D05 Bus #2B (ROB-Control Yes Will require 1Q2013 1427700 Open RB MCC #2)

Centers screwdriver to open.

125V DC/ TB Tight D02-83125-2---

Battery Bus #2, (01) Motor thumbscrews.

P06 Feed to Main Control Yes Will require 1Q2013 1427700 Open Bus #2A-1 Centers screwdriver to open.

125V DC/ RB Tight D02-83125 ----- 125V DC (01) Motor thumbscrews.

Control Yes Will require 1Q2013 1427700 Open P06 D

b Centers screwdriver to Panel #2 open.

Table E-2 Page 1 of 8 E-4

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 COMPONENT EQUIPMENT ACCESSIBLE IF NOT MILESTONE TRACKING STATUS/

ID DESCRIPTION CLASS (Y/N)

ACCESSIBLE, COMPLETION NUMBER (IR INSPECTION WHY?

No.)

RESULTS Tools required.

Internal 24/48V DC/

(01) Motor inspection of D02-9802-A----

Cotr No mountings will 4Q2024 IR 1440223 Open P06 Distribution Contro require WO 99100514 Panel #2A Centers removal of cover over breakers Energized D02-7328 ------ 480V AC/

(02) Low 480VAC I R 1440224 S35Voltage No cabinets.

D2R24 WO 99053231 Open Switchgear Electrical safety hazard.

Energized D02-7329 ------ 480V AC/

(02) Low 480VAC IR 1440233 S35 Voltage No cabinets.

D2R25 WO #463253 Open Switchgear 29 Switchgear Electrical safety hazard.

Energized D02-6723 ------ 4160V AC/

(03) Medium 4160VAC IR 1440236 23 Voltage No cabinets.

D2R26 WO 1080302 Open S35 Switchgear 23 Switchgear Electrical safety hazard.

480V AC/

Energized 480V AC/

~480 VACIR1403 D02-7329 ------ Transformer 29, (04)

No cabinets.

D2R25 IR 1440233 T10 Feed to Transformers Eetcal WO #463253 Open Swithgea 29Electrical Switchgear 29 safety hazard.

250V DC/

Tight D02-83250-Breaker to TB (14) thumbscrews.

Distribution Yes Will require 1 Q2013 1427700 Open A01-M05 MCC #2 (ROB-Panels screwdriver to Battery #2) open.

Table E-2 Page 2 of 8 E-5

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 IF NOT TRACKING STATUS/

COMPONENT DESCRIPTION EQUIPMENT ACCESSIBLE ACCESSIBLE MILESTONE NUMBER (IR INSPECTION CLASS (YIN)

WHY?

No.)

RESULTS Tools required.

Internal 24/48V DC/

(14) inspection of D02-9802A-Breaker to Distribution No mountings will 4Q2024 IR 1440223Open A21-B11 Battery Charger require WO99100514

  1. 2A(+)

removal of cover over breakers Tools required.

Most sections can be easily accessed.

However the D00-83250-0...

250V DC/

(16) Battery lower left 1Q2013 B05 Battery Charger Chargers Partial section will Partial1427700 Open

  1. 2/3 and Inverters require tool to require tools to remove covers to inspect mounting points.

Tools required.

Most sections can be easily accessed.

However the D02-8300--2A-125V DC/

(16) Battery lower left 1Q2013

-B05 Battery Charger Chargers Partial setion1427700 Open

-B05

  1. 2A and Inverte'rs section will Partial require tools to remove covers to inspect mounting points.

Table E-2 Page 3 of 8 E-6

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 COMPONENT EQUIPMENT ACCESSIBLE IF NOT MILESTONE TRACKING STATUSI ID DESCRIPTION CLASS (Y/N)

ACCESSIBLE, COMPLETION NUMBER (IR INSPECTION WHY?

No.)

RESULTS Tools required.

Most sections can be easily accessed.

D02-8300--2---

125V DC/

(16) Battery However the D

05 Battery Charger Chargers Partial lower left 1PQ2013 1427700 Open B05

  1. 2adIvressection will Partial
  1. 2 and I nverters rqieolt require tools to remove covers to inspect mounting points.

CONTROL (20)

PANEL! D Instrumentati Relaying2and on and C033 Relaying and ontrol Yes N/A 1 Q2013 1427700 Open 0033 Metering Conel CabinetPanels and Cabinets (20)

CONTROL Instrumentati Thumbscrews DOO-2223-PANEL! DG on and may require a 0041 Excitation Control screwdriver to Cabinet Panels and open.

Cabinets (20)

CONTROL Instrumentati NO OTHER D02-0902-PANELS/

on and YES N/A 7/16/2012 N/A ADVERSE 0003 Control Panel Control SEISMIC 902-3 Panels and CONDITIONS Cabinets Table E-2 Page 4 of 8 E-7

12QO108.30-R-oo1, Rev. 1 Correspondence No.: RS-12-167 COMPONENT EQUIPMENT ACCESSIBLE MILESTONE TRACKING STATUS/

ID DESCRIPTION EQUIPMET AE ACCESSIBLE, COMPLETION NUMBER (IR INSPECTION CLASS (YIN)

WHY?

No.)

RESULTS (20)

CONTROL Instrumentati NO OTHER D02-0902-PANELS/

on and ADVERSE 0015 Control Panel Control SEISMIC 902-15 Panels and CONDITIONS Cabinets (20)

CONTROL Instrumentati NO OTHER D02-0902-PANELS/

on and ADVERSE 0036 Control Panel Control SEISMIC 902-36 Panels and CONDITIONS Cabinets (20)

CONTROL Instrumentati NO OTHER D02-0902-PANELS/

on and ADVERSE 0039 Control Panel Control SEISMIC 902-39 Panels and CONDITIONS Cabinets

.(20)

CONTROL Instrumentati D02-0902-PANELS/

on and 0041 CoNtL ontrol Yes N/A 1Q2013 1427700 Open 0041 Control Panel Control 902-41 Panels and Cabinets (20)

CONTROL Instrumentati D02-2252-PANEL!/DG on and 00102-252 PA L

M and CotrlYes N/A 1Q2013 1427700 Open 0010 Metering and Control Relay Cabinet Panels and Cabinets Table E-2 Page 5 of 8 E

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 IF NOT TRACKING STATUS /

COMPONENT EQUIPMENT ACCESSIBLE MILESTONE ID DESCRIPTION CLASS (Y/N)

ACCESSIBLE, COMPLETION NUMBER (IR INSPECTION WHY?

No.)

RESULTS (20)

CONTROL Instrumentati D02-2252-PANEL/ DG on and 0021 Excitation Control Yes N/A 1Q2013 1427700 Open Cabinet Panels and Cabinets (20)

This is a HPCI/ HPCI Instrumentati switch, not a D02-2380 ------

Turbine on and panel.

IR 1440221 PSH Pressure Control No Inspection will 1 Q2019 WO 654287 Open Switch Panels and require some Cabinets disassembly to inspect.

Tools required.

(20)

Internal DISTRIBUTION Instrumentati inspection of D02-7828-1-1--

PANELS/

on and mountings will N/A N/A NA P06 Distribution Control require Panel 28-1-1 Panels and removal of Cabinets cover over breakers Table E-2 Page 6 of 8 E-9

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 COMPONENT EQUIPMENT ACCESSIBLE IF NOT MILESTONE TRACKING STATUSI ID DESCRIPTION CLASS (Y/N)

ACCESSIBLE, COMPLETION NUMBER (IR INSPECTION WHY?

No.)

RESULTS Tools required.

There are two panels at this point. The larger of the two can be CONTROL (20) opened. The PANEL/ Unit 2 onrunt smaller 1Q2013 D02-DGCP Diesel Control Partial (mounted on Partial 1427700 Open Generator Panels and the right side)

Control Panel cannot be Cabinets opened without the use of tools. The panel label is located on the smaller panel.

D02-NGC CONTROL (20)

(This is PANEL/ Unit 2 Instrumentati on and assumed to be Neutral Control Yes N/A 1Q2013 1427700 Open EPN 2-6600-Grounding Panels and NGT)

Cabinet Canets Cabinets INSTRUMENT NO OTHER D02 -2202-RAC KS/

(18 )

ADVE RS E 0020 InSt Instruments YES N/A 7/16/2012 N/A SEISM 0070A Instrument SEISMIC on Racks Rack 2202-70A CONDITIONS INSTRUMENT (18)

D02-2202-RACKS/

(8 0023 InSt Instruments Yes N/A 1Q2013 1427700 Open 0073A Instrument on Racks Rack 2202-73A Table E-2 Page 7 of 8 E-1 0

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 COMPONENT EQUIPMENT ACCESSIBLE IF NOT MILESTONE TRACKING STATUSI ID DESCRIPTION CLASS (Y/N)

ACCESSIBLE, COMPLETION NUMBER (IR INSPECTION WHY?

No.)

RESULTS INSTRUMENT Thumbscrews D02-2252-RACKS/

(18)mareuea 0084 InSt Instruments Yes may rewdre a 1Q2013 1427700 Open 0084 Instrument onRcsscrewdriver to Rack 2252-84 open.

The item is a switch, not a D02-0302-CRD/ West (18) panel.

IR 1440222 0082A-LS Bank SDV Tank Instruments No Inspection will 3Q2014 WO 1114955 Open Level Switch on Racks require some disassembly to inspect.

Table E-2 Page 8 of 8 E-11

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 F

Peer Review Report This appendix includes the Peer Review Team's report, including the signed Peer Review Checklist for SWEL from Appendix F of the EPRI guidance document. (Ref. 1)

F-1

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Peer Review Report For Near Term Task Force (NTTF) Recommendation 2.3 Seismic Walkdown Inspection of Dresden Unit 2 October 22, 2012 Prepared by Peer Reviewers Bruce M. Lory (Team Leader)

Walter Diordievic Tribhawan K. Ram Bruce M. Lory Peer Review Team Leader Certification Signature Date 10/22/12 Sheet 1 of 13 F-2

12Q0108.30-R-OO1, Rev. 1 Correspondence No.: RS-12-167 IIntroduction 1.1 OVERVIEW This report documents the independent peer review for the Near Term Task Force

'(NTTF) Recommendation 2.3 Seismic Walkdowns performed by Stevenson &

Associates (S&A) for Unit 2 of Dresden Generating Station. The peer review addresses the following activities:

Review of the selection of the structures, systems, and components, (SSCs) that are included in the Seismic Walkdown Equipment List (SWEL)

Review of a sample of the checklists prepared for the Seismic Walkdowns & Walk-Bys Review of any licensing basis evaluations Review of the decisions for entering the potentially adverse conditions in to the plant's Corrective Action Plan (CAP)

Review of the final submittal report 1.2 PEER REVIEWERS The peer reviewers for Dresden Unit 2 are Messrs. Walter Djordjevic, Bruce M. Lory, and Tribhawan K. Ram, all of S&A. Mr. Lory is designated the Peer Review Team Leader. Mr. Djordjevic served as Peer Review Team Leader for SWEL development.

Other than a peer review of "in progress" seismic walkdown inspections, none of the aforementioned engineers were directly involved in the seismic walkdown inspection of equipment so that they could maintain their independence from the project. Mr.

Djordjevic is an advanced degree structural engineer and has over thirty years of nuclear seismic experience and has been trained as a Seismic Capability Engineer (EPRI SQUG training), EPRI IPEEE Add-on, Seismic Fragility and Seismic Walkdown Engineer (SWE) training. Mr. Lory is a mechanical engineer with 33 years of experience, has been trained as a Seismic Capability Engineer (EPRI SQUG training), is instructor of the Fundamentals of Equipment Seismic Qualification training course for EPRI, and is the co-instructor of the Fukushima Seismic Walkdown training course in response to NTTF 2.3. Mr. Ram is an advanced degree nuclear engineer with over 25 years of nuclear power plant experience. Mr. Lory led the seismic peer, review activities and Mr. Djordjevic led the SWEL selection peer review. Resumes for the peer reviewers are included in Appendix A of the report.

1.3 SWEL DEVELOPMENT The SWEL development was performed by Mr. Tony Perez of S&A. The peer review of the SWEL development was concurrent with the SWEL development and any revisions to the SWEL after initial plant acceptance were peer reviewed before approval. The completed SWEL Peer Review Checklist is found in Attachment 1. The discussion for the SWEL development peer review is found in Section 2.

Sheet 2 of 13 F-3

12QO108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 1.4 SEISMIC WALKDOWN INSPECTION The peer review of the seismic walkdown inspection started on July 16, 2012 with a peer check of the actual walkdowns Dresden Unit 2 by Mr. Bruce Lory. Mr. Lory joined the walkdown team for a portion of the day's planned walkdowns to observe the conduct of walkdowns and adherence to the Seismic Walkdown Guidance (SWG)l. An interview was conducted by Messrs. Djordjevic and Lory with the SWE inspection team on September 7, 2012 after review of a sample of the Unit 1 Seismic Walkdown Checklists (SWC) and Area Walk-By Checklists (AWC) to ascertain the quality and procedural compliance with the SWG. The discussion of the sample SWC and AWC is provided in Section 3.

Seismic Walkdown Guidance For Resolution of Fukushima Near-Term Task Force Recommendation 2.3: Seismic, EPRI Report 1025286, June 2012.

Sheet 3 of 13 F-4

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 2Peer Review - Selection of SSCs 2.1 PEER REVIEW ACTIVITY - SELECTION OF SSCS The guidance in EPRI Technical Report 1025286, Seismic Walkdown Guidance for Resolution of Fukushima Near-Term Task Force Recommendation 2.3.- Seismic, dated June 2012 {Reference 1}, Section 3: Selection of SSCs was used as the basis for this review.

This peer review was based on reviews of the following documents:

UFSAR chapters 6 and 9 SWEL 1 List P&IDs M-31 and M-50: Fuel Pool Cooling System This peer review was based on interviews with the following individual(s) who was (were) directly responsible for development of the SWEL:

Tony Perez This peer review utilized the checklist shown in Reference 1 Appendix F: Checklist for Peer Review of SSC Selection.

2.2 UNIT 2 SWEL 1 DEVELOPMENT For SWEL 1 development, the following actions were completed in the peer review process:

1.

Verification that the SSCs selected represented a diverse sample of the equipment required to perform the following five safety functions:

A.

Reactor Reactivity Control (RRC)

B.

Reactor Coolant Pressure Control (RCPC)

C.

Reactor Coolant Inventory Control (RCIC)

D.

Decay Heat Removal (DHR)

E.

Containment Function (CF)

This peer review determined that the SSCs selected for the seismic walkdowns represent a diverse sample of equipment required to perform the five safety functions. This conclusion was based on a review of UFSAR chapters 6 and 9, and SWEL 1 which determined that all five safety functions (RRC, RCPC, RCIC, DHR, and CF) are adequately represented.

Sheet 4 of 13 F-5

12Q.108.30-R-;

O1, Rev. 1 Correspondence No.: RS-12-167

2.

Verification that the SSCs selected include an appropriate representation of items having the following sample selection attributes:

A.

Various types of systems B.

Major new and replacement equipment C.

Various types of equipment D.

Various environments E.

Equipment enhanced based on the findings of the IPEEE F.

Risk insight consideration This peer review determined that the SSCs selected for the Seismic walkdowns include a sample of items that represent each attribute/consideration identified above. The justification for this conclusion is: a) Based on a review of UFSAR chapters referenced above and the SWEL 1 list, it was determined that appropriate variety.of equipment and systems are represented (e.g., EDG, EDG Fuel Oil Transfer, EDG Cooling Water, LPCI, HPCI, Batteries, Battery Chargers, Low and Med Vol Switchgear and MCCs); b) The "New or Replace" equipment are indicated as such; c) A variety of location environments are included: e.g., MCCs (TB and RB), Pumps (TB and RB), Tanks and Heat Exchangers (TB and RB), and Valves (RB @ EL 476.5, 517.5, and 570); d) The IPEEE Enhancement related equipement is indicated as such; and e) The risk quantification has been included in the "Comments" column.

Note: Because of accessibility reasons, some equipment has appropriately been deferred to Outage.

2.3 UNIT 2 SWEL 2 DEVELOPMENT For SWEL 2 development, the following actions were completed in the peer review process:

1.

Verification that SFP related items were considered and appropriately added to SWEL 2.

This peer review determined that there were no spent fuel pool cooling system Seismic Category 1 items. This determination is based on a review of FSAR chapter 9 and Fuel Pool Cooling System P&lDs M-31 and M-50.

2.

Verification that appropriate justification was documented for spent fuel pool related items that were not added to SWEL 2.

This peer review determined that an appropriate level of justification was documented for having no items on SWEL 2. The justification for not including any Seismic Category I Structure has appropriately been documented in the interim Sheet 5 of 13 F-6

12QO1O8.3O-R-OO1, Rev. 1 Correspondence No.: RS-12-167 report. There are no rapid drain down related components in SWEL 2. Appropriate justification for this item is included in the interim report as well.

2.4 PEER REVIEW FINDINGS - SELECTION OF SSCs This peer review found that the process for selection for SWEL 2 SSCs was consistent with the process outlined in Reference 1 Section 3: Selection of SSCs..

The peer review checklist for the SWEL is contained in Attachment 1 of this document.

This peer review resulted in no additional findings.

2.5 RESOLUTION OF PEER REVIEW COMMENTS - SELECTION OF SSCs All comments initiated through the peer review process were minor and were resolved.

There are no outstanding issues that require resolution.

2.6 CONCLUSION

OF PEER REVIEW - SELECTION OF SSCS This peer review concludes that the process for selecting SSCs to be included on the seismic walkdown equipment list appropriately followed the process outlined in Reference 1, Section 3: Selection of SSCs. It is further concluded that the SWEL sufficiently represents a broad population of plant Seismic Category 1 equipment and systems to meet the objectives of the NRC 50.54(f) Letter.

Sheet 6 of 13 F-7

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 3

1Review of Sample Seismic Walkdown & Area Walk-Bys Checklists 3.1 OVERVIEW A peer review of the SWCs and AWCs was performed along with an interview which was conducted by Messrs. Djordjevic and Lory with the SWE inspection team in accordance with the SWG requirements. The SWE trained walkdown engineers were Messrs. Jim Griffith and David Carter and Mr. B. Weight of Exelon.

3.2 SAMPLE CHECKLISTS Table 3-1 lists the SWC and AWC samples which represent 17% of the SWC and 24%

of the AWC. The sample includes the equipment inspected during the peer review and other equipment items from other classes to introduce diversity to the sampling

-procedure.

Table 3-1: Table of SWC and AWC Samples from Seismic Walkdown Inspection for Unit 2 No.

Equipment Walkdown Item Location Observations (GIP)

Class D02-0902-0003 20 Control Panel 902-3 Control None noted Room, El 534 ft D02-0902-0015 20 Control Panel 902-15 Control Loose wireway in back Room, El panel.

IR 1389213 534 ft created.

D02-83250-B04 15 250VDC Battery #2 Turbine Bldg, None noted El 549 ft D02-8300-BC-15 125VDC Battery #2 Turbine Bldg, None noted B04 Feed to TB Battery El 549 ft Bus #2 D02-0902-0041 20 Control Panel 902-41 Turbine Bldg, None noted El 517 ft D02-0902-0039 20 Control Panel 902-39 Turbine Bldg, None noted El 517 ft Sheet 7 of 13 F-8

12Qo108.30-R-OO1, Rev. I Correspondence No.: RS-12-167 No.

Equipment Walkdown Item Location Observations (GIP)

Class D00-5741-7 Control Rm Turbine Bldg, None noted 0048AV72 Ventilation/CCSW El 534 ft Cooling Supply Valve DOO-9400-9 Control Rm Turbine Bldg, None noted 0104AF05 Ventilation/AFU El 534 ft Booster Fan D00-9400-11 Control Rm Turbine Bldg, None noted 0101-FIG Ventilation /AFU El 534 ft Heater D02-6723-S35 3

4160 VAC Turbine Bldg, None noted Switchgear 23 El 534 ft D02-0902-0036 20 Control Panel 902-36 N/A, 534 ft Several loose bolts with missing nuts in the conduit clamps above the 902-36 back panel in the main control room. IR 1389209 created.

D02-8300-2A-16 125VDC Battery Turbine Bldg, None noted B05 Charger #2A El 549 ft D02-8300 16 125VDC Battery Turbine Bldg, None noted B05 Charger #2 El 549 ft D02-83125 1

125VDC TB Battery Turbine Bldg, None noted P06 El 549 ft D02-9802A-14 24/48VDC Breaker to Turbine Bldg, None noted A21-B1 1 Battery Charger #2A El 549 ft D02-9802A-1 24/48VDC Turbine Bldg, None noted AP06 Distribution Panel El 549 ft

  1. 2A D00-83250 16 250VDC Battery Turbine Bldg, Two lights above U2 and B05 Charger #2/3 El 549 ft U2/3 25OVDC battery chargers with open S-hooks. IR 1389329 created.

D02-83250-14 250VDC Breaker to Turbine Bldg, Portable eyewash station A01-M05 TB MCC #2 El 549 ft not secured and did not meet distance requirements of DAP 03-Sheet 8 of 13 F-9

12Qo108.30-R-eo1, Rev.

1 Correspondence No.: RS-12-167 No.

Equipment Walkdown Item Location Observations (GIP)

Class 20, "Restraint of Portable Equipment."

IR 1389735 created.

D02-2202-18 Instrument Rack Turbine Bldg, None noted 0070A 2202-70A El 517 ft Area (AWC) 250VDC Battery Rm Turbine Bldg, None noted El 549 ft Area (AWC) 125VDC Battery Rm Turbine Bldg, None noted El 549 ft Area (AWC)

Aux. Elect Equip Rm None noted Area (AWC)

Control Room - Near Control Cart staged for Cabinets 3, 15, & 36 Room, El maintenance work in 534 ft control room back panel area did not meet distance requirements of DAP 03-20, "Restraint of Portable Equipment." IR 1389231 created.

Area (AWC)

Cribhouse (vicinity of Cribhouse, El None noted 2/3 EDG Cooling 490 ft Water Pump)

Area (AWC) 125VDC Battery Rm Turbine Bldg, None noted El 549 ft Area (AWC)

Ventilation Rm Turbine Bldg, None noted El 534 ft Area (AWC)

Swgr 23 Area Turbine Bldg, None noted El 534 ft 3.3 EVALUATION OF FINDINGS There were no findings of seismic significance. The scaffolding and seismic housekeeping procedures were reviewed by the SWEs in order to gain a full understanding of the plant practices. No significant concerns were noted in Unit 2 with Sheet 9 of 13 F-1 0

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 regard to scaffold erection. The scaffolds were properly tied off and braced, and properly tagged with respect to the procedure.

With regard to seismic housekeeping, there were instances found of open S-hooks in the plant. Generally, if they were found to not to contribute to a credible seismic interaction they were adjudged acceptable and not dispositioned to an IR. Similarly, if an item posed a potential proximity hazard to a vital component and it was removed "on the spot" in accordance with the housekeeping procedure, then it was not dispositioned to an IR. However, in all instances the Seismic Walkdown Checklist (SWC) documented the details of the occurrence, the action taken (if any) and the conclusion rendered by the SWE inspectors. Importantly, if the situation warranted a correction then an IR was specifically generated for that component or area in the case of area walk-bys.

The peer review of the SWCs included a recommendation for panels/cabinets which could be opened and inspected for loose or missing component mounting hardware. It was recommended that a comment be put under question 11 to denote what were the results of the internal inspection. If no loose or missing mounting hardware was found or if mounting hardware was found loose/missing, a sentence to that affect should be made in the SWC.

Sheet 10 of 13 F-11

1200108.30-R-OO1, Rev. 1 Correspondence No.: RS-12-167 4Review of Licensing Basis Assessments 4.1 OVERVIEW Because none of the issues identified during the Seismic Walkdowns or Area Walk-Bys were determined to be "Potentially Adverse Seismic Conditions, no Licensing Basis Evaluations were performed.

Sheet 11 of 13 F-1 2

12Q0108.30-R-O01, Rev. 1 Correspondence No.: RS-12-167 Review Final Submittal Report & Sign-off 5

The entire final submittal report has been reviewed by Messrs. W. Djordjevic and B. Lory and found to meet the requirements of the EPRI 1025286 - Seismic Walkdown Guidance (Ref. 1).

Sheet 12 of 13 F-13

12Qo108.30-R-eo.

, Rev. 1 Correspondence No.: RS-12-167 6References

1) EPRI Technical Report 1025286, Seismic Walkdown Guidance for Resolution of Fukushima Near-Term Task Force Recommendation 2.3: Seismic, dated June 2012 See Section 9 of report for additional references.

Sheet 13 of 13 F-14

- Peer Review Checklist for SWEL

.12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Sheet 1 of 2 Peer Review Checklist for SWEL Instructions for Completing Checklist This peer review checklist may be used to document the review of the Seismic Walkdown Equipment List (SWEL) in accordance with Section 6 Peer Review. The space below each question in this checklist should be used to describe any findings identified during the peer review process and how the SWEL may have changed to address those findings. Additional space is provided at the end of this checklist for documenting other comments.

1. Were the five safety functions adequately represented in the SWEL 1 selection?

Y[

NEI Appropriate equipment has been included to maintain the five safety functions: RPC, DHR, RCIC, RCPC, and CF

2. Does SWEL 1 include an appropriate representation of items having the following sample selection attributes:
a. Various types of systems?

Various system types (e.g., HPCI, LPCI, ADS/SRV, CRD, DG, RBCCW, SW, and support systems such as MCCs and distribution panels) have been included.

b. Major new and replacement equipment?

"New or Replace" equipment (from the mahor MOD list) are included in the list.

c. Various types of equipment?

The equipment represents all required 21 types except 13 and 19. The screenings

  1. 1, #2, and #3 resulted in no equipment in the latter two categories.
d. Various environments?

Appropriate environments (e. g., REACTOR and TURBINE buildings) have been included.

e. Equipment enhanced based on the findings of the IPEEE (or equivalent) program?

Included as indicated in the column, "IPEEE Enhancement."

YZ N[-

Y0NNE YZ NEI Y[RN[:

Y[RNEI F-1 5

- Peer Review Checklist for SWEL 12-o108.30-R-oo1, Rev. 1 Correspondence No.: RS-12-167 Sheet 2 of 2 Peer Review Checklist for SWEL

f. Were risk insights considered in the development of SWEL 1?

Riso quantifications provided in the [CommentsLcolumn YZ NM

3. For SWEL 2:
a. Were spent fuel pool related items considered, and if applicable included in SWEL 2?

There is no equipment on SWEL2.

b. Was an appropriate justification documented for spent fuel pool related items not included in SWEL 2?

Provided in the Submittal Report YE N[:

YZ NEI

4. Provide any other comments related to the peer review of the SWELs.

All items on SWEL 1 have a Seismic Licensing basis.

5. Have all peer review comments been adequately addressed in the final SWEL?

YN NEI

'7-K Cca, Peer Reviewer #1: TO3 Ram Date: LY2EL/12 Peer Reviewer #2: Walter D[Drdevic Date: D12[112 F-1 6

12Q0108.30-R-001, Rev. I Correspondence No.: RS-12-167 G

IPEEE Vulnerability Status Table G-1 lists the plant improvements, the IPEEE/SQUG proposed resolution, the actual resolution and resolution date.

G-1

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Table G-1. IPEEE Improvements Status Equipment ID Description of Condition/

IPEEE Report Proposed Actual Resolution of Condition Resolution Vulnerability Resolution of Condition Date Hydraulic Control

1) No seismic capacity
1) No actions required. Upon
1) Condition resolved in 1)6/1997 Unit based on earthquake further review, Hydraulic original IPEEE report.

D02-0305 ------ experience or generic Control Unit consists of H20 seismic testing ruggedness accumulator and valves which D03-0305 ------ data is available for class 0 are in the earthquake

2) The worst case gas bottle 2)1/4/2000 H20 equipment.

experience and generic seismic with a single chain has been

2) Nearby gas bottles are testing ruggedness data. Rack verified for adequacy based restrained by only a single load path and anchorage are on seismic testing (Ref. NDIT
chain, separately analyzed and are No. SECDR- 00-001).

acceptable. CRD piping and scram header very well seismically supported.

RESOLUTION #11

2) Gas bottles need a second chain near the bottom.

RESOLUTION #1 Motor Control MCCs are not anchored to Provide positive anchorage Condition has been deleted 3/31/2000 Centers the equipment pad.

system.

from the Program. The MCCs D02-7820 RESOLUTION #9 power the Refuse Pumps.

M05 The Refuse Pumps are not being credited for Isolation D03-7830 Condenser makeup for the M05 loss of dam failure scenario; therefore, the MCCs are not required for safe shutdown or included in the SPEL.

Table G-1 Page 1 of 33 G-2

12Qo108.30-R-eo1, Rev. 1 Correspondence No.: RS-12-167 Equipment ID Description of Condition/

IPEEE Report Proposed Actual Resolution of Condition Resolution Vulnerability Resolution of Condition Date Bus and Panel

1) Locker/storage cabinet
1) Positively anchor locker or'
1) Locker/storage cabinet
1) 5/1996 D02-8302A ----- located next to bus on rear re-locate it.

relocated. Condition M05 side.-

RESOLUTION #5 resolved in original IPEEE report.

2) Seismic demand exceeds
2) Develop realistic, median 2) capacity.

amplified floor spectra to 10130/2003 potentially reduce seismic

2) Realistic median centered 13 demand to an acceptable level, response spectra were not useful. Modification added RESOLUTION #11 bracing to improve capacity.

Ref. EC 341875 & WO 558649 Motor Control Adjacent MCC 35-1 is Anchorage modification needed.

Anchorage has been 5/30/2003 Center inadequately anchored (only RESOLUTION #9 modified. Ref. EC 7583 & WO D03-7839-2----

tack welded in rear).

99103698 M05 Bus and Panel Seismic demand exceeds Develop realistic, median Realistic median centered 10/30/2003 D02-83125 ----- capacity.

amplified floor spectra to response spectra were not P06 potentially reduce seismic useful. Modification added demand to an acceptable level, bracing to improve capacity.

RESOLUTION #11 Ref. EC 341875 &

WO 558649 Bus and Panel

1) Seismic demand exceeds 1&2) Develop realistic, median 1&2) Realistic median Unit 2 D03-8303A capacity.

amplified floor spectra to centered response spectra 10/30/2003 M05

2) Embedded angle pullout potentially reduce seismic were not useful. Modification Unit 3 D03-8303B ----- capacity is insufficient to demand to an acceptable level, added bracing to improve 11/5/2003 M05 hold down the cabinet RESOLUTION #11 capacity. Ref. EC 341875 &

D03-83125 ----- during the event of SSE.

WO 558649 (Unit 2)

P06 EC 341876 &

D02-8302B-.....-WO 558699 (Unit 3)

M05 WO_558699

_(Unit_3)

Table G-1 Page 2 of 33 G-3

12QO108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Equipment ID Description of Condition/

IPEEE Report Proposed Actual Resolution of Condition Resolution Vulnerability Resolution of Condition Date Switchgear Spare Breakers are too Relocate spare breakers A walkdown confirmed that 1/7/2003 D02-67241---S35 close RESOLUTION #5 the spare breakers have been relocated.

Motor Control Overhead unanchored Positively secure emergency A walkdown confirmed that 5/6/1999 Center emergency light # 251C

light, the emergency light has been D02-7829-8 ----

(battery powered).

RESOLUTION #3 positively secured.

M05 Panel A 6' long (tall) cable tray Determine whether or not Condition resolved in original 4/1996 D02-8302B-1---

raceway system hanger panel(s) contains essential IPEEE report. Panels do not P06 which is rod hung and relays. If it does, brace contain essential relays; D02-83125-1---

laterally unbraced may raceway to preclude impact therefore, no actions are P06 sufficiently displace to potential.

required to preclude ihnpact impact the Panel.

RESOLUTION #6 potential.

Panel

1) Lights overhead have
1) Close Open S-Hooks.
1) Condition resolved in
1) 5/1996 D03-8303A1 open hooks.

RESOLUTION #2 original IPEEE report. The S-P06

2) D.G. stack rises adjacent
2) Evaluate seismic structural hooks have been closed.

to panel and is a potential integrity of exhaust stack interaction hazard.

2) The seismic structural
2) 3/26/1998 RESOLUTION #6.

integrity is acceptable based on evaluation (Ref. SEWS, Rev. 1).

Table G-1 Page 3 of 33 G-4

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Equipment ID Description of Condition/

IPEEE Report Proposed Actual Resolution of Condition Resolution Vulnerability Resolution of Condition -

Date Motor Control

1) Nearby gas bottles
1) Gas bottles need a second
1) The worst case gas bottle 1)1/4/2000 Center secured by only 1 chain, chain near the bottom.

with a single chain has been D02-7829-2----

2) Lights overhead have RESOLUTION #1 verified for adequacy based M05 on seismic testing (Ref. NDIT open hooks.
2) Close open S-hooks.

No. SEC-DR-00-001).

3) Unrestrained flammable RESOLUTION #2 storage cabinet adjacent to
3) Positively anchor cabinet or
2) The S-hooks have been
2) 5/1996 re-locate, closed. Condition resolved in RESOLUTION #5 original IPEEE report.
3) The cabinet has been
3) 5/1996 relocated. Condition resolved in original IPEEE report.

Panel

1) Lights overhead have
1) Close open S-Hooks.
1) The S-hooks have been
1) 5/1996 D03-8303B1 ----

open hooks.

RESOLUTION #2 closed. Condition resolved in P06

2) Emergency light #329
2) Positively secure emergency original IPEEE report.

D03-9802-A ---- (battery powered) not light.

2) A walkdown has confirmed
2) 5/6/1999 P06 secured.

D03-9802-B ----

RESOLUTION #3 that the light has been P06 positively secured.

Panel Lights overhead have open Close open S-Hooks.

The S-hooks have been 5/1996 D03-8303A1-1--

hooks.

RESOLUTION #2 closed. Condition resolved in P06 original IPEEE report.

D03-83125-3---

P06 Table G-1 Page 4 of 33 G-5

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Equipment ID Description of Condition/

IPEEE Report Proposed Actual Resolution of Condition Resolution Vulnerability Resolution of Condition Date Motor Control Lights overhead have open Close open S-Hooks.

The S-hooks have been 5/1996 Center and Pane.l hooks.

RESOLUTION #2 closed. Condition resolved in D02-7828-3 ----

original IPEEE report.

M05 D02-7829-4 ----

M05 D03-7838-2 ----

M05 D03-7838-3 ----

M05 D02-2202-0073AP05 D02-2202-0073BP05 D03-2203-0006 D02-2252-0084-P05 Table G-1 Page 5 of 33 G-6

1200108.30-R-0o1, Rev. 1 Correspondence No.: RS-12-167 Equipment ID Description of Condition/

IPEEE Report Proposed Actual Resolution of Condition Resolution Vulnerability Resolution of Condition Date Motor Control Nearby gas bottles only Gas bottles need a second

1) The worst case gas bottle
1) 1/4/2000 Center and Panel restrained by a single chain chain near the bottom.

with a single chain has been D02-7828-7 RESOLUTION #1 verified for adequacy based M05 on seismic testing (Ref. NDIT D03-7838-1 -

No. SEC-DR-00-001).

P06 D02-9205-A-....

V05

2) The NDIT identified the D02-9205-B-...

gas bottle by MCC D03-V05 7838-1-1 as much smaller D02-9206-A ----

and not represented by the V05 test gas bottle; therefore, D02-9206-B ----

required a lower support and V05 chain. A walkdown confirmed D03-9206-A ----

that the gas bottle has been V05 relocated away from the D03-9206-B ----

MCC.

V05 Motor Control

1) Nearby gas bottles only
1) Gas bottles need a second
1) The worst case gas bottle 1)1/4/2000 Center and Panel restrained by a single chain, chain near the bottom.

with a single chain has been D02-83250 ----- 2) Anchorage capacity less RESOLUTION #1 verified for adequacy based M05 than demand 2median on seismic testing (Ref. NDIT M0 ta dmad2)

Develop realistic, mein No. SEC-DR-00-001).

amplified floor spectra to potentially reduce seismic

2) Per Attachment 2 to
2) 3/30/2000 demand to an acceptable level, response to NRC RAI, Dresden Letter PSLTR #00-RESOLUTION #11 0068, no actions are required.

Table G-1 Page 6 of 33 G-7

12Qo108.30-R-eo1, Rev. 1 Correspondence No.: RS-12-167 Equipment ID Description of Condition/

IPEEE Report Proposed Actual Resolution of Condition Resolution Vulnerability Resolution of Condition Date Motor Control

1) Nearby gas bottles only
1) Gas bottles need a second
1) The worst case gas bottle.

1)1/4/2000 Center and Panel restrained by a single chain, chain near the bottom.

with a single chain has been D02-9802-A----

2) Anchorage capacity less RESOLUTION #1 verified for adequacy based P06 than demand on seismic testing (Ref. NDIT
2) Develop realistic, median No. SEC-DR-00-001) amplified floor spectra to potentially reduce seismic
2) Per Attachment 2 to
2) 3/30/2000 demand to an acceptable level, response to NRC RAI, Dresden Letter PSLTR #00-RESOLUTION #11 0068, no actions are required.

Panel The internal cable tray Restrain cross-members by Proposed modifications to Unit 2 D02-0902-0015 raceway system hanger is "tying" them to front and back restrain cross-members have 10/29/2001 D02-0902-0017 rod hung and transversely panels. This will preclude been completed.

Unit 3 D02-0902-0019 unrestrained. It can impact hazard as well as Modification EC 7526 &

10/22/2002 D02-0902-0036 displace sufficiently to connecting front and rear WO 558649 (Unit 2) and D03-0903-0015 impact the Panel which has portions of the main control EC 7527 &

D03-0903-0017 only 1" clearance from the board increasing anchorage WO 558699 (Unit 3)

D03-0903-0019 end of the cross-member.

capacity seismic margin. Crimp D03-0903-0036 Cabinets do contain light hooks.

D02-0902-0004 essential relays.

RESOLUTION #6 D03-0903-0004 Table G-1 Page 7 of 33 G-8

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Equipment ID Description of Condition/

IPEEE Report Proposed Actual Resolution of Condition Resolution Vulnerability Resolution of Condition Date Panel

1) Located adjacent to a
1) Insert neoprene or similar
1) Neoprene padding has 1)

D03-0903-0046 conduit pull-box and it is an soft material between pull-box been installed between the 12/17/1999 impact hazard.

and cabinet to reduce pull-box and cabinet in

2) Adjacent tool box significance of impact.

accordance with WR adjudged a hazard.

RESOLUTION #6 990056423 to reduce

2) Re-locate storage tool box.

significance of impact.

2) The tool box has been
2) 5/1996 RESOLUTION #5 relocated. Condition resolved in original IPEEE report.

Panel and Adjacent emergency lights Positively restrain emergency A walkdown has confirmed 5/6/1999 Transformer

  1. 293, #299, #220, and #313
lights, that the lights have been D02-2202-0008 (battery powered) are RESOLUTION #3 positively restrained. Light D02-7229 ------ missing straps or are
  1. 299 should be #229.

T10 1 unrestrained.

D02-0902-0041 Battery Charger Overhead emergency light Positively restrain emergency A walkdown has confirmed 5/6/1999 D03-9802-

  1. 329 (battery powered) is
light, that the Emergency light 3BNEGBO5 shelf mounted and RESOLUTION #3
  1. 329 has been positively D03-9802-unrestrained, restrained.

3BPOSBO5 IIIII

'Actual equipment number is D02-7329 ------

T10 Table G-1 Page 8 of 33 G-9

12Q0108.30-R-001, Rev. I Correspondence No.: RS-12-167 Equipment ID Description of Condition/

IPEEE Report Proposed Actual Resolution of Condition Resolution Vulnerability Resolution of Condition Date Switchgear

1) Overhead trolley hoist is
1) Use a clamp or similar
1) Condition for 2-7328
1) 4/1996 for D02-7328 ------ an impact hazard and needs device to prevent the hoist from resolved in original IPEEE 2-7328.

S35 to be parked.

rolling freely.

report based on confirmation D02-7329 ------ 2) Emergency light #299 RESOLUTION #4 of no essential relays in the S35(battery powered) not 2)switchgear.

No actions are restrained,

2) Secure emergency light.

required for 2-7329 as the RESOLUTION #3 hoist is a tool that has an

3) Anchorage capacity less annual preventative than demand
3) Develop realistic, median annal preventive amplified floor spectra to maintenancintion (P potentially reduce seismic 184453-01) controlled by demand to an acceptable level.

Procedure MA-DR-MM 58001 that checks the locking RESOLUTION #11 device..

2) The light has been
2) 5/6/1999 positively restrained. The correct light number is 229.

3)

3) Per Attachment 2 to 03/30/2000 response to NRC RAI, Dresden Letter PSLTR #00-0068, no actions are required.

Switchgear Overhead trolley hoist, open

1) Use a clamp or similar
1) Condition resolved in
1) 4/1996 D03-7338 ------ S-hook on overhead device to prevent the hoist from original IPEEE report. No S35 florescent light and racking rolling freely.

actions are required since it crank hanging between RESOLUTION #4 has been verified that there breaker and transformer are are no essential relays within all impact hazards.

2) Close open S-Hooks.

the switchgear.

RESOLUTION #2

2) The S-Hooks have been 2)5/96
3) Secure or re-locate crank.

closed. Condition resolved in RESOLUTION #5 original IPEEE report.

Table G-1 Page 9 of 33 G-10

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Equipment ID Description of Condition/

IPEEE Report Proposed Actual Resolution of Condition Resolution Vulnerability Resolution of Condition Date Switchgear Overhead trolley hoist, open

1) Use a clamp or similar
1) Condition resolved in
1) 4/1996 D03-7339 ------ S-hook on overhead device to prevent the hoist from original IPEEE report. No S35 florescent light, racking rolling freely.

actions are required since it crank hanging between RESOLUTION #4 has been verified that there breaker and transformer and are no essential relays within adjacent unanchored 4KV

2) Close open S-Hooks.

the switchgear.

gear box locker are all RESOLUTION #2 impact hazards.

3) Secure or re-locate crank.
2) The S-Hooks have been
2) 5/1996 RESOLUTION #5 closed. Condition resolved in original IPEEE report.
4) Anchor or re-locate locker.

RESOLUTION #5

3) The racking crank has 3)08/1 2/1 995 been relocated in accordance with Mod E12-3-95-221 &

WO 95054280. Condition resolved in original IPEEE report.

4)

4) The locker has been 08/11/1995 relocated in accordance with E12-3-95-220 & WO 95054281. Condition resolved in original IPEEE report.

Table G-1 Page 10 of 33 G-11

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Equipment ID Description of Condition/

IPEEE Report Proposed Actual Resolution of Condition Resolution Vulnerability Resolution of Condition Date Switchgear Safety equipment locker

1) Anchor or re-locate locker.
1) Equipment locker has
1) 5/1996 D03-6734 ------ adjacent to cubicle, spare RESOLUTION #5 been relocated. Condition S35 breakers marginally chained resolved in original IPEEE to wall, and additional
2) Secure or re-locate spare report.

unanchored spare cubicles

2) Spare breakers have been 2)5/1996 5' away from line-up are RESOLUTION #5 relocated. Condition resolved interaction hazards.

in original IPEEE report.

Panel

1) Panel is not bolted to
1) Determine whether or not
1) Panels D02-2202-70A
1) Unit 2 D03-2202-0070A adjacent panel panel(s) contains essential and D03-2203-70A are bolted 10/29/2001.

D03-2203-0070B

2) Panel D03-0903-0052 is relays. If they do, connect to adjacent Panels D02-Unit 3 D02-0902-0033 missing a bolt and is (bolt) panels together to 2202-70B and D03-2203-9/26/2000 D02-2203-0070A adjacent to Safe Shutdown preclude impact potential.

70B, respectively. Panel D03-D02-2202-0070B Panels D03-2203-70A & B RESOLUTION #8 2203-70B is also bolted to D02-0902-0039 the adjacent panel 903-27 D02-0902-0047

2) Repair/Replace Bolt (Ref. ECN No. 12- 00854E).

D03-0903-0047 RESOLUTION #14 The remaining panels have D03-0903-0032 been bolted to adjacent panels by modification EC 7528 & WO 99134628 (Unit

2) and EC 7529 & WO 99134630 (Unit 3).
2) No actions are required. A subsequent walkdown has
2) 5/6/1999 verified that all bolts are tightened in place.

Table G-1 Page 11 of 33 G-12

12Q-108.30-R-OO1, Rev. 1 Correspondence No.: RS-12-167 Equipment ID Description of Condition/

IPEEE Report Proposed Actual Resolution of Condition Resolution Vulnerability Resolution of Condition Date Panel Panel not bolted to adjacent Determine whether or not The "low boy" console 10/13/2002 D02-0902-0046 "low boy" console.

panel(s) contains essential (economic generation control relays. If they do, connect (EGC) panel) has been (bolt) panels together to retired and removed via preclude impact potential.

modification EC 7998 & WO RESOLUTION #8 99204714.

Panel

1) One anchor projected out
1) The loose anchor has been
1) Condition resolved in
1) 6/1996 D02-0902-0028 and loose.

fixed.

original USI A-46 report. The

2) There is 1/4" gap RESOLUTION #14 loose anchor has been fixed.

between the panel and the

2) Shim the gap to close it.
2) No actions are required. A surface of the concrete and subsequent walkdown found
2) 5/6/1999 panel contains essential RESOLUTION #6 the panel to be true level and relays.
3) Develop realistic, median any gap between the
3) Anchorage capacity less amplified floor spectra to concrete and panel to be than demand.

potentially reduce seismic insufficient to create an demand to an acceptable level, interaction.

RESOLUTION #11

3) Additional evaluation of the 3) panel determined its HCLPF 03/31/2000 capacity to be > 0.3g.

Table G-1 Page 12 of 33 G-13

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Equipment ID Description of Condition/

IPEEE Report Proposed Actual Resolution of Condition Resolution Vulnerability Resolution of Condition Date Panel

1) Panel is not bolted to
1) Determine whether or not
1) The panel contains
1) 9/26/2000 D03-0903-0033 adjacent panel.

panel(s) contains essential essential relays. Modification

2) There is 1/8" gap relays. If they do, connect EC 7529 & WO 99134630 between the panel and the (bolt) panels together to bolted the panel to adjacent surface of the concrete and preclude impact potential.

panel.

panel contains essential RESOLUTION #8

2) No actions are required. A
2) 5/6/1999 relays.
2) Shim the gap to close it.

subsequent walkdown found the panel to be true level and RESOLUTION #6 any gap between the concrete and panel to be insufficient to create an interaction.

Cooler The attached piping may not Coolers are rod hung and thus Modifications to laterally Unit 2 D03-5746-A ----

have enough flexibility, flexible. Laterally restrain restrain coolers to preclude 10/25/2001.

H15 coolers to preclude piping piping rupture potential have Unit 3 D03-5746-B ----

rupture potential or evaluate been completed. EC 7619 &

10/20/2002.

H15 effects of loss of service water WO 99188333 (Unit 2) and D02-5746-A----

inventory and loss of cooling EC 18034 & WO 99126056 H15 capability.

(Unit 3).

D02-5746-B----

RESOLUTION #7 H15 Battery Charger Anchorage is inadequate (2 Equipment has been modified Condition resolved in original 12/23/96 D03-8300--3---

clips).

to improve anchorage (Mod IPEEE report. Modification B05 E12-3-96-225).

E12-3-96-225 & WO RESOLUTION #9 96097752 has improved anchorage of the battery charger.

Table G-1 Page 13 of 33 G-14

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Equipment ID Description of Condition/

IPEEE Report Proposed Actual Resolution of Condition Resolution Vulnerability Resolution of Condition, Date Battery Charger Unanchored.

Equipment has been modified Condition resolved in original Unit 2/3 DOO-83250-0---

to improve anchorage (Mod IPEEE report. Battery 01/09/97 B05 El 2-0-96-213 & E12-2-96-236).

chargers have been modified Unit 2 D02-83250-2---

RESOLUTION #9 to improve anchorage 01/21/97 B05 (Modifications E12-0-96-213

& WO 96097748 and E12 96-236 & WO 96097749).

Vertical Pump Nozzle loads should be Provide nozzle loads for Pump anchorage evaluations 3/27/98 002-1502-A ----

considered in the ANCHOR evaluation, have been performed with P30 evaluation but information RESOLUTION #9 inclusion of nozzle loads D02-1502-B ----

on nozzle loads is (Ref. revision 1 of SEWS for P30 incomplete.

pumps).

D02-1502-C ----

P30 D02-1502-D ----

P30 Horizontal Pump Piping vertically supported Provide nozzle loads for Pump anchorage evaluations 3/27/98 D03-1501-but has very little lateral evaluation, have been performed with 0044AP30 restraint and therefore RESOLUTION #9 inclusion of nozzle loads D03-1501-piping loads should be (Ref. revision 1 of SEWS for 0044BP30 considered in evaluating the pumps).

D03-1501-anchorage but information 0044CP30 on nozzle loads is D03-1501-incomplete.

0044DP30 Table G-1 Page 14 of 33 G-15

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Equipment ID Description of Condition/

IPEEE Report Proposed Actual Resolution of Condition Resolution Vulnerability Resolution of Condition Date Valve Did not meet GIP offset Valve extended operator Calculation CE091.0208 04/14/94 D02-2301-0005-rules.

accelerations from IE79-14 shows all valves have greater V20 1-0005-piping analysis to be obtained than 0.3g capacity.

V20 and used in the evaluation.

D03-2301-0008-RESOLUTION #11 V20 Valve AOVs are supported off 1/2" Perform more rigorous analysis The 1/2" diameter tubing has 8/2/1999 D02-8501-diameter tubing.

and/or modify support of the been qualified based on 0005AV05

valve, subsequent evaluation (Ref.

D02-8501-DOC ID #5995877).

0005BV05 RESOLUTION #11 Valve The condulet coming from Repair condulet.

Condulet cover has been 12/1997 D02-0302-the valve was open RESOLUTION #14 installed. Condition resolved 0019AV27 exposing the wires.

in original IPEEE report (Work Request 94038586).

Horizontal Pump Unrestrained emergency Positively secure emergency A walkdown has confirmed 5/6/1999 D02-5203 ------ light #209 (battery powered)

light, that the light has been P30 is overhead.

positively secured.

D03-5203 ------

RESOLUTION #3 P30 Table G-1 Page 15 of 33 G-16

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Equipment ID Description of Condition/

IPEEE Report Proposed Actual Resolution of Condition Resolution Vulnerability Resolution of Condition Date Switchgear

1) Spare breakers are too
1) Relocate spare breakers.
1) The spare breakers have
1) 5/1996 D02-6723 ------ close.

RESOLUTION #5 been relocated. Condition S35

2) Open hooks on light 2resolved in original IPEEE D02-6724 ------ fixtures is overhead.

report.

S35 RESOLUTION #2

3) Panel 2-6724 is not
2) T2 bolted to adjacent panels.
3) Not applicable. Condition
2) The S-hooks have been
2) 5/1996 rclosed.

Condition resolved in reportl original IPEEE report.

RESOLUTION #8

3) Condition resolved in
3) 4/12/1996 original IPEEE report. No actions are required. A subsequent walkdown verified that the panels are bolted together.

Switchgear

1) A safety equipment locker
1) Positively anchor locker or
1) The locker has been
1) 5/1996 D02-67231 ----- immediately adjacent to re-locate it.

relocated. Condition resolved S35 switchgear is an interaction RESOLUTION #5 in original IPEEE report.

D03-67341 ----- hazard.

S35

2) Close upper and lower sight
2) Condition relosved in
2) PCB storage tank behind glass valves to prevent loss of IPEEE, Rev. 1 report. Sight
2) 3/31/2000 switchgear is rod hanger oil if the glass breaks, or glass valves have been restrained at mid-height. It restrain bottom of tanks to closed to prevent loss of oil if is a flooding hazard preclude it from moving, the glass breaks.

because of sight glass at bottom of tank and essential RESOLUTION #6 relays inside the switchgear.

Table G-1 Page 16 of 33 G-17

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Equipment ID Description of Condition/

IPEEE Report Proposed Actual Resolution of Condition Resolution Vulnerability Resolution of Condition Date Panel

1) Overhead heater has only
1) Repair overhead heater
1) The heater support has
1) 8/15/1997 D03-2203-0073A support rod and should have support.

been repaired in accordance D03-2203-0073B two. Thus, it is an impact RESOLUTION #14 with WR 960044408.

hazard.

2) Close lighting S-hook.
2) The S-hook has been
2) Overhead lighting RESOLUTION #2 closed. Condition resolved in 2)5/1996 one open S-hook and is anoriginal IPEEE report.

impact hazard.

3) Seismically evaluate fire
3) Overhead fire line is piping and determine status.
3) No actions are required.

judged not to be seismically RESOLUTION #7 Fire piping has been

3) 8/26/1999 seismically evaluated to be quaflooding hazard because of adequate (ref. DOC ID#

essential relays inside 6012466).

panel.

Valve Suction line of pump (4-1/2" Restrain line so it cannot The suction line of the pump 10/9/2003 D03-0302-in diameter) touches the impose force onto the valve, has been moved away from 0157AV05 valve yoke.

RESOLUTION #6 the valve yoke to preclude interaction. (Ref. WO 1#468530) 1 Table G-1 Page 17 of 33 G-18

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Equipment ID Description of Condition/

IPEEE Report Proposed Actual Resolution of Condition Resolution Vulnerability Resolution of Condition Date Valve

1) Potential impact with
1) Determine piping
1) No actions are required.

1)

D03-1501-nearby piping, grating or displacement from piping Valve 3-1501-32B has been Valve 0032BV20 steel.

analysis and compare to evaluated for its yoke 3-1501-32B D02-1 601-0023--

V27

2) Valve 2-1601-23 is available clearance, displacement and found to be 8/4/1999 D03-0203-missing a bolt.

RESOLUTION #6 within the available clearance Valve D0302B03 2with the grating (Ref. DOC 2-1601-23 0002BV05

2) Install missing bolt.

ID# 5996462). Valve 2-1601-08/14/2003 RESOLUTION #14 23 was replaced per EC 331868 & WO 407776 and Valve Valve 3-0203-2B 3-0203-2B is qualified per per DRE0O-calculation DREOO-0061.

0061 08/23/2000

2) Bolt has been installed in accordance with Work 2)6/6/1998 Request 950096788-01.

Panel Base channel is secured to Modify anchorage to an Anchorage modified to 1/17/2001 D02-2252-0010 floor by 4 friction clips (one acceptable, positive anchorage positive anchorage design via in each corner) design.

EC 7663 & WO 99135802.

Neighboring Neutral RESOLUTION #10 Grounding Cabinet is secured by friction clips.

Table G-1 Page 18 of 33 G-19

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-1.67 Equipment ID Description of Condition/

IPEEE Report Proposed Actual Resolution of Condition Resolution Vulnerability Resolution of Condition Date Panel Panel is right against a Determine whether or not The panel has been bolted to 1/24/2002 DO-NGC column support on one side panel(s) contains essential the adjacent panel and to the and an adjacent panel on relays. If they do, connect column support via the other.

(bolt) panels together to modification EC 7663 & WO preclude impact potential.

99135800.

Insert neoprene or like material between column and panel, or positively secure panel to column.

RESOLUTION #6 Panel Panel is too close to two Determine whether or not The panels contain essential 9/14/2001 D00-2223-0033 adjacent panels that it is not panel(s) contains essential relays. The panels have D00-2223-0041 bolted to.

relays. If they do, connect been bolted together via (bolt) panels together to modification EC 7662 & WO preclude impact potential.

99135801.

RESOLUTION #8 Damper

1) Damper hung in poorly
1) Repair ductwork.
1) The duct support rod has 1)

D03-5772-0102-supported ductwork (already RESOLUTION #14 been replaced in accordance 10/23/1996 D05 sagging).

2) Close S-Hooks.

with WR 960043286.

2) Overhead light has open RESOLUTION #2 S-Hooks.
2) The S-hooks have been closed. Condition resolved in
2) 5/1996 original IPEEE report.

Table G-1 Page 19 of 33 G-20

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Equipment ID Description of Condition/

IPEEE Report Proposed Actual Resolution of Condition Resolution Vulnerability Resolution of Condition Date Battery Rack

1) There are spaces
1) Tighten battens so they are 1 & 2) Determination of 1 & 2) Unit 2 D02-9802-A ----

between the batteries and snug (1/16" or less gap) or qualified life not required.

03/20/1998 B04 along the front and back of insert spacers to make up the New batteries have been Unit 3 D02-9802-B ----

the batteries.

gaps.

installed in accordance with 04/22/1997 B04

2) The battery cells are RESOLUTION #12 modifications M12-2-95-003 D03-9802-A----

/&

WOs 97077161 / 97094589 B04 more than 10 years old.

2) Determine qualified life of and D03-9802-B ----

cells or replace.

M12-3-95-003 & WOs B04 RESOLUTION #13 95068434 with proper spacers.

Battery Rack The Styrofoam, on the front Insert "full height" Styrofoam Repairs to insert proper 10/19/1999 D02-8300--BC--

and back, is not full-height spacers, or secure (glue or tie) spacers have been B04 and could easily slip out spacers to rack (or battery completed. Repairs D02-83250 ----- during a seismic event, cells) so that they cannot slide implemented via Engineered B04 out.

Repairs (Ref. DOC ID#

D03-8300--BC--

RESOLUTION #12 6043969).

B04 D03-83250 -----

B04 Table G-1 Page 20 of 33 G-21

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Equipment ID Description of Condition/

IPEEE Report Proposed Actual Resolution of Condition Resolution Vulnerability Resolution of Condition Date CCSW Pump Bolt type is not covered by Capacity of Cinch Anchor is Condition resolved in original 12/1997 Cooler the GIP - Cinch Anchor.

based on "Lead Expansion IPEEE report. See preceding D02-5700-Anchor Load Capacity in column for details.

0030AH15 Reactor Building at the D02-5700-Savannah River Site",

0030BH15 Westinghouse Savannah River D02-5700-Company, RTR-2661, Aug. 15, 0030CH15 1989 (Ref. 23). The resulting D02-5700-anchorage capacity was shown 0030DH15 to exceed the design basis D03-5700-seismic demand loads and 0030AH 15 Condition is resolved.

D03-5700-RESOLUTION #10 030BH 157 D03-5700-0030CH 15 D03-5700-0030DH 15 Switchgear Spare breakers which are Secure or re-locate spare Spare breakers have been 5/1996 D03-67331 ------ unanchored are potential breakers.

relocated. Condition S35 interaction hazards.

RESOLUTION #5 resolved in original IPEEE report Vertical Tank Tank is supported by ring Evaluate ring foundation.

The ring foundation has been 04/11/1998 DOO-3303-A----

foundation.

RESOLUTION #9 qualified based on evaluation T05, D00-3303-B-(Ref. Stevenson &

--- T05 Associates Calculation 98Q4006-C-002).

Table G-1 Page 21 of 33 G-22

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Equipment ID Description of Condition/

IPEEE Report Proposed Actual Resolution of Condition Resolution Vulnerability Resolution of Condition Date Panel Base channel is secured to Modify anchorage to an The panel anchorage has 1/17/2001 D02-2252-0021 floor by 4 friction clips (one acceptable, positive anchorage been modified to a positive in each corner) design.

anchorage design via Neighboring Neutral RESOLUTION #10 modification EC 7663 & WO Grounding Cabinet is 99135802.

secured by friction clips.

Pressure Indicators are supported by Anchor indicators to wall.

Condition has been deleted 3/30/2000 Indicators piping and not attached to RESOLUTION #6 from the Program. The 2/3-4041-1A & 1B wall which could result in pressure indicators are seismic interaction, associated with Refuse Pumps. The Refuse Pumps are not being credited for Isolation Condenser makeup for the loss of dam failure scenario; therefore, the pressure indicators are not required for safe shutdown or included in the SPEL.

Iso Cond Heat Isolation condenser has no Condition resolved (see S&L No actions are required. The 10/27/1997 Exchangers anchor bolts at outboard calculation 8900-15-EO-S) existing configuration has D02-1302---H15, piers. Load taken by center been verified to be adequate D03-1302---H15 pier.

RESOLUTION # 14 per S&L calculation 8900 RESOLTION#

14EO-S.

Condition resolved in original IPEEE report Table G-1 Page 22 of 33 G-23

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Equipment ID Description of Condition/

IPEEE Report Proposed Actual Resolution of Condition Resolution Vulnerability Resolution of Condition Date Heat Exchanger Support steel requires Completed Modification of Condition resolved in original

1) 04/03/96 D02-1503-A ----

evaluation, support steel (Mods:

IPEEE report. See preceding

2) 04/03/96 H15
1) E12-2-95-242, WO 96021982 column & respective Work
3) 09/15/96 D03-1503-A ----
2) El 2-2-95-243, WO 96021981 Orders.
4) 09/12/96 H15 D02-1503-B ----
3) E12-3-95-258, WO 96030678 H15
4) El 2-3-95-259, WO 96030680 D03-1503-B ----

RESOLUTION #9 H15 Accumulator The accumulator has one Install (repair) missing bolt.

No actions are required.

10/6/1999 D02-4798-A----

bolt missing.

RESOLUTION #14 Upon further review, the A10 accumulator is designed to be installed with one U-bolt.

A subsequent walkdown verified that the U-bolt is in place (Ref. DOC ID#

6034842).

Control Panel/

Neighboring Neutral Modify anchorage to an The anchorage of the Neutral 1/24/2002 DG Exciter Grounding Cabinet is acceptable, positive anchorage Grounding Cabinet has been D03-2252-0021 -

secured by friction clips.

design.

modified to a positive P06 RESOLUTION #10 anchorage design via EC 7664 & WO 99135800.

D02-2202-0006-Overhead light is only Fix overhead light The light has been secured 5/1996 P06 secured by one chain RESOLUTION #14 properly. Condition resolved in original IPEEE report.

Table G-1 Page 23 of 33 G-24

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Equipment ID Description of Condition/

IPEEE Report Proposed Actual Resolution of Condition Resolution Vulnerability Resolution of Condition Date Cable Tray &

An enveloping support in the This Condition is resolved by Condition resolved in original 07/01/1996 Conduit Raceway Unit 2 Battery Room area Condition analysis. A limit IPEEE report per calculation Systems was chosen for limited analysis per Section 8.4.8 of 93C2806.4-C-002.

LAR001 analytical review. The Reference 14 was performed support is a 4-tier, rod hung and the hanger passes.

trapeze supporting 4 trays.

Dresden rod fatigue data The support has two obtained from actual cyclic different types of ceiling testing of the Dresden field anchorages: embedded threaded rods including the strut and weldment to weldment anchorage plate from building steel. Loads SEP Project 8050 (Ref. 22) was exceed the allowables for used to evaluate the rods.

the rod fatigue check.

Based on the "Generic Rod Acceptability Curves", it was shown that the Dresden rods will sustain the SSE demand loads.

RESOLUTION #15 Table G-1 Page 24 of 33 G-25

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Equipment ID Description of Condition/

IPEEE Report Proposed Actual Resolution of Condition Resolution Vulnerability Resolution of Condition Date Cable Tray &

An enveloping support in the This Condition is resolved by Condition resolved in original 07/01/1996 Conduit Raceway Auxiliary Electrical Condition analysis. A limit IPEEE report per calculation Systems Equipment Room was analysis per Section 8.4.8 of 93C2806.4-C-002 LAR004 chosen for limited analytical Reference 14 was performed review. The support is a and the hanger passes.

four tier rod hung trapeze RESOLUTION #15 supporting 4 trays. The support has two different types of ceiling anchorages:

embedded strut and weldment to building steel.

The loads for the embedded strut version exceed the allowables for the vertical capacity check. The loads for the welded attachment to building steel version exceed, by a small amount, the allowables for the rod fatigue check and are considered acceptable.

Table G-1 Page 25 of 33 G-26

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Equipment ID Description of Condition/

IPEEE Report Proposed Actual Resolution of Condition Resolution Vulnerability Resolution of Condition Date Cable Tray &

The main "spine of the This Condition is resolved by Condition resolved in original 05/1996 Conduit Raceway cables connecting the Condition analysis. A limit IPEEE report.

Systems Reactor building with the analysis per Section 8.4.8 of LAR005 Control room. A large two-Reference 14 was performed bay system carrying 12-44" and the hanger passes.

trays in one bay (one side)

RESOLUTION #15 and 4-44" trays on the other side in a floor-to-ceiling system. The bolting connections at the ceiling connection (anchorage) do not pass the vertical capacity check.

Table G-1 Page 26 of 33 G-27

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Equipment ID Description of Condition/

IPEEE Report Proposed Actual Resolution of Condition Resolution Vulnerability Resolution of Condition Date Cable Tray &

An enveloping support in the This Condition is resolved by Condition resolved in original 07/01/1996 Conduit Raceway Unit 3 Turbine Building, El.

Condition analysis. A IPEEE report per calculation Systems 538, was chosen for limited redundancy and consequence 93C2806.4-C-002.

LAR006 analytical review. The analysis per Section 8.4.8 of support is a two tier, rod Reference 14 was performed hung trapeze supporting 2 and the hanger passes.

trays. The support Dresden rod fatigue data anchorage is weldment to obtained from actual cyclic building steel. The support testing of the Dresden field loads exceed the allowables threaded rods including the for the rod fatigue check.

weldment anchorage plate from SEP Project 8050 (Ref. 23) was used to evaluate the rods.

Based on the "Generic Rod Acceptability Curves", it was shown that the Dresden rods will sustain the SSE demand loads.

RESOLUTION #15 Table G-1 Page 27 of 33 G-28

12Q0108.30-R-001,' Rev. 1 Correspondence No.: RS-12-167 Equipment ID Description of Condition/

IPEEE Report Proposed Actual Resolution of Condition Resolution Vulnerability Resolution of Condition Date Cable Tray &

An enveloping support in the Use Blume Report methodology The worst case hangers have 05/05/1999 Conduit Raceway Unit 2 Turbine Building, El.

to qualify support for rod been reassessed for actual Systems 517, was chosen for limited fatigue.

tray loadings, spans and analytical review. The RESOLUTION #15 configurations. Actual LAR007 support is a four tier, rod loading and spans were hung trapeze supporting 4 found to be smaller than trays. The support those used in the original anchorage is an embedded assessment. The strut. The support loads assessment (S&A Calculation exceed the allowables for DRE99-0029) showed the the rod fatigue check.

worst case hangers were acceptable without modification.

Table G-1 Page 28 of 33 G-29

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Equipment ID Description of Condition/

IPEEE Report Proposed Actual Resolution of Condition Resolution Vulnerability Resolution of Condition Date Cable Tray &-

An enveloping support in the This Condition is resolved by Condition resolved in original 05/1996 Conduit Raceway Reactor Building, El. 517, Condition analysis. A limit IPEEE report.

Systems was chosen for limited analysis per Section 8.4.8 of LAR008 analytical review. The Reference 14 was performed support is a two bay, three and the hanger passes.

tier/bay, rod hung trapeze Dresden rod fatigue data supporting 1 tray/tier. The obtained from actual cyclic support has two different testing of the Dresden field types of ceiling anchorages:

threaded rods including the embedded strut and weldment anchorage plate from weldment to building steel.

SEP Project 8050 (Ref. 23) was The loads for the embedded used to evaluate the rods.

strut version exceed the Based on the "Generic Rod allowables for the vertical Acceptability Curves", it was capacity check. The loads shown that the Dresden rods for the welded attachment to will sustain the SSE demand building steel version loads.

exceed the allowables for the rod fatigue check.

Cable Tray &

The support is a 1/2" field Determine actual weight per Outliner Resolved. Actual 03/16/1998 Conduit Raceway threaded rod trapeze foot of the bus duct and weight per foot of the conduit Systems supporting 16" dia. bus duct, compare to the 98 lbs/ft.

duct is < 20 lbs/ft compared LAR009 24" to "top tier". The limiting capacity.

to 98 lbs/ft capacity (NDIT seismic capacity based on RESOLUTION #15 No. SEC-DR-98-046).

rod fatigue is 98 lbs/ft. The actual weight (amount of cable inside the conduit) is currently unknown.

Table G-1 Page 29 of 33 G-30

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Equipment ID Description of Condition/

IPEEE Report Proposed Actual Resolution of Condition Resolution Vulnerability Resolution of Condition Date Unit 2 Turbine The hangers at the entrance Determine if block wall capacity The wall capacity is no longer 11/15/1999 Building (including to the turbine building, east needs to be evaluated. If so required since the cable tray DIG Room), El.

of the truck bay, are rod determine the block wall is not supported off the wall 517 RACE010 hung on one side and bolted capacity.

per Doc ID 6065125. The to a strut embedded in a RESOLUTION #15 cable tray has been verified block wall on the other side.

to be adequate per the resolution to LAR007.

Diesel fuel Oil Sight glass interaction issue.

Perform additional evaluation.

Additional evaluation found 10/28/1996 Storage Day Tank RESOLUTION #6 the sight glass to be DOO-5202-T05 seismically adequate and there is no interaction issue (Ref. Rev. 1 of SEWS)

Drywell/Torus 3g analysis shows yoke Evaluate actual demand The valves have been 8/4/1999 Nitrogen Makeup overstress.

accelerations.

evaluated for actual demand Valves D02-1601-RESOLUTION#1 1 accelerations and found to be 0057-V20 and seismically adequate (Ref.

D03-1601-0057-DCC I D# 5996462).

V20 General Nearby gas bottle Revise Procedure DHP 0220-Procedure DHP 0220-02 has 7/30/2002 interaction. Procedure DHP 02 to address to address gas been superseded by 0220-02.

bottle interaction concerns.

Procedure SA-AA-122.

RESOLUTION #1 General Inadequate seismic Develop a new procedure or Procedure DAP 03-20, 6/7/2000 housekeeping procedure.

revise housekeeping procedure "Restraint of Portable DAP 03-11.

Equipment" has been revised RESOLUTION #5 to address seismic housekeeping concerns.

Table G-1 Page 30 of 33 G-31

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Equipment ID Description of Condition/

IPEEE Report Proposed Actual Resolution of Condition Resolution Vulnerability Resolution of Condition Date Hydrogen Seal Oil Anchorage is inadequate.

Provide positive anchorage.

The panels' anchorage has Unit Panels D02-2257-been modified to positive 201/12/2001 7 and D03-2253-7 anchorage. Modification Unit 3 DCPs 9900205 (EC 7546 &

04/06/2000 WO 99102056) for Unit 2 and 9900204 (EC 7545 & WO 99102057) for Unit 3 Generator Core Monitors not anchored or Provide positive anchorage or The monitors have been Unit 2 Monitors D02-restrained have potential for restrain the monitors.

restrained by modification 01/12/2001 5341-15 and D03-hydrogen leakage.

DCPs 9900205 (EC 7546 &

Unit 3 5341-15 WO 99102056) for Unit 2 and 04/06/2000 9900204 (EC 7545 & WO 99102057) for Unit 3.

Dresden Dam Seismically qualified path for Provide a path from Unit 2 Modification EC 341458 (WO 10/28/2003 failure concern Isolation Condenser Diesel Generator Cooling Water 00558712) provided a tie-in makeup water is not system (seismically qualified) to from Unit 2 Diesel Generator available.

Isolation Condenser makeup Cooling Water to Isolation pumps.

Condenser makeup pumps.

Dresden Dam Alternate path for makeup Provide an alternate path to Modifications to provide tie-Unit 2 failure concern water to Units 2 and 3 CCSW heat exchangers.

ins to CCSW heat 11/4/2003 CCSW heat exchangers exchangers have been Unit 3 does not-exist.

completed via EC 34.1459 11/4/2003 (WO 558719) for Unit 2 and EC 341461 (WO 558720) for Unit 3.

Table G-1 Page 31 of 33 G-32

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Equipment ID Description of Condition/

IPEEE Report Proposed Actual Resolution of Condition Resolution Vulnerability Resolution of Condition Date Iso Condenser Isolation Condenser Provide anchorage or seismic Seismic restraints for the 8/25/2003 Makeup Pump makeup pump diesel oil day restraints for the diesel oil day Isolation Condenser makeup Diesel Oil Day tanks and batteries are not tank batteries, pump diesel oil day tanks and Tanks 2/3-5215-A anchored.

batteries been added via and 2/3-5215-B modification EC 341881 (WO and batteries 2/3-557293) 4312-4A and 2/3-43123B Relays (Various)

Various vulnerabilities such Perform additional evaluation of Evaluation of various relay Calc as low ruggedness relays, the relays for seismic adequacy models such as General DRE99-0003 demand exceeds capacity, or replace them with qualified Electric HFA, HGA, IAV and 11/1/1999 no GERS, etc.

relays.

IAC and other manufacturers' Calc relays was completed.

DRE99-0020 Calculations DRE99-0003 5/21/1999 and DRE99-0020.

Relays that did not pass evaluation were replaced with qualified relays via the following modifications.

Cardox relays and timers 9/27/2003 Model H45 and H47 for EDGs. Modification EC 7535 (W099127497).

Relays associated with Unit 9/30/2003 2/3 EDG such as GE Model CFF and HFA, and EMD Model 8263337. Modification EC 8259 (WO 541917).

Table G-1 Page 32 of 33 G-33

12Q0108.30-R-001, Rev. 1 Correspondence No.: RS-12-167 Equipment ID Description of Condition/

IPEEE Report Proposed Actual Resolution of Condition Resolution Vulnerability Resolution of Condition Date Relays associated with Unit 2 8/12/2003 EDG such as GE Model CFF and HFA, and EMD Model 8263337. Modification EC 8260 (WO 545850).

Relays associated with Unit 3 9/8/2003 EDG such as GE Model CFF and HFA, and EMD Model 8263337. Modification EC 8261 (WO 545846).

Removed Square D pressure 11/4/2003 switch 2-2303-PS4 form HPCI system. Modification EC 8262 (WO 522055).

GE relays Model IAV and 10/23/2003 HFA in switchgear 29.

Modification EC 8263 (WO 558722)..

Unit 3 auto blowdown relays, 12/19/2003 GE Model HFA in panel 3-2203-32. Modification EC 8264 (WO 522226).

Table G-1 Page 33 of 33 G-34