MONTHYEARML11188A1452011-07-0101 July 2011 Request for License Amendment to Adopt National Fire Protection Association 805 Performance-Based Standard for Fire Protection for Light Water Reactor Generating Plants Project stage: Request ML11256A0302011-09-0202 September 2011 Supplement to Request for License Amendment to Adopt National Fire Protection Association (NFPA) 805 Performance-Based Standard for Fire Protection for Light Water Reactor Generating Plants (2001 Edition) Project stage: Supplement ML11255A0222011-09-13013 September 2011 Informs Licensee That Application for Amendment to Change Fire Protection Licensing Basis to NFPA 805 Is Acceptable for Review Project stage: Other ML1131204962011-11-0808 November 2011 Transmit Audit Plan for the Proposed Amendment Converting the Fire Protection Program to NFPA 805 Project stage: Other ML1131205002011-11-0808 November 2011 Audit Plan - D.C. Cook Proposed Amendment to Convert Fire Protection Program to NFPA 805 Project stage: Other ML1131302492011-11-0808 November 2011 E-mail Transmitting 4 NRC Staff Documents to Support the Audit of the Proposed Conversion of the Fire Protection Program to NFPA 805 Project stage: Other ML1131302592011-11-0808 November 2011 Questions and Issues to Be Addressed During the Audit Project stage: Other ML1131302602011-11-0808 November 2011 Questions and Comments About the Probabilistic Risk Analysis Project stage: Other ML1131302612011-11-0808 November 2011 Additional Questions/Comments on the Monitoring Program, Documentation, Etc Project stage: Other ML1131302622011-11-0808 November 2011 List of Plant Components for Walkdown Project stage: Other ML12017A2512012-01-27027 January 2012 RAI for the Proposed Amendment to Transition the Fire Protection Program to NFPA 805 Project stage: RAI ML1135607092012-01-27027 January 2012 Letter Transmitting an RAI on the Application for Amendment to Transition the Fire Protection Program to NFPA 805 Project stage: RAI AEP-NRC-2012-29, Response to Request for Additional Information Regarding the Application for Amendment to Transition the Fire Protection Program to National Fire Protection Association Standard 8052012-04-27027 April 2012 Response to Request for Additional Information Regarding the Application for Amendment to Transition the Fire Protection Program to National Fire Protection Association Standard 805 Project stage: Response to RAI AEP-NRC-2012-58, Response to Request for Additional Information Regarding the Application for Amendment to Transition the Fire Protection Program to National Fire Protection Association Standard 8052012-08-0909 August 2012 Response to Request for Additional Information Regarding the Application for Amendment to Transition the Fire Protection Program to National Fire Protection Association Standard 805 Project stage: Response to RAI ML12230A3032012-08-14014 August 2012 Draft Redacted Second-round RAI Re NFPA 805 Amendment Project stage: Draft RAI ML12255A3952012-09-0606 September 2012 Redacted Draft Second-Round RAI the Proposed NFPA 805 Amendment Project stage: Draft Approval ML12276A3002012-10-11011 October 2012 RAI on the Application for Amendment to Transition the Fire Protection Program to National Fire Protection Standard 805 Project stage: RAI ML12285A1792012-10-11011 October 2012 D C Cook NFPA 805 RAI Project stage: Other AEP-NRC-2012-92, Response to Second Round Request for Additional Information Regarding Application for Amendment to Transition the Fire Protection Program to National Fire Protection Association Standard 8052012-10-15015 October 2012 Response to Second Round Request for Additional Information Regarding Application for Amendment to Transition the Fire Protection Program to National Fire Protection Association Standard 805 Project stage: Request ML12326A9982012-11-0909 November 2012 Response to Second-Round Request for Additional Information Item 54.b and Submittal of Revised Tables Re the Application for Amendment to Transition to National Fire Protection Association Standard 805 Project stage: Request ML12326A9992012-11-0909 November 2012 Donald C, Cook, Units 1 and 2 - Enclosure 1, 2 & 4 to AEP-NRC-2012-101, Response to Second-Round RAI Item 54.b, and Submittal of Revised Tables Re the Application for Amendment to Transition to National Fire Protection Association Standard Project stage: Request ML12326B0002012-11-0909 November 2012 Donald C, Cook, Units 1 and 2 - Enclosure 4 (Cont.) to AEP-NRC-2012-101, Response to Second-Round RAI Item 54.b, and Submittal of Revised Tables Re the Application for Amendment to Transition to National Fire Protection Association Standard Project stage: Request ML12345A3272012-12-13013 December 2012 Request for Additional Information on the Application for Amendment to Transition the Fire Protection Program to National Fire Protection Association Standard 805 Project stage: RAI ML13028A1132013-01-14014 January 2013 Response to Third Round Request for Additional Information Regarding the Application for Amendment to Transition the Fire Protection Program to National Fire Protection Association Standard 805 Project stage: Request AEP-NRC-2013-09, Revised Response to First Round Request for Additional Information Re Application for Amendment to Transition the Fire Protection Program to National Fire Protection Association Standard 8052013-02-0101 February 2013 Revised Response to First Round Request for Additional Information Re Application for Amendment to Transition the Fire Protection Program to National Fire Protection Association Standard 805 Project stage: Request ML13014A5492013-02-0101 February 2013 Request for Additional Information on the Application for Amendment to Transition the Fire Protection Program to National Fire Protection Association Standard 805 Project stage: RAI ML13085A1842013-04-22022 April 2013 Review and Conclusion of Indiana Michigan Power Companys Resolution of Facts and Observations in Support of DC Cooks Transition to NFPA 805 Project stage: Other ML13085A1902013-04-22022 April 2013 DC Cook Table U Record of Review March 22 2013 Project stage: Other ML13085A2462013-04-22022 April 2013 DC Cook Table V-1 & V-2 Record of Review March 22 2013 Project stage: Request AEP-NRC-2013-17, Response to a Request for Additional Information (RAI 29.01, 61, and 62) Regarding the Application for Amendment to Transition the Fire Protection Program to National Fire Protection Association Standard 8052013-05-0101 May 2013 Response to a Request for Additional Information (RAI 29.01, 61, and 62) Regarding the Application for Amendment to Transition the Fire Protection Program to National Fire Protection Association Standard 805 Project stage: Response to RAI AEP-NRC-2013-55, Response to a Request for Additional Information Regarding the Application for Amendment to Transition the Fire Protection Program to National Fire Protection Association Standard 805 TAC (ME6629 and ME6630)2013-06-21021 June 2013 Response to a Request for Additional Information Regarding the Application for Amendment to Transition the Fire Protection Program to National Fire Protection Association Standard 805 TAC (ME6629 and ME6630) Project stage: Response to RAI ML13210A2042013-09-0606 September 2013 Request for Additional Information on the Application for Amendment to Transition the Fire Protection Program to National Fire Protection Association Standard 805 Project stage: RAI AEP-NRC-2013-75, Response to a Request for Additional Information (RAI 63) Regarding the Application for Amendment to Transition the Fire Protection Program to National Fire Protection Association Standard 8052013-09-16016 September 2013 Response to a Request for Additional Information (RAI 63) Regarding the Application for Amendment to Transition the Fire Protection Program to National Fire Protection Association Standard 805 Project stage: Response to RAI ML13140A3982013-10-24024 October 2013 Issuance of Amendment Nos. 322 and 305 - Transition to NFPA 805 Risk-Informed, Performance-Based Fire Protection Program in Accordance with 10 CFR 50.48(c) and NFPA 805 Project stage: Approval 2012-08-14
[Table View] |
Similar Documents at Cook |
|---|
|
Text
INDIANA Indiana Michigan Power MICHIGAN Cook Nuclear Plant POWER" One Cook Place Bridgman, Mi 49106 A unit oftAmerican Electric Power IndlianaMichiganPowef cum November 9, 2012 AEP-NRC-2012-101 10 CFR 50.90 Docket Nos.: 50-315 50-316 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D. C. 20555-0001 Donald C. Cook Nuclear Plant Units 1 and 2 Response to Second-Round Request for Additional Information Item 54.b, and Submittal of Revised Tables Regarding the Application for Amendment to Transition to National Fire Protection Association Standard 805 (TAC Nos. ME6629 and ME6630)
This letter provides Indiana Michigan Power Company's (A&M's) response to the remaining question from the second round of U. S. Nuclear Regulatory Commission (NRC) requests for additional information (RAls) regarding a proposed license amendment to transition the Donald C. Cook Nuclear Plant (CNP), Units 1 and 2, to an National Fire Protection Association Standard 805 (NFPA 805) based fire protection program.
Documents referenced in this transmittal letter are identified in Enclosure 2. By Reference 1 and 2, I&M proposed to amend CNP Units 1 and 2 Facility Operating Licenses DPR-58 and DPR-74 to adopt a new fire protection program based on NFPA 805, in accordance with 10 CFR 50.48(a) and (c).
Reference 1, Enclosure 2, hereafter referred to as the Transition Report, provided information associated with the CNP transition to NFPA 805. By References 3 and 4, the NRC transmitted the first round of RAIs regarding the proposed amendment. References 5, 6, and 7 transmitted I&M's responses to the Reference 3 and 4 RAIs. By Reference 8, the NRC transmitted a second round of RAIs. Reference 9 provided I&M's responses to the Reference 8 second-round RAIs, except for RAI-54.b. Reference 8 and 9 documented A&M's intention to provide the response to RAI-54.b no later than November 9, 2012. This letter provides I&M's response to RAI-54.b.
Reference 9 also documented I&M's intention to provide two revised tables to replace tables that were included in the Transition Report provided in the original amendment request (Reference 1).
The first table, Table B-i, "Transition of Fundamental Fire Protection Program and Design Elements (NFPA 805, Chapter 3)," has been revised to incorporate changes identified in Reference 9 and changes resulting from responses to the first round of RAIs, along with the necessary re-pagination.
Security-Related Information -Withhold From Public Disclosure Under 10 CFR 2.390.
Enclosures 3 and 5 to this letter contain security-related information.
Upon removal of Enclosures 3 and 5, this letter and other enclosures are uncontrolled.
U. S. Nuclear Regulatory Commission AEP-NRC-2012-101 Page 2 The second table, Table W2, "Fire Initiating Event Scenarios Contributing More than 1% of the Calculated Fire Risk for Unit 2," has been revised to correct a discrepancy in which risk related values in the three right columns of the table were inadvertently transposed. to this letter provides an affirmation statement. Enclosure 2 identifies documents referenced in this letter and Enclosure 3. Enclosure 3 provides I&M's response to Reference 8, RAI-54.b. Enclosure 4 provides a revised Table B-1. Enclosure 5 provides a revised Table W2.
Copies of this letter and its enclosures are being transmitted to the Michigan Public Service Commission and Michigan Department of Environmental Quality, in accordance with the requirements of 10 CFR 50.91.
This letter contains no new or modified regulatory commitments.
Should you have any questions regarding this proposed amendment, please contact Mr. Michael K. Scarpello, Regulatory Affairs Manager, at (269) 466-2649.
Sincerely, Michael H. Carlson Site Support Services Vice President JRW/kmh
Enclosures:
- 1. Affirmation.
- 2. Identification of Documents Referenced in this Letter.
- 3. Response to RAI-54.b.
- 4. Revised Table B-A, "Transition of Fundamental Fire Protection Program and Design Elements (NFPA 805, Chapter 3)."
- 5. Revised Table W2, "Fire Initiating Event Scenarios Contributing More than 1% of the Calculated Fire Risk for Unit 2."
c:
C. A. Casto, NRC Region III J. T. King, MPSC S. M. Krawec, AEP Ft. Wayne, w/o enclosures MDEQ - RMD/RPS NRC Resident Inspector T. J. Wengert, NRC Washington, DC Security-Related Information -Withhold From Public Disclosure Under 10 CFR 2.390.
Enclosures 3 and 5 to this letter contain security-related information.
Upon removal of Enclosures 3 and 5, this letter and other enclosures are uncontrolled.