0612112012 U.S. Nuclear Regulatory Commission Operations Center Event Report Paze I Part 21 (PAR)
Event#
48042 Rep Org: ROSEMOUNT NUCLEAR INSTRUMENTS, INC. Notification Date / Time: 06/21/2012 15:03 (EDT)
Supplier: ROSEMOUNT NUCLEAR INSTRUMENTS, INC.
Event Date I Time: 06/14/2012 (CDT)
Last Modification: 06/21/2012 Region:
3 Docket #:
City: CHANHASSEN Agreement State:
Yes County:
License #:
State: MN NRC Notified by: JEFF CHIVERS Notifications:
DANIEL HOLODY R1DO HQ Ops Officer: DONG HWA PARK ALAN BLAMEY R2DO Emergency Class: NON EMERGENCY JULIO LARA R3DO 10 CFR Section:
GEOFFREY MILLER R4DO 21.21(d)(3)(i)
DEFECTS AND NONCOMPLIANCE PART 21 GRP BY EMAIL PART 21 - RELIABILITY DEGRADATION OF RESISTORS IN TRIP UNITS AND READOUT ASSEMBLIES "Certain 710DU Trip Units may not perform their intended safety function as a result of certain wire wound precision resistors experiencing a degradation of reliability. Additionally, certain 710DU Readout Assemblies used to calibrate 710DU Trip Units may experience degraded digital display accuracy during calibration due to a similar cause. Rosemount Nuclear Instruments, Inc. does not have complete information relating to specific plant applications and therefore cannot determine the potential effects of the condition on plant operation.
"This notification affects certain Model 71ODU Trip Units and certain 71ODU Readout Assemblies shipped from Rosemount Nuclear Instruments, Inc between March 16, 2005 and May 10, 2012."
The shipments were distributed to Ginna, Nine Mile Point, Fermi, Columbia Generating Station, Fitzpatrick, River Bend Station, Grand Gulf, Quad Cities, Peach Bottom, LaSalle, Limerick, Dresden, Perry, Hope Creek, Hatch, Brunswick, Browns Ferry, and Monticello.
Rosemount Nuclear Instruments, Inc.
8200 Market Boulevard ROSEM OUNT IChanhassen, MN 55317 USA Nuclear Tel 1.(952) 949-5210 Fax 1 (952) 949-5201
"!ýRFjq~MountjNuclearo 21 June 2012 U.S. Nuclear Regulatory Commission Washington, DC 20555-0001 Attn: Document Control Desk Re: Notification under 10 CFR Part 21 on certain Rosemount Model 710DU Trip Units and 710DU Readout Assemblies Pursuant to 10 CFR Part 21, section 21.21(b), Rosemount Nuclear Instruments, Inc. (RNII) is writing to inform you that certain 710DU Trip Units may not perform their intended safety function as a result of certain wirewound precision resistors experiencing a degradation of reliability. Additionally, certain 71ODU Readout Assemblies used to calibrate 71ODU Trip Units may experience degraded digital display accuracy during calibration due to a similar cause.
Rosemount Nuclear Instruments, Inc. does not have complete information relating to specific plant applications and therefore cannot determine the potential effects of the condition on plant operation.
This notification affects certain Model 71ODU Trip Units and certain 71ODU Readout Assemblies shipped from RNII between March 16, 2005 and May 10, 2012.
1.0 Name and address of the individual providing the information:
Mr. Marc D. Bumgarner Vice President & General Manager Rosemount Nuclear Instruments, Inc.
8200 Market Boulevard Chanhassen, MN 55317 2.0 Identification of items supplied:
Certain 71ODU Master and Slave Trip Units, as well as certain 71ODU Readout Assemblies shipped from RNII between March 16, 2005 and May 10, 2012. See the enclosed Appendix A for the list of units shipped by customer and/or plant site.
3.0 Identification of firm supplying the item:
Rosemount Nuclear Instruments, Inc.
8200 Market Boulevard Chanhassen, MN 55317 4.0 Nature of the failure and potential safety hazard:
71ODU Master and Slave Trip Units use wirewound precision resistors in various circuit applications, including the following qualified safety functions: 4 to 20mA loop current sense, RTD resistance input bridge, trip point comparator, voltage regulation, and circuit power-up. Non-qualified circuit functions include gross failure comparator, gross failure Page 1 of 4
output, and analog meter indication. 71ODU Readout Assemblies use wirewound resistors in digital display circuitry used to calibrate 710DU Master and Slave Trip Units.
RNII has recently identified an increased failure rate of wirewound resistors during manufacturing testing, as well as an increase in field returns resulting from wirewound resistor failures. Through third party testing and consultation with the manufacturer of the wirewound resistors, it has been determined that certain manufacturing lots may be more prone to premature failure. Circuit card assemblies using resistors from the suspect manufacturing lots were assembled into 710DU product and shipped from RNII between March 16, 2006 and May 10, 2012. Additionally, five 71ODU Master Trip Units were shipped from RNII between March 16, 2005 and June 14, 2010 following a resistor replacement process that used resistors from the suspect manufacturing lots.
The suspected cause of reduced reliability is the use of aggressive flux with higher chlorine content during the supplier's resistor manufacturing process. In certain cases, the flux can penetrate the resistor end cap and corrode the resistive wire element. The failure mode typically experienced -is an electrically "open" condition. However, additional failures have been identified by RNII where the resistance value may drift outside of the specified tolerance interval.
RNII has evaluated resistor applications in the 71ODU product family for the potential impact of an electrically "open" failure mode as well as for a drift in resistance. These conditions may cause the following situations:
71ODU Master and Slave Trip Units Qualified Safety Function o
Drift in the 71ODU trip point setting.
o Drift in the 71ODU trip reset differential setting.
o Failure of the trip logic to activate. In this case, though a trip condition exists, trip output would not change state.
o Inadvertent activation of the trip logic.
o Failure of the 71 ODU Master or Slave Trip Unit to power up from a de-energized state.
Non-Qualified Function o
Drift in the 71ODU high gross fail setting or low gross fail setting.
o Failure of the high gross fail or low gross fail logic to activate. In this case, though a gross failure condition exists the gross failure output would not be activated.
o Inadvertent gross failure indication.
o Inaccurate or off-scale reading of the 710DU Master Trip Unit analog indicating meter.
ROSEMOUNT' Nuclear Page 2 of 4
71ODU Readout Assembly Degradation of the accuracy of the 710DU Readout Assembly digital display. This condition may result in errors during trip point calibration of the 710DU Master and Slave Trip Unit.
As a result of the above analysis, RNII determined on June 14, 2012 that a substantial safety hazard may exist for 71ODU Master and Slave trip units and 71ODU Readout Assemblies, and is therefore issuing this notification.
5.0 The corrective action which Is taken, the name of the individual or organization responsible for that action, and the length of time taken to complete that action:
(a) RNII has scrapped all inventories of the suspect resistor manufacturing lots.
(b) RNII has worked with the resistor manufacturer to verify that a less aggressive flux is in use and appropriate manufacturing process changes have been implemented to prevent reoccurrence of this issue.
(c) RNII has required the resistor manufacturer to conduct additional reliability screening on all future manufacturing lots shipped for use in RNII products.
(d) RNII has increased manufacturing burn in time from 48 to 100 hours0.00116 days <br />0.0278 hours <br />1.653439e-4 weeks <br />3.805e-5 months <br /> for all 71ODU Trip Units and 71ODU Readout Assemblies to provide increased detectability of resistor reliability concerns.
Mr. Marc Bumgamer, VP&GM of Rosemount Nuclear Instruments, Inc. is responsible for any further action related to this issue.
6.0 Any advice related to the potential failure of the Item:
RNII recommends that users review the application where any of the potentially affected Model 71 ODU Trip Units or Readout Assemblies are used to determine any safety considerations in the operation of the plant. RNII can provide the following information to address potentially affected product:
For 710DU Master and Slave Trip Units affected by this notification o As of June 14, 2012, approximately 2.5% of 710DU Master and Slave Trip Units shipped between March 16, 2006 and May 10, 2012 have been returned to RNII due to confirmed wirewound resistor failures.
Master and Slave Trip Units can be returned to RNII at the customer's discretion and suspect wirewound resistors will be replaced with resistors manufactured and screened as outlined in section 5.0.
- Alternatively, RNII will provide a kit of resistors manufactured and screened as outlined in section 5.0 to allow customers to replace the resistors.
ROSEMOUNT' Nuclear Page 3 of 4
For 710DU Readout Assembly units affected by this notification RNII has not confirmed any field failures of 71ODU Readout Assemblies manufactured between March 16, 2006 and May 10, 2012 that were a result of wirewound resistor failures.
Readout assemblies can be returned to RNII at the customer's discretion and suspect wirewound resistors will be replaced with resistors manufactured and screened as outlined in section 5.0.
Rosemount Nuclear Instruments, Inc. is committed to the nuclear industry and remains dedicated to the supply of high quality products to our customers. If you have any questions, or require additional information related to this issue, please contact: Mike Dougherty (208) 865-1112 or Tracy Kaluzniak (952) 949-7159.
Sincerely, Marc D. Bumgarner Vice President & General Manager Rosemount Nuclear Instruments, Inc.
Enc.:
Appendix A-List of Affected 710DU Master and Slave Trip Units and 710DU Readout Assemblies by Company Name and/or Plant Site ROSEMOUNT" Nuclear Page 4 of 4
APPENDIX A: 10 CFR PART 21 NOTIFICATION - 21 JUNE 2012 CONSTELLATION ENERGY GROUP PURCHASE SERIAL RNII ORDER NUMBER MODEL NUMBER NUMBER SHIP DATE SITE SALES ORDER 6606785 710DUlTT44051 539080 29-Apr-09 GINNA NUCLEAR POWER PLANT 2269995 7718089 710DUOTS 541134 16-Mar-10 NINE MILE POINT NUCLEAR STATION 2506386 7718089 710DUOTS 541135 16-Mar-10 NINE MILE POINT NUCLEAR STATION 2506386 7718089 710DUOTS 541136 16-Mar-10 NINE MILE POINT NUCLEAR STATION 2506386 7718089 710DUOTS 541137 16-Mar-10 NINE MILE POINT NUCLEAR STATION 2506386 7718089 710DUOTS 541204 6-Apr-10 NINE MILE POINT NUCLEAR STATION 2506386 7722154 710DUOTS 543828 18-May-11 NINE MILE POINT NUCLEAR STATION 3035200 7722154 710DUOTS 543829 18-May-11 NINE MILE POINT NUCLEAR STATION 3035200 7722154 710DUOTT45171 543891 18-May-11 NINE MILE POINT NUCLEAR STATION 3035200 7722154 710DUOTT45171 543892 18-May-11 NINE MILE POINT NUCLEAR STATION 3035200 7722154 710DUOTT43016 543893 18-May-11 NINE MILE POINT NUCLEAR STATION 3035200 7722154 710DUOTT43016 543894 18-May-11 NINE MILE POINT NUCLEAR STATION 3035200 7722154 710DUOTT37156 544072 8-Jun-11 NINE MILE POINT NUCLEAR STATION 3035200 7722154 710DU0TT37156 544073 8-Jun-11 NINE MILE POINT NUCLEAR STATION 3035200 Appendix A: 10 CFR Part 21 21-June-12 Constellation Energy Group Page 1 of 1
APPENDIX A: 10 CFR PART 21 NOTIFICATION - 21 JUNE 2012 DETROIT EDISON CO PURCHASE SERIAL RNII ORDER NUMBER MODEL NUMBER NUMBER SHIP DATE SITE SALES ORDER NM-388901 710DUOTT27000 527013 12-Dec-03 FERMI PLANT 1225541 NM-388901 710DUOTT27000 527102 6-Jan-04 FERMI PLANT 1225541 4700155721 710DUOTT27000 537367 12-Sep-08 FERMI PLANT 2172228 4700155721 710DUOTT27000 537368 12-Sep-08 FERMI PLANT 2172228 4700155721 710DUOTT27000 537369 12-Sep-08 FERMI PLANT 2172228 4700155721 710DUOTT27000 537370 12-Sep-08 FERMI PLANT 2172228 4700155721 710DUOTT27000 537371 12-Sep-08 FERMI PLANT 2172228 4700183721 710DUOTR27000 538379 19-Dec-08 FERMI PLANT 2231827 4700226599 710DUOTT27000 539254 9-Jun-09 FERMI PLANT 2329889 4700253478 710DUOTT27000 539894 9-Sep-09 FERMI PLANT 2403447 4700253478 710DUOTT27000 539967 22-Sep-09 FERMI PLANT 2403447 4700253478 710DUOTI-27000 539968 22-Sep-09 FERMI PLANT 2403447 4700253478 710DUOTT27000 539969 22-Sep-09 FERMI PLANT 2403447 4700253478 710DUOTT27000 539970 22-Sep-09 FERMI PLANT 2403447 Appendix A: 10 CFR Part 21 21-June-12 Detroit Edison Co Page 1 of 1
APPENDIX A: 10 CFR PART 21 NOTIFICATION - 21 JUNE 2012 ENERGY NORTHWEST PURCHASE SERIAL RNII ORDER NUMBER MODEL NUMBER NUMBER SHIP DATE SITE SALES ORDER 00327926 REV 001 710DUOTT45059 538869 13-Mar-09 COLUMBIA GENERATING SYSTEM 2281215 00327926 REV 001 710DUOTT45059 538870 13-Mar-09 COLUMBIA GENERATING SYSTEM 2281215 00327926 REV 001 710DUOTT45059 538871 13-Mar-09 COLUMBIA GENERATING SYSTEM 2281215 00327926 REV 001 710DUOTT45059 538872 13-Mar-09 COLUMBIA GENERATING SYSTEM 2281215 00327926 REV 001 710DUOTS 538878 13-Mar-09 COLUMBIA GENERATING SYSTEM 2281215 00327926 REV 001 710DUOTS 538879 13-Mar-09 COLUMBIA GENERATING SYSTEM 2281215 00327926 REV 001 710DUOTS 538880 13-Mar-09 COLUMBIA GENERATING SYSTEM 2281215 00327926 REV 001 710DUOTS 538881 13-Mar-09 COLUMBIA GENERATING SYSTEM 2281215 333286 710DUOTS 543451 26-Apr-11 COLUMBIA GENERATING SYSTEM 3051192 333286 710DUOTT45059 543452 26-Apr-11 COLUMBIA GENERATING SYSTEM 3051192 333286 710DUOT745059 544304 30-Jun-11 COLUMBIA GENERATING SYSTEM 3051192 333286 710DUOTS 544323 30-Jun-11 COLUMBIA GENERATING SYSTEM 3051192 Appendix A: 10 CFR Part 21 21-June-12 Energy Northwest Page 1 of 1
APPENDIX A: 10 CFR PART 21 NOTIFICATION - 21 JUNE 2012 ENTERGY CORP PURCHASE SERIAL RNII ORDER NUMBER MODEL NUMBER NUMBER SHIP DATE SITE SALES ORDER 4500546789 710DUOTT27000 531979 3-Apr-06 JAMES A FITZPATRICK NPP 1674754 4500546789 710DUOTT27000 531980 3-Apr-06 JAMES A FITZPATRICK NPP 1674754 4500546789 710DUOTT27000 531981 3-Apr-06 JAMES A FITZPATRICK NPP 1674754 4500546789 710DUOTT27000 531982 3-Apr-06 JAMES A FITZPATRICK NPP 1674754 4500546789 710DUOTT27000 531983 3-Apr-06 JAMES A FITZPATRICK NPP 1674754 4500554310 710DUOTR34033 534673 7-May-07 JAMES A FITZPATRICK NPP 1848593 4500554310 710DUOTR34033 534674 7-May-07 JAMES A FITZPATRICK NPP 1848593 4500554310 710DUOTR34033 534675 7-May-07 JAMES A FITZPATRICK NPP 1848593 10174727 REVO01 710DUOTR34033 536358 3-Mar-08 JAMES A FITZPATRICK NPP 2028404 10174727 REV001 710DUOTR34033 536359 3-Mar-08 JAMES A FITZPATRICK NPP 2028404 10174727 REV001 710DUOTR34033 536360 3-Mar-08 JAMES A FITZPATRICK NPP 2028404 10174727 REVO01 710DUOTR34033 536361 3-Mar-08 JAMES A FITZPATRICK NPP 2028404 10174727 REVO01 710DUOTR34033 536401 5-Mar-08 JAMES A FITZPATRICK NPP 2028404 10174727 REV001 710DUOTR34033 536402 5-Mar-08 JAMES A FITZPATRICK NPP 2028404 10174727 REVO01 710DUOTR34033 536403 5-Mar-08 JAMES A FITZPATRICK NPP 2028404 10174727 REVO01 710DUOTR34033 536404 5-Mar-08 JAMES A FITZPATRICK NPP 2028404 10174727 REV001 710DUOTR34033 536405 5-Mar-08 JAMES A FITZPATRICK NPP 2028404 10190952 710DUOTT24015 537190 21-Jul-08 RIVER BEND STATION 2107483 10190952 710DUOTT24015 537191 21-Jul-08 RIVER BEND STATION 2107483 10235125 710DUOTT27000 539664 4-Aug-09 JAMES A FITZPATRICK NPP 2377485 10235125 710DUOTT27000 539665 4-Aug-09 JAMES A FITZPATRICK NPP 2377485 10235125 710DUOTT27000 539666 4-Aug-09 JAMES A FITZPATRICK NPP 2377485 10235125 710DUOTT27000 539667 4-Aug-09 JAMES A FITZPATRICK NPP 2377485 10235125 710DUOTT27000 539668 4-Aug-09 JAMES A FITZPATRICK NPP 2377485 10235125 710DUOTT27000 539669 4-Aug-09 JAMES A FITZPATRICK NPP 2377485 10239775 REV 001 710DUlTS 540349 23-Nov-09 RIVER BEND STATION 2354981 10239775 REV 001 710DUlTS 540350 23-Nov-09 RIVER BEND STATION 2354981 10239775 REV 001 710DUlTS 540351 23-Nov-09 RIVER BEND STATION 2354981 00076959 REV 001 REL 00290 710DUOTS 541044 1-Mar-10 JAMES A FITZPATRICK NPP 2449691 00076959 REV 001 REL 00290 710DUOTS 541045 1-Mar-10 JAMES A FITZPATRICK NPP 2449691 10260754 710DUOTT27000 540940 9-Mar-10 JAMES A FITZPATRICK NPP 2456225 10260754 710DUOTT27000 540941 9-Mar-10 JAMES A FITZPATRICK NPP 2456225 10260754 710DUOTT27000 540942 9-Mar-10 JAMES A FITZPATRICK NPP 2456225 10260754 710DU0TT27000 540943 9-Mar-10 JAMES A FITZPATRICK NPP 2456225 10260754 710DUOnT27000 540944 9-Mar-10 JAMES A FITZPATRICK NPP 2456225 Appendix A: 10 CFR Part 21 21-June-12 Entergy Corp Page 1 of 2
10260754 710DUOTT27000 540945 9-Mar-10 JAMES A FITZPATRICK NPP 2456225 10260754 710DUOTT27000 540983 9-Mar-10 JAMES A FITZPATRICK NPP 2456225 10260754 710DU01T27000 540984 9-Mar-10 JAMES A FITZPATRICK NPP 2456225 10260754 710DUOTT27000 540985 9-Mar-10 JAMES A FITZPATRICK NPP 2456225 10260754 710DU01T27000 540986 9-Mar-10 JAMES A FITZPATRICK NPP 2456225 10260754 710DUOTT27000 540987 9-Mar-10 JAMES A FITZPATRICK NPP 2456225 10260754 710DUOT-27000 540988 9-Mar-10 JAMES A FITZPATRICK NPP 2456225 10260754 710DUOTT27000 541096 9-Mar-10 JAMES A FITZPATRICK NPP 2456225 10260754 710DUOTT27000 541097 9-Mar-10 JAMES A FITZPATRICK NPP 2456225 10260754 710DUOTT27000 541098 9-Mar-10 JAMES A FITZPATRICK NPP 2456225 10260754 710DUOTT27000 541099 9-Mar-10 JAMES A FITZPATRICK NPP 2456225 10260754 710DU0T-27000 541100 9-Mar-10 JAMES A FITZPATRICK NPP 2456225 10278466 710DUOTS 541341 17-May-10 RIVER BEND STATION 2546604 10278466 710DUOTS 541342 17-May-10 RIVER BEND STATION 2546604 10272854 710DU0TF27000 541375 26-May-10 GRAND GULF NUCLEAR STATION 2519319 10272854 710DUOTT27000 541376 26-May-10 GRAND GULF NUCLEAR STATION 2519319 10272854 710DUOTT27000 541377 26-May-10 GRAND GULF NUCLEAR STATION 2519319 10280539 REV 001 710DUOTS 541472 8-Jun-10 JAMES A FITZPATRICK NPP 2558329 10280539 REV 001 710DUOTS 541473 8-Jun-10 JAMES A FITZPATRICK NPP 2558329 10280539 REV 001 710DUOTS 541474 8-Jun-10 JAMES A FITZPATRICK NPP 2558329 10318875 710DUOTR34033 544301 28-Jun-11 JAMES A FITZPATRICK NPP 3114461 10312497 710DUOTS 544318 30-Jun-11 JAMES A FITZPATRICK NPP 3072521 10312497 710DUOTS 544319 30-Jun-11 JAMES A FITZPATRICK NPP 3072521 10312497 710DUOTS 544320 30-Jun-11 JAMES A FITZPATRICK NPP 3072521 10312497 710DUOTS 544321 30-Jun-11 JAMES A FITZPATRICK NPP 3072521 10312497 710DUOTS 544322 30-Jun-11 JAMES A FITZPATRICK NPP 3072521 10340184 REV 003 710DUOTR34033 546158 10-May-12 JAMES A FITZPATRICK NPP 3274736 10340184 REV 003 710DUOTR34033 546159 10-May-12 JAMES A FITZPATRICK NPP 3274736 10340184 REV 003 710DUOTR34033 546160 10-May-12 JAMES A FITZPATRICK NPP 3274736
- NOTE: THESE 710 UNITS WERE ORIGNALLY SHIPPED TO QUAD CITIES NUCLEAR STATION (EXELON GENERATION CO LLC)
BUT WERE TRANSFERRED TO JAMES A FITZPATRICK NPP IN JUNE 2010.
Appendix Ak 10 CFR Part 21 21-June-12 Entry Corp Page 2 of 2
APPENDIX A: 10 CFR PART 21 NOTIFICATION - 21 JUNE 2012 EXELON GENERATION CO LLC PURCHASE SERIAL RNII ORDER NUMBER MODEL NUMBER NUMBER SHIP DATE SITE SALES ORDER 00076959 REL 00071 710DUOTT23032 532762 11-Jul-06 QUAD CITIES NUCLEAR STATION 1675760 0007696959 RLS 00084 710DUOTT36157 533005 10-Aug-06 QUAD CITIES NUCLEAR STATION 1711118 0007696959 RLS 00084 710DUOTT36157 533006 10-Aug-06 QUAD CITIES NUCLEAR STATION 1711118 00076959 REV 001 REL 00088 710DUOT-T27000 533359 15-Sep-06 QUAD CITIES NUCLEAR STATION 1728559 00076959 REV 001 REL 00081 710DUOTT23032 533518 31-Oct-06 QUAD CITIES NUCLEAR STATION 1699406 00076959 REV 001 REL 00081 710DUOTT23032 533519 31-Oct-06 QUAD CITIES NUCLEAR STATION 1699406 90 102205 REV 2 REL 27 710DUOTT16000 534342 27-Mar-07 PEACH BOTTOM ATOMIC POWER STATION 1817498 90 102205 REV 2 REL 27 710DUOTT16000 534343 27-Mar-07 PEACH BOTTOM ATOMIC POWER STATION 1817498 90 102205 REV 2 REL 27 710DUOTT16000 534344 27-Mar-07 PEACH BOTTOM ATOMIC POWER STATION 1817498 90 102205 REV 2 REL 27 710DUOTT16000 534345 27-Mar-07 PEACH BOTTOM ATOMIC POWER STATION 1817498 90 102205 REV 2 REL 27 710DUOTT16000 534346 27-Mar-07 PEACH BOTTOM ATOMIC POWER STATION 1817498 90 102205 REV 2 REL 27 710DUOTT16000 534347 27-Mar-07 PEACH BOTTOM ATOMIC POWER STATION 1817498 90 102205 REV 2 REL 27 710DUOTT16000 534348 27-Mar-07 PEACH BOTTOM ATOMIC POWER STATION 1817498 90 102205 REL80 REV1 710DUOTT16000 536067 19-Dec-07 PEACH BOTTOM ATOMIC POWER STATION 1999720 90 102205 REL8O REV1 710DUOTT16000 536068 19-Dec-07 PEACH BOTTOM ATOMIC POWER STATION 1999720 00076959 RELOO172 REV001 710DUORA1 536069 19-Dec-07 LASALLE PLANT 2020297 90 102205 REL83 REV2 710DUOTT27000 536152 28-Dec-07 LIMERICK GENERATING STATION 2042177 90 102205 REL83 REV2 710DUOTT27000 536153 28-Dec-07 LIMERICK GENERATING STATION 2042177 00076959 REV 001 REL 00206 710DUOTT27000 538083 12-Nov-08 QUAD CITIES NUCLEAR STATION 2188911 90 102205 REV 1 REL 116 710DUOTT16000 538163 2-Dec-08 PEACH BOTTOM ATOMIC POWER STATION 2223588 90 102205 REV 1 REL 116 710DUOTT16000 538164 2-Dec-08 PEACH BOTTOM ATOMIC POWER STATION 2223588 90 033192 REV 2 710DUOTS 540030 12-Oct-09 LIMERICK GENERATING STATION 2409253 90 033192 REV 2 710DUOTS 540031 12-Oct-09 LIMERICK GENERATING STATION 2409253 00076959 REV 002 REL 00299 710DUOTR16026 540966 22-Feb-10 DRESDEN PLANT 2483512 00076959 REV 002 REL 00299 710DUOTR16026 540967 22-Feb-10 DRESDEN PLANT 2483512 00076959 REV 002 REL 00299 710DUOTR16026 540968 22-Feb-10 DRESDEN PLANT 2483512 00076959 REV 002 REL 00299 710DUOTR16026 540969 22-Feb-10 DRESDEN PLANT 2483512 00076959 REV 001 REL 00290 710DUOTS 541042 1-Mar-10 QUAD CITIES NUCLEAR STATION 2449691 00076959 REV 001 REL 00290 710DUOTS 541043 1-Mar-10 QUAD CITIES NUCLEAR STATION 2449691 00076959 REV 001 REL 00290 710DUOTS 541046 1-Mar-10 QUAD CITIES NUCLEAR STATION 2449691 00076959 REV 001 REL 00290 710DUOTS 541047 1-Mar-10 QUAD CITIES NUCLEAR STATION 2449691 00076959 REV 001 REL 00290 710DUOTS 541048 1-Mar-10 QUAD CITIES NUCLEAR STATION 2449691 00076959 REV 002 REL 00299 710DUOTS 541140 22-Mar-10 DRESDEN PLANT 2483512 Appendix A: 10 CFR Part 21 21-June-12 Exelon Generation Co LLC Page 1 of 3
00076959 REV 002 REL 00299 710DUOTS 541141 22-Mar-10 DRESDEN PLANT 2483512 00076959 REV 002 REL 00299 710DUOTS 541142 22-Mar-10 DRESDEN PLANT 2483512 90 076959 REL 3 710DUOTT16000 541183 6-Apr-10 PEACH BOTTOM ATOMIC POWER STATION 2511250 go 076959 REL 3 710DUOTI16000 541184 6-Apr-10 PEACH BOTTOM ATOMIC POWER STATION 2511250 00076959 REV 002 REL 00299 710DUOTR16026 541217 14-Apr-10 DRESDEN PLANT 2483512 00076959 REV 002 REL 00299 710DUOTR16026 541218 14-Apr-10 DRESDEN PLANT 2483512 00076959 REV 002 REL 00299 710DUOTR16026 541219 14-Apr-10 DRESDEN PLANT 2483512 00076959 REV 002 REL 00299 710DUOTR16026 541220 14-Apr-10 DRESDEN PLANT 2483512 90 039033 REV 1 710DUOTT27000 541822 8-Sep-10 LIMERICK GENERATING STATION 2590013 90 039033 REV 1 710DUOTT27000 541823 8-Sep-10 LIMERICK GENERATING STATION 2590013 90039879 710DUOTT27000 541997 21-Oct-10 LIMERICK GENERATING STATION 2621218 90039879 710DUOTT27000 541998 21-Oct-10 LIMERICK GENERATING STATION 2621218 90039879 710DU0TT27000 541999 21-Oct-10 LIMERICK GENERATING STATION 2621218 00076959 REL 00333 710DUOTS 542309 6-Dec-10 QUAD CITIES NUCLEAR STATION 2637850 00076959 REL 00333 710DUOTS 542310 6-Dec-10 QUAD CITIES NUCLEAR STATION 2637850 00076959 REL 00333 710DUOTS 542311 6-Dec-10 QUAD CITIES NUCLEAR STATION 2637850 00076959 REL 00333 710DUOTS 542312 6-Dec-10 QUAD CITIES NUCLEAR STATION 2637850 00076959 REL 00333 710DUOTS 542313 6-Dec-10 QUAD CITIES NUCLEAR STATION 2637850 00076959 REL 00333 710DUOTS 542314 6-Dec-10 QUAD CITIES NUCLEAR STATION 2637850 00076959 REL 00333 710DUOTS 542315 6-Dec-10 QUAD CITIES NUCLEAR STATION 2637850 00076959 REL 00333 710DUOTS 542316 6-Dec-10 QUAD CITIES NUCLEAR STATION 2637850 00076959 REL 00333 710DUOTS 542317 6-Dec-10 QUAD CITIES NUCLEAR STATION 2637850 00076959 REL 00333 710DUOTS 542318 6-Dec-10 QUAD CITIES NUCLEAR STATION 2637850 90 076959 REL 7 710DUOTT16000 542150 7-Dec-10 PEACH BOTTOM ATOMIC POWER STATION 2642603 90 076959 REL 7 710DUOTT16000 542151 7-Dec-10 PEACH BOTTOM ATOMIC POWER STATION 2642603 00076959 REL 00334 710DUOTR16026 543399 4-Apr-11 QUAD CITIES NUCLEAR STATION 2637870 00076959 REL 00334 710DUOTR16026 543400 4-Apr-11 QUAD CITIES NUCLEAR STATION 2637870 00076959 REV 001 REL 00363 710DUOTT36157 543690 15-Apr-11 QUAD CITIES NUCLEAR STATION 3034193 00076959 REV 001 REL 00363 710DU0TT36157 543692 18-Apr-11 QUAD CITIES NUCLEAR STATION 3034193 00076959 REV 001 REL 00363 710DUOTT36157 543693 18-Apr-11 QUAD CITIES NUCLEAR STATION 3034193 00076959 REV 001 REL 00363 710DUOTT36157 543691 19-Apr-11 QUAD CITIES NUCLEAR STATION 3034193 00076959 REV 001 REL 00363 7100UOTT36157 543689 20-Apr-11 QUAD CITIES NUCLEAR STATION 3034193 00076959 REL 00334 710DUOTR16026 543765 26-Apr-11 QUAD CITIES NUCLEAR STATION 2637870 00076959 REL 00334 710DUOTR16026 543766 26-Apr-11 QUAD CITIES NUCLEAR STATION 2637870 00076959 REL 00334 710DUOTR16026 543767 26-Apr-11 QUAD CITIES NUCLEAR STATION 2637870 00076959 REL 00334 710DUOTR16026 543768 26-Apr-11 QUAD CITIES NUCLEAR STATION 2637870 00076959 REL 00334 710DUOTR16026 543769 26-Apr-11 QUAD CITIES NUCLEAR STATION 2637870 Appendix A: 10 CFR Part 21 21-June-12 Exelon Generation Co LLC Page 2 of 3
00076959 REL 00334 710DUOTR16026 543770 26-Apr-11 QUAD CITIES NUCLEAR STATION 2637870 00076959 REL 00334 710DUOTR16026 543771 26-Apr-11 QUAD CITIES NUCLEAR STATION 2637870 00076959 REL 00334 710DUOTR16026 543772 26-Apr-11 QUAD CITIES NUCLEAR STATION 2637870 00076959 REV 001 REL 00345 710DUOTS 543781 29-Apr-11 DRESDEN PLANT 3000577 00076959 REV 001 REL 00345 710DUOTS 543782 29-Apr-11 DRESDEN PLANT 3000577 00076959 REV 001 REL 00345 710DUOTS 543783 29-Apr-11 DRESDEN PLANT 3000577 00076959 REV 001 REL 00345 710DUOTS 543784 29-Apr-11 DRESDEN PLANT 3000577 00076959 REV 001 REL 00345 710DUOTS 543785 29-Apr-11 DRESDEN PLANT 3000577 00076959 REV 001 REL 00345 710DUOTS 543786 29-Apr-11 DRESDEN PLANT 3000577 00076959 REV 001 REL 00359 710DUOTT27000 543852 5-May-11 QUAD CITIES NUCLEAR STATION 3035249 00076959 REV 001 REL 00345 710DUOTR16026 543864 11-May-11 DRESDEN PLANT 3000577 00076959 REV 001 REL 00345 710DUOTR16026 543865 11-May-11 DRESDEN PLANT 3000577 00076959 REV 001 REL 00345 710DUOTR16026 543866 11-May-11 DRESDEN PLANT 3000577 00076959 REV 001 REL 00345 710DUOTR16026 543867 11-May-11 DRESDEN PLANT 3000577 00076959 REV 001 REL 00345 710DUOTR16026 543868 11-May-11 DRESDEN PLANT 3000577 00076959 REV 001 REL 00345 710DUOTR16026 543869 ll-May-11 DRESDEN PLANT 3000577 00076959 REV 001 REL 00345 710DUOTR16026 543870 ll-May-11 DRESDEN PLANT 3000577 00076959 REV 001 REL 00345 710DUOTR16026 543871 11-May-11 DRESDEN PLANT 3000577 00076959 REV 001 REL 00345 710DUOTS 543934 18-May-11 DRESDEN PLANT 3000577 00076959 REV 001 REL 00345 710DUOTS 543935 18-May-11 DRESDEN PLANT 3000577 00076959 REV 001 REL 00345 710DUOTS 543936 18-May-11 DRESDEN PLANT 3000577 00076959 REV 001 REL 00345 710DUOTS 543937 18-May-11 DRESDEN PLANT 3000577 00076959 REV 001 REL 00345 710DUOTR16026 543939 18-May-11 DRESDEN PLANT 3000577 00076959 REV 001 REL 00345 710DUOTR16026 543938 24-May-11 DRESDEN PLANT 3000577 00076959 REL 00383 710DUOTS 544315 29-Jun-11 DRESDEN PLANT 3103005 00076959 REL 00383 710DUOTS 544316 29-Jun-11 DRESDEN PLANT 3103005 00076959 REL 00383 710DUOTS 544317 29-Jun-11 DRESDEN PLANT 3103005 00076959 REL 00392 710DUOTT27000 545148 16-Nov-11 QUAD CITIES NUCLEAR STATION 3187215 00076959 REL 00392 710DUOTT27000 545149 16-Nov-11 QUAD CITIES NUCLEAR STATION 3187215 00076959 REL 00392 710DUOTT27000 545150 16-Nov-11 QUAD CITIES NUCLEAR STATION 3187215 00076959 REL 00397 710DUOTT27000 545554 5-Jan-12 QUAD CITIES NUCLEAR STATION 3213642 00076959 REL 00397 710DU0TT27000 545555 5-Jan-12 QUAD CITIES NUCLEAR STATION 3213642 00076959 REV 001 REL 00403 710DUOTT27000 545668 1-Feb-12 QUAD CITIES NUCLEAR STATION 3234340 00076959 REV 001 REL 00406 710DUOTR16026 545735 20-Feb-12 DRESDEN PLANT 3248533 00076959 REL 00424 710DUOTS 545849 9-Mar-12 QUAD CITIES NUCLEAR STATION 3274764 00076959 REL 00424 710DUOTS 545850 9-Mar-12 QUAD CITIES NUCLEAR STATION 3274764 Appendix A: 10 CFR Part 21 21-June-12 Exelon Generation Go LLC Page 3 of 3
APPENDIX A: 10 CFR PART 21 NOTIFICATION - 21 JUNE 2012 FIRST ENERGY CORP PURCHASE SERIAL RNII ORDER NUMBER MODEL NUMBER NUMBER SHIP DATE SITE SALES ORDER 45183445 710DUOTT27000 531827 17-Mar-06 PERRY PLANT 1662617 45183445 710DUOTT27000 531828 17-Mar-06 PERRY PLANT 1662617 45183445 710DU0TT27000 531829 17-Mar-06 PERRY PLANT 1662617 45183445 710DUOTT27000 531830 17-Mar-06 PERRY PLANT 1662617 45183445 710DUOTT27000 531831 17-Mar-06 PERRY PLANT 1662617 45183445 710DUOTT27000 531833 17-Mar-06 PERRY PLANT 1662617 45183445 710DUOTT27000 531834 17-Mar-06 PERRY PLANT 1662617 45289894 710DUOTT27000 538680 19-Feb-09 PERRY PLANT 2262953 45289894 710DUOTT27000 538681 19-Feb-09 PERRY PLANT 2262953 45289894 710DUOTT27000 538682 19-Feb-09 PERRY PLANT 2262953 45289894 710DUOTT27000 538683 19-Feb-09 PERRY PLANT 2262953 45289894 710DUOTT27000 538684 19-Feb-09 PERRY PLANT 2262953 45289894 710DUOTT27000 538685 19-Feb-09 PERRY PLANT 2262953 45289894 710DUOTT27000 538686 19-Feb-09 PERRY PLANT 2262953 45289894 710DU0TT27000 538687 19-Feb-09 PERRY PLANT 2262953 45289894 710DUOT"27000 538688 19-Feb-09 PERRY PLANT 2262953 45289894 710DUOTT27000 538689 19-Feb-09 PERRY PLANT 2262953 45289894 710DUOTT27000 538728 20-Feb-09 PERRY PLANT 2262953 45289894 710DUOTT27000 538729 20-Feb-09 PERRY PLANT 2262953 45289894 710DU0TI-27000 538730 20-Feb-09 PERRY PLANT 2262953 45289894 710DU0TT27000 538731 20-Feb-09 PERRY PLANT 2262953 45289894 710DUOTT27000 538732 20-Feb-09 PERRY PLANT 2262953 45289894 710DUOTT27000 538733 20-Feb-09 PERRY PLANT 2262953 45289894 710DU0TT27000 538734 20-Feb-09 PERRY PLANT 2262953 45289894 710DU0TT27000 538735 20-Feb-09 PERRY PLANT 2262953 45289894 710DUOTT27000 538736 20-Feb-09 PERRY PLANT 2262953 45289894 710DU0TT27000 538737 20-Feb-09 PERRY PLANT 2262953 45289894 710DUOTT27000 538832 5-Mar-09 PERRYPLANT 2262953 45289894 710DUOTT27000 538833 5-Mar-09 PERRY PLANT 2262953 45289894 710DUOTT27000 538834 5-Mar-09 PERRY PLANT 2262953 45289894 710DUO1T27000 538835 5-Mar-09 PERRY PLANT 2262953 45289894 710DUOTT27000 538836 5-Mar-09 PERRY PLANT 2262953 45289894 710DUOTT27000 538837 5-Mar-09 PERRY PLANT 2262953 45289894 710DUOTT27000 538838 5-Mar-09 PERRY PLANT 2262953 45289894 710DUOTT27000 538839 5-Mar-09 PERRY PLANT 2262953 45289894 710DUOTT27000 538840 5-Mar-09 PERRY PLANT 2262953 Appendix A: 10 CFR Part 21 21-June-12 First Energy Corp Page 1 of 4
45289894 710DUOTT27000 538841 5-Mar-09 PERRY PLANT 2262953 45289894 710DUOTT27000 538942 26-Mar-09 PERRY PLANT 2262953 45289894 710DU01T27000 538943 26-Mar-09 PERRY PLANT 2262953 45289894 710DUOTT27000 538944 26-Mar-09 PERRY PLANT 2262953 45289894 710DU0"T27000 538945 26-Mar-09 PERRY PLANT 2262953 45289894 710DUOTT27000 538946 26-Mar-09 PERRY PLANT 2262953 45289894 710DU0TT27000 538947 26-Mar-09 PERRY PLANT 2262953 45289894 710DUOTT27000 538948 26-Mar-09 PERRY PLANT 2262953 45289894 710DUOTT27000 538949 26-Mar-09 PERRY PLANT 2262953 45289894 710DU0TT27000 538950 26-Mar-09 PERRY PLANT 2262953 45289894 710DU0TT27000 538951 26-Mar-09 PERRY PLANT 2262953 45289894 710DUOTT27000 538986 1-Apr-09 PERRY PLANT 2262953 45289894 7100UOTT27000 538987 1-Apr-09 PERRY PLANT 2262953 45289894 710DUOTT27000 538988 1-Apr-09 PERRY PLANT 2262953 45289894 710DUOTT27000 538989 1-Apr-09 PERRY PLANT 2262953 45289894 710DUOTT27000 538990 1-Apr-09 PERRY PLANT 2262953 45289894 710DUOTT27000 538991 1-Apr-09 PERRY PLANT 2262953 45289894 710DU0TT27000 538992 1-Apr-09 PERRY PLANT 2262953 45289894 710DUOTT27000 538993 1-Apr-09 PERRY PLANT 2262953 45289894 710DU0TT27000 538994 1-Apr-09 PERRY PLANT 2262953 45289894 710DU0TT27000 538995 1-Apr-09 PERRY PLANT 2262953 45289894 710DU0TT27000 539020 8-Apr-09 PERRY PLANT 2262953 45289894 710DUOTT27000 539021 8-Apr-09 PERRY PLANT 2262953 45289894 710DU01T27000 539022 8-Apr-09 PERRY PLANT 2262953 45289894 710DUOTT27000 539023 8-Apr-09 PERRY PLANT 2262953 45289894 710DUOTT27000 539024 8-Apr-09 PERRY PLANT 2262953 45289894 710DU01T27000 539025 8-Apr-09 PERRY PLANT 2262953 45289894 710DUOTT27000 539026 8-Apr-09 PERRY PLANT 2262953 45289894 710DU0TT27000 539027 8-Apr-09 PERRY PLANT 2262953 45289894 710DUOTT27000 539028 8-Apr-09 PERRY PLANT 2262953 45289894 71ODUOTT27000 539029 8-Apr-09 PERRY PLANT 2262953 45289894 710DUOTT27000 539055 23-Apr-09 PERRY PLANT 2262953 45289894 710DUOTT27000 539056 23-Apr-09 PERRY PLANT 2262953 45289894 710DUOTT27000 539057 23-Apr-09 PERRY PLANT 2262953 45289894 710DU0TT27000 539058 23-Apr-09 PERRY PLANT 2262953 45289894 710DUOTT27000 539059 23-Apr-09 PERRY PLANT 2262953 45289894 710DU0"T27000 539060 23-Apr-09 PERRY PLANT 2262953 45289894 710DU0"127000 539061 23-Apr-09 PERRY PLANT 2262953 45289894 710DUOTT27000 539062 23-Apr-09 PERRY PLANT 2262953 45289894 710DUOTT27000 539063 23-Apr-09 PERRY PLANT 2262953 45289894 710DUOTT27000 539064 23-Apr-09 PERRY PLANT 2262953 Appendix A: 10 CFR Part 21 21-June-12 First Energy Corp Page 2 of 4
45295059 710DUOTS 539065 23-Apr-09 PERRY PLANT 2292382 45295059 710DUOTS 539066 23-Apr-09 PERRY PLANT 2292382 45295059 710DUOTS 539067 23-Apr-09 PERRY PLANT 2292382 45295059 710DUOTS 539068 23-Apr-09 PERRY PLANT 2292382 45295059 710DUOTS 539069 23-Apr-09 PERRY PLANT 2292382 45295059 710DUOTS 539070 23-Apr-09 PERRY PLANT 2292382 45289894 710DUOTT27000 539081 29-Apr-09 PERRY PLANT 2262953 45289894 710DUOTT27000 539082 29-Apr-09 PERRY PLANT 2262953 45289894 710DUOTT27000 539083 29-Apr-09 PERRY PLANT 2262953 45289894 710DU01T27000 539084 29-Apr-09 PERRY PLANT 2262953 45289894 710DUOTT27000 539085 29-Apr-09 PERRY PLANT 2262953 45289894 710DUOTT27000 539086 29-Apr-09 PERRY PLANT 2262953 45289894 710DUOTT27000 539087 29-Apr-09 PERRY PLANT 2262953 45289894 710DUOTT27000 539088 29-Apr-09 PERRY PLANT 2262953 45289894 710DUOTT27000 539089 29-Apr-09 PERRY PLANT 2262953 45289894 710DUOTT27000 539090 29-Apr-09 PERRY PLANT 2262953 45289894 710DUOTT27000 539195 22-May-09 PERRY PLANT 2262953 45289894 710DUOlT27000 539196 22-May-09 PERRY PLANT 2262953 45289894 710DU0TT27000 539197 22-May-09 PERRY PLANT 2262953 45289894 710DUOTT27000 539198 22-May-09 PERRY PLANT 2262953 45289894 710DUOTT27000 539199 22-May-09 PERRY PLANT 2262953 45289894 710DUOTT27000 539200 22-May-09 PERRY PLANT 2262953 45289894 710DUOTT27000 539201 22-May-09 PERRY PLANT 2262953 45289894 710DU01T27000 539202 22-May-09 PERRY PLANT 2262953 45289894 710DU01T27000 539203 22-May-09 PERRY PLANT 2262953 45289894 710DUOTT27000 539204 22-May-09 PERRY PLANT 2262953 45304789 710DUOTS 539465 8-Jul-09 PERRY PLANT 2346104 45304789 710DUOTS 539466 8-Jul-09 PERRY PLANT 2346104 45304789 710DUOTS 539467 8-Jul-09 PERRY PLANT 2346104 45304789 710DUOTS 539468 8-Jul-09 PERRY PLANT 2346104 45304789 710DUOTS 539469 8-Jul-09 PERRY PLANT 2346104 45304789 710DUOTS 539470 8-Jul-09 PERRY PLANT 2346104 45304789 710DUOTS 539471 8-Jul-09 PERRY PLANT 2346104 45304789 710DUOTS 539472 8-Jul-09 PERRY PLANT 2346104 45304789 710DUOTS 539473 8-Jul-09 PERRY PLANT 2346104 45304789 710DUOTS 539474 8-Jul-09 PERRY PLANT 2346104 45322862 710DUOTS 540902 15-Feb-10 PERRY PLANT 2459610 45322862 710DUOTS 540903 15-Feb-10 PERRY PLANT 2459610 45322862 710DUOTS 540904 15-Feb-10 PERRY PLANT 2459610 45322862 710DUOTS 540905 15-Feb-10 PERRY PLANT 2459610 45326719 710DUOTS 541205 7-Apr-10 PERRY PLANT 2481060 Appendix A: 10CFR Part 21 21-June-12 First Energy Corp Page 3 of 4
45326719 710DUOTS 541206 7-Apr-10 PERRY PLANT 2481060 45326719 710DUOTS 541207 7-Apr-10 PERRY PLANT 2481060 45339280 710DUOTS 541704 21-Jul-10 PERRY PLANT 2552474 45339280 710DUOTS 541705 21-Jul-10 PERRY PLANT 2552474 45357810 710DUOTT27000 543043 4-Mar-11 PERRY PLANT 2683856 45357810 710DUOTT27000 543044 4-Mar-11 PERRY PLANT 2683856 45357810 710DUOTr27000 543908 24-May-11 PERRY PLANT 2683856 45357810 710DUOTT27000 543909 24-May-11 PERRY PLANT 2683856 45357810 710DUOTT27000 543910 24-May-11 PERRY PLANT 2683856 45357810 710DU01T27000 543911 24-May-11 PERRY PLANT 2683856 45357810 710DU0TT27000 544194 14-Jun-11 PERRY PLANT 2683856 45357810 710DUOTT27000 544195 14-Jun-11 PERRY PLANT 2683856 45357810 710DUOTT27000 544196 14-Jun-11 PERRY PLANT 2683856 45357810 710DUOTT27000 544197 14-Jun-11 PERRY PLANT 2683856 45357810 710DUOTT27000 544198 14-Jun-11 PERRY PLANT 2683856 45357810 710DUOTT27000 544199 14-Jun-11 PERRY PLANT 2683856 45357810 710DUOTT27000 544200 14-Jun-11 PERRY PLANT 2683856 45357810 710DUOTT27000 544201 14-Jun-11 PERRY PLANT 2683856 45357810 710DUOTT27000 544271 24-Jun-11 PERRY PLANT 2683856 45357810 710DUOTT27000 544272 24-Jun-11 PERRY PLANT 2683856 45357810 710DUOTT27000 544273 24-Jun-11 PERRY PLANT 2683856 45357810 710DUOTT27000 544274 24-Jun-11 PERRY PLANT 2683856 45357810 710DUOTT27000 544275 24-Jun-11 PERRY PLANT 2683856 45357810 710DU0T-27000 544276 24-Jun-11 PERRY PLANT 2683856 45357810 710DUOT-27000 544277 24-Jun-11 PERRY PLANT 2683856 45357810 710DUOTT27000 544278 24-Jun-11 PERRY PLANT 2683856 45357810 710DUOTT27000 544279 24-Jun-11 PERRY PLANT 2683856 45357810 710DUOTT27000 544280 24-Jun-11 PERRY PLANT 2683856 45366579 710DUOTS 544371 14-Jul-11 PERRY PLANT 3072515 45366579 710DUOTS 544372 14-Jul-11 PERRY PLANT 3072515 45366579 710DUOTS 544373 14-Jul-11 PERRY PLANT 3072515 45366579 710DUOTS 544374 14-Jul-11 PERRY PLANT 3072515 45366579 710DUOTS 544375 14-Jul-11 PERRY PLANT 3072515 45366579 710DUOTS 544376 14-Jul-11 PERRY PLANT 3072515 45366579 710DUOTS 544377 14-Jul-11 PERRY PLANT 3072515 45366579 710DUOTS 544378 14-Jul-11 PERRY PLANT 3072515 45366590 710DUOTT27000 544405 25-Jul-11 PERRY PLANT 3072516 45366590 710DUOTT27000 544406 25-Jul-11 PERRY PLANT 3072516 Appendix A: 10 CFR Part 21 21-June-12 First Energy Corp Page 4 of 4
APPENDIX A: 10 CFR PART 21 NOTIFICATION - 21 JUNE 2012
_ GE NUCLEAR ENERGY PURCHASE SERIAL RNII ORDER NUMBER MODEL NUMBER NUMBER SHIP DATE SITE SALES ORDER 431002981 710DU0TT66588 532540 15-Jun-06 LUNGMEN UNIT 2 1713894 431002981 710DUOTT66588 532541 15-Jun-06 LUNGMEN UNIT 2 1713894 431002981 710DUOTT66588 532542 15-Jun-06 LUNGMEN UNIT 2 1713894 431002981 710DU0TT66588 532543 15-Jun-06 LUNGMEN UNIT 2 1713894 431002981 710DUOTT87038 532544 15-Jun-06 LUNGMEN UNIT 2 1713894 431002981 710DUOTT79034 532545 15-Jun-06 LUNGMEN UNIT 2 1713894 431002981 710DU0TT79034 532546 15-Jun-06 LUNGMEN UNIT 2 1713894 431002981 710DUOT-79034 532547 15-Jun-06 LUNGMEN UNIT 2 1713894 431002981 710DUOTT79034 532548 15-Jun-06 LUNGMEN UNIT 2 1713894 431002981 710DUOTT98029 532551 15-Jun-06 LUNGMEN UNIT 2 1713894 431002981 710DUOTT66053 532552 15-Jun-06 LUNGMEN UNIT 2 1713894 431002981 710DU0TT79034 532549 23-Jun-06 LUNGMEN UNIT 2 1713894 431002981 710DUOTT79034 532550 23-Jun-06 LUNGMEN UNIT 2 1713894 431002981 710DUOTT79591 532553 27-Jun-06 LUNGMEN UNIT 2 1713894 431002981 710DUOTT79591 532554 27-Jun-06 LUNGMEN UNIT 2 1713894 431002981 710DUOTT79591 532555 27-Jun-06 LUNGMEN UNIT 2 1713894 431002981 710DUOTT79591 532556 27-Jun-06 LUNGMEN UNIT 2 1713894 431002981 710DUOTT79591 532557 27-Jun-06 LUNGMEN UNIT 2 1713894 431002981 710DUORA1 532811 24-Jul-06 LUNGMEN UNIT 2 1713894 431002981 710DUORA1 532812 24-Jul-06 LUNGMEN UNIT 2 1713894 431002981 710DUORA1 532813 24-Jul-06 LUNGMEN UNIT 2 1713894 431002981 710DUORA1 532814 24-Jul-06 LUNGMEN UNIT 2 1713894 431006298 710DUOTT37032 532793 26-Jul-06 HOPE CREEK PLANT 1729031 431006298 710DUlTS 535169 20-Jul-07 PERRY PLANT 1729031 431006298 710DUlTS 535170 20-Jul-07 PERRY PLANT 1729031 431006298 710DUlTS 535171 20-Jul-07 PERRY PLANT 1729031 431006298 710DUlTS 535172 20-Jul-07 PERRY PLANT 1729031 431006298 710DUITS 535173 20-Jul-07 PERRY PLANT 1729031 431006298 710DUlTS 535174 20-Jul-07 PERRY PLANT 1729031 Appendix A: 10 CFR Part 21 21-June-12 GE Nuclear Energy Page 1 of I
APPENDIX A: 10 CFR PART 21 NOTIFICATION - 21 JUNE 2012 GEORGIA POWER CO PURCHASE SERIAL RNII ORDER NUMBER MODEL NUMBER NUMBER SHIP DATE SITE SALES ORDER 6070198 710DUOTS 534197 26-Feb-07 HATCH ELECTRIC GENERATING PLANT 1799841 6070198 710DUOTS 534198 26-Feb-07 HATCH ELECTRIC GENERATING PLANT 1799841 6070196 710DUITT24250 535455 18-Aug-07 HATCH ELECTRIC GENERATING PLANT 1799293 6070196 710DUlTT24250 535456 18-Aug-07 HATCH ELECTRIC GENERATING PLANT 1799293 Appendix A: 10 CFR Part 21 21-June-12 Georgia Power Co Page 1 of 1
APPENDIX A: 10 CFR PART 21 NOTIFICATION - 21 JUNE 2012 PROGRESS ENERGY CAROLINAS LLC PURCHASE SERIAL RNII ORDER NUMBER MODEL NUMBER NUMBER SHIP DATE SITE SALES ORDER 00332289 REV 002 710DUOTT27000 535306 8-Aug-07 BRUNSWICK PLANT 1957647 00332289 REV 002 710DUOTT27000 535307 8-Aug-07 BRUNSWICK PLANT 1957647 00332289 REV 002 710DUOTT27000 535375 14-Aug-07 BRUNSWICK PLANT 1957647 00332289 REV 002 710DUOTT27000 535376 14-Aug-07 BRUNSWICK PLANT 1957647 00363836 REV 001 710DUOTS 536898 27-May-08 BRUNSWICK PLANT 2076129 00363836 REV 001 710DUOTS 536899 27-May-08 BRUNSWICK PLANT 2076129 00363836 REV 001 710DUOTS 536900 27-May-08 BRUNSWICK PLANT 2076129 00363836 REV 001 710DUOTS 536901 27-May-08 BRUNSWICK PLANT 2076129 452798 710DUOTT27000 539994 28-Sep-09 BRUNSWICK PLANT 2387217 452798 710DUOTT27000 539995 28-Sep-09 BRUNSWICK PLANT 2387217 452798 710DUOTT27000 539996 28-Sep-09 BRUNSWICK PLANT 2387217 568319 710DUOTS 544438 5-Aug-11 BRUNSWICK PLANT 3113033 568319 710DUOTS 544439 5-Aug-11 BRUNSWICK PLANT 3113033 568319 710DUOTS 544440 5-Aug-11 BRUNSWICK PLANT 3113033 568319 710DUOTS 544441 5-Aug-11 BRUNSWICK PLANT 3113033 568319 710DUOTS 544442 5-Aug-11 BRUNSWICK PLANT 3113033 Appendix A: 10 CFR Part 21 21-June-12 Progress Energy Carolinas ILLC Page I of I
APPENDIX A: 10 CFR PART 21 NOTIFICATION - 21 JUNE 2012 TENNESSEE VALLEY AUTHORITY PURCHASE SERIAL RNII ORDER NUMBER MODEL NUMBER NUMBER SHIP DATE SITE SALES ORDER 00000151 REV 003 RISE 00081 710DUOTT27000 527665 7-May-04 BROWNS FERRY NUCLEAR PLANT 1273299 00000151 REV 003 RISE 00081 710DUOTI27000 527669 7-May-04 BROWNS FERRY NUCLEAR PLANT 1273299 00000151 REV 003 RISE 00081 710DU0TR27000 528182 13-Oct-04 BROWNS FERRY NUCLEAR PLANT 1273299 00000151 RLSE 00184 710DU0TT36590 531822 16-Mar-06 BROWNS FERRY NUCLEAR PLANT 1616878 00000151 RLSE 00184 710DUOTT36590 531823 16-Mar-06 BROWNS FERRY NUCLEAR PLANT 1616878 00000151 RLSE 00184 710DUOTT36590 531824 16-Mar-06 BROWNS FERRY NUCLEAR PLANT 1616878 00000151 REL 00198 710DU0TT27000 531873 20-Mar-06 BROWNS FERRY NUCLEAR PLANT 1673527 00000151 REL 00198 710DUOTT27000 531874 20-Mar-06 BROWNS FERRY NUCLEAR PLANT 1673527 00000151 REL 00207 710DUORA1 533154 21-Aug-06 CENTRAL LAB SERVICES 1709915 00000151 REL 00207 710DUORA1 533155 21-Aug-06 CENTRAL LAB SERVICES 1709915 00000151 REL 00207 710DUORA1 533156 21-Aug-06 CENTRAL LAB SERVICES 1709915 00000151 REL 00207 710DUORA1 533395 21-Sep-06 CENTRAL LAB SERVICES 1709915 00000151 REL 00207 710DUORA1 533396 21-Sep-06 CENTRAL LAB SERVICES 1709915 00000151 REL 00207 710DUORA1 533397 21-Sep-06 CENTRAL LAB SERVICES 1709915 00000151 RELO0290 710DU0TT36590 537055 18-Jun-08 BROWNS FERRY NUCLEAR PLANT 2127736 00000151 REL 00317 710DU0TT23028 539387 16-Jun-09 BROWNS FERRY NUCLEAR PLANT 2352229 00000151 REL 00317 710DUOTT23028 539388 16-Jun-09 BROWNS FERRY NUCLEAR PLANT 2352229 70478 710DUOTT27000 541185 6-Apr-10 BROWNS FERRY NUCLEAR PLANT 2490138 82135-1 710DUOTT27000 541245 15-Apr-10 BROWNS FERRY NUCLEAR PLANT 2529897 130944-1 710DUOTT27000 541805 8-Sep-10 BROWNS FERRY NUCLEAR PLANT 2586636 130944-1 710DUOTT27000 541806 8-Sep-10 BROWNS FERRY NUCLEAR PLANT 2586636 373453 710DUOTR34170 545801 2-Mar-12 BROWNS FERRY NUCLEAR PLANT 3276499 Appendix A: 10 CFR Part 21 21-June-12 Tennessee Valley Authority Page 1 of 1
APPENDIX A: 10 CFR PART 21 NOTIFICATION - 21 JUNE 2012 U-SHUN ENTERPRISE CO LTD PURCHASE SERIAL RNII ORDER NUMBER MODEL NUMBER NUMBER SHIP DATE SITE SALES ORDER F-263-99-R1 (350-980180626W) 710DUOTR27000 541112 1-Apr-10 CHINSHAN PLANT 2493883 F-263-99-R1 (350-980180626W) 710DUOTR27000 541113 1-Apr-10 CHINSHAN PLANT 2493883 F-023-100 (351-000109068F) 710DUOTT70062 545608 15-Feb-12 KUOSHENG NUCLEAR POWER PLANT 3156637 F-023-100 (351-000109068F) 710DUOTT79026 545614 15-Feb-12 KUOSHENG NUCLEAR POWER PLANT 3156637 F-023-100 (351-0OO109068F) 710DUOTT70017 545643 15-Feb-12 KUOSHENG NUCLEAR POWER PLANT 3156637 F-023-100 (351-000109068F) 710DUOTT70017 545644 15-Feb-12 KUOSHENG NUCLEAR POWER PLANT 3156637 F-023-100 (351-000109068F) 710DUOTS 545659 15-Feb-12 KUOSHENG NUCLEAR POWER PLANT 3156637 F-023-100 (351-000109068F) 710DUOTS 545664 15-Feb-12 KUOSHENG NUCLEAR POWER PLANT 3156637 F-023-100 (351-000109068F) 710DUOTS 545665 15-Feb-12 KUOSHENG NUCLEAR POWER PLANT 3156637 F-023-100 (351-000109068F) 710DUOTS 545678 15-Feb-12 KUOSHENG NUCLEAR POWER PLANT 3156637 F-023-100 (351-000109068F) 71ODUOTS 545681 15-Feb-12 KUOSHENG NUCLEAR POWER PLANT 3156637 F-023-100 (351-000109068F) 710DUOTS 545686 15-Feb-12 KUOSHENG NUCLEAR POWER PLANT 3156637 F-023-100 (351-000109068F) 710DUOTT45595 545714 15-Feb-12 KUOSHENG NUCLEAR POWER PLANT 3156637 F-023-100 (351-000109068F) 710DUOTT45595 545715 15-Feb-12 KUOSHENG NUCLEAR POWER PLANT 3156637 F-023-100 (351-000109068F) 710DUOTT45596 545718 15-Feb-12 KUOSHENG NUCLEAR POWER PLANT 3156637 Appendix A: 10 CFR Part 21 21-June-12 U-Shun Enterprise Co Ltd Page 1 of I
APPENDIX A: 10 CFR PART 21 NOTIFICATION - 21 JUNE 2012 XCEL ENERGY PURCHASE SERIAL RNII ORDER NUMBER MODEL NUMBER NUMBER SHIP DATE SITE SALES ORDER 00004461 REV 001 710DUOTR34033 532860 2-Aug-06 MONTICELLO NUCLEAR GENERATING PLANT 1692442 00004461 REV 001 710DUORA1 533202 30-Aug-06 MONTICELLO NUCLEAR GENERATING PLANT 1692442 9092 710DU01T36032 533963 9-Jan-07 MONTICELLO NUCLEAR GENERATING PLANT 1783335 9092 710DUOTr36032 533964 9-Jan-07 MONTICELLO NUCLEAR GENERATING PLANT 1783335 12877 710DU0TT36054 534139 2-Feb-07 MONTICELLO NUCLEAR GENERATING PLANT 1833660 12877 710DUOTT36054 534140 2-Feb-07 MONTICELLO NUCLEAR GENERATING PLANT 1833660 12877 710DUOTT36054 534141 2-Feb-07 MONTICELLO NUCLEAR GENERATING PLANT 1833660 12877 710DUOTT36054 534142 2-Feb-07 MONTICELLO NUCLEAR GENERATING PLANT 1833660 18976 710DUOTT36032 535437 16-Aug-07 MONTICELLO NUCLEAR GENERATING PLANT 1938902 18976 710DUOTT36032 535438 16-Aug-07 MONTICELLO NUCLEAR GENERATING PLANT 1938902 18976 710DUOTI36032 535581 17-Sep-07 MONTICELLO NUCLEAR GENERATING PLANT 1938902 18976 710DUOTT36032 535582 17-Sep-07 MONTICELLO NUCLEAR GENERATING PLANT 1938902 18976 710DUOTI36032 535583 17-Sep-07 MONTICELLO NUCLEAR GENERATING PLANT 1938902 18976 710DUOTT36032 535584 17-Sep-07 MONTICELLO NUCLEAR GENERATING PLANT 1938902 18976 710DUOTT36032 535585 17-Sep-07 MONTICELLO NUCLEAR GENERATING PLANT 1938902 18976 710DUOTr36032 535586 17-Sep-07 MONTICELLO NUCLEAR GENERATING PLANT 1938902 18976 710DUOTT36032 535587 17-Sep-07 MONTICELLO NUCLEAR GENERATING PLANT 1938902 18976 710DUOTI36032 535588 17-Sep-07 MONTICELLO NUCLEAR GENERATING PLANT 1938902 18976 710DU0TT36032 535589 17-Sep-07 MONTICELLO NUCLEAR GENERATING PLANT 1938902 18976 710DUOTT36032 535590 17-Sep-07 MONTICELLO NUCLEAR GENERATING PLANT 1938902 18976 710DUOTT36032 535591 17-Sep-07 MONTICELLO NUCLEAR GENERATING PLANT 1938902 18976 710DUOTT36032 535592 17-Sep-07 MONTICELLO NUCLEAR GENERATING PLANT 1938902 18976 710DUOTT36032 535593 17-Sep-07 MONTICELLO NUCLEAR GENERATING PLANT 1938902 18976 710DU0TT36032 535594 17-Sep-07 MONTICELLO NUCLEAR GENERATING PLANT 1938902 18976 710DU0TT36032 535595 17-Sep-07 MONTICELLO NUCLEAR GENERATING PLANT 1938902 22576 710DUOTS 536692 6-May-08 MONTICELLO NUCLEAR GENERATING PLANT 2091657 22576 710DUOTS 536693 6-May-08 MONTICELLO NUCLEAR GENERATING PLANT 2091657 22576 710DUOTS 536694 6-May-08 MONTICELLO NUCLEAR GENERATING PLANT 2091657 22576 710DUOTS 536695 6-May-08 MONTICELLO NUCLEAR GENERATING PLANT 2091657 22576 710DUOTS 536696 6-May-08 MONTICELLO NUCLEAR GENERATING PLANT 2091657 22576 710DUOTS 536697 6-May-08 MONTICELLO NUCLEAR GENERATING PLANT 2091657 22576 710DUOTS 536698 6-May-08 MONTICELLO NUCLEAR GENERATING PLANT 2091657 22576 710DUOTS 536699 6-May-08 MONTICELLO NUCLEAR GENERATING PLANT 2091657 22576 710DUOTS 536700 6-May-08 MONTICELLO NUCLEAR GENERATING PLANT 2091657 Appendix A: 10 CFR Part 21 21-June-12 Xcel Energy Page 1 of I