Exelno Exelon Generation Company, LLC www.exeloncorp.com Quad Cities Nuclear Power Station Nucear 22710 2o6th Avenue North Cordova, I L 61242-9740 SVP-12-040 10 CFR 50.36a April 27, 2012 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D.C. 20555 Quad Cities Nuclear Power Station, Units 1 and 2 Renewed Facility Operating License Nos. DPR-29 and DPR-30 NRC Docket Nos. 50-254 and 50-265

Subject:

Radioactive Effluent Release Report for 2011

Reference:

Letter from William R. Gideon (Exelon Generation Company, LLC) to U. S. NRC, "Radioactive Effluent Release Report for 2010," dated April 27, 2011 Pursuant to Technical Specifications Section 5.6.3 and 10 CFR 50.36a, enclosed is the Quad Cities Nuclear Power Station Radioactive Effluent Release Report for January through December 2011. There were two abnormal releases that occurred during 2011. These releases, which resulted in a minor contribution to normal plant radioactive effluents, are discussed in detail in the report.

In addition, pursuant to Technical Specifications Section 5.5.1.c.3 and Offsite Dose Calculation Manual (ODCM) Section 12.7.4.3.3, enclosed is the current ODCM (CY-QC-1 70-301, Revision

10) which was revised in 2011.

The final enclosure (Attachment 3) is a correction to the Radioactive Effluent Release Report for 2010 which was submitted by the referenced letter.

Should you have any questions concerning this letter, please contact Mr. Wally J. Beck at (309) 227-2800.

Respectfully, Tim Hanley Site Vice President Quad Cities Nuclear Power Station

April 27, 2012 U. S. Nuclear Regulatory Commission Page 2 Attachments:

1. 2011 Annual Radioactive Effluent Release Report
2. CY-QC-170-301, Revision 10, Offsite Dose Calculation Manual
3. Errata/Correction to the 2010 Annual Radioactive Effluent Release Report cc:

Regional Administrator-NRC Region III NRC Senior Resident Inspector - Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Effluent & Waste Disposable Summary Gaseous Effluents - Summation of all Releases Period:

January - December 2011 Unit:

1 & 2 at Est.

A. Fission &.Activation Gases Unit Quarter 1 Quarter Quarter Quarter Total Total 2

3 4

Error %

1. Total Release Ci 1.11E+02 9.85E+01 3.82E+01 3.20E+01 2.80E+02 12.7
2.

Average Release Rate for the period pCi/sec 1.43E+01 1.25E+01 4.80E+00 4.02E+00

3.

Percent of ODCM limit(1) 1.08E-02 9.45E-03 3.41 E-03 3.13E-03 2.75E-03 2.42E-03 9.06E-04 8.03E-04 B. Iodine-131

1. Total Iodine-131 Ci 2.12E-03 3.17E-03 4.49E-04 2.39E-04 5.98E-03 41.7
2.

Average Release Rate for the period gCi/sec 2.73E-04 4.04E-04 5.65E-05 3.OOE-05

3.

Percent of ODCM limit N/A (2)

N/A(2)

N/A(2)

N/A(2)

C. Particulates >8 Days (3)

1.

Particulates with >8 day half-life Ci 2.20E-03 1.10E-03 6.01E-04 3.04E-04 4.21 E-03 I 32.2

2.

Average Release Rate for the period iiCi/sec 2.83E-04 1.40E-04 7.57E-05 3.82E-05

3.

Percent of ODCM limit N/A(2)

N/A(2)

N/A(2)

N/A(2)

4.

Gross Alpha Radioactivity Ci

<LLD (4)

<LLD(4 )

<LLD(4 )

<LLD(4)

D. Tritium

1. Total Release Ci 1.44E+01 1.58E+01 2.29E+01 1.89E+01 7.20E+01 ]i6.3I[
2.

Average Release Rate for the period pCi/sec 1.85E+00 2.01 E+00 2.88E+00 2.37E+00

3.

Percent of ODCM limit N/A(2)

N/A(2)

N/A(2)

N/A(2)

E. Carbon-14

1. Total Release Ci 7.36E+00 5.95E+00 7.58E+00 7.54E+00 2.84E+01 i N/Ai]i
2.

Average Release Rate for the period iCi/sec 9.46E-01 7.57E-01 9.53E-01 9.45E-01

3.

Percent of ODCM limit N/A (2)

N/A(2)

N/A(2)

N/A(2)

F. Iodine-131 & 133, Tritium, Particulates >8 days, & Carbon-14

1. PercentofODCM Limit 4.73E+00 F6.88E+00 1.12E+00 7.07E-01 (1)

% Noble gas gamma/noble gas beta dose limits (2)

Percent of ODCM limit is captured in aggregate in section F (3)

Nuclides with less than 8 day half-lives are not included per the ODCM, with the exception of those with regulatory required LLDs (La-1 40 and Mo-99)

(4)

Gaseous LLDs reported on page 6 of 72 Page 1 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Effluent & Waste Disposable Summary Gaseous Effluents Release Point Main Chimney (Elevated)

Period:

Januaryv-December 2011 Jnit:

1 &2 Nuclides I

Continuous Mode Batch Mode Released I

I

1. Fission Unit Quarter Quarter Quarter Quarter Total Quarter Quarter Quarter Quarter Total gases 1

2 3

4 1

2 3

4 Kr-85 Ci

<LLD(1)

<LLD(1 )

<LLD(1)

<LLD(1 )

<LLD(1 )

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

Kr-85m Ci 4.66E-01 4.07E-01 4.03E-01 1.46E-01 1.42E+00 N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

Kr-87 Ci 3.1OE+00 2.68E+00 1.01 E+00 8.99E-01 7.70E+00 N/A(2)

N/A(2 )

N/A(2 )

N/A(2)

N/A(2)

Kr-88 Ci 1.93E+00 1.73E+00 9.81 E-01 5.43E-01 5.18E+00 N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

Xe-1i33 Ci 4.59E-01 1.20E+00 7.69E-01 2.67E-01 2.70E+00 N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

X3-133m Ci

<LLD(1)

<LLD(')

4.72E-02

<LLD(')

4.72E-02 N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

Xe-1 35 Ci 4.OOE+00 3.13E+00 4.93E+00 8.11E-01 1.29E+01 N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

Xe-135m Ci 2.07E+01 1.93E+01 6.21E+00 6.01E+00 5.23E+01 N/A(2)

N/A(2)

N/A72 )

N/A(2)

N/A(2)

Xe-138 Ci 8.02E+01 6.98E+01 2.37E+01 2.31E+01 1.97E+02 N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

Ar-41 Ci 8.06E-02 1.17E-01 1.79E-01 1.74E-01 5.51 E-01 N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

Period Total Ci 1.11 E+02 9.85E+01 3.82E+01 3.20E+01 2.80E+02 N/A(2)

N/A(2)

N/A(2)

N/AM 2 )

N/A(2)

2. lodines II 1-131 Ci 2.09E-03 3.07E-03 4.40E-04 2.39E-04 5.83E-03 N/A(2)

N/A(2)

N/A(2 N/A(2)

N/A(2) 1-133 Ci 1.15E-02 5.70E-03 3.09E-03 1.97E-03 2.22E-02 N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2) 1-135 Ci 4.64E-03 3.11E-03

<LLD(1)

<LLD(1) 7.74E-03 N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

Period Total Ci 1.82E-02 1.19E-02 3.53E-03 2.21 E-03 3.58E-02 N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

3. Particulates > 8 days (3) 1 1

Sr-89 Ci 4.77E-04 2.01E-04 1.85E-04 1.45E-04 1.01E-03 N/A(2)

N/A (2) -N/A(

2 N/A(2 )

N/A(2)

Sr-90 Ci

<LLD(1)

<LLD()

<LLD(1 )

<LLD(0

<LLD(1)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

Cs-134 Ci

<LLD(')

<LLD(')

<LLD(1)

<LLD(1' )

LD1 N/A(2)

N/A( 2)

N/A(2 )

N/A(2 )

NfA( 2)

Cs-137 Ci

<LLD(')

<LLD(')

<LLD(1)

<LLD(')

<LLD(1)

N/A(2)

N/A( 2)

N/A(2 ))

N/A(2)

N/A(2 )

Ba-140 Ci 8.11 E-04 3.21 E-04 1.92E-04 5.79E-05 1.38E-03 N/A(2 )

N/A( 2)

N/A( 2 )

N/A(2 )

N/A(2 )

La-140 Ci 8.11 E-04 3.21 E-04 1.92E-04 5.79E-05 1.38E-03 N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

Cr-51 Ci

<LLD(1)

<LLD(')

<LLD(')

<LLD(1)

<LLD(1 )

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

Mn-54 Ci

<LLD(')

<LLD(1 )

<LLDY1)

<LLD(')

<LLD(')

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

Co-58 Ci

<LLD(1)

<LLD(1)

<LLD(1)

<LLD(1 )

<LLD(1)

N/A(2 )

N/A(2)

N/A(2 )

N/A(2 )

N/A( 2)

Co-60 Ci 7.31 E-05 11.12E-04

<LLD(1 )

<LLD(')

1.85E-04 N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

Mo-99 Ci

<LLD(')

<LLD(1)

<LLD(1 )

<LLD(1)

<LLD(1 )

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

Ag-110m Ci

<LLD(1)

<LLD(1 )

<LLD(1)

<LLD(1)

<LLD(1)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/AW2 )

Ce-141 Ci

<LLD(') <LLD(')

<LLD(')

<LLDO*)

<LLD(')

Ni/A(2)

N/A2 N/A2

/()NA2 Ce-144 Ci

<LLD(1 )

<LLD(1 )

<LLD(1 )

<LLDO1)

<LLD(')

N/A(2)

N/A(2)

N/A( 2 )

N/A(2)

N/A(2)

Period Total Ci 2.17E-03 11.08E-03 5.69E-04 2.61 E-04 3.96E-03 N/A(2 )

N/A(2 )

N/A(2 )

N/A(2 )

N/A(2)

(1)

(2)

(3)

Gaseous LLDs reported on page 6 of 72 No gaseous batch releases performed Nuclides with less than 8 day half-lives are not included per the ODCM, with the exception of those with regulatory required LLDs (La-1 40 and Mo-99)

Page 2 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Effluent & Waste Disposable Summary Gaseous Effluents Release Point Reactor Vents (Mixed Mode)

Period:

January - December 2011 Unit:

1 & 2 Nuclides Released Continuous Mode Batch Mode 11

1. Fission gases Unit t

Kr-85 ci Kr-85m ci Kr-87 Ci Kr-88 Ci Xe-133 Ci Xe-133m Ci Xe-135 ci Xe-135m ci Xe-1 38 Ci Ar-41 Qi Period Total Ci

2. lodines 1-131 Ci 3.42E-05 1.08E-04 8.83E-06 1-133 Ci

<LLD"'

1.06E-041 <LL[

1-135 Ci Period Total

3. Particulates

> 8 days(3)

Ci 3.42E-05 2.14E-04 8.83E-06 9,

9, Sr-89 C

Sr-90 Ci Cs-134 Ci Cs-137 ci

<LLD(')

<LLD(')

<LLD(')

NfA(2)

N/A (2 )

N/A( 2)

N/A (2)

N/ (2)___

<LD')

LLD0

<jj5Di A(2 N/A~2 N/A2 N/A2 NA2

<LLD~1 Fl) j7D(T

<LLD(')

N/A(2)

N/A(2)

N/A12)

N/A (2 )

9.94E-06j 1.19E-05 2.18E-05 N/A(2)

N/A~2 N/A(2T N/A(2)

N/A~2 Ba-140 Ci

<LLD'1"

<LLD"1'

<LLD"1' I<LLD"'

<LLD(')

N/AP2)

La-140 Ci

<LLD(1 )

<LLD(1)

Cr-51 Ci

<LLD(1 )

<LLD(1)

Mn-54 Ci

<LLD(')

<LLD(')

Co-58 Ci

<LLD(1 )

<LLD(')

1

<LLD(')

N/A~ 2 N/A (2)

N/A(2 N/A(2)

LN/A(2)

1 N/Azk'
1
1 Co-60 Ci 3.24E-05 1.49E-04 I2.23E-05 I3.13E-05 2.35E-04]I Mo___99_ ]Cij

<LLD('

<LLD(')

Ag-ib1 m JCi

<LLD(')

<LLD(')

1 N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

NfA( 2 )

N/A/ 2 A

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

.1 Ce-141 Ci

<LLD"1 )

<LLD"1)

Ci

<LLD(')

<LLD(')

<LLD(') J 1015 C

<LLD('

<LLD11

<LLD(')

<LL Period Total Ci 3.24E-05 1.49E-04 3.22E-05 4.32E-05 IL2.57E-04 1

N/A(2)

A ____

A.

I _________

S ii JL I _________

A __________

I _________

I _________

(1)

(2)

(3)

Gaseous LLDs reported on page 6 of 72 No gaseous batch releases Nuclides with less than 8 day half-lives are not included per the ODCM, with the exception of those with regulatory required LLDs (La-140 and Mo-99)

Page 3 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Effluent & Waste Disposal Summary Liquid Effluents - Summation of all Releases Period:

January - December 2011 Unit:

1 & 2 Quarter Quarter Quarter Est.

A. Fission & Activation Products Unit Quarter 1 Q

Q Q

Total Total 2

3 4 IError %

1.

Total Release (not including tritium, Ci

<LLD(2) 6.49E-03 9.14E-04 1.25E-03 8.65E-03 4.8 gases & alpha)

2.

Average diluted concentration iCi/mL N/A 1.78E-11 1.85E-12 3.31 E-12 during period

3.

Percent of applicable limit(1 )

WB N/A 6.87E-02 1.23E-05 2.99E-04 Organ N/A 4.34E-02 2.45E-05 1.51 E-04

4.

Maximum diluted concentration during batch discharges lCi/mL N/A 2.19E-08 N/A N/A B. Tritium

1.

Total Release Ci

<LLD(2) 5.07E-01 1.49E-03 3.59E-04 5.98E-03 4.1

2.

Average diluted concentration gCi/mL N/A 1.39E-09 3.02E-12 9.50E-13 during period

__Ci/m L

_N/A 1.39E-09 3.02E-12 9.50E-13

3.

Percent of applicable limit N/A 4.07E-05 1.43E-07 4.77E-08 C. Dissolved & Entrained Gases

1.

Total Release Ci

<LLD(2)

<LLD(2)

<LLD(2)

< <LLD 2

<LLD (2)

N/A

2.

Average diluted concentration flCi/ml N/A N/A N/A N/A during period

_Ci/mL _N/A N/A N/A N/A

3.

Percent of applicable limit N/A N/A N/A N/A D. Gross Alpha Activity

[

[1.

Total Release I

Ci

.<LLD1 21

<LLD1 21 [<LLD 121 I<LLD 1 21

<LLD(2 )I N/A E. Volume of Waste Released (prior to LI dilution)

Liters I.OOE+O0 2.28E+05 6.19E+04 3.71E+04 3.27E+05 F. Volume of Dilution Water Liters 2.72E+11 3.64E+11 4.94E+11 3.78E+11 1.51E+12 during period L1 1

(1)

(2)

Whole body/organ (ODCM)

Liquid LLDs reported on page 7 of 72 Page 4 of 72

Quad Cities Nuclear Power Station 2011 Annual. Radioactive Effluent Release Report Effluent & Waste Disposal Summary Liquid Effluents Release Po int Mississippi River Period:

Januarv - December 2011 Unit:

1 & 2 Nuclides Continuous Mode Batch Mode Released j __

1. Fission Unit Quarter Quarter Quarter Quarter Total Quarter Quarter Quarter Quarter Total 1

2 3

4 1

2 3

4 Activation Products Sr-89 Ci

<LLD(1 )

<LLD(1 )

<LLD(1 )

<LLD(1)

<LLD(1 )

N/A(2)

<LLD(1 )

N/A(2)

N/A(2)

<LLD(1)

Sr-90 Ci

<LLD(1 )

<LLD(1 )

<LLD(')

<LLD(1)

<LLD(1 )

N/A(2))

<LLD11 )

N/A(2)

N/A(2)

<LLD(1 )

Cs-134 Ci

<LLD(1 )

<LLD(')

<LLD(1 )

<LLD(1)

<LLD(')

N/A(2)

<LLD(1 )

N/A(2)

N/A(2)

<LLD(1)

Cs-137 Ci

<LLD(1 )

<LLD(1)

<LLD(1 )

3.OOE-05 3.OOE-05 N/A(2) 4.46E-05 N/A(2)

N/A(2) 4.46E-05 1-131 Ci

<LLD(1 )

<LLD(1)

<LLD(')

<LLD(')

<LLD(')

N/A(2)

<LLD(1 )

N/A(2)

N/A(2)

<LLD(')

Co-58 Ci

<LLD(')

1.14E-07 1.05E-04 6.50E-05 1.70E-04 N/A(2) 4.57E-05 N/A(2)

N/A(2) 4.57E-05 Co-60 Ci

<LLD(1 )

2.51E-07 5.80E-04 7.91E-04 1.37E-03 N/A(2) 4.74E-03 N/A(2)

N/A(2) 4.74E-03 Fe-55 Ci

<LLD(1 )

<LLD(')

<LLD(')

<LLD(')

<LLD(')

N/A(2)

<LLD(')

N/A(2)

N/A(2)

<LLD(')

Fe-59 Ci

<LLD(1)

<LLD(1)

<LLD(1 )

<LLD(')

<LLD(1 )

N/A(2)

<LLD(1 )

N/A(2))

N/A(2))

<LLD(1 )

Zn-65 Ci

<LLD(')

<LLD(1)

<LLD(1 )

3.70E-05 3.70E-05 N/A(2) 1.40E-04 N/A(2)

N/A(2) 1.40E-04 Mn-54 Ci

<LLD(')

<LLD(')

8.11E-05 2.35E-04 3.16E-04 N/A(2) 1.52E-03 N/A(2)

N/A(2) 1.52E-03 Cr-51 Ci

<LLD(1)

<LLD(1)

<LLD(1 )

<LLD(1 )

<LLD(')

N/A(2)

<LLD(1)

N/A(2)

N/A(2)

<LLD(1 )

Mo-99 Ci

<LLD(1)

<LLD(1)

<LLD(1 )

<LLD(1)

<LLD(1 )

N/A(2)

<LLD(1)

N/A(2)

N/A(2)

<LLD(1 )

Ag-110m Ci

<LLD(1)

<LLD(')

<LLD(1 )

<LLD(1)

<LLD(1 )

N/A(2)

<LLD(1)

N/A (2)

N/A(2)

<LLD(1 )

Ni-63 Ci

<LLD(')

<LLD(')

1.48E-04 8.87E-05 2.37E-04 N/A(2)

<LLD(')

N/A(2)

N/A(2)

<LLD(')

Total for Ci

<LLD(')

3.66E-07 9.14E-04 1.25E-03 2.16E-03 N/A(2) 6.49E-03 N/A(2)

N/A(2) 6.49E-03 Period

2. Tritium Total Tritium Ci

<LLD(')

<LLD(1) 1.49E-03 3.59E-04 1.85E-03 N/A(2) 5.07E-01 N/A(2)

N/A(2) 5.07E-01 for Period

3. D&EG Xe-133 Ci

<LLD(')

<LLD(')

<LLD(1 )

<LLD(')

<LLD(')

N/A(2)

<LLD(1 )

N/A(2)

N/A(2)

<LLD(')

Xe-135 Ci

<LLD(')

<LLD(1)

<LLD(1 )

<LLD(1 )

<LLD(1 )

N/A(2)

<LLD(1)

N/A(2)

N/A(2)

<LLD(1 )

4. Gross Alpha Activity Total Gross Ci

<LLD(')

<LLD(1)

<LLD(1 )

<LLD')

<LLD(')

N/A(2)

<LLD(1)

N/A(2)

N/A(2)

<LLD(1 )

Alpha for period I

I I

(1)

Liquid LLDs reported on page 7 of 72 (2)

No liquid releases performed in this period Page 5 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Effluent & Waste Disposable Summary GASEOUS EFFLUENT LLDs (Most Restrictive)

NUCLIDE LOWER LIMITS OF DETECTION (LLDs)

UNIT LLD Value ODCM Required LLD

1. Fission gases Kr-85 uCi/cc 3.02E-06 None Kr-85m uCi/cc 1.35E-08 None Kr-87 uCi/cc 5.33E-08 1 E-04 Kr-88 uCi/cc 5.57E-08 1E-04 Xe-133 uCi/cc 2.89E-08 1E-04 Xe-133m uCi/cc 9.51E-08 1E-04 Xe-135 uCi/cc 1.12E-08 1E-04 Xe-135m uCi/cc 1.24E-06 None Xe-138 uCi/cc 3.12E-06 1E-04 Ar-41 uCi/cc 3.14E-08 None NUCLIDE LOWER LIMITS OF DETECTION (LLDs)

UNIT LLD Value ODCM Required LLD*

2. lodines 1-131 uCi/cc 5.85E-13 1E-12 1-133 uCi/cc 7.54E-12 1E-10 1-135 uCi/cc 1.29E-08 None NUCLIDE LOWER LIMITS OF DETECTION (LLDs)

UNIT LLD Value ODCM Required LLD*

3. Particulates and Tritium H-3 uCi/cc 1.01 E-11 1E-06 Sr-89 uCi/cc 6.85E-13 1E-11 Sr-90 uCi/cc 1.26E-13 1E-11 Cs-134 uCi/cc 5.04E-13 1E-11 Cs-137 uCi/cc 6.14E-13 1E-11 Ba-140 uCi/cc 1.79E-12 None La-140 uCi/cc 2.61 E-12 None Mn-54 uCi/cc 4.19E-13 1E-11 Co-58 uCi/cc 5.42E-13 1E-11 Fe-59 uCi/cc 9.97E-13 1E-11 Co-60 uCi/cc 8.54E-13 1E-11 Zn-65 uCi/cc 9.33E-13 1E-11 Mo-99 uCi/cc 8.34E-12 1E-11 Ce-141 uCi/cc 5.71 E-13 1E-11 Ce-144 uCi/cc 2.17E-12 1E-11 Aq-10rn uCi/cc 4.06E-13 None Cr-51 uCi/cc 2.83E-12 None Gross Alpha uCi/cc 2.72E-12 1 E-11
  • ODCM REC LLDs for weekly samples. These may be increased by a factor of 10 for daily samples Page 6 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Effluent & Waste Disposable Summary LIQUID EFFLUENT LLDs (Most Restrictive)

NUCLIDE LOWER LIMITS OF DETECTION (LLDs)

ODCM Required LLD UNIT LLD Value

3. Liquids H-3 uCi/cc 1.06E-06 1E-05 Sr-89 uCi/cc 1.86E-08 5E-08 Sr-90 uCi/cc 8.09E-09 5E-08 Fe-55 uCi/cc 3.80E-07 1 E-06 Kr-85 uCi/cc 1.65E-05 None Kr-87 uCi/cc 1.93E-07 1E-05 Kr-88 uCi/cc 2.01 E-07 1E-05 Xe-133 uCi/cc 1.36E-07 1E-05 Xe-133m uCi/cc 4.17E-07 1E-05 Xe-135 uCi/cc 5.90E-08 1E-05 Xe-138 uCi/cc 5.87E-06 1E-05 Mn-54 uCi/cc 6.98E-08 5E-07 Co-58 uCi/cc 6.60E-08 5E-07 Co-60 uCi/cc 7.85E-08 5E-07 Zn-65 uCi/cc 1.05E-07 5E-07 Mo-99 uCi/cc 3.78E-07 5E-07 1-131 uCi/cc 5.85E-08 1 E-06 Cs-134 uCi/cc 9.75E-08 5E-07 Cs-137 uCi/cc 9.95E-08 5E-07 Ce-141 uCi/cc 8.38E-08 5E-07 Ce-144 uCi/cc 3.62E-07 5E-06 Gross Alpha uCi/cc 9.90E-08 1 E-07 Fe-59 uCi/cc 1.28E-07 5E-07 Ni-63 uCi/cc 7.70E-08 None Cr-51 uCi/cc 3.88E-07 None Ag-110m uCi/cc 6.46E-08 None Page 7 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Supplemental Information Facility: Quad Cities Nuclear Power Station (QCNPS)

January - December 2011 Licensee: Exelon Generation Company

1.

Regulatory Limits

a.

For Noble Gases:

Dose rate (per site)

1.

Less than 500 mrem/year to the whole body

2.

Less than 3000 mrem/year to the skin.

Dose Gamma Radiation (per unit)

1.

Less than or equal to 5 mrad/quarter.

2.

Less than or equal to 10 mrad/year.

Beta Radiation (per unit)

1.

Less than or equal to 10 mrad/quarter.

2.

Less than or equal to 20 mrad/year.

b,c.

For Iodine-1 31, Iodine-1 33, Carbon-14, and for all radionuclides in particulate form with half-lives greater than 8 days.

Dose Rate

1.

Less than 1500 mrem/year. (per site)

Dose (per unit)

1.

Less than or equal to 7.5 mrem/quarter.

2.

Less than or equal to 15 mrem/year.

d.

For Liquid: (per unit)

Less than or equal to 1.5 mrem to the whole body during any calendar quarter.

Less than or equal to 5 mrem to any organ during any calendar quarter.

Less than or equal to 3 mrem to the whole body during any calendar year.

Less than or equal to 10 mrem to any organ during any calendar year.

Page 8 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Supplemental Information

2.

Maximum Permissible Concentration a,b,c. For fission and activation gases, iodines, and particulates with half-lives greater than 8 days, allowable release limits are calculated by solving equations 2.0-5 and 2.0-6 from the Offsite Dose Calculation Manual Part II Chapter 2. The alarm setpoint is conservatively set at approximately 10% of the 10CFR20 limit.

d.

For liquid effluents, with the exception of tritium and dissolved & entrained noble gasses, allowable release limits are calculated by solving equations 2.0-1 and 2.0-2 from the Offsite Dose Calculation Manual Part II Chapter 2. The MPC values used for the monitors were as follows:

Radwaste discharge 1.55E-05 jiCi/ml Service water 1.OOE-05 OCi/ml The allowable release limits for tritium and dissolved & entrained noble gases are as follows:

Tritium: 3.OOE-03 uCi/mL taken from Reg Guide 1.21 Dissolved & Entrained noble gases: 2.OOE-04 uCi/mL taken from NUREG 1302

3.

Average Energy The average gamma energy used to calculate the alarm setpoints for the noble gas monitors was:

9.59E-01 MeV for Quarter 1 9.61 E-01 MeV for Quarter 2 9.49E-01 MeV for Quarter 3 8.79E-01 MeV for Quarter 4

4.

Measurements and Approximations of Total Radioactivity

a.

Fission and Activation Gases

b.

lodines

c.

Particulates

d.

Carbon-14 a,b,c. The main chimney and reactor building ventilation exhaust systems are continually monitored for iodines and particulates. These samples are pulled every 7 days and analyzed by gamma isotopic. The particulate papers are composited every 31 days and sent to a vendor for Sr-89/90 and gross alpha analysis. Noble gas grab samples are pulled and analyzed by gamma isotopic weekly. Tritium samples are pulled and analyzed every month.

Page 9 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Supplemental Information The Sr-89/90 and gross alpha curies released values reported are actual. On a real time basis, the portion of the "percent of applicable limit" for these contributors is reported based on projections using the previous available data.

The actual results are obtained by editing the ODCM software inputs when the vendor results become available. Therefore, the "percent of applicable limits" in this report are actual.

The continuous strip chart recorders for the monitors on the release points are reviewed for spikes and the activity released is calculated. An additional calculated activity for noble gases is added to the main chimney release each month. This calculation is done because most of the grab samples show less than the lower limit of detection due to the low amount of activity and the large dilution flow at the sample point. The calculation takes into account the normal offgas train and the gland sealing steam contribution to the release.

The average flow at the release points is used to calculate the curies released.

There are no ground level releases from QCNPS. All monitored releases are considered either elevated or mixed mode.

d.

Carbon-14 Quad Cities has conservatively estimated it's Carbon-14 generation and release in accordance with EPRI Technical Report 1021106, "Estimation of Carbon-14 in Nuclear Power Plant Gaseous Effluents". The Quad Cities estimate of 2.84E+01 Ci of Carbon-14 and the resultant 2.84E+01 Ci of 14CO 2 released is based upon a normalized Carbon-14 production rate of 5.10E+00 Ci/GWTh-yr, a gaseous release fraction of 1.00, a 14CO 2 fraction of 1.00, a reactor power rating of 5914 MWTh (2957 MWTh/unit for 2 units), and a calculated Effective Full Power days based upon Total Core Therms data.

e.

Liquid Effluents The River Discharge Tanks are analyzed before discharge by gamma isotopic. A composite representative portion of this sample is saved. This is composited with other discharges that occurred every 31 days and is analyzed for tritium and gross alpha. The monthly composites are composited quarterly and sent to a vendor for Fe-55, Ni-63, and Sr-89/90 analyses. The discharge bay is sampled every 31 days and analyzed by gamma isotopic for tritium and gross alpha. It is sampled quarterly and sent to a vendor for Fe-55, Ni-63, and Sr-89/90 analysis.

On a real time basis, the portion of the "percent of applicable limit" for these contributors is based on projections using scaling factors. The actual results are obtained by editing the ODCM software inputs when the vendor results become available. Therefore, the "percent of applicable limits" in this report are actual.

Page 10 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Supplemental Information The tank volumes and activities are used to calculate the curies released for the River Discharge Tank. The total water released during the quarter and the activity is used to calculate the diluted activity released at the discharge bay, from batch discharges.

f.

Estimated Total Error Percent The estimated total error percents were calculated by taking the square root of the sum of the squares of errors for sampling and measurement parameters.

g.

Less than the Lower Limit of Detection (<LLD)

Samples are analyzed such that the Technical Specification LLD requirements are met. When a nuclide is not detected during the quarter, then <LLD is reported. The most conservative LLDs used for counting effluent samples are included in this report.

5.

Batch Releases

a.

Liquid

1.

Number of releases:

2

2.

Total time:

1.14E+03 minutes

3.

Maximum time:

9.31 E+02 minutes

4.

Average time:

5.72E+02 minutes

5.

Minimum time:

2.13E+02 minutes

6.

Average stream flow:

56.2 gpm (discharge) 2.53E+05 gpm (dilution)

b.

Gaseous

1. NONE
6.

Abnormal Releases

a.

Liquid A leak into the 1A RHR (Residual Heat Removal) heat exchanger, service water side, developed in May 2011. This produces a monitored liquid effluent release via the continuous liquid release pathway each time that the "A" loop of the Unit-1 RHR system is started. The activity identified from the leak is included in the monthly effluent calculations and is also included in the "continuous" liquid section of this report. A temporary modification to pressurize the service water side of the affected heat exchanger was installed in September 2011, which significantly reduced the leakage rate. This leak is scheduled to be repaired during refuel outage Q1 R22, in March 2013. The radioactive effluent releases from this leak will continue to be trended until after the repair.

Page 11 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Supplemental Information

b.

Gaseous An air sample taken from the doorway of the Floor Drain Surge Tank Building vestibule on September 30, 2011 was obtained due to Max Recycle Ventilation being secured. Cs-1 37 at a concentration just above detection limits was identified. Conservative volume assumptions were used to estimate the total radioactivity released to the environment, and the overall impact is insignificant to normal station effluent, but still meets the definition of "abnormal" per Regulatory Guide 1.21, has been accounted for in station effluent calculations. This release totaled 8.OOE-04 uCi of Cs-137. This radioactivity was added to the normal monthly station radioactive gaseous effluent for September 2011.

7.

Radiological Impact on Man

a.

Liquid Dose to a Member of the Public for 2011 Total Body: 1.04E-03 mrem Organ: 2.19E-03 mrem

b.

Gaseous Dose to a Member of the Public for 2011 Total Body: 4.20E-02 mrem Skin: 6.87E-04 mrem Organ (Particulate/Iodine/C-1 4): 1.OOE+00 mrem The Quad Cities calculated annual doses from Carbon-14 releases have been calculated using the methodologies outlined in the ODCM. The resultant estimated releases of Carbon-14 resulted in a dose contribution of 1.24E-01 mrem/yr to organ dose (12.4%) and 3.91 E-02 mrem/yr to total body dose (93%).

The maximum expected annual dose contribution from Carbon-14 has been calculated to be 2.08E-01 mrem/yr organ dose and 4.15E-02 mrem/yr total body dose. This was obtained using maximum gross thermal capacity maintained for 365 days for both units.

Quad Cities conservatively calculates a "bounding dose" for gaseous effluents.

The ODCM methodology determines the maximum parameters associated with each of the 16 meteorological sectors around the site. The highest of these parameters are applied to one location to determine the maximum potential for offsite doses. This calculation assumes that all available uptake pathways are present and are being used at the "maximum exposed individual" usage factors listed in Regulatory Guide 1.109. This methodology bounds the highest expected annual dose to an individual.

Page 12 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Supplemental Information

c.

Direct Radiation Dose to a Member of the Public for 2011 Total Body: 7.59E+00 mrem 30.4% of 40 CFR 190 Limit of 25 mrem/year (Whole Body and Organ). Thyroid dose of 1.33% of 40 CFR 190 Limit (75 mrem).

d.

Total Body Doses to the Population and Average Doses to Individuals in the Population from All Receiving-Water-Related-Pathways:

Not applicable for QCNPS

e.

Total Body Doses to the Population and Average Doses to Individuals in the Population from Gaseous Effluents to a Distance of 50 Miles:

Not applicable for QCNPS

f.

Doses From Liquid and Gaseous Effluent to Members of the Public Due to Their Activities Inside the Site Boundary for the Report Period:

Not applicable for QCNPS. Any member of the public that is onsite for a significant period will be issued an occupational dosimeter.

g.

Liquid and Gaseous Effluent Radiation Monitors and Instrumentation Unavailability for the Period Beyond the Requirements of the ODCM, Including Sampling Deviation:

No ODCM monitors were unavailable for greater than 30 days in 2011.

Page 13 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report 1 OCFR20.1301 (a)(1) Compliance Assessment Quad Cities Station Unit One and Unit Two Assessment Period 01/01/2011 THROUGH 12/31/2011 10CFR20.1301(a)(1) Limit 100.0 mrem/year Quad Cities Unit 1

-4 1*.

)d r-., _,

1

,rd I',,*.* Ath r'-,*.

^

Submitted by:

Date:

Z(54P'ý2Z-Reviewed by:

David C. Basham Date: 25Ak2]z Page 14 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Maximum Doses Resulting From Airborne Releases/Compliance Status Quad Cities Station - Unit One/Unit Two Unit One Annual Unit Two 10 CFR 50 APP. I Annual Yearly Objective Unit One

% of APP. I Unit Two

% of APP. I Type of Dose Gamma Air (mrad)

Beta Air (mrad)

Organ (mrem)

Critical Person Critical Organ 4.46E-04 2.34E-04 1.35E-01 Child Bone 4.46E-04 2.34E-04 1.35E-01 Child Bone 10.0 20.0 15.0 4.46E-03 1.17E-03 8.99E-01 Child Bone 4.46E-03 1.17E-03 8.99E-01 Child Bone The calculation of the above doses was done by an independent contractor utilizing GASPAR II, an NRC approved program. The calculation was done with current year meteorological data and default equation multipliers outlined in Reg Guide 1.109 and NUREG 0133. These values are provided as a comparison to the conservative dose calculations performed by Quad Cities Station.

Page 15 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: January -

March 2011 Stability Class -

Extremely Unstable 196Ft-33Ft Delta-T (F)

Winds Measured at 33 Feet Wind Speed (in mph)

Wind Direction N

NNE NE 1-3 0

0 0

4-7 1

0 3

8-12 13-18 19-24

> 24 Total 0

0 4

0 0

0 0

0 0

0 0

0 1

0 7

ENE E

ESE SE SSE S

SSW SW WSW W

WNW NW NNW Variable 0

0 0

0 0

0 0

3 14 3

1 1

4 1

4 4

5 5

2 0

0 2

0 7

6 0

17 0

0 0

0 6

6 1

4 0

0 12 0

14 0

0 0

0 0

0 1

0 2

1 0

2 0

0 2

0 3

2 0

0 0

0 0

0 3

0 5

2 0

Total 0

37 44 0

0 0

81 0

Hours of calm in this stability class:

0 Hours of missing wind measurements in this stabi Hours of missing stability measurements in all s

lity class:

tability cl asses:

4 Page 16 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: January -

March 2011 Stability Class - Moderately Unstable

- 196Ft-33Ft Delta-T (F)

Winds Measured at 33 Feet Wind Wind Direction 1-3 4-7 N

0 NNE 0

NE 0

ENE 0

E 0

ESE 0

SE 0

SSE 0

S 0

SSW 0

SW 0

WSW 0

W 0

WNW 0

NW 0

NNW 0

Variable 0

1 2

1 1

2 0

1 0

0 1

0 2

0 0

2 0

0 Speed (in mph) 8-12 13-18 0

0 0

0 0

0 1

0 1

1 0

0 1

0 0

0 0

0 0

0 1

0 1

0 0

0 2

0 4

0 1

0 0

0 19-24 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

> *24 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

Total 1

2 1

2 4

0 2

0 0

1 1

3 0

2 6

1 0

Total 0

13 12 0

0 26 Hours of calm in Hours of missing Hours of missing this stability class:

wind measurements in this stability measurements in 0

stability class:

0 all stability classes:

4 Page 17 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: January - March 2011 Stability Class - Slightly Unstable 196Ft-33Ft Delta-T (F)

Winds Measured at 33 Feet Wind Speed (in mph)

Wind Direction N

NNE NE ENE E

ESE SE SSE S

SSW SW WSW W

WNW NW NNW Variable 1-3 4-7 8-12 13-18 19-24

> 24 Total 7

2 3

8 17 6

3 5

2 2

5 6

13 11 13 8

0 Total 0

55 52 4

0 0

ill Hours of calm in Hours of missing Hours of missing this stability class:

wind measurements in this stability measurements in 0

stability class:

0 all stability classes:

4 Page 18 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: January -

March 2011 Stability Class Neutral 196Ft-33Ft Winds Measured at 33 Feet Delta-T (F)

Wind Speed (in mph)

Wind Direction 1-3 4-7 8-12 13-18 19-24

> 24 Total N

NNE NE ENE E

ESE SE SSE 6

37 40 3

18 17 5

19 20 7

50 25 0

3 5

0 8

49 20 10 4

28 22 3

31 19 7

30 S

11 4

9 6

9 0

2 5

0 0

0 0

0 4

0 83 0

41 0

49 0

82 0

87 0

59 0

53 0

46 0

20 0

12 0

38 0

63 0

113 0

129 0

182 0

71 SSW SW 3

24 11 7

38 14 WSW W

WNW NW NNW Variable Total 4

54 45 10 3

60 53 13 2

88 91 1

45 22 1

3 0

54 0

0 0

0 0

0 0

0 0

0 410 0

0 78 586 0

1128 Hours of calm in Hours of missing Hours of missing this stability class:

0 wind measurements in this stabil stability measurements in all st ity class:

0 ability classes:

4 Page 19 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: January -

March 2011 Stability Class - Slightly Stable Winds Measured at 196Ft-33Ft Delta-T (F) 33 Feet Wind Direction N

NNE NE ENE E

ESE SE SSE S

SSW SW WSW W

WNW NW NNW Variable Total Wind Speed (in mph) 1-3 4-7 8-12 13-18 19-24

> 24 Total 7

11 6

14 12 25 8

9 3

15 37 11 10 29 17 7

23 12 12 14 12 10 4

13 4

23 8

27 17 24 9

0 1

2 5

6 3

1 3

0 0

0 0

0 0

0 0

1 5

1 1

0 0

15 0

29 0

35 0

43 0

63 0

56 0

42 0

35 0

22 0

18 0

29 0

40 0

48 0

66 0

49 0

57 0

24 8

40 13 8

35 7

41 10 14 0

0 147 380 5

8 0

0 109 0

0 0

656 Hours of calm in this stability class:

Hours of missing wind measurements in this Hours of missing stability measurements in 0

stability class:

0 all stability classes:

4 Page 20 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: January -

March 2011 Stability Class - Moderately Stable Winds Measured at 196Ft-33Ft 33 Feet Delta-T (F)

Wind Speed (in mph)

Wind Direction N

NNE NE ENE E

1-3 2

4 3

7 7

4-7 8-12 13-18 19-24

> 24 Total 0

0 1

4 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

2 4

4 0

11 0

7 ESE SE SSE S

SSW SW WSW 10 8

7 4

1 4

0 18 0

15 0

12 0

8 W

WNW NW NNW Variable Total 4

5 1

4 0

0 0

0 0

0 0

0 0

1 5

1 5

5 3

5 0

72 34 0

106 Hours of calm in Hours of missing Hours of missing this stability class:

wind measurements in this stability measurements in 3

stability class:

0 all stability classes:

4 Page 21 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Stability Period of Record: January - March 2011 Class Extremely Stable 196Ft-33Ft Winds Measured at 33 Feet Delta-T (F)

Wind Speed (in mph)

Wind Direction N

1-3 1

4-7 8-12 13-18 19-24

> 24 Total 0

NNE NE ENE E

ESE 0

0 2

4 0

0 0

SE SSE S

SSW SW WSW W

WNW NW NNW Variable Total 7

5 5

3 1

2 0

3 0

0 2

36 0

0 0

0 0

1 0

0 2

9 8

5 7

0 3

1 0

0 0

0 0

2 0

3 0

0 2

0 0

0 44 Hours of calm in Hours of missing Hours of missing this stability class:

wind measurements in this stability measurements in 1

stability class:

0 all stability classes:

4 Page 22 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Stability Period of Record: January -

Class - Extremely Unstable Winds Measured at 296 March 2011 296Ft-33Ft Feet Delta-T (F)

Wind Speed (in mph)

Wind Direction N

NNE NE ENE E

ESE SE SSE S

SSW SW WSW W

WNW NW NNW Variable Total 1-3 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 4-7 8-12 13-18 19-24

> 24 Total 0

0 0

0 0

0 0

0 2

0 2

0 0

0 0

0 1

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

4 0

3 1

4 0

4 0

0 2

0 0

0 0

0 19 Hours of calm in this stability class:

0 Hours of missing wind measurements in this stability class:

0 Hours of missing stability measurements in all stability classes:

4 Page 23 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: January -

Stability Class - Moderately Unstable Winds Measured at 296 March 2011 296Ft-33Ft Delta-T (F)

Feet Wind Speed (in mph)

Wind Direction N

NNE NE 1-3 0

0 0

4-7 0

0 8-12 13-18 19-24

> 24 Total 0

1 0

0 0

0 0

0 0

0 0

1 0

7 ENE 0

0 11 0

16 E

ESE SE SSE S

SSW SW WSW W

WNW NW NNW Variable Total 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 1

0 0

0 0

0 0

0 0

3 1

2 0

2 0

0 3

0 0

2 0

0 0

0 0

0 0

0 0

0 0

0 0

0 1

1 5

4 4

4 4

1 3

0 3

3 0

0 6

1 32 18 0

57 Hours of calm in this stability class:

Hours of missing wind measurements in this Hours of missing stability measurements in 0

stability class:

0 all stability classes:

4 Page 24 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: January -

Stability Class - Slightly Unstable Winds Measured at 296 March 2011 296Ft-33Ft Delta-T (F)

Feet Wind Speed (in mph)

Wind Direction N

NNE NE 1-3 0

0 0

4-7 8-12 13-18 19-24

> 24 Total 1

1 1

6 2

5 ENE E

0 0

0 0

1 10 2

0 ESE SE SSE S

SSW SW WSW W

WNW NW NNW Variable 0

0 0

1 3

0 2

0 0

5 7

0 13 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 9

3 3

5 0

6 8

3 4

8 7

3 6

2 8

6 0

0 0

12 0

0 5

0 Total 0

12 44 35 4

0 95 Hours of calm in Hours of missing Hours of missing this stability class:

wind measurements in this stability measurements in 0

stability class:

4 all stability classes:

4 Page 25 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: January -

March 2011 Stability Class - Neutral 296Ft-33Ft Delta-T (F)

Winds Measured at 296 Feet Wind Direction N

NNE NE ENE E

ESE SE SSE S

SSW SW WSW W

WNW NW NNW Variable Wind Speed (in mph) 1-3 4-7 8-12 13-18 19-24

> 24 Total 1

3 1

1 4

2 1

1 1

0 3

2 0

2 0

1 0

17 5

10 16 20 7

8 14 5

7 6

14 15 20 22 17 0

15 12 16 40 37 14 13 13 14 6

20 30 28 41 50 28 0

377 34 14 39 49 28 14 17 15 7

8 15 15 46 86 93 30 0

510 11 13 13 6

15 9

14 8

5 6

13 8

17 17 23 9

0 187 7

85 5

52 6

85 0

112 7

i1 0

46 1

54 5

56 0

32 1

28 0

57 7

76 11 117 13 179 0

188 6

91 0

0 69 1369 Total 23 203 Hours of calm in Hours of missing Hours of missing this stability class:

wind measurements in this stability measurements in 0

stability class:

15 all stability classes:

4 Page 26 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: January -

March 2011 Stability Class - Slightly Stable

- 296Ft-33Ft Winds Measured at 296 Feet Delta-T (F)

Wind Speed (in mph)

Wind Direction 1-3 4-7 8-12 13-18 19-24

> 24 Total N

1 NNE NE ENE E

ESE SE SSE 0

0 0

1 0

0 1

4 10 2

10 3

13 1

5 3

4 14 13 0

1 0

1 0

6 4

4 7

21 8

8 2

9 0

11 12 S

1 3

1 3

7 8

0 16 0

18 0

19 0

32 0

37 1

26 0

27 0

23 2

33 2

47 2

38 1

35 6

46 0

37 1

33 0

18 5

13 11 2

24 14 SSW SW WSW W

WNW NW NNW 2

0 1

1 0

0 4

4 22 1

11 16 6

5 0

9 18 12 1

9 27 2

12 14 0

4 0

0 Variable Total 0

4 6

0 1

0 8

42 153 8

0 200 0

1 68 15 486 Hours of calm in Hours of missing this stability class:

0 wind measurements in this stability class:

1 Hours of missing stability measurements in all stability classes:

4 Page 27 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: January - March 2011 Stability Class - Moderately Stable

- 296Ft-33Ft Delta-T (F)

Winds Measured at 296 Feet Wind Speed (in mph)

Wind Direction N

NNE NE ENE E

ESE SE SSE S

SSW SW WSW W

WNW NW NNW Variable 1-3 4-7 0

0 2

0 1

0 0

0 0

0 0

0 0

0 0

0 0

0 2

4 2

1 0

1 0

0 1

2 1

1 0

3 0

0 8-12 13-18 19-24

> 24 1

3 0

0 2

1 0

0 1

0 0

0 3

1 0

0 4

0 0

0 4

3 1

0 7

5 0

0 1

6 2

0 1

4 5

0 2

1 3

0 1

1 0

0 0

1 0

0 1

2 0

0 2

1 0

0 0

0 0

0 0

0 0

0 0

0 0

0 Total 4

5 7

6 6

8 13 9

10 7

4 2

4 3

3 0

0 Total 3

18 30 29 11 0

91 Hours of calm in Hours of missing Hours of missing this stability class:

wind measurements in this stability measurements in 0

stability class:

0 all stability classes: 4 Page 28 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: January -

March 2011 Stability Class - Extremely Stable 296Ft-33Ft Delta-T (F)

Winds Measured at 296 Feet Wind Directio N

NNE NE ENE E

ESE SE SSE S

SSW SW WSW W

WNW NW NNW Variable Total Wind Speed (in mph) 1-3 4-7 8-12 13-18 19-24

> 24 Total 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

2 1

4 0

0 0

7 0

19 Hours of calm in this stability class:

Hours of missing wind measurements in this Hours of missing stability measurements in 0

stability class:

0 all stability classes:

4 Page 29 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: April - June 2011 Stability Class - Extremely Unstable

- 196Ft-33Ft Delta-T (F)

Winds Measured at 33 Feet Wind Direction N

NNE NE ENE E

ESE SE SSE S

SSW SW WSW W

WNW NW NNW Variable Wind Speed (in mph) 1-3 4-7 8-12 13-18 19-24

> 24 Total 1

1 2

3 0

3 7

11 8

12 22 1

3 3

1 1

0 2

16 8

2 3

19 13 3

3 5

11 3

16 20 6

4 0

3 18 12 8

4 25 20 14 11 17 33 4

22 24 7

5 0

Total 0

79 134 14 0

0 227 Hours of calm in Hours of missing Hours of missing this stability class:

wind measurements in this stability measurements in 0

stability class:

0 all stability classes:

5 Page 30 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: April - June 2011 Stability Class -

Moderately Unstable

-. 196Ft-33Ft Delta-T (F)

Winds Measured at 33 Feet Wind Speed (in mph)

Wind Direction 1-3 4-7 8-12 13-18 19-24

> 24 Total N

NNE NE ENE E

ESE 0

0 0

0 0

0 0

3 0

2 5

0 7

5 2

2 4

0 1

1 0

2 1

5 5

SE SSE S

SSW SW WSW W

WNW NW NNW Variable 0

2 2

2 0

0 1

1 1

0 0

0 0

0 0

0 1

1 0

0 0

5 0

0 0

0 0

0 0

0 0

0 0

4 5

7 5

0 0

12 0

0 0

0 0

6 2

4 6

2 1

1 10 0

12 5

1 1

0 3

0 1

0 0

9 0

0 1

2 0

0 Total 0

38 36 0

0 79 0

Hours of calm in this stability class:

0 Hours of missing wind measurements in this stability class:

Hours of missing stability measurements in all stability classes:

5 Page 31 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: April - June 2011 Stability Class - Slightly Unstable Winds Measured at 196Ft-33Ft 33 Feet Delta-T (F)

Wind Speed (in mph)

Wind Direction 1-3 4-7 8-12 13-18 19-24

> 24 Total N

0 0

NNE NE ENE E

ESE SE SSE S

SSW SW WSW 0

0 0

0 0

0 0

0 2

4 5

4 5

5 8

2 4

3 1

6 1

3 2

6 6

0 2

1 2

3 6

6 1

3 0

0 0

1 1

1 2

2 0

0 0

0 0

1 4

1 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

10 3

0 0

0 7

8 8

0 13 0

16 0

0 0

2 6

4 0

11 0

10 W

WNW NW NNW Variable Total 0

0 0

0 0

9 2

2 4

0 0

0 0

0 0

0 0

0 13 0

13 0

16 0

12 0

0 0

4 7

0 0

80 49 13 0

142 Hours of calm in this stability class:

0 Hours of missing wind measurements in this stabil ity class:

0 Hours of missing stability measurements in all stability classes:

5 Page 32 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: April - June 2011 Stability Class -

Neutral 196Ft-33Ft Delta-T (F)

Winds Measured at 33 Feet Wind Speed (in mph)

Wind Direction 1-3 4-7 8-12 13-18 19-24

> 24 Total N

2 0

4 23 7

11 NNE NE ENE E

ESE SE SSE S

SSW SW 0

0 3

6 2

18 9

2 12 23 1

26 22 16 0

17 16 2

1 29 25 11 5

15 3

11 1

2 2

0 0

0 0

0 29 0

18 0

32 0

43 0

66 0

35 0

66 0

21 0

16 0

13 0

45 0

40 0

47 0

80 0

59 0

30 4

7 WSW W

WNW NW NNW Variable Total 3

26 16 1

19 18 0

11 34 0

14 58 2

29 24 2

2 8

4 0

0 54 0

0 0

0 0

0 1

1 27 0

0 2

0 286 0

0 27 272 0

640 Hours of calm in Hours of missing Hours of missing this stability class:

wind measurements in this stability measurements in 0

stability class:

0 all stability classes:

5 Page 33 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: April - June 2011 Stability Class - Slightly Stable Winds Measured at 196Ft-33Ft 33 Feet Delta-T (F)

Wind Speed (in mph)

Wind Direction 1-3 4-7 8-12 13-18 19-24

> 24 Total N

NNE NE ENE E

ESE SE SSE S

SSW 5

16 12 5

14 13 8

21 16 21 25 11 21 36 44 11 41 34 18 35 20 7

22 6

7 SW WSW W

WNW NW NNW Variable Total 13 19 15 55 4

34 2

0 2

7 8

0 33 0

32 0

51 0

62 0

107 0

90 0

74 0

31 0

13 0

34 0

77 0

46 0

43 0

45 0

47 0

16 6

24 12 9

24 10 7

28 12 0

0 1

2 0

0 0

25 0

0 0

0 0

0 0

0 1

12 1

158 0

413 3

0 206 0

1 0

802 Hours of calm in Hours of missing Hours of missing this stability class:

wind measurements in this stability measurements in 0

stability class:

0 all stability classes:

S Page 34 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: April - June 2011 Stability Class - Moderately Stable 196Ft-33Ft Winds Measured at 33 Feet Delta-T (F)

Wind Direction N

NNE NE ENE E

ESE SE SSE S

SSW SW WSW W

WNW NW NNW Variable Wind Speed (in mph) 1-3 4-7 8-12 13-18 19-24

> 24 Total 11 4

21 14 17 0

0 0

1 1

0 0

0 0

0 0

0 0

0 0

11 0

4 0

21 0

15 0

18 0

31 0

35 19 12 25 10 0

0 4

6 0

10 0

0 0

0 0

0 0

4 5

7 5

4 5

2 Total 146 39 2

0 0

0 187 Hours of calm in this stability class:

Hours of missing wind measurements in this Hours of missing stability measurements in 3

stability class:

0 all stability classes:

5 Page 35 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: April -

June 2011 Stability Class - Extremely Stable Winds Measured at 196Ft-33Ft Delta-T (F) 33 Feet Wind Direction N

NNE NE ENE E

Wind Speed (in mph) 1-3 4-7 8-12 13-18 19-24

> 24 Total ESE SE SSE S

SSW SW WSW W

WNW 4

4 6

2 12 15 12 5

1 0

2 3

6 0

0 0

0 0

3 1

1 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

12 0

18 0

13 0

6 0

1 0

0 0

2 0

3 0

6 0

1 0

1 0

1 0

1 0

81 4

4 6

2 NW NNW 0

Variable Total 1

76 0

5 Hours of calm in this stability class:

18 Hours of missing Hours of missing wind measurements in this stability class:

stability measurements in all stability cl 0

asses:

5 Page 36 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: April - June 2011 Stability Class - Extremely Unstable 296Ft-33Ft Delta-T (F)

Winds Measured at 296 Feet Wind Speed (in mph)

Wind Direction N

NNE NE ENE E

ESE SE SSE S

SSW SW WSW W

WNW NW NNW Variable 1-3 4-7 8-12 13-18 19-24

> 24 Total 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

1 0

0 0

0 3

1 1

1 3

0 0

0 0

0 0

0 7

4 0

5 3

2 4

4 7

0 0

2 6

0 0

0 0

0 0

1 0

2 1

1 8

2 0

0 1

0 2

0 0

0 0

1 0

0 0

0 1

2 4

0 0

0 0

0 0

0 0

8 5

1 5

5 6

7 15 14 3

0 3

6 2

0 0

Total 0

0 10 44 18 8

80 Hours of calm in Hours of missing Hours of missing this stability class:

wind measurements in this stability measurements in 0

stability class:

0 all stability classes:

5 Page 37 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: April -

Stability Class -

Moderately Unstable Winds Measured at 296 June 2011 296Ft-33Ft Delta-T (F)

Feet Wind Speed (in mph)

Wind Direction 1-3 4-7 8-12 13-18 19-24

> 24 Total N

0 0

NNE NE ENE E

ESE SE SSE S

SSW SW WSW 2

7 2

2 1

5 5

4 3

0 0

1 0

1 0

3 3

2 0

15 0

0 0

4 8

3 8

8 1

1 6

4 1

18 0

15 1

7 8

3 1

14 0

2 2

1 0

W WNW NW NNW Variable Total 0

0 0

0 0

0 0

0 0

0 0

0 11 2

0 0

13 2

1 1

0 7

3 2

0 0

0 0

0 9

5 5

0 2

0 2

36 58 30 6

132 Hours of calm in this stability class:

0 Hours of missing wind measurements in this stabi lity class:

0 Hours of missing stability measurements in all stability classes:

5 Page 38 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: April - June 2011 Stability Class - Slightly Unstable 296Ft-33Ft Delta-T (F)

Winds Measured at 296 Feet Wind Direction N

NNE NE ENE E

ESE SE SSE S

SSW SW WSW W

WNW NW NNW Variable Total Wind Speed (in mph) 1-3 4-7 8-12 13-18 19-24

> 24 Total 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

1 3

1 2

4 0

0 0

2 4

2 2

1 1

1 1

0 1

4 6

3 4

6 5

4 5

4 4

1 4

9 0

2 0

2 2

0 5

3 6

5 4

1 0

3 5

12 6

2 5

0 4

11 10 13 11 18 13 9

14 14 9

11 21 22 3

8 0

0 25 62 61 30 13 191 Hours of calm in Hours of missing Hours of missing this stability class:

wind measurements in this stability measurements in 0

stability class:

0 all stability classes:

5 Page 39 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: April -

June 2011 Stability Class - Neutral 296Ft-33Ft Delta-T (F)

Winds Measured at 296 Feet Wind Direction N

NNE NE ENE E

ESE SE SSE S

SSW SW WSW W

WNW NW NNW Variable Wind Speed (in mph) 1-3 4-7 8-12 13-18 19-24

> 24 Total 3

5 10 7

15 6

2 5

4 2

7 3

3 S

1 7

0 5

14 10 27 20 16 12 13 9

9 12 4

10 14 18 16 0

40 12 13 36 32 24 16 7

11 13 22 21 33 42 28 13 0

1 16 12 33 14 22 18 4

8 23 15 5

21 28 5

1 0

0 3

6 10 4

13 16 2

3 4

2 4

4 1

4 0

0 49 50 51 113 86 81 64 31 37 51 58 37 71 91 56 38 0

Total 5

85 209 363 226 76 964 Hours of calm in Hours of missing Hours of missing this stability class:

wind measurements in this stability measurements in 0

stability class:

34 all stability classes:

5 Page 40 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: April June 2011 Stability Class - Slightly Stable

- 296Ft-33Ft Delta-T (F)

Winds Measured at 296 Feet Wind Speed (in mph)

Wind Direction N

NNE NE ENE E

ESE SE SSE S

SSW SW WSW W

WNW NW NNW Variable 1-3 4-7 8-12 13-18 19-24

> 24 Total 10 6

8 19 14 11 10 17 12 10 4

4 12 6

9 7

0 6

6 13 20 8

24 24 14 18 29 24 11 12 20 10 2

0 0

2 4

0 4

17 18 8

16 17 6

2 2

7 2

1 0

18 18 31 41 28 57 60 41 46 65 39 21 26 37 23 14 0

Total 2

37 159 241 106 20 565 Hours of calm in Hours of missing Hours of missing this stability class:

wind measurements in this stability measurements in 0

stability class:

0 all stability classes:

5 Page 41 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Stability Wind Direction N

NNE NE ENE E

ESE SE SSE S

SSW SW WSW W

WNW NW NNW Variable Quad Cities Generating Station Period of Record: April -

June 2011 Class - Moderately Stable 296Ft-33Ft Delta-T (F)

Winds Measured at 296 Feet Wind Speed (in mph) 1-3 4-7 8-12 13-18 19-24

> 24 Total 2

2 2

2 1

4 11 16 7

6 1

0 0

2 0

0 0

6 5

9 7

15 13 23 21 18 9

5 6

7 4

6 4

0 Total 4

32 57 56 9

0 158 Hours of calm in this stability class:

Hours of missing wind measurements in this Hours of missing stability measurements in 0

stability class:

0 all stability classes:

5 Page 42 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: April -

Stability Class - Extremely Stable Winds Measured at 296 June 2011 296Ft-33Ft Delta-T (F)

Feet Wind Speed (in mph)

Wind Direction 1-3 4-7 8-12 13-18 19-24

> 24 Total N

NNE NE ENE E

ESE SE SSE 0

0 0

0 0

0 0

1 0

0 0

0 0

1 1

1 1

0 0

0 0

0 0

0 5

6 3

6 5

S SSW SW WSW W

WNW NW NNW Variable 0

1 0

0 0

0 0

0 0

0 0

0 3

0 0

5 6

6 6

0 0

0 0

0 0

Total 3

20 18 13 0

0 54 Hours of calm in this stability class:

Hours of missing wind measurements in this Hours of missing stability measurements in 1

stability class:

0 all stability classes:

5 Quad Cities Generating Station Page 43 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: July - September 2011 Class -

Extremely Unstable 196Ft-33Ft Stability Delta-T (F)

Winds Measured at 33 Feet Wind Speed (in mph)

Wind Direction 1-3 4-7 8-12 13-18 19-24

> 24 Total N

0 13 13 NNE NE ENE 0

0 0

0 0

0 E

3 1

4 3

5 4

17 ESE SE SSE S

SSW SW WSW 0

13 0

16 0

5 4

2 2

1 2

3 1

1 2

3 7

0 0

6 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

26 0

21 0

16 0

17 0

0 0

0 0

7 3

6 4

7 0

6 0

15 0

0 8

9 0

17 0

11 0

16 0

11 W

WNW NW NNW Variable 0

11 0

9 0

9 0

15 0

21 0

0 1

Total 0

135 64 0

0 199 Hours of calm in this stability class:

Hours of missing wind measurements in this Hours of missing stability measurements in 0

stability class:

0 all stability classes:

6 Page 44 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Stability Wind Direction N

NNE NE ENE E

ESE SE SSE S

SSW SW WSW Period of Record: July - September 2011

]lass -

Moderately Unstable 196Ft-33Ft Delta-T (F)

Winds Measured at 33 Feet Wind Speed (in mph) 1-3 0

0 0

0 0

0 0

0 0

0 1

0 4-7 S

6 8-12 13-18 19-24

> 24 Total 2

4 0

7 0

10 3

5 4

5 7

8 4

2 6

2 8

3 2

5 0

0 1

0 2

0 0

0 0

1 1

2 2

0 0

0 0

0 0

0 0

0 0

0 0

4 5

5 5

9 8

4 2

7 3

W WNW NW NNW Variable Total 1

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 10 0

0 0

0 5

4 5

0 2

75 16 0

93 Hours of calm in this stability class:

Hours of missing wind measurements in this Hours of missing stability measurements in 0

stability class:

0 all stability classes:

6 Page 45 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: July -

Stability Class - Slightly Unstable Winds Measured at September 2011

- 196Ft-33Ft 33 Feet Delta-T (F)

Wind Direction N

NNE NE Wind Speed (in mph) 1-3 4-7 8-12 13-18 19-24

> 24 Total 1

1 0

6 5

ENE 0

14 E

0 0

6 8

ESE SE SSE 0

11 0

S 6

3 5

6 5

2 0

1 0

0 0

1 0

0 0

1 2

2 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

7 8

0 8

0 11 0

14 0

12 0

0 0

6 5

7 7

SSW SW WSW W

WNW NW 2

2 15 2

12 3

17 0

17 0

14 0

21 0

12 0

12 0

17 3

7 0

10 0

13 NNW Variable Total 0

0 4

0 24 0

0 15 139 0

178 Hours of calm in Hours of missing Hours of missing this stability class:

0 wind measurements in this stabi stability measurements in all s

lity class:

0 tability classes:

6 Page 46 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: July -

September 2011 Stability Class - Neutral Winds Measured at 33 Wind Speed (it 196Ft-33Ft Delta-T (F)

Feet

-i mph)

-18 19-24

> 24 Total Wind Direction N

NNE NE ENE E

ESE SE SSE S

SSW SW WSW W

WNW NW NNW Variable 1-3 4-7 8-12 13-2 5

4 4

S 4

4 S

2 7

12 3

8 S

7 6

0 22 21 14 10 21 31 30 13 17 14 27 17 15 18 14 24 1

17 4

2 0

0 2

2 0

0 0

1 1

8 5

5 1

0 48 41 30 20 14 26 37 36 18 19 21 40 21 31 29 32 32 1

Total 83 309 8

0 0

448 Hours of calm in Hours of missing Hours of missing this stability class:

wind measurements in this stability measurements in 0

stability class:

all stability cl 0

asses:

6 Page 47 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: July -

September 2011 Stability Class - Slightly Stable Winds Measured at Wind Speed Wind 196Ft-33Ft Delta-T (F) 33 Feet (in mph)

Direction N

NNE NE ENE E

ESE SE SSE S

SSW SW WSW W

WNW NW NNW Variable Total 1-3 4-7 8-12 13-18 19-24

> 24 Total 23 14 12 12 29 28 21 12 9

9 12 8

12 16 18 14 0

249 43 17 14 6

15 42 15 19 12 6

31 26 28 23 59 38 1

395 7

4 0

1 1

2 1

0 0

0 0

4 4

0 10 5

0 39 0

0 0

0 0

0 0

0 0

0 0

2 0

0 0

1 0

3 73 35 26 19 45 72 37 31 21 15 43 40 44 39 87 58 1

0 686 Hours of calm in Hours of missing Hours of missing this stability class:

wind measurements in this stability measurements in 0

stability class:

0 all stability classes:

6 Page 48 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Stability Period of Record: July -

Class -

Moderately Stable Winds Measured at September 2011 196Ft-33Ft Delta-T (F) 33 Feet Wind Speed (in mph)

Wind Direction 1-3 4-7 8-12 13-18 19-24

> 24 Total N

NNE NE ENE E

ESE SE SSE S

SSW SW WSW W

WNW 20 20 25 12 22 35 31 14 13 5

8 6

11 22 0

27 0

22 0

26 0

12 0

23 0

35 0

32 0

14 0

13 0

0 0

6 8

8 0

11 0

23 0

38 0

33 NW NNW Variable Total 28 10 26 0

298 7

0 32 0

0 0

1 0

0 0

0 0

0 0

0 0

0 0

331 Hours of calm in this stability class:

12 Hours of missing Hours of missing wind measurements in this stability class:

0 stability measurements in all stability classes:

6 Page 49 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: July -

Stability Class - Extremely Stable Winds Measured at September 2011 196Ft-33Ft Delta-T (F) 33 Feet Wind Speed (in mph)

Wind Direction 1-3 4-7 8-12 13-18 19-24

> 24 Total N

6 7

0 0

0 0

0 0

0 0

0 0

6 NNE 7

NE ENE E

ESE SE SSE S

SSW SW WSW W

WNW NW NNW Variable Total 3

21 17 31 28 9

4 2

9 7

6 7

4 3

2 166 0

0 3

0 21 0

17 0

32 0

28 0

0 0

0 0

0 0

0 0

0 9

4 2

9 7

6 8

8 3

2 0

172 Hours of calm in this stability class:

83 Hours of missing wind.measurements in this stability class:

0 Hours of missing stability measurements in all stability classes:

6 Page 50 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: July - September 2011 Stability Class - Extremely Unstable

- 296Ft-33Ft Delta-T (F)

Winds Measured at 296 Feet Dir Wind Speed (in mph)

Wind ection 1-3 4-7 8-12 13-18 19-24

> 24 Total N

NNE NE ENE E

ESE SE SSE S

SSW SW WSW W

WNW NW NNW Variable 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 4

0 2

1 0

0 0

1 0

0 0

0 0

0 0

7 1

2 1

0 0

0 2

10 0

0 0

0 0

1 3

0 0

0 0

0 0

0 0

0 0

6 4

1 0

0 0

1 3

0 Total 0

0 13 20 1

2 36 Hours of calm in this stability class:

Hours of missing wind measurements in this Hours of missing stability measurements in 0

stability class:

0 all stability classes:

6 Page 51 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Stability Wind Period of Record: July -

September 2011 Class - Moderately Unstable 296Ft-33Ft Delta-T (F)

Winds Measured at 296 Feet Wind Speed (in mph)

Direction 1-3 4-7 8-12 13-18 19-24

> 24 Total N

NNE NE ENE E

ESE SE SSE S

SSW SW WSW W

WNW NW 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

2 9

11 0

10 1

3 1

3 2

3 2

3 1

7 2

2 1

0 3

1 3

4 3

5 0

1 2

3 4

8 2

0 0

1 3

3 3

1 4

0 2

0 3

3 0

0 0

0 0

0 0

0 0

11 0

10 0

22 0

18 0

0 0

0 1

1 0

0 2

0 0

3 0

8 0

0 0

0 0

0 6

4 5

6 8

9 5

9 4

0 10 0

19 NNW Variable Total 2

11 0

0 0

0 0

24 71 44 0

147 Hours of calm in this stability class:

Hours of missing wind measurements in this Hours of missing stability measurements in 0

stability class:

0 all stability classes:

6 Page 52 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: July - September 2011 Stability Class - Slightly Unstable

- 296Ft-33Ft Delta-T (F)

Winds Measured at 296 Feet Wind Speed (in mph)

Wind Direction 1-3 4-7 8-12 13-18 19-24

> 24 Total N

NNE NE ENE 0

0 2

1 11 0

12 E

ESE SE SSE S

SSW 0

0 0

0 0

3 8

5 7

2 9

7 4

3 2

7 7

5 3

2 3

7 4

2 0

0 0

0 2

1 2

0 2

2 3

1 1

2 0

0 0

0 0

0 0

0 0

1 0

0 0

4 2

0 2

0 9

0 5

0 14 0

11 0

16 0

15 0

15 0

14 0

13 0

8 0

13 SW WSW W

WNW NW NNW Variable 0

1 7

7 1

16 10 0

15 0

12 0

17 0

34 0

15 0

12 0

20 0

0 0

0 8

4 4

7 5

11 1

0 0

1 Total 3

112 91 22 0

237 Hours of calm in this stability class:

0 Hours of missing wind measurements in this stability class:

0 Hours of missing stability measurements in all stability classes:

6 Page 53 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: July - September 2011 Stability Class - Neutral 296Ft-33Ft Delta-T (F)

Winds Measured at 296 Feet Wind Speed (in mph)

Wind Direction 1-3 4-7 8-12 13-18 19-24

> 24 Total N

NNE NE ENE E

ESE SE SSE 4

14 22 17 0

15 19 0

13 15 8

4 1

6 1

0 0

0 5

0 13 8

2 15 14 0

1 8

19 19 8

14 12 5

16 5

S 2

8 15 17 SSW SW 0

13 7

12 8

17 3

13 WSW W

WNW NW NNW Variable Total 1

2 7

16 6

1 2

6 2

0 5

8 4

3 0

0 63 1

44 0

32 0

22 0

32 0

51 0

36 0

28 0

44 0

44 0

37 4

34 0

47 3

50 5

50 2

56 9

16 15 2

11 13 13 2

12 11 16 1

9 24 17 0

0 0

233 0

0 0

25 172 181 44 15 670 Hours of calm in Hours of missing Hours of missing this stability class:

wind measurements in this stability measurements in 0

stability class:

0 all stability classes:

6 Page 54 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: July -

September 2011 Stability Class - Slightly Stable 296Ft-33Ft Delta-T (F)

Winds Measured at 296 Feet Wind Speed (in mph)

Wind Direction 1-3 4-7 8-12 13-18 19-24

> 24 Total N

NNE 1

15 36 26 1

11 21 18 3

0 0

0 NE 1

0 5

14 6

2 ENE 8

s E

0 13 22 7

ESE 0

3 15 22 2

13 13 SE 0

0 SSE 2

21 8

S 1

SSW 2

SW 0

0 9

17 3

10 13 5

13 19 3

6 18 0

16 12 4

1 4

5 6

6 1

0 1

0 81 0

51 0

26 0

15 0

43 0

44 0

29 0

35 0

32 0

34 0

43 1

29 0

29 0

16 1

54 0

43 WSW 0

1 W

WNW 0

2 3

4 8

NW 4

10 24 13 NNW 0

0 4

22 16 Variable Total 0

0 0

229 1

0 46 0

0 9

81 237 2

604 Hours of calm in this stability class:

Hours of missing wind measurements in this Hours of missing stability measurements in 0

stability class:

0 all stability classes:

6 Page 55 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: July - September 2011 Stability Class - Moderately Stable

- 296Ft-33Ft Winds Measured at 296 Feet Delta-T (F)

Wind Direction Wind Speed (in mph) 1-3 4-7 8-12 13-18 19-24

> 24 Total N

0 10 9

11 NNE NE ENE 3

2 9

18 17 9

7 8

10 9

12 5

4 4

E ESE SE SSE S

1 2

1 0

2 1

1 3

1 1

3 4

17 9

9 9

7 12 0

16 10 2

0 0

0 0

0 0

0 0

3 0

1 0

0 0

0 0

6 0

32 0

47 0

23 0

23 0

26 0

24 0

31 0

19 0

28 0

24 0

16 0

16 SSW SW WSW W

WNW 3

13 5

4 0

4 8

7 3

8 4

2 1

0 2

0 4

0 15 0

16 NW 3

10 NNW Variable Total 1

0 2

0 4

0 2

2 0

94 0

9 0

0 21 74 158 0

353 Hours of calm in Hours of missing Hours of missing this stability class:

wind measurements in this stability measurements in 0

stability class:

0 all stability classes:

6 Page 56 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: July - September 2011 Stability Class - Extremely Stable

- 296Ft-33Ft Winds Measured at 296 Feet Delta-T (F)

Wind Speed (in mph)

Wind Direction N

NNE 1-3 0

4-7 8-12 13-18 19-24

> 24 Total 2

1 NE 4

ENE E

2 3

0 0

ESE SE SSE 3

4 5

7 2

2 0

1 1

3 7

2 6

S SSW SW WSW W

WNW NW NNW Variable Total 2

0 0

0 0

0 0

2 0

2 18 3

3 0

0 1

0 1

3 6

3 3

0 0

0 1

0 0

0 0

0 0

0 0

0 1

0 0

0 0

0 0

0 0

0 1

0 0

0 0

0 11 0

12 0

10 0

13 0

28 0

15 0

17 0

10 6

6 4

8 4

10 7

5 3

2 0

1 3

0 7

3 1

2 0

0 0

5 0

0 0

0 1

4 5

0 12 47 71 24 0

155 Hours of calm in Hours of missing Hours of missing this stability class:

0 wind measurements in this stability class:

0 stability measurements in all stability classes:

6 Page 57 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: October -

December 2011 Stability Class -

Extremely Unstable 196Ft-33Ft Delta-T (F)

Winds Measured at 33 Feet Wind Speed (in mph)

Wind Direction N

NNE NE ENE E

ESE 1-3 0

4-7 8-12 13-18 19-24

> 24 Total 0

0 0

0 0

0 0

0 0

0 3

7 4

SE SSE 0

0 0

S 0

0 0

0 0

0 3

5 5

4 5

0 0

4 0

2 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 12 0

1 0

0 0

0 6

0 9

SSW SW WSW 0

13 0

20 0

17 0

25 W

WNW 0

0 0

0 0

0 3

1 3

1 1

0 NW NNW Variable Total 1

0 0

0 2

0 0

0 0

0 0

3 2

8 1

3 0

0 57 28 0

87 Hours of calm in this stability class:

0 Hours of missing wind measurements in this stability class:

0 Hours of missing stability measurements in all stability classes:

0 Page 58 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: October - December 2011 Stability Class - Moderately Unstable 196Ft-33Ft Delta-T (F)

Winds Measured at 33 Feet Wind Speed (in mph)

Wind Direction N

NNE NE ENE E

ESE SE SSE S

SSW SW WSW W

WNW NW NNW Variable 1-3 0

0 0

0 0

0 4-7 8-12 13-18 19-24

> 24 Total 0

1 0

0 1

0 0

0 0

0 0

0 0

0 0

0 1

1 0

0 1

1 3

2 0

4 2

0 11 0

0 0

0 0

0 1

4 8

3 0

Total 0

26 15 2

0 0

43 Hours of calm in this stability class:

0 Hours of missing wind measurements in this stabil ity class:

0 Hours of missing stability measurements in all stability classes:

0 Page 59 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: October Stability Class - Slightly Unstable Winds Measured at December 2011 196Ft-33Ft Delta-T (F) 33 Feet Wind Speed (in mph)

Wind Direction 1-3 4-7 8-12 13-18 19-24

> 24 Total N

NNE NE ENE E

ESE SE SSE S

SSW SW WSW W

0 0

0 0

0 0

0 0

0 0

0 0

5 5

0 0

0 1

2 3

0 0

0 0

0 6

8 4

4 0

10 0

14 WNW NW NNW Variable Total 0

0 1

0 0

0 6

6 4

6 4

0 0

0 8

9 6

9 5

0 0

0 0

5 0

0 0

0 0

0 12 0

15 0

0 9

0 1

67 33 0

106 Hours of calm in this stability class:

0 Hours of missing wind measurements in this stabil ity class:

0 Hours of missing stability measurements in all stability classes:

0 Page 60 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: October Stability Class -

Neutral Winds Measured at December 2011 196Ft-33Ft Delta-T (F) 33 Feet Wind Speed (in mph)

Wind Direction 1-3 4-7 8-12 13-18 0

27 51 11 19-24

> 24 Total N

NNE NE ENE E

ESE SE 0

23 16 1

17 1

24 3

13 1

0 1

4 8

8 8

1 0

3 2

8 6

8 0

0 0

0 0

0 0

0 1

2 2

0 0

0 0

0 0

0 0

89 0

47 0

19 0

26 0

17 0

8 SSE S

SSW SW WSW W

WNW NW NNW Variable Total 2

14 3

18 1

30 11 0

12 0

14 0

24 0

27 0

43 0

29 0

78 0

101 0

76 0

38 4

20 3

3 46 27 3

30 52 16 2

34 38 1

16 21 2

0 0

42 0

0 0

241 0

0 29 336 0

648 Hours of calm in Hours of missing Hours of missing this stability class:

wind measurements in this stability measurements in 0

stabil ity class:

0 all stability classes:

0 Page 61 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: October Stability Class -

Slightly Stable Winds Measured at December 2011 196Ft-33Ft Delta-T (F) 33 Feet Wind Speed (in mph)

Wind Direction 1-3 4-7 8-12 13-18 19-24

> 24 Total N

NNE NE ENE E

ESE SE SSE S

SSW SW WSW W

WNW NW NNW Variable Total 2

23 10 4

12 14 2

21 20 6

13 4

14 3

17 12 29 17 37 15 40 6

3 0

3 5

5 3

8 4

0 0

0 0

0 0

0 0

0 0

0 4

0 0

19 0

38 0

38 0

47 0

25 0

21 0

20 0

44 0

59 0

60 0

76 0

64 0

70 0

78 0

93 0

90 0

36 10 49 17 19 43 2

11 47 12 10 49 19 15 59 19 11 55 20 5

28 0

146 0

536 3

0 158 0

0 0

859 Hours of calm in this stability class:

Hours of missing wind measurements in this Hours of missing stability measurements in 4

stability class:

0 all stability classes:

0 Page 62 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: October Stability Class -

Moderately Stable Winds Measured at December 2011 196Ft-33Ft Delta-T (F) 33 Feet Wind Speed (in mph)

Wind Direction 1-3 4-7 8-12 13-18 19-24

> 24 Total N

NNE NE ENE E

ESE SE SSE S

SSW SW WSW 2

1 3

3 9

0 2

1 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 2

3 4

3 0

9 19 14 29 13 21 18 0

33 0

42 0

39 0

21 W

12 3

7 4

7 3

5 7

0 9

2 2

3 2

7 0

0 0

0 0

0 0

5 9

7 9

WNW NW NNW Variable 0

10 0

0 0

5 7

0 Total 135 73 0

0 0

0 208 Hours of calm in Hours of missing Hours of missing this stability class:

0 wind measurements in this stabil stability measurements in all st ity class:

0 ability classes:

0 Page 63 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: October Stability Class -

Extremely Stable Winds Measured at December 2011 196Ft-33Ft Delta-T (F) 33 Feet Wind Speed (in mph)

Wind Direction 1-3 4-7 8-12 13-18 19-24

> 24 Total N

NNE NE ENE E

1 2

6 6

21 2

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 3

2 6

6 ESE SE SSE S

SSW SW WSW W

WNW NW NNW Variable 65 19 36 11 10 6

7 5

8 11 7

3 0

0 21 0

84 0

37 0

11 0

10 0

0 0

0 6

7 5

8 0

11 0

7 0

3 0

0 Total 205 22 0

0 0

0 227 Hours of calm in this stability class:

26 Hours of missing wind measurements in this stability class:

0 Hours of missing stability measurements in all stability classes:

0 Page 64 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: October - December 2011 Stability Class -

Extremely Unstable 296Ft-33Ft Delta-T (F)

Winds Measured at 296 Feet Wind Speed (in mph)

Wind Direction 1-3 4-7 8-12 13-18 19-24

> 24 Total N

0 0

NNE NE ENE 0

0 0

0 E

ESE SE 0

SSE S

SSW SW 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

4 0

0 0

0 0

0 0

0 0

1 0

0 0

0 0

0 0

WSW W

0 0

0 0

0 0

0 7

8 6

0 0

0 0

0 0

0 7

WNW 0

0 0

0 0

0 0

NW NNW 0

0 0

Variable Total 0

0 0

11 10 22 Hours of calm in this stability class:

0 Hours of missing wind measurements in this stability class:

0 Hours of missing stability measurements in all stability classes:

0 Page 65 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: October - December 2011 Stability Class - Moderately Unstable 296Ft-33Ft Delta-T (F)

Winds Measured at 296 Feet Wind Speed (in mph)

Wind Direction 1-3 4-7 8-12 13-18 19-24

> 24 Total N

NNE NE ENE E

ESE SE SSE S

SSW SW WSW 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

3 1

0 0

0 0

0 0

2 0

4 0

0 0

0 0

0 1

0 2

2 0

0 1

0 0

0 0

0 0

0 0

0 0

0 6

1 0

0 0

0 0

7 0

W WNW NW NNW 0

0 0

4 4

0 0

5 1

0 0

6 3

0 0

0 0

0 0

0 0

0 0

0 0

0 7

0 1

6 2

2 14 Variable Total 0

0 0

1 0

9 0

0 19 15 2

45 Hours of calm in this stability class:

0 Hours of missing wind measurements in this stability class:

0 Hours of missing stability measurements in all stability classes:

0 Page 66 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: October -

December 2011 Stability Class - Slightly Unstable

- 296Ft-33Ft Delta-T (F)

Winds Measured at 296 Feet Wind Direction N

NNE NE ENE E

ESE SE SSE S

SSW SW WSW W

WNW NW NNW Variable Wind Speed (in mph) 1-3 4-7 8-12 13-18 19-24

> 24 Total 9

1 0

1 3

3 4

12 9

19 10 3

11 13 12 6

0 Total 0

17 45 28 20 6

116 Hours of calm in Hours of missing Hours of missing this stability class:

wind measurements in this stability measurements in 0

stability class:

0 all stability classes:

0 Page 67 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: October - December 2011 Stability Class -

Neutral 296Ft-33Ft Winds Measured at 296 Feet Delta-T (F)

Wind Speed (in mph)

Wind Direction 1-3 4-7 8-12 13-18 19-24

> 24 Total N

NNE NE ENE 0

1 0

6 31 61 16 3

18 15 10 7

16 16 13 1

10 22 1

6 11 E

3 7

2 6

ESE SE SSE 1

0 3

5 2

1 0

1 3

4 118 8

55 4

56 1

39 0

26 0

11 2

27 0

31 3

15 1

6 11 10 S

0 4

14 17 11 10 56 SSW SW WSW W

WNW 1

10 14 30 23 2

7 20 20 4

4 6

84 2

55 3

50 2

107 0

17 20 6

0 17 30 29 29 1

12 28 37 37 14 129 NW NNW Variable Total 0

1 9

28 25 34 7

22 31 16 4

100 3

80 0

0 10 127 0

305 0

315 0

204 0

0 63 1024 Hours of calm in Hours of missing Hours of missing this stability class:

wind measurements in this stability measurements in 0

stability class:

0 all stability classes:

0 Page 68 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: October - December.2011 Stability Class Slightly Stable 296Ft-33Ft Delta-T (F)

Winds Measured at 296 Feet Wind Speed (in mph)

Wind Direction N

NNE NE ENE E

ESE SE SSE S

SSW SW WSW W

WNW NW NNW Variable 1-3 4-7 8-12 13-18 19-24

> 24 Total 14 7

3 5

0 0

2 7

17 17 4

11 11 14 11 13 0

8 3

7 11 0

3 10 22 25 29 13 15 27 31 34 8

0 0

1 2

0 0

2 4

12 33 38 7

11 19 7

6 1

0 143 28 13 13 16 2

5 18 48 84 102 26 40 63 54 51 26 0

Total 5

36 136 246 23 589 Hours of calm in Hours of missing Hours of missing this stability class:

wind measurements in this stability measurements in 0

stability class:

0 all stability classes:

0 Page 69 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Stability Period of Record: October Class - Moderately Stable Winds Measured at 2 December 2011

- 296Ft-33Ft 96 Feet Delta-T (F)

Wind Direction 1-3 Wind Speed (in mph) 4-7 8-12 13-18 19-24

> 24 Total N

NNE NE ENE 0

0 0

0 0

0 E

ESE SE 2

0 0

0 4

0 0

1 2

2 2

0 2

2 3

3 0

0 0

1 1

7 0

0 4

0 0

0 0

0 1

4 0

10 0

0 0

0 4

0 0

4 5

5 5

13 SSE S

SSW SW WSW W

WNW 1

0 1

1 0

0 0

0 9

14 10 7

28 24 0

23 0

35 0

61 0

17 0

11 8

4 3

5 3

5 4

6 1

1 0

0 0

0 0

8 7

NW NNW 0

0 0

1 0

5 2

4 0

0 12 0

11 8

0 0

0 0

0 0

5 0

Variable Total 4

17 56 99 42 0

218 Hours of calm in this stability class:

Hours of missing wind measurements in this Hours of missing stability measurements in 0

stability class:

3 all stability classes:

0 Page 70 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Joint Frequency Tables Quad Cities Generating Station Period of Record: October -

December 2011 Stability Class -

Extremely Stable

- 296Ft-33Ft Delta-T Winds Measured at 296 Feet (F)

Wind Direction N

NNE NE ENE E

ESE SE SSE S

SSW SW WSW W

WNW NW NNW Variable Wind Speed (in mph) 1-3 4-7 8-12 13-18 19-24

> 24 Total 0

0 6

3 1

3 3

1 0

0 3

0 0

0 0

1 4

0 0

0 0

0 0

0 0

0 0

0 0

9 6

3 7

2 1

0 0

6 1

2 9

5 12 10 0

5 23 2

10 20 0

34 0

31 0

34 0

14 0

15 1

2 0

6 4

4 7

8 0

0 2

1 0

0 0

4 2

0 4

0 0

6 5

2 0

8 0

10 0

0 0

2 0

0 Total 2

34 65 76 13 0

190 Hours of calm in this stability class:

0 Hours of missing wind measurements in this stabil ity class:

1 Hours of missing stability measurements in all stability classes:

0 Page 71 of 72

Quad Cities Nuclear Power Station 2011 Annual Radioactive Effluent Release Report Solid Waste and Irradiated Fuel Shipments A. Solid Waste Shipped Offsite for Burial or Disposal (Not irradiated fuel)

1. Types of Waste Types of Waste Total Total Period Est. Total Quantity Activity (Ci)

Error %

(M3 )

a. Spent resins, filter sludges, evaporator bottoms, etc 1.17E+02 6.13E+02 2011 2.50E+01
b. Dry compressible waste, contaminated equip, etc 2.15E+03 1.04E+01 2010 2.50E+01
c. Irradiated components, control rods, etc N/A N/A N/A N/A
d. Other (describe) Combined Packages of a. and b.

N/A N/A N/A N/A

2. Estimate of major nuclide composition (by waste type)

Major Nuclide Composition

a.

Co-60 5.72E+01 Fe-55 3.30E+01 Cs-1 37 6.37E+00 Zn-65 1.19E+00 Ni-63 1.13E+00

b.

Mn-54 2.87E+00 Fe-55 4.31 E+01 Co-60 4.15E+01 Zn-65 6.65E+00 Co-58 2.48E+00 Ni-63 1.10E+00

c.

N/A N/A

d.

N/A N/A

3. Solid Waste Disposition Number of Shipments 31 32 21 Mode of Transportation Highway Highway Rail Destination Processor Disposal Disposal B. Irradiated Fuel Shipments (disposition)

Number of Shipments N/A Mode of Transportation Highway Destination Disposal C. Changes to the Process Control Program No changes made.

Page 72 of 72 CY-QC-170-301, Revision 10, Offsite Dose Calculation Manual Errata/Correction to the 2010 Annual Radioactive Effluent Release Report Errata/Correction to the 2010 ARERR The following list identifies each piece of errata data that has been identified within the previous year. The following pages reflect the affected original submitted page and the edited page. The edited page contains revision bars to track the changes. At the top of each page, the year of the appropriate report is outlined. The errors in the report are inconsequential. The Station Corrective Action Program was utilized to capture these errors and to provide a tracking mechanism to correct the data from the 2010 Radiological Effluent Release Report.

Errata data from 2010 ARERR:

1. During review of the 2010 Radiological Effluent Release Report, it was identified that the report contained incorrect data for the following values in the Gaseous Effluent via the Main Chimney nuclide tables: annual total Sr-89 value, annual total Cs-1 37, and the particulate total activities for the 4 th quarter and annual total.
  • Gaseous Effluent Release Point - Main Chimney Sr-89 Reported Annual Total Value: 2.01 E-03 Corrected Annual Total Value: 1.09E-03 Cs-i 37 Reported Annual Total Value: <LLD Corrected Annual Total Value: 6.51 E-06 4 th Quarter Particulate Total Reported Quarterly Particulate Total: 4.50E-03 Corrected Quarterly Particulate Total: 1.95E-03 Annual Particulate Total Reported Annual Particulate Total: 5.42E-03 Corrected Annual Particulate Total: 4.50E-03
2. The "Liquid Effluents -- Summation of all Releases" table contained errors in the "Average Diluted Concentration" section of the tables, and are corrected in this attachment.

Quad Cities Nuclear Power Station 2010 Annual Radioactive Effluent Release Report Effluent & Waste Disposable Summary Gaseous Effluents Release Point Main Chimney (Elevated)

Period:

January - December 2010 Unit:

1 & 2 Nuclides continuous Mode Batch Mode Nuclides Continuous Mode Batch Mode Released

1. Fission Un Quarter Quarter Quarter Quarter Total Quarter Quarter Quarter Quarter gases it 1

2 3

4 1

2 3

4 Kr-85 Ci

<LLD(1 )

<LLD(1 )

<LLD(1)

<LLD(1 )

<LLD(1 )

N/A(2)

N/A(2)

N/A(2)

N/A(2)

Kr-85m Ci 3.78E-01 1.25E+00 4.72E-01 4.98E-01 2.60E+00 N/A(2)

N/A(2)

N/A(2)

N/A(2)

Kr-87 Ci 2.38E+00 2.52E+00 3.05E+00 3.31 E+00 1.13E+01 N/A(2)

N/A(2)

N/A(2)

N/A(2)

Kr-88 Ci 1.53E+00 1.75E+00 1.93E+00 2.04E+00 7.26E+00 N/A(2)

N/A(2)

N/A(2)

N/A(2)

Xe-133 Ci 5.37E-01 2.02E+00 6.26E-01 6.20E-01 3.80E+00 N/A(2)

N/A(2)

N/A( 2)

N/A(2)

Xe-1 35 Ci 1.94E+00 2.04E+00 2.53E+00 3.28E+00 9.79E+00 N/A(2)

N/A(2)

N/A(2)

N/A(2)

Xe-135m Ci 1.42E+01 1.64E+01 1.93E+01 2.15E+01 7.15E+01 N/A(2)

N/A(2)

N/A(2)

N/A(2)

Xe-138 Ci 5.59E+01 6.23E+01 7.77E+01 8.25E+01 2.78E+02 N/A( 2)

N/A(2)

N/A(2)

N/A(2)

Ar-41 Ci 1.90E-01 8.89E-01 1.80E-01 1.15E-01 1.37E+00 N/A 2)

N/A(2)

N/A(2)

N/A(2)

Total for Period Ci 7.71E+01 8.92E+01 11.06E+02 1.14E+02 3.86E+02 N/A(2)

N/A(2)

N/A(2)

N/A(2)

2. lodines 1-131 Ci 1.60E-03 2.32E-03 1.96E-03 1.91E-03 7.79E-03 N/A (2)

N/A(2)

N/A(2)

N/A(2)

N/A_(2) 1-133 Ci 7.48E-03 1.32E-02 1.17E-02 1.21E-02 4.46E-02 N/A()

N/Am N/A(2)

N/A(2)

N/A(2) 1-135 Ci 1.50E-03 5.52E-03 4.16E-03

<LLD(1) 1.12E-02 N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

Total for Period Ci 1.06E-02 2.11E-02 1.78E-02 1.40E-02 6.35E-02 N/A(2)

N/A( 2)

N/A(2)

N/A(2)

N/A(2)

3. Particulates Sr-89 Ci 1.28E-04 I 1.42E-04 I 3.93E-04 I

Sr-90 Ci

<LLD(1)

<LLD(1)

<LLD(1)

Cs-134 Ci

<LLD(1)

<LLD(1)

<LLDF' Cs-137 Ci

<LLD(')

<LLD(')

6.51E-06 Ba-140 Cii1 1.82E-04 6.13E-05 9.18E-04 I

La-140 Ci 2.46E-05 1.48E-04 4.78E-04 6.24E-04 1.28E-03 N/At Cr-51 Ci

<LLD(')

<LLD(1)

<LLD(1 )

<LLD(1 )

<LLD(1 )

N/A' Mn-54 Ci

<LLD(')

<LLD(1)

<LLD(')

<LLD(')

<LLD(')

N/A' Co-58 Ci

<LLD(1)

<LLD(1)

<LLD(1 )

<LLD(1 )

<LLD(1)

N/A' Co-60 Ci 2.13E-05

<LLD(')

4.52E-05 4.95E-05 1.16E-04 N/A' Mo-99 Ci

<LLD(')

<LLD(')

<LLD(')

<LLD(')

<LLD(') IN/A' Ag-110m Ci

<LLD(1)

<LLD(1 )

<LLD(')

<LLD(')

<LLDO1)

N/A' Ce-141 Ci

<LLD(1)

<LLD(1 )

<LLD(')

<LLD(')

<LLD(1' N/Al Ce-144 Ci

<LLD(')

<LLD(')

<LLD(')

<LLD(1 )

<LLD(1)

N/A' Total for Period Ci 3.56E-04 3.52E-04 1.84E-03 4.50E-03 5.42E-03 N/A' (1)

(2)

Gaseous LLD's reported on No gaseous batch releases page 6 of 72 Page 2 of 72

Quad Cities Nuclear Power Station 2010 Annual Radioactive Effluent Release Report Effluent & Waste Disposable Summary Gaseous Effluents Release Point Main Chimney (Elevated)

Period:

January - December 2010 Unit:

1 & 2 Nuclides

[

Continuous Mode Batch Mode Released

1. Fission Un Quarter Quarter Quarter Quarter Total Quarter Quarter Quarter Quarter Total gases it 1

2 3

4 1

2 3

4 Kr-85 Ci

<LLD(1"

<LLD(')

<LLD(1)

<LLD(1 )

<LLD(1)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

N/A(2)

Kr-85m Ci 3.78E-01 1.25E+00 4.72E-01 4.98E-01 2.60E+00 N/A(2)

N/A(2)

N/A 2)

N/A(2)

N/A(2)

Kr-87 Ci 2.38E+00 2.52E+00 3.05E+00 3.31 E+00 1.13E+01 N/A727 N/AT2 )

N/A(2)

N/A7 2)

N/A(2)

Kr-88 Ci 1.53E+00 1.75E+00 1.93E+00 2.04E+00 7.26E+00 N/A72)

N/A22 )

N/A(2)

N/A( 2)

N/A(2)

Xe-1 33 Ci 5.37E-01 2.02E+00 6.26E-01 6.20E-01 3.80E+00 N/A(2)

N/A(2)

N/A 2)

N/A 2)

N/A 2)

Xe-1 35 Ci 1.94E+00 2.04E+00 2.53E+00 3.28E+00 9.79E+00 N/A(2)

N/A(2)

N/A52 )

N/A(2)

N/A(2)

Xe-135m Ci 1.42E+01 1.64E+01 1.93E+01 2.15E+01 7.15E+01 N/A(2 )

N/A(2 )

N/A(2 )

N/A(2 )

N/A(2 )

Xe-138 Ci 5.59E+01 6.23E+01 7.77E+01 8.25E+01 2.78E+02 N/A(2 )

N/A(2 )

N/A(2 )

N/A(2 )

N/A(2 )

Ar-41 Ci 1.90E-01 8.89E-01 1.80E-01 1.15E-01 1.37E+00 N/A(2 )

N/A527 N/A(2 )

N/A72 )

N/A(2 )

Total for Period Ci 7.71 E+01 8.92E+01 11.06E+02 1.14E+02 3.86E+02 N/A(2)

N/A(2)

N/A(2 )

N/AI2 )

N/AI2 )

2. lodines 1-131 Ci 1.60E-03 12.32E-03 11.96E-03 11.91 E-03 B 7.79E-03 1-133 Cii1 7.48E-03 11.32E-02 1.171 1-135 Ciii 1.50E-03 15.52E-03 14.16E-031 <LLD(" 11 1.12E-02 Total for Period Cii11 1.06E-02 1 2.11 E-02 1 1.78E-02 1 1.40E-0211I 6.35E-02
3. Particulates Sr-89 Ci Sr-90 Ci Cs-134 Ci Cs-137 Ci Ba-140 Ci La-140 Ci Cr-51 Ci Mn-54 Ci Co-58 Ci Co-60 Ci Mo-99 Ci Ag-110m Ci Ce-141 Ci Ce-144 Ci Total for Period Ci I

I1 (1)

(2)

Gaseous LLD's reported on page 6 of 72 No gaseous batch releases Page 2 of 72

Quad Cities Nuclear Power Station 2010 Annual Radioactive Effluent Release Report Effluent & Waste Disposal Summary Liquid Effluents - Summation of all Releases January - December 2010 Ur Period:

nit:

1 & 2 A.

Fission & Activation Products Unit Quarter Quarter Quarter Quarter Total Est.

1 2

3 4

Total Error %

1. Total Release (not including tritium, Ci 4.77E-04 3.27E-03 1.79E-02

<LLD(2) 2.17E-02 4.1 gases & alpha) 2 Average diluted concentration during

[iCi/mL 3.09E-10 1.27E-08 5.79E-09

<LLD(2) period

3.

Percent of applicable limit(')

WB 2.77E-02 3.01 E-01 9.10E-02

<LLD(2)

Organ 2.26E-02 1.51 E-01 5.73E-02

<LLD(2)

4.

Maximum diluted concentration during gCi/mL 3.24E-10 1.27E-08 6.39E-09

<LLD(2) batch discharges B.

Tritium

1. Total Release (3)

Ci 6.06E+00 3.82E+00 4.89E+00 3.35E+00 1.81 E+01 4.1

2.

Average diluted concentration during period iiCi/mL 3.94E-06 1.48E-05 1.58E-06 8.98E-09

3.

Percent of applicable limit 6.03E-02 6.63E-02 1.66E-02 2.99E-04 C. Dissolved & Entrained Gases

1. Total Release
2.

Average diluted concentration during period

3.

Percent of aDDlicable limit D.

Gross Alpha Activity

1. Total Release Ci

<LLD

<LLD

<LLD

<LLD

<LLD 14.8 E.

Volume Of Waste Released (prior Liters 4.04E+05 1.01 E+05 4.06E+05 0.OOE+00 9.10E+05 to dilution)

F.

Volume Of Dilution Water Used Liters 2.38E+11 4.26E+11 4.90E+11 3.73E+11 1.53E+12 During Period (1)

(2)

(3)

Whole body/organ (ODCM)

Liquid LLD's reported on page 7 of 72 Total Ci's include those considered in Abnormal Release Page 4 of 72

Quad Cities Nuclear Power Station 2010 Annual Radioactive Effluent Release Report Effluent & Waste Disposal Summary Liquid Effluents - Summation of all Releases January - December 2010 Ur Period:

it:

1 & 2 A.

Fission & Activation Products Unit Quarter Quarter Quarter Quarter Total Est.

1 2

3 4

Total Error %

1. Total Release (not including tritium, Ci 4.77E-04 3.27E-03 1.79E-02

<LLD(2 )

2.17E-02 4.1 gases & alpha) 2 Average diluted concentration during iiCi/mL 2.00E-12 7.67E-12 3.65E-1 1

<LLD(2) period

3.

Percent of applicable limit(1)

WB 2.77E-02 3.01 E-01 9.10E-02

<LLD(2)

Organ 2.26E-02 1.51 E-01 5.73E-02

<LLD(2)

4.

Maximum diluted concentration during gICi/mL 3.24E-10 1.27E-08 6.39E-09

<LLD(2) batch discharges M

t B.

Tritium

1. Total Release (3)

Ci 6.06E+00 3.82E+00 I4.89E+00 3.35E+00 1.81E+01 4.1]

2.

Average diluted concentration during period giCi/mL 2.55E-08 8.97E-09 9.98E-09 8.98E-09

3.

Percent of applicable limit I

6.03E-02 6.63E-02 1.66E-02 2.99E-04 C.

Dissolved & Entrained Gases

1. Total Release Ci

<LLD(2)

<LLD(2) 2.73E-04

<LLD(2) 2.73E-04 14i.

2.

Average diluted concentration during gCi/mL

<LLD(2 )

<LLD(2 )

5.57E-13

<LLD(2 )

period

__Ci/mL

<LLD(2_

<LLD(_)

5

3.

Percent of applicable limit N/A N/A 4.43E-05 N/A D. Gross Alpha Activity D. Total Release Ci

<LLD

<LLD

<LLD

<LLD

<LLD 14.8 E. Volume Of Waste Released (prior Liters 4.04E+05 1.01 E+05 4.06E+05 0.00E+00 9.1ý0E+05 to dilution)

F.Volume Of Dilution Water Used Liters 2.38E+1 1 4.26E+1 1 4.90E+1 1 3.73E+1 1 1.53E+12 During Period (1)

Whole body/organ (0DCM)

(2)

Liquid LLD's reported on page 7 of 72 (3)

Total Ci's include those considered in Abnormal Release Page 4 of 72