UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 May 2,2012 LICENSEE:

Nine Mile Point Nuclear Station, LLC FACILITY:

Nine Mile Point, Unit No.1

SUBJECT:

SUMMARY

OF APRIL 3,2012, PRE-APPLICATION MEETING WITH NINE MILE POINT NUCLEAR STATION, LLC REGARDING THE PROPOSED NATIONAL FIRE PROTECTION ASSOCIATION STANDARD 805 (NFPA-805)

LICENSE AMENDMENT REQUEST (TAC NO. ME8158)

On April 3, 2012, a Category 1 public meeting was held between the U.S. Nuclear Regulatory Commission (NRC) and representatives of the Nine Mile Point Nuclear Station, LLC (NMPNS) at NRC Headquarters, One White Flint North, 11555 Rockville Pike, Rockville, Maryland. The purpose of the meeting was to discuss NMPNS's planned submittal of a license amendment request to transition its fire protection licensing basis to NFPA-805.

A member of the public was in attendance by telephone. Public Meeting Feedback forms were not received. Enclosure 1 is a list of meeting attendees and Enclosure 2 is a copy of the licensee's slides presented at the meeting (Agencywide Documents Access and Management System (ADAMS) Accession No. ML121210044).

Please direct any inquiries to me at 301-415-1030 or Richard. Guzman@nrc.gov Sincerely, Richard V. Guzman, Senior Project Manager Plant licenSing Branch 1-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-410

Enclosures:

1. List of Attendees
2. Licensee's Handouts/Slides cc w/encls: Distribution via Listserv

LIST OF ATrENDEES APRIL 3. 2012. PRE-APPLICATION MEETING WITH CONSTELLATION ENERGY NUCLEAR GROUP (CENG)

NINE MILE POINT NUCLEAR STATION (NMPNS)

REGARDING THE PROPOSED NATIONAL FIRE PROTECTION ASSOCIATION STANDARD 805 (NFPA-805) LICENSE AMENDMENT REQUEST NAME Alex Klein Donnie Harrison Rich Guzman Bhalchandra Vaidya Leslie Fields Jay Robinson Manuel Jimenez Paul Lain Bernard Litkett Charles Moulton Harry Barrett Sampson Lee Stephen Dinsmore Paul Swift S.L. Naron Richard Neild Peter Mazzaferro Dennis Vandeputte Ned Tyler Saeed Savar*

Bridget Frymire*

Leroy Kreider*

Bob Layton*

  • by telephone FOR NINE MILE POINT, UNIT NO.1 ORGANIZATION NRC NRC NRC NRC NRC NRC NRC NRC NRC NRC NRC NRC NRC CENG CENG CENG CENG CENG CENG CENG New York State Department of Public Service Engineering Planning and Management, Inc.

(Pacific Northwest National Laboratory)

MEETING SLIDES

MEETING SLIDES

a joint venture of-------..,

O~ion -1~eDF Nine Mile Point Nuclear Station, Unit 1 NFPA 80S License Amendment Request Pre-Application Meeting with NRC Staff April 3, 2012

Introductions

  • Nine Mile Point Nuclear Station Representatives Paul Swift NMPNS Manager Engineering Services Peter Mazzaferro CENG Project Director, NFPA 805 Richard Neild NMPNS Project Manager, I\\JFPA 805 Larry Naron NMPNS Supervisor PRA Services Ned Tyler CENG Licensing Engineer Dennis Vandeputte NMPNS Licensing Engineer

Agenda

  • Overview of NMP1 Design Features
  • Current Fire Protection Licensing Basis
  • Implementation Overview

I IW!! Wf\\lUltl aI_

o=:--

"'::erw I Overview of Nine Mile Point Unit 1 (NMP1)

Design Features

  • Single unit Boiling Water Reactor, 1850 MWt
  • BWR/2 reactor design with 5 reactor recirculation loops (non-jet pump plant)
  • Mark I Containment
  • Isolation Condensers
  • Initial Operating License issued in 1969
  • Renewed Operating License issued - expires in 2029 CENG.

4

NMPl Current Fire Protection Licensing Basis

  • Branch Technical Position APCSB 9.5-1 Appendix A (addressed in UFSAR Appendix lOA)
  • Current Exemptions
  • Operator Actions - None required NRC approval CENG.

NFPA 805 Transition Project Overview

  • License Amendment Request (LAR) committed submittal date - June 29, 2012
  • Target submittal date - May 31, 2012
  • Using the Nuclear Energy Institute (NEI) LAR template
  • Preparation and internal review activities are in progress
  • Web portal established to support NRC review CENG.

6

NFPA 805 Transition Project Overview

- Technical Specifications being revised Reviewed existing exemptions

- Will not be transitioning any exemptions to NFPA 805 design basis 1\\10 additional items that require requesting 1\\1 RC approval have been identified CENG.

Compliance with NFPA 805

  • NFPA 805 Chapter 3 Compliance Review performed using NEI 04-02, Revision 2 guidance as supplemented by FAQ 07-0036 Review documented in B-1 Table (Attachment A of LAR)

Results

- One Modification

> Removal of H2 Bulk Storage in Turbine Building

- Seismic Hose Stations

- Items that Comply with Prior NRC Approval

> Cables that do not meet IEEE 383 flame test (Req. 3.3.5.3)

> Fire water provided by Lake Ontario - (Reqs. 3.5.1, 3.5.2)

CENG.

Compliance with NFPA 805

  • Non-Power Operations Review performed using NEI 04-02, Revision 2 guidance as supplemented by FAQ 07-0040 Results of Review
  • All success paths identified
  • Complete component list by Key Safety Function (KSF)
  • High Risk Evolutions
  • Pinch Points identified
  • Recommendations to manage Fire Risk CENG.

I!ptiv<<lttY&(j~

o=---~I Compliance with NFPA 805

  • Radioactive Release Review performed using NEI 04-02, Revision 2 guidance as supplemented by FAQ 09-0056 Plant evaluated on a Fire Zone basis Credit engineering controls for gaseous and liquid effluents Revise Pre-Fire Plans and Training material to clarify monitoring and control requirements CENG.

10 9

Compliance with NFPA 805

  • Nuclear Safety Capability Assessment Review performed using NEI 04-02, Revision 2 guidance as supplemented by FAQ 08-0054 Fire Area Review CT Circuit Automatic System Initiation Breaker Coordination Multiple Spurious Operations review Results:
  • Safe and Stable is defined to be Cold Shutdown
  • 24 Total Fire Areas
  • No Fire Areas to be transitioned deterministically
  • All 24 Fire Areas to be transitioned using RI-PB method CENG,.

11 Compliance with NFPA 805

  • Recovery Actions Review performed using NEI 04-02, Revision 2 guidance as supplemented by FAQ 07-0030 Primary Control Station

Compliance with NFPA 805

  • Monitoring Program Following FAQ 10-0059, Revision 5 guidance NSEL and FPRA Components

- Include any new functions in existing Maintenance Rule Program NPO Components, Rad Release Systems, FP Programmatic Include in normal System and Program Health Monitoring FP Systems and Features

- Low Safety Significant - Normal System/Program Health Monitoring

- High Safety Significant - NFPA 805 Specific Monitoring Program that mirrors Maintenance Rule Program and uses same software CENG.

13 PRA Development/Results

  • Fire PRA built on a high quality Internal Events model Internal Events model peer reviewed to RG 1.2001 Revision 1
  • Fire PRA peer reviewed by BWROG in October 2011

- IlStrong FPRA model with sound technical approachesll

- "The best we/ve seen and likely the best in the industryll

- 4 "Best ll practices

- All F&Os subsequently addressed

- No unreviewed methods used CENG.

  • 14

PRA Development/Results

  • Overall Plant Risk

- Total CDF = 2.06E-S/yr and LERF = 2.84E-6/yr llCDF =8.73E-6 and llLERF =9.00E-7

15 Implementation Overview

  • Modifications Planned (15)

No Major Modifications

  • Minor Circuit mods
  • Minor mechanical mods
  • Cable re-routes
  • Provide a portable generator for battery charging
  • Process/Procedure Changes Training Operator Response for Recovery Actions Fire Brigade Response Design Change Process CENG.

16

Summary

  • Complete LAR to be submitted on or before June 29, 2012
  • Nothing unique or unusual
  • No alternative Fire PRA methods
  • Transition Schedule Implement procedure/process changes 6 months after SER Completion of modifications 1St Refueling Outage after SER CENG.
  • 17

May 2,2012 LICENSEE:

Nine Mile Point Nuclear Station, LLC FACILITY:

Nine Mile Point, Unit No.1

SUBJECT:

SUMMARY

OF APRIL 3,2012, PRE-APPLICATION MEETING WITH NINE MILE POINT NUCLEAR STATION, LLC REGARDING THE PROPOSED NATIONAL FIRE PROTECTION ASSOCIATION STANDARD 805 (NFPA-805)

LICENSE AMENDMENT REQUEST (TAC NO. ME8158)

On April 3, 2012, a Category 1 public meeting was held between the U.S. Nuclear Regulatory Commission (NRC) and representatives of the Nine Mile Point Nuclear Station, LLC (NMPNS) at NRC Headquarters, One White Flint North, 11555 Rockville Pike, Rockville, Maryland. The purpose of the meeting was to discuss NMPNS's planned submittal of a license amendment request to transition its fire protection licensing basis to NFPA-805.

A member of the public was in attendance by telephone. Public Meeting Feedback forms were not received. Enclosure 1 is a list of meeting attendees and Enclosure 2 is a copy of the licensee's slides presented at the meeting (Agencywide Documents Access and Management System (ADAMS) Accession No. ML121210044).

Please direct any inquiries to me at 301-415-1030 or Richard.Guzman@nrc.gov Sincerely, Ira!

Richard V. Guzman, Senior Project Manager Plant licensing Branch 1-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-410

Enclosures:

1. List of Attendees 2, Licensee's Handouts/Slides cc w/encls: Distribution via Listserv DISTRIBUTION:

PUBLIC LPL1-1 Branch Reading RidsAcrsAcnw_MailCTR Resource RGuzman, NRR RidsNrrDorlLpl1-1 Resource RidsNrrLASLittie Resource RidsOgcRp Resource RidsRgn1 MailCenter Resource RidsNrrPmNineMilePoint GDentel, RI RidsNrrDraAfpb Resource RidsNrrDraApla Resource LFields, NRR JRobinson, NRR MJimenez, NRR PLain, NRR BLitkett, NRR CMoulton, NRR HNarrett, NRR SLee, NRR SDinsmore, NRR ADAMS Accession No. PKG ML121210049, Meeting Notice ML120720054, M

f Summary ML121210654, Pubr andoutS ML121210044 *Concurrence via e-mal 'I ee Ing IC H IloFFICE DORLlLPL 1-1/PM RGuzman DATE 5/1/12 DORLlLPL 1-1/LA*

SLittie 5/1/12 DORLlLPL 1-1/BC GWilson 5/2/12 DORLlLPL 1-1/PM RGuzman 5/2/12 OFFICIAL RECORD COpy